M5M BB
M5M BB
Watertube Boilers
2000-6000 MBTU
Boiler Book
07/2018
BOILER BOOK M5M
CONTENTS
PRODUCT OFFERING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Standard Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Optional Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Insurance/Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
DIMENSIONS AND RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
APPLICATION DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Emissions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Feedwater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Blowdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Boiler Stacks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Hot Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Figures
Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
M5M Dimension Diagram - Steam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
M5M Dimension Diagram - Hot Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Tables
M5M Steam Dimensions Inches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
M5M Steam Dimensions Millimeters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
M5M Ratings Steam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
M5M Hot Water Dimensions Inches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
M5M Hot Water Dimensions Millimeters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
M5M Ratings Hot Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Gas line capacity - Schedule 40 metallic pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Gas line capacity - Schedule 40 metallic pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Model M5M Hot Water – Pressure Drop and Maximum Flow Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Model M5M Hot Water – Maximum Circulating Rate/Temperature Drop . . . . . . . . . . . . . . . . . . . . . . . . . 19
Boiler Operating Temperature and Minimum Overpressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Model M5M Steam Boiler Water Make-up Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Model M5M Boiler Water Quality Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Model M5M required Natural Gas pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2
BOILER BOOK M5M
PRODUCT OFFERING
The Model M5M Boiler is a compact carbon steel, extended fin, watertube boiler. Heat transfer
design is configured in a 2-pass gas travel across the watertube surfaces. The pressure vessel is
constructed to conform to the A.S.M.E. Code, either Section IV for low pressure steam @ 15 PSIG
MAWP [maximum allowable working pressure] hydronic heating @ 140 PSIG or Section I for MAWP
greater than 15 PSIG steam or hot water greater than 250 degrees F.
The vessel [boiler] consists of two rows on each side of the vessel, of formed seamless tubes with
extended fin surfaces and downcomers connected to the steam drum and lower drum. To reduce
standby losses, the vessel is insulated with a fiberglass blanket and removable steel jacket.
Complete with an integral burner for Natural Gas, the complete burner/boiler package is UL and cUL
Approved, listed, and labeled.
Standard Equipment
The standard boiler/burner package is described below. Optional controls, trim, and devices may be
added to meet project requirements, and some of those options are noted, following this standards
list.
1. Boiler
A. Designed, constructed, and hydrostatically tested in accordance with the A.S.M.E. Boiler and Pressure
Vessel Code. The complete vessel is mounted on a structural steel frame.
B. Upper drum includes a hand hole in the rear head for drum water side inspection.
C. Connections on steam units are included for the following:
•Feedwater Makeup w/internal dispersion tube.
•Surface Blowoff.
•Steam Supply.
•Safety Relief Valve.
D. Connections on hot water units are included for supply water and internal circulating pump.
E. Lower Drum includes hand holes at each end for waterside inspection. A drain/blowoff tapping is provided
at the front, bottom centerline.
F. Refractory is limited to the furnace floor, lower drum, and burner throat tile. High temperature insulation
is installed on the front water wall and furnace access door.
G. Two lifting eyes are provided on the top centerline of the upper drum for ease of installation.
H.Furnace inspection/access door is provided in the rear via a removable access plug.
I. The exhaust gas vent is located at the top front centerline of the boiler. A stack thermometer is shipped
loose for field installation by the installing contractor into the stack.
J. The complete vessel is fully insulated [2" fiberglass blanket] under a preformed, sectional steel jacket.
K. Factory painted using hard-finish enamel.
3
BOILER BOOK M5M
B. Burner shall be equipped to burn Natural Gas and shall be the high radiant surface combustion pre mix
design.
C. To ensure proper air for pre purge and combustion is provided by the fan, a combustion air proving switch
is provided
D. Responding to system demand from the drum mounted sensor the burner operates in the full modulation
firing mode. Ultra-violet [UV] flame scanner is provided for flame presence during firing.
E. An Ignition transformer is provided.
F. Pilot is spark ignited gas.
G. Gas Train consists of the following:
•Primary gas shutoff valve with integral proof of closure switch.
•A manual shutoff valve located ahead of the primary gas valve.
•A plugged leakage test connection and a second manual shutoff valve for tightness
checking of the primary shutoff valve.
•Separate Gas Pressure Regulators for the pilot train and main gas train.
•Low Gas Pressure and High Gas Pressure Switches.
•A second motorized gas valve is provided in addition to the primary valve on size 6000
units.
The pilot gas train includes a manual shutoff valve and solenoid shutoff valve.
4
BOILER BOOK M5M
Alarm Horn
ALWCO reset (optional)
DEMAND switch
(remote/off/local)
Optional Equipment
For more detailed information on optional equipment, contact the local Cleaver-Brooks authorized
representative. In summary, options could include the following:
5
BOILER BOOK M5M
Insurance/Codes
The boiler package can be equipped to meet various insurance or code requirements. Some of these
insurance/code requirements are:
1. Factory Mutual [FM Global] - Recommended guidelines as described by FM pertain to boilers rated at
greater than 2.5 MMBTU/hr input on gas and 2.8 MMBTU/hr input on oil. Boilers that are labeled and
tested in accordance with an independent testing lab such as UL or CSA and are below these inputs are
exempt from these recommendations.
The Model M5M boiler is UL listed and labeled.
2. XL GAP [Formerly GE GAP/IRI] Recommended guidelines as described by XL GAP pertain to boilers rated
at 400,000 Btu/hr input to 12.0 MMBTU/hr input. For these boilers, the requirements are the same as for
A.S.M.E CSD-1 requirements. Above 12.0 MMBTU/hr input, the requirements defer to the NFPA 85
standards for single burner boilers.
3. A.S.M.E. CSD-1 - Recommended guidelines as described by this Code pertain to boilers rated at 400,000
Btu/hr input to 12.0 MMBTU/hr input. Above 12.0 MMBTU/hr input, the requirements defer to the NFPA
85 standards for single burner boilers.
6
BOILER BOOK M5M
7
BOILER BOOK M5M
U Base to Steam Nozzle 15# 73.5 73.5 73.5 76.5 76.5 76.5 76.5 76.5
Base to Steam Nozzle 150# 73.5 73.5 73.5 73.5 73.5 76.5 76.5 76.5
V Base to Top of Control Panel 76.5 76.5 76.5 76.5 76.5 76.5 76.5 76.5
W Drum Centerline Spacing 54 54 54 54 54 54 54 54
X Base to Lower Drum Center 8.25 8.25 8.25 8.25 8.25 8.25 8.25 8.25
Connections
AA O.D. Stack Sleeve Connection 12 12 12 12 12 16 16 16
EE Bottom Blowdown 15# 1 1/4 1 1/4 1 1/4 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2
Bottom Blowdown 150# 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4
8
BOILER BOOK M5M
9
BOILER BOOK M5M
Input Max. BTU/Hr. 2,000,000 2,500,000 3,000,000 3,500,000 4,000,000 4,500,000 5,000,000 6,000,000
KCAL/Hr. 504,000 630,000 756,000 882,000 1,008,000 1,134,000 1,260,000 1,512,000
Natural Gas (1000 Btu/ FT3/Hr 2000 2500 3000 3500 4000 4500 5000 6000
ft3)
Natural Gas M3/Hr 57 71 85 99 113 127 142 170
Steam Capacity (from lb/hr 1656 2070 2484 2898 3312 3726 4105 4933
and at 212 deg F) kg/hr 751 939 1127 1315 1502 1690 1862 2238
MAWP PSI 15/150 15/150 15/150 15/150 15/150 15/150 15/150 15/150
BAR 1.0/10.3 1.0/10.3 1.0/10.3 1.0/10.3 1.0/10.3 1.0/10.3 1.0/10.3 1.0/10.3
Water Content (Stan- Gallons (U.S.) 65.3 90.0 90.0 112.9 112.9 139.4 139.4 163.0
dard) Gallons (Imp.) 54.4 74.9 74.9 94.0 94.0 116.1 116.1 135.7
Liters 247.3 340.5 340.5 427.3 427.3 527.8 527.8 616.9
Water Content (Low Gallons (U.S.) 31.9 43.8 43.8 54.6 54.6 68.0 68.0 74.7
Water Volume) Gallons (Imp.) 26.6 36.5 36.5 45.5 45.5 56.6 56.6 62.2
Liters 120.9 165.9 165.9 206.8 206.8 257.3 257.3 282.8
Weight w/o Water Pounds 3,100 3,700 3,700 4,100 4,100 4,700 4,700 5,400
(Shipping) Kg 1406 1678 1678 1860 1860 2132 2132 2449
Operating Weight (Stan- Pounds 3,644 4,450 4,450 5,041 5,041 5,862 5,862 6,758
dard) Kg 1653 2018 2018 2287 2287 2659 2659 3066
Operating Weight (Low Pounds 3,366 4,065 4,065 4,555 4,555 5,266 5,266 6,023
Water Volume) Kg 1527 1844 1844 2066 2066 2389 2389 2732
Flue Gas Mass Flow @ lb/hr 2266 2832.5 3399 3965.5 4532 5098.5 5665 6798
100% Firing (Natural kg/h 1028 1285 1542 1799 2056 2313 2570 3084
Gas)
10
BOILER BOOK M5M
11
BOILER BOOK M5M
12
BOILER BOOK M5M
13
BOILER BOOK M5M
Input Max. BTU/Hr. 2,000,000 2,500,000 3,000,000 3,500,000 4,000,000 4,500,000 5,000,000 6,000,000
KCAL/Hr. 504,000 630,000 756,000 882,000 1,008,000 1,134,000 1,260,000 1,512,000
Natural Gas (1000 FT3/Hr 2000 2500 3000 3500 4000 4500 5000 6000
Btu/ft3)
Natural Gas M3/Hr 57 71 85 99 113 127 142 170
Output 100% Firing BTU/Hr. 1,630,000 2,037,500 2,445,000 2,852,500 3,260,000 3,667,500 4,075,000 4,890,000
KCAL/Hr. 410,760 513,450 616,140 718,830 821,520 924,210 1,026,900 1,232,280
MAWP PSI 140 140 140 140 140 140 140 140
BAR 9.7 9.7 9.7 9.7 9.7 9.7 9.7 9.7
Operating Temp., Max. °F 250 250 250 250 250 250 250 250
°C 121 121 121 121 121 121 121 121
Weight w/o Water Pounds 3,100 3,700 3,700 4,100 4,100 4,700 4,700 5,400
(Shipping) Kg 1406 1678 1678 1860 1860 2132 2132 2449
Operating Weight Pounds 3,900 4,792 4,792 5,458 5,458 6,366 6,366 7,342
Kg 1769 2174 2174 2476 2476 2888 2888 3330
Standby Heat Loss BTU/Hr 4,000 5,000 6,000 7,000 8,000 9,000 10,000 12,000
Watts 1172 1465 1758 2051 2344 2637 2930 3516
Flue Gas Mass Flow @ lb/hr 2266 2832.5 3399 3965.5 4532 5098.5 5665 6798
100% Firing (Natural kg/h 1028 1285 1542 1799 2056 2313 2570 3084
Gas)
14
BOILER BOOK M5M
APPLICATION DATA
The following information is provided for the Model M5M boiler. Additional information may be obtained from
your local Cleaver-Brooks authorized representative.
Emissions
Controlled emissions shall be <20 PPM NOx and <50 PPM CO for natural gas fuel operation without the use of
FGR [Flue Gas Recirculation].
Feedwater
Steam boilers require make-up water for steam production. This make-up can be a combination of condensate
return and raw make-up, 100% condensate return or 100% raw make-up. Proper treatment of make-up water
and boiler water is essential to the longevity and performance of the boiler. Table 9 depicts the rate of make-up
required and Table 10 shows the recommended water quality guidelines.
As a minimum, raw make-up should be piped into a water softener and then to a feed tank, which also can be
the container that receives the system condensate returns. Chemical feed is recommended to be fed via a quill
into the water make-up line feeding the boiler.
Blowdown
As steam is produced; unwanted solids are left behind in the boiler water and become concentrated within the
vessel. If these constituents are allowed to adhere to the heat transfer surfaces, they will impede the flow of
energy into the water. Their removal requires proper blowdown that will include bottom and possibly surface
blowoff. For proper TDS control, surface blowoff with a TDS monitoring device is recommended. Local codes will
dictate the manner of treating the blowdown affluent.
Boiler Stacks
General - The Model M5M boiler operates with a positive vent pressure and a vent gas temperature that is non-
condensing. Therefore, the stack must be a positive pressure design.
Proper design and installation of the flue gas venting is critical to efficient and safe operation of the burner. The
vent should be designed with proper supports and clearances from combustible materials. Use insulated vent
pipe spacers where the vent passes through walls and roofs.
The design of the stack and breeching must provide the required draft at each boiler stack connection. Although
constant pressure at the flue gas outlet is not required, it is necessary to size the breeching and stack to limit flue
gas pressure variations. Consideration of the draft must be given where lengthy runs of breeching are employed
or unusually high stacks. Please note: the allowable pressure range for design of the stack and breeching is
negative 0.25" w.c. (-62 Pa) to a positive 0.25" w.c. (+62 Pa) for proper light offs and combustion. NOTE: This
pressure range does not pertain to the boiler room, that is, the boiler room must be neutral or slightly positive,
never negative when using air from the boiler room for combustion.
When two or more Model M5M boilers are connected to a common breeching/stack, one should evaluate the
affects of pressure variations that may occur during boiler sequencing while boilers are firing. It may be
determined that some type of mechanical draft system be employed to ensure proper draft at each boiler is
maintained.
Combustion Air - An adequate volume of uncontaminated air to support proper combustion and equipment
ventilation must be supplied. Air shall be free of chlorides, halogens, fluorocarbons, construction dust or other
15
BOILER BOOK M5M
Determine the area of the boiler room air supply openings for [2] size 4500 Model M5M boilers at 750 feet
elevation; each have a rating of 107 boiler horsepower. The air openings will be 5 feet above the floor level.
The total boiler horsepower (bhp): 107 x 2 = 214 bhp.
From (6.C.) above, total air required = 214 bhp x 10 = 2140 cfm.
Air Velocity: From (7.A.) above = 250 fpm.
Area required: From the formula in (5) above, 2140 cfm/250 fpm = 8.56 square feet total.
Area opening: 8.56 divided by 2 = 4.28 ft2 per opening (2 required).
Consult local codes, which may supersede these requirements.
Gas Piping
General - The Model M5M boiler requires appropriate gas supply pressure and volume for proper operation and
long burner life. The gas requirements specified in this section must be satisfied to ensure efficient and stable
combustion. Installation must follow these guidelines and of the local authorities that have installation
jurisdiction.
Gas Train Components - Model M5M boilers are equipped with a gas train that meets the requirements of UL as
standard. These components also comply with the recommendations of FM, XL GAP [formerly IRI/GE GAP] and
ASME CSD-1. The gas train and its components have been designed and tested to operate for the highest
combustion efficiency.
Gas Pressure Requirements - For proper and safe operation, each Model M5M boiler requires a stable gas
pressure supply. The pressure requirements are listed in the gas pressure table.
16
BOILER BOOK M5M
Gas Piping - Model M5M units are standardly equipped with a gas pressure regulator. If upstream
pressure to the standard regulator will be greater than 3 psig, an additional upstream regulator
should be provided with a pressure relief valve.
For buildings or boiler rooms with gas supply pressure exceeding 28" w.c., a “full lockup” type
regulator is recommended along with proper overpressure protection. In addition to the regulator, a
plug type or “butterball” type gas shutoff cock should be provided upstream of the regulator for use
as a service valve. This is also required to provide positive shutoff and isolate the boiler gas train
during gas piping tests.
Drip legs are required on any vertical piping at the gas supply to each boiler so that any dirt, weld
slag, or debris can deposit in the drip leg rather than into the boiler gas train. The bottom of the drip
leg should be removable without disassembling any gas piping. The connected piping to the boiler
should be supported from pipe supports and not supported by the boiler gas train or the bottom of
the drip leg.
All gas piping and components to the boiler gas train connection must comply with NFPA 54, local
codes, and utility requirements as a minimum. Only gas approved fittings, valves, or pipe should be
used. Standard industry practice for gas piping is normally Schedule 40 block iron pipe and fittings.
Gas Supply Pipe Sizing - For proper operation of a single unit or multiple units, we recommend that
the gas pipe be sized to allow no more than 0.3" w.c. pressure drop from the source [gas header or
utility meter] to the final unit location. The gas supplier [utility] should be consulted to confirm that
sufficient volume and normal pressure are provided to the building at the discharge side of the gas
meter or supply pipe. [For installations of new boilers into an existing building, gas pressure should
be measured with a manometer to ensure sufficient pressure is available].
A survey of all connected gas using devices should be made. If appliances other than the boiler are
connected to the gas supply line, then a determination should be made of how much flow volume
[cfh = cubic feet per hour] will be demanded at one time and the pressure drop requirements when
all appliances are operating.
The total length of gas piping and all fittings must be considered when sizing the gas piping. Total
equivalent length should be calculated from the utility meter or source to the final connection. As a
minimum guideline, gas piping Tables 7 and 8 should be used. The data in these tables is from the
NFPA source book, 2006 edition.
17
BOILER BOOK M5M
18
BOILER BOOK M5M
Hot Water
For hydronic heating, maximum circulating rates are shown in Table 9 & 10 relative to system
temperature drop. To prevent the heated water from flashing to steam, minimum overpressure is
noted in Table 10A below. As a recommendation, a low boiler water pressure control can be provided
to alert the boiler room attendant that overpressure of the boiler has decreased below the minimum
setting.
Table 9: Model M5M Hot Water – Pressure Drop and Maximum Flow Rate
MODEL NO. Delta T = 20º F Delta T = 30º F Delta T = 40º F Delta T = 50º F
DP GPM DP GPM DP GPM DP GPM
2000 0.96 165.2 0.43 110 0.24 83 0.16 66
2500 1.49 206.5 0.67 138 0.38 103 0.24 83
3000 2.13 247.6 0.95 165 0.54 124 0.34 99
3500 1.32 289 0.59 193 0.34 145 0.22 116
4000 1.72 330.8 0.77 220 0.44 166 0.28 132
4500 2.18 372.1 0.97 248 0.55 186 0.35 149
5000 2.68 413.4 1.20 276 0.68 207 0.43 166
6000 3.86 496 1.72 331 0.97 248 0.63 199
NOTE: Return water temperature must be >140F.
Table 10: Model M5M Hot Water – Maximum Circulating Rate/Temperature Drop
MODEL NO. SYSTEM TEMPERATURE DROP [0 F]
(HP) 10 20 30 40 50 60 70 80 90 100
MAXIMUM CIRCULATING RATE - GPM
2000 (47) 330 165 110 83 66 55 47 41 37 33
2500 (59) 413 206 138 103 83 69 59 52 46 41
3000 (71) 494 248 165 124 99 83 71 62 55 50
3500 (83) 578 289 193 145 116 97 83 72 64 58
4000 (95) 661 331 220 166 132 110 95 83 74 66
4500 (107) 740 372 248 186 149 124 106 93 83 74
5000 (119) 826 413 275 207 165 138 118 103 92 83
6000 (143) 992 496 330 248 198 166 142 124 110 99
NOTE: Return water temperature must be >140F.
HP = Horsepower
Table 10A: Boiler Operating temperature and minimum overpressure
Outlet Water Temperature Degrees F (C) Minimum System Operating Pressure Boiler Design Pressure
160 – 180 (71 – 82) 12 (0.83) 160 (11.03)*
181 – 185 (83 – 85) 15 (1.03) 160 (11.03)*
186 – 195 (86 – 91) 18 (1.24) 160 (11.03)*
196 – 210 (92 – 99) 20 (1.38) 160 (11.03)*
211 – 220 (100 – 104) 22 (1.52) 160 (11.03)*
221 – 230 (105 – 110) 25 (1.72) 160 (11.03)*
231 – 240 (111 – 115) 30 (2.07) 160 (11.03)*
241 – 250 (116 – 121) 43 (2.96) 160 (11.03)*
251 – 260 (122 – 126) 55 (3.79) 200 (13.79)**
261 – 270 (127 – 132) 70 (4.83) 200 (13.79)**
271 – 280 (133 – 137) 82 (5.65) 200 (13.79)**
281 – 290 (138 – 143) 100 (6.9) 200 (13.79)**
291 – 300 (144 – 149) 112 (7.72) 200 (13.79)**
301 – 310 (150 – 154) 124 (8.55) 200 (13.79)**
311 – 320 (155 – 160) 140 (9.65) 200 (13.79)**
321 – 330 (161 – 165) 160 11.03) 200 (13.79)**
331- 340 (166 – 171) 170 (11.72) 250 (17.24)**
341 – 350 (172 – 176) 180 (12.41) 250 (17.24)**
355 (179) 190 (13.10) 250 (17.24)**
*Boiler built per ASME Code Section IV For Heating Boilers bearing the “H” Stamp
**Boiler built per ASME Code Section I For Power Boilers bearing the “S” Stamp.
19
BOILER BOOK M5M
pH 8.5 - 10.5
Iron 0.1 ppm
Oxyen 0.007 mg/liter
Silica < 200 ppm
Specific Conductivity 3500 umho/cm
Total Dissolved Solids 2500
Suspended Solids 15 ppm
Total Alkalinity 300 ppm as CaCO3
20
BOILER BOOK M5M
21
BOILER BOOK M5M