ML201711 Conext MPPT 80 600 Installation Guide 975 0540-01-01 Rev F ENG
ML201711 Conext MPPT 80 600 Installation Guide 975 0540-01-01 Rev F ENG
http://solar.schneider-electric.com
Conext™ MPPT 80 600
Solar Charge Controller
Installation Guide
http://solar.schneider-electric.com
Copyright © 2013-2017 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric
Industries SAS or its affiliated companies.
Exclusion for Documentation
UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER
(A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION
PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION;
(B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT,
INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY
SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK; AND
(C) REMINDS YOU THAT IF THIS DOCUMENT IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN
TO MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS
CONTAINED WITH THE ENGLISH LANGUAGE VERSION WHICH IS POSTED AT HTTP://SOLAR.SCHNEIDER-ELECTRIC.COM.
Scope
This Guide provides safety guidelines, detailed planning and setup information,
procedures for installing the charge controller, and information about
troubleshooting. It does not provide details about particular brands of
photovoltaic (PV) panels or batteries.
Audience
This Guide is intended for qualified personnel planning to install the charge
controller. Qualified personnel have training, knowledge, and experience in:
Organization
This Guide is organized into three chapters and one appendix:
Conventions Used
This Guide uses the term charge controller to refer to the Conext MPPT 80 600
Solar Charge Controller.
975-0540-01-01 F iii
Related Information
You can find information about using the charge controller in the Conext MPPT 80
600 Solar Charge Controller Operation Guide (Document Part Number
975-0560-01-01). It is provided with the charge controller and is also available at
www.schneider-electric.com.
You can find more information about Schneider Electric as well as its products
and services at http://solar.schneider-electric.com.
iv 975-0540-01-01 F
Read these instructions carefully and look at the equipment to become familiar
with the device before trying to install, operate, service or maintain it. The
following special messages may appear throughout this bulletin or on the
equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this signal word.
975-0540-01-01 F v
Safety Information
1. Before using the charge controller, read all instructions and cautionary
markings on the unit, the batteries, and all appropriate sections of this
manual.
2. Use of accessories not recommended or sold by the manufacturer may result
in a risk of fire, electric shock, or injury to persons.
3. The charge controller is designed to be permanently connected to your AC
and DC electrical systems. The manufacturer recommends that all wiring be
done by a certified technician or electrician to ensure adherence to the local
and national electrical codes applicable in your jurisdiction.
4. To avoid a risk of fire and electric shock, make sure that existing wiring is in
good condition and that wire is not undersized. Do not operate the charge
controller with damaged or substandard wiring.
5. Do not operate the charge controller if it has been damaged in any way.
6. This unit does not have any user-serviceable parts. Do not disassemble the
charge controller except where noted for connecting wiring and cabling. See
your warranty for instructions on obtaining service. Attempting to service the
unit yourself may result in a risk of electrical shock or fire. Internal capacitors
remain charged after all power is disconnected.
7. To reduce the risk of electrical shock, disconnect both AC and DC power
from the inverter before attempting any maintenance or cleaning or working
on any components connected to the charge controller. Putting the unit in
Standby mode will not reduce this risk.
8. The charge controller must be provided with an equipment-grounding
conductor.
9. Do not expose this unit to rain, snow, or liquids of any type. This product is
designed for indoor use only. Damp environments will significantly shorten
the life of this product and corrosion caused by dampness will not be
covered by the product warranty.
10. To reduce the chance of short-circuits, always use insulated tools when
installing or working with this equipment. Do not leave tools inside the unit.
11. Remove personal metal items such as rings, bracelets, necklaces, and
watches when working with electrical equipment.
vi 975-0540-01-01 F
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E or CSA Z462.
• This equipment must only be installed and serviced by qualified electrical
personnel.
• Never operate energized with covers removed.
• Energized from multiple sources. Before removing covers identify all
sources, de-energize, lock-out, and tag-out and wait 2 minutes for circuits
to discharge.
• Always use a properly rated voltage sensing device to confirm all circuits
are de-energized.
• Thoroughly inspect the charge controller prior to energizing. Verify that no
tools or materials have been inadvertently left behind.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Disconnect positive and negative PV conductors before servicing. PV
conductors are to be treated as Hazardous Live and must be
disconnected.
• Normally GROUNDED conductors may be UNGROUNDED and
ENERGIZED when a GROUND FAULT is indicated on the front panel. Must
be serviced by qualified personnel.
Failure to follow these instructions will result in death or serious injury.
WARNING
LIMITATIONS ON USE
Do not use the charge controller with life support equipment or other medical
equipment or devices.
Failure to follow these instructions can result in death or serious injury.
975-0540-01-01 F vii
CAUTION
BURN HAZARD
Do not touch the charge controller’s heatsink during operation or before
servicing immediately after ceasing operation.
Failure to follow these instructions can result in injury.
NOTICE
LIGHTNING PROTECTION
To protect the charge controller’s insulation and conductors from damage due
to a sudden over-voltage surge such as a lightning strike, install a DC-rated
lightning arrestor on the DC input line.
Failure to follow these instructions can damage the equipment.
viii 975-0540-01-01 F
DANGER
HAZARD OF ELECTRIC SHOCK, BURN, FIRE, AND EXPLOSION
Batteries contain corrosive electrolyte and can give off explosive gases.
Battery circuits present a shock and energy hazard. Observe proper
precautions when working with batteries and battery circuits, including:
• Always wear eye protection when working with batteries.
• Wear rubber gloves and boots when handling batteries.
• Remove all jewellery before performing electrical work.
• Install batteries in a well-ventilated area to help prevent the possible buildup of
explosive gases.
• Do not dispose of batteries in a fire.
• Do not open or damage the batteries. Exposure to electrolyte is harmful to eyes
and skin. It is toxic.
• Do not mix battery types.
• Do not smoke in the vicinity of a battery.
• Use insulated tools when working with batteries.
• When connecting batteries, always verify proper voltage and polarity.
• Do not short-circuit the battery.
• Always use proper lifting techniques when handling batteries.
• Determine if the battery is inadvertently grounded and if so, remove the source
from ground. Contact with any part of a grounded battery can result in electrical
shock. Remove these grounds during installation and maintenance.
• When using Lithium Ion batteries, ensure that the battery pack being used
includes a certified Battery Management System (BMS) with safety protocols.
Failure to follow these instructions will result in death or serious injury.
For full installation instructions and safety information, see the documentation
provided with the batteries. Consult the MSDS for the batteries for first aid
procedures, emergency procedures, and clean-up instructions.
975-0540-01-01 F ix
CAUTION
Unauthorized changes or modifications to the equipment could void the user’s
authority to operate the equipment.
x 975-0540-01-01 F
1 Introduction
Features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–2
Charge Controlling - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–3
Typical Installation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1–3
2 Installation
Materials List and Tool Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–2
Required Accessories- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–3
PV Array Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–3
Mounting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–3
Choosing a Location - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–4
Removing the Wiring Compartment Cover - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–6
Removing Knockouts - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–7
Mounting the Charge Controller - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–9
PV Grounding- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10
Chassis Grounding - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10
Internal Ground Fault Protection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–10
Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–11
Connector Locations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–11
Wire Size and Over-current Protection Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–12
PV Current Rating - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–12
Minimum Wire Gauge - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–12
Over-current Protection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–12
Connecting the Charge Controller - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–14
Connecting Multiple PV Array Strings to One Unit - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–17
Connecting Multiple Units - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–18
Auxiliary Output Connections- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–19
Network Installation- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–20
Network Components - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–20
Network Layout - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–21
Connecting Network Cables Between Multiple Units - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–21
Installing the Battery Temperature Sensor- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–23
Commissioning- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–25
Conext SCP - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–25
Conext Config Tool - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–25
Setting the Device Number - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–26
Configuring Connections and Charger Settings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–27
Copying Settings to Another Charge Controller - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2–28
975-0540-01-01 F xi
3 Troubleshooting
Charge Controller Troubleshooting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–2
Replacing the Ground Fault Protection Fuse- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–4
Ground Faults in a Normally Ungrounded Array - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3–5
A Specifications
Electrical Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–2
MPPT Voltage Range - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–3
Operating Below the PV Array Voltage Full Power Range - - - - - - - - - - - - - - - - - - - - - - - - - - A–3
Default Battery Charger Settings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–5
Mechanical Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–5
Accessories- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–6
Conext Config Tool- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–6
Regulatory Approvals - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A–7
Index - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - IX–1
xii 975-0540-01-01 F
975-0540-01-01 F 1–1
Features
The Conext MPPT 80 600 Solar Charge Controller (charge controller) tracks the
maximum power point of a PV array to deliver the maximum available current for
optimum charging of batteries. The charge controller can be used with 24 VDC
and 48 VDC battery systems only.
Key product features include a 600 VDC maximum input voltage, a Fast Sweep™
MPPT tracking algorithm, and built-in ground fault protection. For information on
additional product features, see the Conext MPPT 80 600 Solar Charge Controller
Operation Guide (Document Part Number 975-0560-01-01).
The high input voltage operating range allows a high-voltage and low-current PV
array to be connected to the charge controller. A high-voltage PV array
configuration can eliminate the need for a combiner box and associated DC
circuit breakers as well as incorporate the use of smaller AWG wire for array
wiring. This simplified array configuration reduces wiring costs, installation labor
costs, and allows for long home-run wiring with minimal power loss.
The Fast Sweep MPPT algorithm frequently conducts a very fast sweep of the full
operational array voltage window to dynamically determine the array’s maximum
power point. This feature optimizes the high energy harvest of the solar array,
regardless of conditions such as temperature or shading.
The charge controller is equipped with built-in ground fault protection for a
negative, positive, or ungrounded PV array and is compatible with all PV module
manufacturers. The charge controller regulates the available power from a PV
source only. It is not designed to regulate power from other types of power
sources.
1–2 975-0540-01-01 F
Charge Controlling
The charge controller regulates the PV array current to an appropriate level for
24 V or 48 V batteries. It produces up to 80 amps of charging current for both
2560 watts at 24 V, or 4800 watts at 48 V.
The charge controller can be configured to use a two-stage (no float) or three-
stage charging algorithm. The charging algorithm assures that the battery is
optimally charged with the available amount of solar energy. See the Conext
MPPT 80 600 Solar Charge Controller Operation Guide for more information on
two-stage and three-stage charging as well as the different stages.
Typical Installation
A typical Conext XW+ installation (see Figure 1-1) with charge controller includes
the following Conext devices:
Conext
SCP
100 ADC
Conduit Box
PV Array
Typical PV array:
• 200–240 W modules
+ - + - + - + -
• 10–12 modules per string
• 4800 W maximum for 48 V
Battery Bank systems (2 strings)
• 2560 W maximum for 24 V
systems (1 string)
975-0540-01-01 F 1–3
975-0540-01-01 F 2–1
DANGER
HAZARD OF ELECTRIC SHOCK, BURNS, FIRE, AND EXPLOSION
Installation of this equipment should only be planned and performed by
qualified personnel in accordance with all applicable installation codes. See
“Audience” on page iii for the definition of qualified personnel.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF ELECTRIC SHOCK, BURNS, FIRE, AND EXPLOSION
RISK OF EQUIPMENT DAMAGE
Unsafe conditions and damage to the charge controller could result if the
instructions and electrical, physical, and environmental installation
specifications in this Guide are not obeyed.
Failure to follow these instructions can result in death or serious injury.
2–2 975-0540-01-01 F
Required Accessories
A Conext System Control Panel (SCP) is required for installation of the charge
controller.
However, in place of the SCP, a Conext ComBox (ComBox) can be used if you
would like to configure and monitor the charge controller through a web-interface
on a PC or laptop.
PV Array Requirements
NOTE
The following information only provides general guidelines. PV array
installation is subject to installation codes and, in some areas, inspection and
approval by the authority having jurisdiction. For example, installations in the
United States must be compliant with NEC and, in particular, Article 690.
WARNING
HAZARD OF ELECTRIC SHOCK AND FIRE
The PV array voltage must never exceed 600 VOC, including the local
temperature correction factor required by the applicable electrical codes. The
PV array maximum circuit current must not exceed 35 A, including the
multiplier required by the applicable electrical codes. For example, the NEC
and the CEC require that the array STC Isc must not exceed 28 A (28 A x 125%
= 35 A).
Failure to follow these instructions can result in death or serious injury.
Mounting
The instructions in this chapter are applicable to a typical stand-alone
installation. Installation procedures will vary according to your specific
application. For special applications, consult a qualified Renewable Energy
System Installer or a Certified Dealer.
975-0540-01-01 F 2–3
Choosing a Location
WARNING
HAZARD OF ELECTRIC SHOCK, BURN, FIRE, AND EXPLOSION
RISK OF EQUIPMENT DAMAGE
The charge controller must be mounted vertically and installed indoors in a
dry, protected location away from flammable materials, sources of high
temperature, moisture, and vibration. The location must also be sheltered from
direct sunlight, dust, and wind-blown debris.
Failure to follow these instructions can result in death or serious injury.
When choosing a wall to install the charge controller, choose a wall that is not
considered a flammable material such as concrete, brick, or metal.
WARNING
HAZARD OF EXPLOSION
Do not install the charge controller in a sealed compartment containing
batteries.
Failure to follow these instructions can result in death or serious injury.
NOTICE
CHARGE CONTROLLER DAMAGE
The charge controller can overheat if installed in a sealed, indoor enclosure.
Do not install the charge controller in a sealed compartment.
Failure to follow these instructions can result in equipment damage.
To help ensure optimal and safe operation, make sure there is adequate
clearance around the charge controller. See Table 2-1 and Figure 2-1. If
clearances are reduced below these minimums, charging performance might be
impaired.
2–4 975-0540-01-01 F
Event ! Event !
E q ualize E q ualize
975-0540-01-01 F 2–5
DANGER
HAZARD OF ELECTRIC SHOCK AND ENERGY
Before removing the wiring compartment cover, make sure all electrical power
sources have been disconnected for at least two minutes. Before energizing
the charge controller, make sure the wiring compartment cover has been
replaced and all fasteners are in place.
Failure to follow these instructions will result in death or serious injury.
Before mounting, remove the wiring compartment cover to access the mounting
holes and the wiring terminals. The wiring compartment cover is secured with
two screws on the front of the charge controller (see Figure 2-2).
The wiring compartment (see Figure 2-3) contains a flexible Lexan™ barrier used
to segregate low voltage battery and high voltage PV wire routing. In some
instances, you must manipulate this barrier to provide a passage for the battery
or PV cables which run through the wiring compartment. In this scenario, you
must take care to avoid intermingling the high voltage PV and low voltage battery
wires.
Lexan barrier
2–6 975-0540-01-01 F
Removing Knockouts
Fourteen knockouts are provided for conduit or cable entry into the charge
controller (see Figure 2-4 and Figure 2-5):
• Three single (one on each side and one on the back) for battery wires:
1.73 in. (44.0 mm).
• Two single on the back and six dual on the sides (three on each side) for PV
array wires: 1.38 in. (35.0 mm).
• Three dual (one on each side and one on the back) for routing BTS and
network cables: 1.11 in. (28.2 mm).
When removing knockouts, make sure no metal shavings or fragments fall into
the wiring compartment. Use bushings or conduits to help protect the wiring from
damage from the rough edges around the knockout holes.
NOTICE
CHARGE CONTROLLER DAMAGE
Do not drill, cut, or punch holes in the charge controller. Use only the
knockouts provided for conduit entry.
Failure to follow these instructions can result in equipment damage.
701.0 (2
150.0 (5.90)
6.5 (0.25)
28.2 (1.11)/ 22.2(0.87)
DUAL KNOCKOUT
146.5 (5.18)
102.5 (4.03)
82.8 3.26)
26.4 (1.03)
35.0 (1.38)
29.0 (1.14)
22.8 (0.90)
62.3 (2.45)
22.8 (0.90)
975-0540-01-01 F 2–7
Charging
Event !
Equalize
673.4 (26.5)
764.0 (30.0)
44.0 (1.73) KNOCKOUT
219.7 (8.65)
2–8 975-0540-01-01 F
¼"
(6 mm)
When choosing a wall to install the solar charge controller, choose a wall that
is not considered a flammable material such as concrete, brick, or metal.
975-0540-01-01 F 2–9
PV Grounding
You can configure the charge controller to be compatible with either negative-
grounded, positive-grounded, or ungrounded (floating) PV arrays. For
information about routing the array ground connection, see Figure 2-9.
Chassis Grounding
For ground conductor requirements for your specific installation, consult your
local electrical code. The recommended size of the chassis ground conductor is
#8 AWG (10 mm2)1.
Grounded Arrays For grounded arrays, the charge controller has two PV ground fault protection
fuse holders (rated 600 VDC, 1 A maximum) located inside the wiring
compartment.
Ungrounded For ungrounded (floating) arrays, the charge controller detects the impedance
(Floating) Arrays between the array and ground, and it indicates a fault if the resistance is too low.
DANGER
HAZARD OF ELECTRIC SHOCK AND FIRE
• Do not ground either PV conductor outside of the unit.
• Grounded arrays:
Install a fuse in the correct holder: (+) or (–). Replace the fuse with the
same type and rating (Littelfuse KLKD 1 or equivalent). Fuses must be
replaced by qualified service personnel only.
• Ungrounded (floating) arrays:
Leave both fuse holders empty.
Failure to follow these instructions will result in death or serious injury.
1.Based on the NEC (NFPA 70) Article 250 for 100 A maximum battery fuse.
2–10 975-0540-01-01 F
Ground fault
protection fuse
holders
Chassis ground
terminals (4)
Wiring
The following sections provide information about wiring.
Connector Locations
Terminal connectors for DC wiring are located inside the wiring compartment.
Labels above the DC wiring terminals identify all the connection points. See
Figure 2-8.
COM NO NC
B_ATT E R Y
+ NE G. GND P V . P OS . G ND PV.
PV- PV+
T E R MIN AL T OR QU E T E R MIN AL T OR QU E
25 lbf.in ( 2.8 N m) 15 lbf.in ( 1.7 N m)
A label providing details on each connector and torque requirements for each
terminal is affixed to the inside of the wiring compartment cover plate.
975-0540-01-01 F 2–11
WARNING
HAZARD OF ELECTRIC SHOCK, ENERGY, AND FIRE
The wiring, over-current protection devices (fuses and circuit breakers), and
installation methods used must conform to all applicable code requirements.
Wiring must be protected from physical damage with appropriate methods
such as the use of conduit and strain relief clamps.
To prevent intermingling with hazardous voltage-level wiring, the BTS, auxiliary
output, and network cables must pass through a different conduit than the PV
and battery cables.
Failure to follow these instructions can result in death or serious injury.
PV Current Rating
The maximum PV array input current specification is 28 A Isc at STC. The gauge
of PV wiring must comply with applicable electrical code requirements and the
total array short circuit current, based on the published ISC rating of the PV
panels installed in the system.
Over-current Protection
WARNING
HAZARD OF ELECTRIC SHOCK, ENERGY, AND FIRE
Over-current protection must be provided, external to the unit, to protect the
PV and battery wiring. External disconnecting means must also be provided
for the PV and battery circuits. Consult applicable electrical codes to establish
the correct fuse or circuit breaker ratings and for required locations of
protection and disconnecting means.
Failure to follow these instructions can result in death or serious injury.
2–12 975-0540-01-01 F
Battery Circuit The DC-rated fuse or circuit breaker between the battery and the charge
controller must be rated—at minimum—100 A and must not exceed the
allowable over-current protection rating for the size of wire being used, in
accordance with applicable electrical codes.
PV Circuit
DANGER
HAZARD OF ELECTRIC SHOCK
The PV array will produce a hazardous voltage with even a small amount of
light. Appropriate measures must be taken to prevent electric shock.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF ELECTRIC SHOCK, ENERGY, AND FIRE
PV wiring must be done by qualified personnel and in accordance with local
electrical codes.
Failure to follow these instructions can result in death or serious injury.
For the PV-disconnect, Schneider Electric recommends using the Square-D 3100
series safety switch (H361 Fusible and HU361 Non-fusible).
When three or more PV array strings connected to one charge controller, each
string must be fused before being combined at the PV input terminal connector
inside the wiring compartment. See “Connecting Multiple PV Array Strings to One
Unit” on page 2–17 for more information.
You can use separate disconnect switches for each PV string and combine these
in the charge controller, as long as the following conditions are met:
975-0540-01-01 F 2–13
DANGER
HAZARD OF ELECTRIC SHOCK
Whenever a PV array is exposed to light, a shock hazard exists at the output
wires or exposed terminals. Open the array disconnect switch before making
the connections.
Failure to follow these instructions will result in death or serious injury.
1. Make sure the PV array disconnect and battery disconnect are turned off.
2. Install a cable clamp into each knockout being used.
NOTICE
REVERSE POLARITY DAMAGE
Before energizing the charge controller from either the PV array or from the
battery, check the polarity of all power connections. Positive (+) must be
connected to positive (+). Negative (–) must be connected to negative (–).
Failure to follow these instructions can result in equipment damage.
9. Connect a second positive (+) cable from the other side of the battery
disconnect to the positive (+) battery terminal.
10. Torque the charge controller’s battery terminals to 25 lbf.in (2.8 Nm) and the
PV terminals to 15 lbf.in (1.7 Nm). Allow some slack on the cables within the
charge controller and secure the wiring with strain reliefs or cable clamps.
2–14 975-0540-01-01 F
In general, the same rules apply for disconnect switches as for battery circuits:
they must be located in all ungrounded conductors. Requirements vary so
consult applicable codes.
NOTICE
LIGHTNING PROTECTION
To protect the charge controller’s insulation and conductors from damage due
to a sudden over-voltage surge such as a lightning strike, install a DC-rated
lightning arrestor on the DC input line.
Failure to follow these instructions can damage the equipment.
975-0540-01-01 F 2–15
For negative-grounded
The positive or negative of the PV array, install fuse here.
battery can be grounded
independent of the array grounding. For positive-grounded PV
array, install fuse here.
BAT
PV - PV +
CHASSIS
GROUND
To inverter
100 ADC
(typical)
Disconnect
(configuration will vary)
48 V battery bank
LEGEND
Ground Ground
DC Positive
DC Negative
Circuit Breaker
Grounding and disconnect locations will vary according to system design and local electrical codes.
Figure 2-9 Typical Wiring Diagram for a Negative-Grounded System (48 V Battery Bank Shown)
2–16 975-0540-01-01 F
WARNING
HAZARD OF FIRE
• As per applicable electrical codes, fuses are required when paralleling
(combining) more than two PV strings.
• Fuses must be installed in a combiner box or in a PV array disconnect
switch.
• These items are not provided with the charge controller.
Failure to follow these instructions can result in death or serious injury.
NOTICE
LIGHTNING PROTECTION
To protect the charge controller’s insulation and conductors from damage due
to a sudden over-voltage surge such as a lightning strike, install a DC-rated
lightning arrestor on the DC input line.
Failure to follow these instructions can damage the equipment.
975-0540-01-01 F 2–17
NOTICE
PV ARRAY AND CHARGE CONTROLLER DAMAGE
Make sure that each charge controller is correctly connected to its own PV
array(s) and that no wires are interconnected between charge controllers.
Failure to follow these instructions can result in equipment damage.
+ – + – + – + –
PV – PV + PV – PV + PV – PV + PV – PV +
Correct wiring—no Incorrect wiring—
interconnection systems are
between systems interconnected
Grounding not shown.
2–18 975-0540-01-01 F
WARNING
HAZARD OF ELECTRIC SHOCK AND FIRE
The auxiliary NO and NC dry contacts are rated up to 60 VDC and up to 8 A.
Do not expose the auxiliary contacts to voltages or currents higher than this
rating. Provide external over-current protection rated at 8 A maximum.
Failure to follow these instructions can result in death or serious injury.
BATTERY
_
+ NEG. GND PV. POS. GND PV.
PV- PV+
975-0540-01-01 F 2–19
Network Installation
The charge controller is a Xanbus-enabled device. Xanbus is a network
communications system which allows the charge controller to communicate
settings and status information to other Xanbus-enabled devices.
Network Components
A Xanbus network consists of the following components:
• Xanbus-enabled devices:
• Conext MPPT 80 600 Solar Charge Controller
• Conext XW+ inverter/charger
• Conext Automatic Generator Start
• Conext System Control Panel or Conext ComBox
• Xanbus power supply—an embedded power supply in the charge controller
provides up to 7 W of power to the Xanbus network to power one SCP and
AGS, not including the auxiliary supply.
To reduce tare losses at night, you can configure the charge controller to shut
off the Xanbus power supply after sunset. See “Disabling Power Supplies at
Night” in the Conext MPPT 80 600 Solar Charge Controller Operation Guide
for more information.
• Network cables—each Xanbus-enabled device is connected by a standard
Ethernet (CAT 5/CAT 5e) patch cable. Do not use crossover cable.
2–20 975-0540-01-01 F
Network Layout
Xanbus-enabled devices are connected with separate lengths of cable. The
devices at each end of the chain must have a terminator inserted into their open
network ports, as shown in Figure 2-13. Total cable length for the Xanbus network
must not exceed 131 feet (40 m).
BATTERY
_ BATTERY
_
+ NEG. GND PV. POS. GND PV. + NEG. GND PV. POS. GND PV.
PV- PV+ PV- PV+
Network
Cable to next device
terminator Conext MPPT 80 600
Solar Charge
Controller cable
WARNING
HAZARD OF ELECTRIC SHOCK
Do not route the network cables with the same conduit or panel as the PV or
battery input and output cables, and make sure the network cables are not
intermingled with other conductors in those systems.
Failure to follow these instructions can result in death or serious injury.
Dual knockouts on the back and sides of the charge controller are provided for
routing the Xanbus network cable (see Figure 2-4). See Figure 2-8 for the location
of the charge controller’s network ports.
975-0540-01-01 F 2–21
NOTE
• Connect only Xanbus-enabled devices. Although the cabling and
connectors used in this network system are the same as ethernet
connectors, this network is not an ethernet system.
• Do not connect one end of the network to the other to make a ring or loop.
1. Remove the wiring compartment cover from each charge controller (see
“Removing the Wiring Compartment Cover” on page 2–6).
2. Remove a knockout from the back or either side of the unit, and then install
an appropriately sized strain relief bushing for the network cable.
3. Connect the network cable to a network port in charge controller #1.
4. Route the cable to charge controller #2.
5. Connect the network cable to a network port in charge controller #2.
6. Connect another network cable to charge controller #2, and then route the
cable to the next device in the network.
7. Make sure the factory-supplied network terminators are inserted into the
empty network ports in the devices at the beginning and end of the network.
There should be no empty network ports in any of the charge controllers.
2–22 975-0540-01-01 F
Note: For all BTS compatible Xanbus-enabled devices in the system, at least one
BTS must be separately installed for each device type associated with a battery.
If there is a group of the same devices forming a multi-unit setup, only one BTS is
required per device type connected to the same battery (same DC association).
See the installation guide of each device for BTS installation instructions.
All networked Xanbus devices share battery temperature information. If there are
multiple battery banks and more than one BTS is used within the system, then the
highest reported temperature will be used as the battery temperature for the
temperature compensation value of the battery charge algorithm.
See Figure 2-8 for the location of the BTS port. Dual knockouts on the back and
sides of the charge controller are provided for routing the BTS cable (see Figure
2-4).
NOTE
If the sensor cable is damaged and the wires are shorted, the charge
controller registers a battery over temperature fault condition. If the BTS wires
have been cut, the charge controller assumes that the BTS is not connected. A
replacement BTS can be ordered from the manufacturer (part number
808-0232-02).
975-0540-01-01 F 2–23
3. Connect the ring terminal on the BTS directly to the negative battery terminal
or positive battery terminal, or use the adhesive backing on the sensor back
to attach the sensor to any side of the battery to be monitored. See
Figure 2-14.
If connecting to the battery terminal, make sure the BTS does not prevent the
power wiring from making the best possible contact with the battery terminal.
If using the adhesive backing, install the BTS on the side of the battery below
the electrolyte level. It is best to place the sensor between batteries and
place the batteries in an insulated box to reduce the influence of the ambient
temperature outside the battery enclosure.
WARNING
HAZARD OF ELECTRIC SHOCK
The BTS cable must not pass through the same conduit used for PV wiring and
battery cables.
Failure to follow these instructions can result in death or serious injury.
4. Pass the other end of the BTS cable through the knockout and strain relief
bushing on the charge controller, and then insert the BTS plug into the BTS
RJ-11 port. See Figure 2-15.
2–24 975-0540-01-01 F
+ –
Commissioning
Conext SCP
You must use the SCP to commission the charge controller. For information about
SCP navigation and menus, see the Conext MPPT 80 600 Solar Charge
Controller Operation Guide.
In place of the SCP, the Conext ComBox (ComBox) (Part Number 865-1055) can
also be used. The ComBox allows you to configure and monitor the charge
controller through a web interface on a PC or laptop. See the Conext ComBox
Owner’s Guide (Document Part Number 975-0679-01-01)
NOTE
You must use the SCP with firmware version 1.05.00 or higher for full compati-
bility with the charge controller. For information on updating your firmware,
contact customer service. The Conext Config Tool is required for upgrading.
Before you begin, make sure you have all important system information such as
the nominal battery voltage, battery type, and battery bank capacity available.
975-0540-01-01 F 2–25
2–26 975-0540-01-01 F
WARNING
HAZARD OF FIRE AND EXPLOSION
Battery charging settings must be configured by qualified personnel in
accordance with the battery manufacturer's recommended charging
instructions.
This section covers basic default settings. See the Conext MPPT 80 600 Solar
Charge Controller Operation Guide for additional configuration information
and details including setting descriptions and value ranges.
Failure to follow these instructions can result in death or serious injury.
1. On the Select Device menu, select XW MPPT80 xx, where xx is the device
number.
The Setup menu opens.
2. Press Enter to select Advanced Settings.
The Config menu opens.
3. Scroll to Multi Unit Config, and then press Enter.
The Multi menu opens.
4. Scroll to Connections, and then press Enter.
The Conn menu opens.
5. Configure PV input (PV In) and DC output or the battery bank (DC Conn). If the
system only has one battery bank, leave DC Conn at the default setting. The PV In
setting allows you to differentiate which array is going to which charge controller.
This setting is used for status reporting only, not for any internal controls. Setting PV
In to a non-default value is optional.
6. Press Exit until the Config menu is displayed.
7. Scroll to Charger Settings, and then press Enter.
The Chgr menu opens.
8. Set the battery type (Batt Type), battery capacity (Batt Capacity), and any
other charger settings required for your system. If you select Custom for the battery
type, you can further configure bulk, absorption, float, and other settings for the
charge cycle in the Custom Settings menu that appears.
9. While in the Chgr menu, make sure the nominal battery voltage (Batt Voltage) is
set correctly. The default value is 48 V. If your system is a 24 V battery system, then
change it to 24 V.
10. Press Exit until the Select Device menu is displayed.
975-0540-01-01 F 2–27
WARNING
HAZARD OF FIRE AND EXPLOSION
• Do not copy settings from one charge controller to another unless the
battery banks are identical: same size, type, and so on.
• See the Conext MPPT 80 600 Solar Charge Controller Operation Guide for
additional configuration information and details including setting
descriptions and value ranges.
Failure to follow these instructions will result in death or serious injury.
Settings that are copied from one charge controller to another are:
• Batt Type
• Batt Capacity
• Max Chg Rate
• Charge Cycle
• ReCharge Volts
• Absorb Time
• Default Batt Temp
• Batt Voltage
• DC Conn
• Custom battery settings (if Custom battery type selected) including Eqlz
Support, Eqlz Voltage, Bulk Voltage, Absorb Voltage, Float
Voltage, and BattTempComp.
If you are commissioning multiple charge controllers, follow these steps to copy
the settings from the configured charge controller to the other charge controllers:
1. On the Select Device menu, select the next charge controller for
configuration.
The Setup menu opens.
2. Press Enter to select Advanced Settings.
The Config menu opens.
3. Scroll to Copy from, and then press Enter to select the charge controller
from which you want to copy. Scroll to select the charge controller with the
device number that matches the first charge controller you configured, and
then press Enter again.
The settings are automatically copied from the selected charge controller.
2–28 975-0540-01-01 F
NOTE
The Copy from command will not give you any indication that it has
completed its task. To check that the charger settings have been copied
properly, view some of the settings you originally configured.
If the PV array voltage exceeds the minimum start voltage, the charge controller
begins charging and the On/Charging LED starts flashing.
If the PV array voltage is not above the start voltage, the charge controller is
powered but not charging. The On/Charging LED stays solid green.
975-0540-01-01 F 2–29
975-0540-01-01 F 3–1
Table 3-1 lists possible problems that could arise with the charge controller.
3–2 975-0540-01-01 F
975-0540-01-01 F 3–3
The ground fault protection fuse blows when a significant leakage current flows
between the PV array and earth ground or when the system has been installed
with deficient wiring. Before replacing the fuse, it is important to have qualified
service personnel, such as a certified electrician or technician, determine the
cause of the ground fault and effect repair.
1. Make sure the PV and battery disconnect switches are open and the charge
controller is de-energized.
2. Remove the wiring compartment cover, as described on page 2–6.
The ground fault protection fuse is located behind the wiring terminals.
3–4 975-0540-01-01 F
3. Remove the blown fuse and replace it with a new AC/DC midget cartridge,
DC-rated 600 VDC, 1 A (Littelfuse KLKD 1 or equivalent). Be careful not to
damage the fuse clips, circuit board, and surrounding components.
4. Replace the wiring compartment cover.
5. Clear the fault and reset the system by removing and then reapplying both
PV and battery power.
1. Make sure the PV and battery disconnect switches are open and the charge
controller is de-energized.
2. Search or troubleshoot for a ground fault on the PV array (for example, a
broken PV panel or pinched PV wire).
3. Clear the fault and reset the system by removing and then reapplying both
PV and battery power.
975-0540-01-01 F 3–5
975-0540-01-01 F A–1
Electrical Specifications
Maximum PV Array Open Circuit Voltage 600 VDC
PV Array Voltage Operating Range 195 to 550 VDC
a
PV Array Voltage Full Power Range 230 to 550 VDC
Maximum Power Point Tracking Range 195 to 510 VDC
PV Input Start Voltage 230 VDC
Maximum Operating Current 23 A
Maximum Array Short Circuit Current at STC 28 A
Absolute Maximum Array Short Circuit Current 35 A
Under Any Conditions (See the Notice on the next page for more
information)
Nominal Battery Voltages 24 and 48 VDC (Default is 48 V)
Battery Voltage Operating Range 16 to 67 VDC
Maximum Charging Current 80 A
Maximum Charging Power 2560 W (nominal 24 V battery bank)
4800 W (nominal 48 V battery bank)
Maximum Power Conversion Efficiency 94% (nominal 24 V battery bank)
96% (nominal 48 V battery bank)
Auxiliary Output Dry contact switching up to 60 VDC, 30 VAC, 8 A
Charger Regulation Method Three stage (bulk, absorption, float)
Two stage (bulk, absorption)
Manual equalization
Tare Lossesb Less than 1.0 W (Xanbus power supply on)
Less than 0.5 W (Xanbus power supply off)
a.Full power output below 230 V is not assured. See “Operating Below the PV Array Voltage Full Power Range” on
page A–3 for more information.
b.These values are based on the following specifications:
- The battery voltage is 48 V.
- The auxiliary power supply is shut off at night. See “Disabling Power Supplies at Night” in the Conext MPPT 80 600 Solar
Charge Controller Operation Guide for more information.
A–2 975-0540-01-01 F
NOTE
• PV array voltages often exceed STC voltage specifications, especially
when the array is cold. A voltage temperature correction factor based on
the local code (i.e., NEC 690 or CEC Section 50), ambient temperature
conditions, and module manufacturer specifications must be applied to the
array STC VOC to keep array voltage within specifications listed above.
• PV array current might exceed STC current specifications, especially under
intense sunlight, certain atmospheric conditions, or from reflections (i.e,
water, snow, or ice). Local codes typically apply a multiplier to the PV array
Isc to determine “maximum current” for design purposes. The “Absolute
Maximum Array Short Circuit Current” specification above includes the
125% multiplier required by the NEC and the CEC. Accordingly, the PV
array STC Isc cannot exceed 28 A.
Note:
Max VOC 600 V
Input current limit 35 A (array Isc including 125% code multiplier)
Output current limit 80 A
Figure A-1 MPPT operational window
975-0540-01-01 F A–3
90
80
70
60
Output 50
Current BatteryVoltage=54V
(Amps) 40 BatteryVoltage=58V
Battery Voltage 64V
BatteryVoltage=64V
30
20
10
0
195 200 205 210 215 220 225 230 235 240
InputVoltage(Volts)
5000
4500
4000
3500
3000
Output
O
Power 2500
BatteryVoltage=54V
(Watts)
2000 BatteryVoltage=58V
BatteryVoltage=64V
1500
1000
500
0
195 200 205 210 215 220 225 230 235 240
InputVoltage(Volts)
A–4 975-0540-01-01 F
Battery Type
Setting Floodeda Gel AGM
Equalize Voltage 64.0 V n/a n/a
ReCharge Voltage 50.0 V 50.0 V 50.0 V
Bulk Voltage 57.6 V 56.8 V 57.2 V
Absorption Voltage 57.6 V 56.8 V 57.2 V
Float Voltage 54.0 V 55.2 V 53.6 V
Absorption Time 360 min 360 min 360 min
Batt Temp Comp -108 mV/C -108 mV/C -84 mV/C
a.When Custom is selected for the battery type, the default settings are
based on the flooded battery type.
The Custom Settings menu item allows you to adjust charging and
equalization voltage for lithium ion and other specialty batteries whose
specifications fall outside of the default settings for the battery types that the
charge controller offers. For more information, see the Conext MPPT 80 600 Solar
Charge Controller Operation Guide.
Mechanical Specifications
Enclosure Type IP20, indoor, ventilated, aluminum sheet metal chassis with 7/8" and
1" (22.22 mm and 27.76 mm) knockouts and aluminum heat sink
Maximum and Minimum Wire Size #6 AWG to #14 AWG (13.5 to 2.5 mm2)
in Conduit
Maximum and Minimum Wire Size #6 AWG to #14 AWG (13.5 to 2.5 mm2)
Rating of PV Terminal Block
Maximum and Minimum Wire Size #2 AWG to #14 AWG (35 to 2.5 mm2)
Rating of Battery Terminal Block
Wire Size Rating of Auxiliary #16 AWG (1.5 mm2)
Output Connector
Operating Temperature Range -20 to +65°C (-4 to 149 °F)
(derate above 45°C) (output power to be derated linearly to zero at 65°C)
Pollution degree 2
Over voltage category CAT II
Storage Temperature -40 to +85°C (-40 to 185°F)
975-0540-01-01 F A–5
Accessories
The SCP (Part Number 865-1050-01) is required for installation of the charge
controller and is strongly recommended for ongoing operation.
As the primary interface to the charge controller, the SCP is used for setup and
configuration. Once installation is complete, you can use the SCP for monitoring
and fault reporting. Only one SCP is required to monitor multiple charge
controllers.
In place of the SCP, the Conext ComBox (ComBox) (Part Number 865-1055) can
also be used. The ComBox allows you to configure and monitor the charge
controller through a web interface on a PC or laptop. See the Conext ComBox
Owner’s Guide (Document Part Number 975-0679-01-01)
NOTE
You must use the SCP with firmware version 1.05.00 or higher for full
compatibility with the charge controller. For information on updating your
firmware, contact customer service. To upgrade, use either the ComBox or
Conext Config Tool.
A–6 975-0540-01-01 F
Regulatory Approvals
Certified to UL 1741 and to CSA 107.1 and carries the c(CSA)us mark.
Australia:
• C-tick marked
975-0540-01-01 F A–7
A connections 2–27
abbreviations iv connecting
accessories A–6 multiple PV array strings 2–17
acronyms iv multiple units 2–18
auxiliary output network cables between multiple units 2–21
connections 2–19 single unit, floating system 2–15
vent fan application 2–19 single unit, negative-grounded system 2–14
single unit, positive-grounded system 2–15
B connections, auxiliary output 2–19
batteries copying settings 2–28
charging current 1–3 current rating 2–12
default charger settings A–5
over-current protection 2–13 D
requirements 1–2 DC terminal connector locations 2–11
safety information ix device number, setting 2–26
sealed 2–4 disconnecting the unit 2–20
battery temperature sensor
attaching to battery terminal 2–24 E
installation diagram 2–25 electrical specifications A–2
installing 2–23
overview 2–23 F
Fast Sweep 1–2
C FCC information x
cables, network 2–20 features 1–2
charge controlling floating PV system 2–10
charging current 1–3 fuse holders, ground fault protection 2–10
overview 1–3 fuses, replacing 3–4
three-stage 1–3
two-stage 1–3 G
charger settings ground fault protection 3–4
configuring 2–27 fuse holders 2–10
default A–5 normally ungrounded array 3–5
chassis grounding 2–10 overview 2–10
clearance requirements 2–5 replacing fuse 3–4
ComBox. See Conext ComBox grounding
commissioning chassis 2–10
charger settings 2–27 PV. See PV grounding
connections 2–27
copying settings 2–28
I
multiple units 2–26
installing battery temperature sensor 2–23
overview 2–25
interference, radio and television reception x
setting device number 2–26
Conext ComBox 1–2
configuring K
knockouts
charger settings 2–27
dimensions 2–8
975-0540-01-01 F IX-1
M Q
maximum power point tracking voltage range A–3 qualified personnel, requirements iii
mechanical specifications A–5
minimum R
clearance requirements 2–5 radio reception interference x
wire gauge 2–12 reception interference x
mounting regulatory approvals A–7
instructions 2–9 removing
orientation 2–4 knockouts 2–7
MPPT voltage range A–3 wiring compartment cover 2–6
multiple PV array strings 2–17 replacing the fuse 3–4
multiple units requirements, PV array 2–3
commissioning 2–26 reverse polarity damage 2–14
connecting 2–18
connecting network cables 2–21 S
copying settings 2–28 safety information
DC wiring diagram 2–18 batteries ix
sealed batteries, mounting with 2–4
N specifications
negative-grounded PV system 2–10 electrical A–2
network mechanical A–5
cables 2–20
components 2–20 T
diagram 2–21 television reception interference x
installation 2–20 terminators, network 2–20
layout 2–21 three-stage charge controlling 1–3
terminators 2–20 troubleshooting 3–2
normally ungrounded array, ground fault protection two-stage charge controlling 1–3
3–5
U
O ungrounded PV system 2–10
over-current protection
battery circuit 2–13 W
PV 2–13 wire gauge, minimum 2–12
requirements 2–12 wiring
DC terminal connector locations 2–11
P diagram 2–16
positive-grounded PV system 2–10 wiring compartment
power supply, Xanbus 2–20 Lexan barrier 2–6
IX–2 975-0540-01-01 F
X
Xanbus
overview 2–20
power supply 2–20
975-0540-01-01 F IX–3
IX–4 975-0540-01-01 F
975-0540-01-01 Rev
975-0540-01-01 F F Printed in India