BDB

This document summarizes the breakdown voltage (BDV) test results for the oil of a 31.5/25MVA power transformer with serial number 2043253. The test was conducted on 18/08/2019 for the NMDC 3.0 MTPY steel plant project in Nagarnar. Six test cycles were performed before and after oil filtration, and the average BDV was recorded for each. The test found the transformer oil to be healthy and suitable for use.

Uploaded by

Prabagaran Prt
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
1K views2 pages

BDB

This document summarizes the breakdown voltage (BDV) test results for the oil of a 31.5/25MVA power transformer with serial number 2043253. The test was conducted on 18/08/2019 for the NMDC 3.0 MTPY steel plant project in Nagarnar. Six test cycles were performed before and after oil filtration, and the average BDV was recorded for each. The test found the transformer oil to be healthy and suitable for use.

Uploaded by

Prabagaran Prt
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 2

LOCATION : PPDS-RMHS STANDARD BDV TEST REPORT

TRANSFORMER SL NO: 2043253 PROJECT : NMDC 3.0 MTPY STEEL PLANT (NAGARNAR)
TRANSFORMER RATING: 25/31.5MVA POWER TRANSF0RMER Date:18/08/2019

POWER TRANSFORMER BDV TEST REPORT

NAME PLATE DETAILS:

Sl. No. 2043253 Vector Group Dyn11


MVA 31.5/25 Type of cooling ONAF/ONAN
Make BHEL-JHANSI Frequency 50 Hz
No Load Voltage at HV (KV) 33.0 Temp rise oil 35°C
No Load Voltage at LV (KV) 6.9 Ambient Temp 50°C
Rated current on HV(A) 551.11/437.39 Insulation Level HV 170Kvp,70KVrms
Rated current on LV(A) 2635.73/2091.85 Impedence Voltage 10.0+ 10% Tolerance
OIL MAKE Standard IS:2026 -1977
OIL Type Insulation Class A
OIL Manf Date Insulation Level LV 75Kvp,28KVrms

1. TRANSFOMER OIL BREAK DOWN VOLTAGE TEST:


ELECTRODE GAP : 2.5mm
ELECTRODE TYPE : MUSHROOM
STIRRER : NONE
IEC STANDARD : 60156-95

2. BEFORE OIL FILTERATION :


OIL TEMP : 26ºC
OIL SAMPLE DATE :
OIL SAMPLE TAKEN AT : Bottom- Valve 85( 15NB)
OIL LEVEL AT CONV TANK:

TIME TAKEN FOR


SL NO TEST CYCLE OIL BREAK DOWN VOLTAGE(KV)
TEST(mins)
1 TEST CYCLE-1 5- mins
2 TEST CYCLE-2 2 -mins
3 TEST CYCLE-3 2 -mins
4 TEST CYCLE-4 2 –mins
5 TEST CYCLE-5 2 –mins
6 TSET CYCLE-6 2 –mins
AVERAGE BREAK DOWN VOLTAGE

SIGNATURE: SIGNATURE: SIGNATURE: SIGNATURE:

NAME: NAME: NAME: NAME:


DESIGN: TESTING ENGINEER DESIGN: SITE INCHARGE. DESIGN: DESIGN:
COMPANY: PMPL COMPANY: PMPL COMPANY: NMDC COMPANY: NMDC
LOCATION : PPDS-RMHS STANDARD BDV TEST REPORT
TRANSFORMER SL NO: 2043253 PROJECT : NMDC 3.0 MTPY STEEL PLANT (NAGARNAR)
TRANSFORMER RATING: 25/31.5MVA POWER TRANSF0RMER Date:18/08/2019

1.AFTER OIL FILTERATION :


OIL TEMP : 26ºC
OIL SAMPLE DATE :
OIL SAMPLE TAKEN AT : Bottom- Valve 85( 15NB)
OIL LEVEL AT CONV TANK :
TIME TAKEN FOR
SL NO TEST CYCLE OIL BREAK DOWN VOLTAGE(KV)
TEST(mins)
1 TEST CYCLE-1 5- mins
2 TEST CYCLE-2 2 -mins
3 TEST CYCLE-3 2 -mins
4 TEST CYCLE-4 2 –mins
5 TEST CYCLE-5 2 –mins
6 TSET CYCLE-6 2 –mins
AVERAGE BREAK DOWN VOLTAGE

INSTRUMEN DETAILS:

EQUIPMENT MAKE MODEL/SL.NO RANGE/CAPACITY CALIBRATION


DETAILS VALID DATE
OIL FILTERATION SAPTHAGIRI HUHVR-5KL/154 5KL/5000LPH
MACHINE INDUSTREIES
BDV TEST KIT MEGGER OTS100AF/101725610 0 -100KV

REMARKES: The BDV test is conducted for transformer OIL and found healthy the OIL was fit for
service .

SIGNATURE: SIGNATURE: SIGNATURE: SIGNATURE:

NAME: NAME: NAME: NAME:


DESIGN: TESTING ENGINEER DESIGN: SITE INCHARGE. DESIGN: DESIGN:
COMPANY: PMPL COMPANY: PMPL COMPANY: NMDC COMPANY: NMDC