Draft Question Bank Module-3
Draft Question Bank Module-3
1. If the voltage level of the electricity distribution system is raised from 11 kV to 33 kV for
the same loading conditions, the distribution losses are reduced by a factor of
3. If the reactive power drawn by a particular load is zero, it means the load is operating at
4. Select the location of installing capacitor bank, which will reduce the electricity
distribution losses to the maximum extent
6. The nearest kVAr compensation required for improving the power factor of a 100 kW
load from 0.8 lag to unity power factor is
a) 0.5% b) 2% c) 3% d) 4%
8. A power factor capacitor designed for 10 kVAR at 415 V was found to be operating at
400 V. The effective capacity of the capacitor would be
9. A four pole induction motor operating at 50 Hz, with 1% slip will run at an actual speed
of
10. With decrease in design speed of induction motors the required capacitive kVAr for
reactive power compensation for the same capacity range will
12. For every 4°C reduction in the air inlet temperature of an air compressor, the power
consumption will normally decrease by….. percentage points for the same output.
a) 1 b) 2 c) 3 d) 4
13. The acceptable pressure drop in mains header at the farthest point of an industrial
compressed air network is
15. A 200 cfm compressor has a loading and unloading period of 10 seconds and 20 seconds
respectively during a compressed air leakage test. The air leakage in the compressed air
system would be
17. Vertical type reciprocating compressors are used in the capacity range of
a) 1% b) 2% c) 3% d) 4%
22. Slip ring induction motors, in general, have a …… design efficiency in comparison with
the squirrel cage induction motors for similar ratings
24. The outer tube connection of the pitot tube is used to measure …… in the fan system
28. Shaft power of the motor driving a pump is 30 kW. The motor efficiency is 0.9 and pump
efficiency is 0.6. The power transmitted to the water is
30. If inlet and outlet water temperatures of a cooling tower are 40 oC and 32oC respectively
and atmospheric DBT and WBT are 35 oC and 28 oC respectively then the approach of
cooling tower is
32. The lowest theoretical temperature to which water can be cooled in a cooling tower is
33. Which of the following ambient conditions will evaporate maximum amount of water in a
cooling tower
34. In general, design chilled water temperature drop across chillers is approximately
a) 5 oC b) 1 oC c) 10 oC d) 15 oC
a) 5 oC b) 12 oC c) 8 oC d) 2.8 oC
36. GLS lamp is
39. If voltage is reduced from 230 V to 200 V for a fluorescent tube light, it will result in
42. The rated efficiency of a diesel generator captive power plant has a range of
43. The maximum unbalanced load between phases should not exceed …… % of the capacity
of the DG set
a) 1.6 lakh kCal/hr b) 2.2 lakh kCal/hr c) 3.0 lakh kCal/hr d) 3.5 lakh kCal/hr
46. The core losses of a transformer are the least if the core is made up of
47. The basic functions of an electronic ballast fitted to a fluorescent tube light exclude one
of the following
49. The nearest kVA rating required for a DG set with 1000 kW connected load, with
diversity factor of 1.5 and 84% loading and 0.8 power factor is
53. If the reactive power drawn by a particular load is zero, it means the load is operating at
54. Select the ideal location of installing capacitor banks, which will reduce the distribution
loss to the maximum extent.
55. A 10 HP/7.5 kW, 415 V, 14.5 A, 1460 RPM, 3 phase rated induction motor, after
decoupling from the driven equipment, was found to be drawing 3 A at no load. The
current drawn by the motor at no load is high because of
56. If voltage applied to a 415 V rated capacitors drops by 5 %, its VAr output drops by
about____.
58. Which of the factors will indicate the performance of a rewound induction motor?
59. A six pole induction motor operating at 50 Hz, with 1% slip will run at an actual speed of
60. With decrease in design speed of squirrel cage induction motors the required capacitive
kVAr for reactive power compensation for the same capacity range will
61. The ratio of current drawn by the induction motor to its rated current does not reflect true
loading of the motor at partial loads mainly due to
62. For every 4°C rise in the air inlet temperature of an air compressor, the power
consumption will normally increase by___ percentage points for the same output.
a) 1 b) 2 c) 3 d) 4
63. Typical acceptable pressure drop in mains header at the farthest point of an industrial
compressed air network is
65. A battery of two reciprocating 250 cfm belt driven compressors installed in a centralized
station, were found to be operating at the same loading period of 60% and unloading
period of 40%. The least cost solution to reduce wastage of energy in this case would be
66. With increase in condensing temperature in a vapor compression refrigeration system, the
specific power consumption of the compressor for a constant evaporator temperature will
a) increases b) decreases
c) sometime increases and sometime decreases d) remains the same
a) increase b) decrease
c) sometime increase and sometime decrease d) remains the same
68. The refrigeration load in TR when 15 m3/hr of water is cooled from 21o C to 15 o
C is
about
71. _____ fans are known as “non-overloading“ because change in static pressure do not
overload the motor
72. A 100 cfm reciprocating compressor was observed to be operating at load - unload
pressure setting of 6.0 kg/cm2g and 7.5 kg/cm2g respectively. This situation will result in
73. The specific ratio as defined by ASME and used in differentiating fans, blowers and
compressors, is given by
a) once b) twice
c) thrice d) none of the above
75. Reducing the fan RPM by 10% decreases the fan power requirement by
78. Input power to the motor driving a pump is 30 kW. The motor efficiency is 0.9 and pump
efficiency is 0.6. The power transmitted to the water is
79. The static pressure of a fan running at 500 RPM is 200 mm wc. If it has to be increased to
250 mmwc then the new speed of the fan would be
80. If inlet and outlet water temperatures of a cooling tower are 42oC and 34oC respectively
and atmospheric DBT and WBT are 39 o C and 30 o C respectively, then the approach of
cooling tower is
a) 3o C b) 4o C c) 5o C d) 8o C
81. Which one from the following types of cooling towers consumes less power?
a) Cross-flow splash fill cooling tower b) Counter flow splash fill cooling tower
c) Counter flow film fill cooling tower d) None of the above
82. Which one of the following is true to estimate the range of cooling tower?
84. Small by-pass lines are installed in pumps some times to _____.
87. Color rendering index of Halogen lamps compared to low pressure sodium vapor lamps is
88. Which of the following options reduces the electricity consumption in lighting system in
a wide spread plant?
a) 50 Hz b) 50kHz c) 30 kHz d) 60 Hz
a) kW & Voltage b) kVA & kVAr c) kW & KVA d) none of the above
93. The main precaution to be taken care by the waste heat recovery device manufacturer to
prevent the problem in a DG set during operation is:
94. In a DG set, the generator is generating 1000 kVA, at 0.7 PF. If the specific fuel
consumption of this DG set is 0.25 lts/ kWh at that load, then how much fuel is consumed
while delivering generated power for one hour.
97. The basic functions of an electronic ballast fitted to a fluorescent tube light exclude one
of the following
98. Select the feature which does not apply to energy efficient motors by design:
99. Energy savings potential of variable torque applications compared to constant torque
application is:
a) re-routing and re-conducting such feeders and lines where the voltage drops are
higher
b) power factor improvement
c) optimum loading of transformers in the system
d) selection of Aluminium Cored Steel Reinforced (ACSR) lines instead of All
Aluminium
Alloy Conductors (AAAC)
a) harmonics occur as spikes at intervals which are multiples of the supply frequency
b) harmonics are multiples of the fundamental frequency
c) devices that draw sinusoidal currents when a sinusoidal voltage is applied create
harmonics
d) transformers operating near saturation level create harmonics
104 In a 11 kV feeder, if the voltage is raised from 11 kV to 22 kV for the same loading
conditions, the voltage drop in the same feeder system would be lower by a factor of
105 A 10 kVAr, 415 V rated power factor capacitor was found to be having terminal supply
voltage of 370 V. The capacity of the power factor capacitor at the operating supply
voltage would be approximately
106 The actual speed of a 2 pole induction motor operating at 49.8 Hz and at a slip of 1.5 % is
given by
109 The approximate size of the capacitor selected for the PF improvement and its installation
at the induction motor terminals may be equal to
110 A 7.5 kW, 415 V, 14.5 A, 1460 RPM, 3 phase rated induction motor with full load
efficiency of 88% draws 10.1 A and 5.1 kW of input power. The percentage loading of
the motor is about
a) for every 4°C rise in the air inlet temperature of an air compressor, the power
consumption will normally increase by one percentage points for the same output.
b) after-coolers remove the moisture in the air before it enters the next stage of
compressor to reduce the work of compression
c) for every 250 mm WC pressure drop increase across the suction path due to
choked filters etc., the compressor power consumption increases by about 2 percent
for the same output
d) centrifugal compressors are better suited for applications requiring very high
capacities, typically above 12,000 cfm
113 The leak test results show load time of 10 seconds and unload time of 20 seconds in a
load-unload reciprocating compressor. If the compressor capacity is 256 cfm, then the
approximate leakage would be
a) 85 cfm b) 170 cfm c) 256 cfm d) 128 cfm
115 The flow output of which of the following changes with the discharge pressure
117 In water cooled refrigeration systems, condenser cooling water temperature should be
closest to
121 A fan with 25 cm pulley diameter is driven by a 1470 rpm motor through a v-belt system.
If the motor pulley is reduced from 20 cm to 15 cm at the same motor rpm and fan pulley
diameter, the fan speed will reduce by
122 For centrifugal fans, the relation between Power (kW) and Speed (N) is given by
2 3
kW1 N kW1 N kW1 N
a) = 1 b) = 12 c) = 13 d) none of the above
kW2 N 2 kW2 N 2 kW2 N 2
123 The pressure flow characteristic curve of a centrifugal fan changes with the following
flow control method
a) inlet guide vane b) inlet damper c) outlet damper d) none of the above
124 The hydraulic power of a motor pump set is 6.9 kW. If the power drawn by the motor is
14.0 kW at a 88% efficiency, the pump efficiency is given by
126 If inlet and outlet water temperatures of a cooling tower are 42 oC and 36oC respectively
and atmospheric DBT and WBT are 39 oC and 32 oC respectively, then the effectiveness
of cooling tower is
a) higher b) lower
c) same d) none of the above
128 The motor efficiency is 0.9 and pump efficiency is 0.6. The power transmitted to the
water is 15.11 kW. The input power to the motor driving the pump is about
129 What is the impact on flow and head when the impeller of a pump is trimmed?
a) both flow and pump head increases b) both head and flow decreases
c) flow decreases and pump head increases d) none of the above
130 In a pumping system the static head is 10 m and the dynamic head is 15 m. If the pump
speed is doubled, then the total head will be
131 Lowering the Cycles of Concentration (C.O.C) in circulating water in a cooling tower, the
blow down quantity will
132 A water pump is delivering 200 cubic metres per hour at ambient conditions. The
impeller diameter is trimmed by 10%. The water flow at the changed condition is given
by
133 Which of the following ambient conditions will evaporate maximum amount of water in a
cooling tower
135 The lowest theoretical temperature to which water can be cooled in a cooling tower is
137 If voltage is reduced for gas discharge lamps to its optimum value, it will result in
139 The ratio of luminous flux emitted by a lamp to the power consumed by the lamp is ___.
a) Illuminance b) Lux
c) Luminous Efficacy d) Colour Rendering Index
141 Typical exit flue gas temperature of a 5 MW DG set operating above 80% load is in the
range of
142 In a DG set, the generator is consuming 150 litre per hour diesel oil. If the specific fuel
consumption of this DG set is 0.25 litres/ kWh at that load, then what is the kVA loading
of the set at 0.6 PF?
143 The factors affecting Waste Heat Recovery from exhaust flue gases of DG set are:
a) DG set loading
b) Temperature of exhaust flue gases after turbo charger
c) Back pressure on the DG set d) all of the above
144 The jacket cooling water in a diesel engine flows at 12.9 m3/hr with a range of 10oC and
accounts for 30% of the engine input energy. The power output of the engine will be
146 The electronic ballast in lighting application does not have one of the following
characteristics
149 The occupancy sensors in a lighting installation are best suited for
151 For the same quantity of power handled by a distribution line, lower the voltage
152 If the efficiencies of a power plant, transmission and distribution systems are 30%, 95%
& 85% respectively, the cascade efficiency of transmission and distribution system is
given by
154 If the apparent power drawn over a recording cycle of 30 minutes is 200kVA for 10
minutes, 3000kVA for 15 minutes and 2000 for 5 minutes. The MD recorder will
commute MD as
155 Select the wrong Statement: Heat Rate of a Thermal Power Station
i) is the heat input in kCal for generating one kWh of electrical output
j) is the heat input in kCal for generating one kW of electrical output
k) is inverse of the efficiency of power generation
l) normally becomes better with increase in power generating capacity of power plant
157 In a brewery, the loading on transformer was 1200 kVA with the power factor of 0.86.
The plant improved the power factor to 0.98 by adding capacitors. What is the reduction
in kVA?
q) Squirrel cage induction motors are normally more efficient than Slip ring induction
motors
r) Higher speed induction motors are normally more efficient than lower speed induction
motors
s) Totally Enclosed Fan Cooled (TEFC) motors are less efficient than Screen Protected
Drip Proof (SPDP) motors
t) Motor efficiency increases with increase in rated capacity of motor
161 Stator phase resistance at 30oC is 0.264 ohms. At 120oC, its value will be
162 An induction motor rated for 7.5 kW and 90 % efficiency, operating at full load, will
164 Which of the following pipe fittings used in compressed air pipe line offers maximum
resistance
165 Leakage test was conducted on a compressor having rated FAD of 600 cfm. (Prior to this
leakage test FAD test was carried and found that the actual FAD of compressor which is
90% of the rated FAD). The leakage test reveals that the compressor is loaded for 16 sec
and unloaded for 66 sec. then what is quantum of leakage?
166 A battery of two reciprocating 250 cfm belt driven compressors installed in a centralized
station, were found to be operating at the same loading period of 60% and unloading
period of 40%. The least cost solution to reduce wastage of energy in this case would be
169 The refrigeration load in TR when 20 m3/hr of water is cooled from 17o C to 10o C is
about
170 The essential parameters to estimate cooling load from airside across air handling unit
(AHU) or a fan coil unit (FCU) is
171 In water cooled refrigeration systems, for efficient performance, condenser cooling water
temperature should be closest to
172 A fan with 30 cm pulley diameter is driven by a 1480 rpm motor through a v-belt system.
If the motor pulley is reduced from 20 cm to 15 cm at the same motor rpm and fan pulley
diameter, the fan speed will reduced by
173 The specific ratio as defined by ASME and used in differentiating fans, blowers and
compressors, is given by
174 Reducing the fan RPM by 20% decreases the fan power requirement approximately by
176 Shaft power of the motor driving a pump is 20 kW. The motor efficiency is 0.9 and pump
efficiency is 0.55 at that operating load. The power transmitted to the water is
178 The efficiency of a centrifugal pump with a Best Efficiency Point of 65 %, at its shut off
head will be
179 There are four pumps with the same friction head. For different static heads as shown
below, the variable speed drive will be most economical for which of the application
180 A pump with 200 mm impeller is delivering a flow of 120 m3/hr. If the flow is to be
reduced to 100 m3/hr by trimming the impeller, what should be the impeller size?
a) 167mm b) 240mm
c) 60mm d) none of the above
181 If flow rate is 10m3/hr and the range is 10oC for a cooling tower, then its Heat load in
kCal will be.
183 Which one of the following is true to estimate the range of cooling tower?
184 The lowest theoretical temperature to which water can be cooled in a cooling tower is
185 For the same dew point, choose the energy efficient compressed air dryers from the
following
a) Desiccant regenerative dryer using heated low pressure air for purging
b) Desiccant regenerative type dryer using by compressed air for purging
c) Desiccant regenerative type dryer having external or internal heating with
electricity or steam heater in addition to reduced or no compressed air purging
d) Refrigerated dryer
186 Ratio of luminous flux (lumen) emitted by a lamp to the power consumed (watt) by the
lamp is called
188 Which of the following does not pertain to the family of variable speed drives?
a) Variable frequency drive b) Hydraulic coupling c) Eddy current drive d) Soft starter
189 If condenser temperature is 30oC and evaporator temperature is 25oC then COP cornot
cycle of the refrigeration system is
a) 0.2 b) 0.6 c) 5 d) none of the above
a) water
b) lithium
c) bromine
d) lithium bromide
a) alternator losses
b) stack loss through flue gases
c) coolant losses
d) radiation losses
195 The DG set rating for a plant with connected load of 800 kW, diversity factor 0.6, and 0.8
PF at average loading of 60% will be
a) 480 kVA
b) 600 kVA
c) 800 kVA
d) 1000 kVA
a) lower slip b) lower shaft speed c) higher starting torque d) all of the above
197 The maximum unbalanced load between phases should not exceed ------% of capacity of
DG sets.
a) 10%
b) 15%
c) 20%
d) 25%
199 Select the Correct statement: Operating power factor of a DG set running in isolation
from the grid supply
200 A 4-pole squirrel cage induction motor operates with 1% slip at full load. What is the
approximate full load RPM of motor you may expect at a grid frequency of 49.5 Hz?
202 A 5 kVAr, 415 V rated power factor capacitor was found to be having terminal supply
voltage of 430 V. The capacity of the power factor capacitor at the operating supply
voltage would be approximately
203 Identify the location of installing capacitor banks, which will result in less reduction in
the distribution losses in a factory
204 The nearest kVAr compensation required for changing the power factor of a 1000 kW
load from 0.9 lead to unity power factor is
a) 70% of No load kVAr of the motor b) 80% of No load kVAr of the motor
c) 90% of No load kVAr of the motor d)100% of No load kVAr of the motor
a) kW b) kVA c) kVAr d) HP
208 Which of the following is not likely to create harmonics in an electrical system
209 For a four pole induction motor operating at 50 Hz, the slip at a shaft speed of 1450 RPM
will be
210 A three phase induction motor loaded at less than 50 %,if operated in star mode, will
result in
a) reduced operating voltage b) electrical downsizing of the motor
c) improved efficiency and power factor d) all of the above
211 The performance of rewinding of an induction motor can be assessed by which of the
following factors
213 With increase in design speed of induction motors the required capacitive kVAr for
reactive power compensation for the same capacity range will
216 Use of hard water for inter cooler of a two stage reciprocating air compressor will
a) reduce work done for compression b) increase pressure drop in water side
c) decrease compressor speed d) reduce air inlet temperature to second stage
217 A 500 cfm reciprocating compressor has a loading and unloading period of 5 seconds and
20 seconds respectively during a compressed air leakage test. The air leakage in the
compressed air system would be
a) 125 cfm b) 100 cfm c) 200 cfm d) none of the above
218 A 1000 cfm reciprocating compressor is operating to meet a constant demand of 500 cfm.
The least cost energy efficient solution will be
220 Which of the following can be used as refrigeration both in vapour compressor and
vapour absorption system
221 A 2 ton air conditioner installed in a room and working continuously for two hours will
remove heat of
222 Which of the following refrigeration systems uses vacuum for operation
223 The refrigeration load in TR when 100 m3/hr of water is cooled from 12OC to 7oC is
225 Integrated Part Load Value (IPLV) in a vapour compression refrigeration refers to
average of ____with partial loads
227 Which of the following flow controls in the fan system will change the system resistance
curve
a) will double the flow b) will double the fan static pressure
c) will not double the flow d) will increase flow by more than two times
a) velocity b) flow
c) the difference between total and static pressures d) static pressure
238 Higher the COC in a cooling tower, the blow down quantity will
239 The most appropriate type of fan used for induced draft cooling tower, among the
following is
a) centrifugal fan with FRP blades b) axial fan with aluminium blades
c) centrifugal fan with aluminum blades d) axial fan with mild steel blades
241 FRP fans consume less energy than aluminium fans because
242 Sodium vapour lamps are not used in indoor applications because they
245 A 1100 kVA DG set is delivering 800 kW output. If the flue gas generated is 8 kgs/kWh
then the total flue gas flow rate in kg/hr is
a) lower slip b) higher shaft speed c) lower starting torque d) all of the above
251 “HEAT RATE” is the heat input in kilo Calories or kilo Joules, for generating
252
Select the wrong Statement: The advantage of PF improvement by capacitor addition in
an electric network is
254 In the city electrical distribution scheme, a proposal is being prepared to upgrade 11 kV
network to 33 kV. The reduction in distribution loss, corresponding to the same quantum
of load in the proposed upgraded system will be
a) 11%
b) 33%
c) 3 times from its original loss value
d) none of the above
255 For the electricity consumers paying electricity bill on two part tariff, maximum demand
recorded is the
256 Busbar Voltages at the main electrical panel of a plant were balanced but at the Motor
Control Circuit (MCC),receiving three phase power from busbars, the line voltages were
found to be unbalanced. The plant had earlier installed three phase shunt capacitors to
improve power factor at MCC. The main reason for this unbalance voltage at MCC
among the following was
259 An induction motor installed with static PF correction capacitors across the motor
terminals got damaged along with capacitors once it was disconnected from the supply.
The possible reason among the following was
a) motor PF was over corrected or critically corrected (unity power factor)
b) charging current of the capacitor was only 80% of the motor magnitising current
c) motor was oversized
d) motor was undersized
260 A 22 kW rated 3 phase induction motor operating at 405 V and drawing 18 kW, 32
amperes will be operating at a power factor of
265 As the „approach‟ increases while other parameters remaining constant, the effectiveness
of a cooling tower
The
266 c The correction factor for actual free air discharge in a compressor capacity test will be ----
--------, when the compressed air discharge temperature is 150 C higher than ambient air
of 400 C.
268 If 30,000 kCal of heat is removed from a room every hour then the refrigeration tonnage
will be nearly equal to
a) 30 TR b) 15 TR c) 10 TR d) 5 TR
270 Chilled water enters evaporator at 120C and leaves at 70C . The flow rate of chilled water
was measured as 5 m3/min. The tons of refrigeration capacity will be
a) 0.827 b)8.27 c) 496 d) none of the above
271 The COP of a vapour compression system is 3.5. If the motor draws power of 10.8 kW at
90% motor efficiency, the cooling effect of vapour compression system will be
a) 34 kW b) 37.8 kW
c) 0.36 kW d) none of the above
272 A centrifugal pump is delivering 200 m3/hr. The impeller diameter is trimmed by 10%.
The new flow (m3/hr.) will be
274 If the delivery valve of the pump is throttled such that it delivers 60% of the rated flow
always, one of the best options for improved energy efficiency pump operation would be
a) trimming of the impeller b) replacing the motor
c) replacing the existing pump with a smaller sized pump d) variable speed drive
275 The In Inclined manometer connected to a pitot tube is sensing ------------- pressure in a
gas stream
278 Changes in impeller diameter in a centrifugal pumps are limited to reducing its diameter
to about--- of its maximum size
280 Which of the following is incorrect statement in the case of cooling towers:
a)"Range" is the difference between the cooling tower water inlet and outlet temperature.
b) "Approach" is the difference between the cooling tower outlet cold water temperature
and ambient wet bulb temperature.
c)'Range' is the only indicator of cooling tower performance.
d) Cooling tower capacity is expressed as heat rejected in TR
281 If flow rate is 10m3/hr and the range is 10oC for a cooling tower, then its heat load in
kCal/hr will be.
283 For a cooling tower, the following two statements are made. What is your judgment ?
Statement A: Surface of heat exchange is the surface area of the water droplets, which is
in contact with air.
Statement B: Area of heat exchange is the surface area of the fill sheets, which is in
contact with air.
285 Squirrel cage induction motors, in general, have a …… design efficiency in comparison
with the Slip ring induction motors for similar ratings
286 Ratio of luminous flux(lumen) emitted by a lamp to the power consumed(watt) by the
lamp is called
288 A centrifugal fan is operating at 700 RPM developing a flow of 2000 Nm3/hr. at a static
pressure of 600 mmWC. If the fan speed is reduced to 600 RPM, the static
pressure will become:
289 The ratio between heat extracted and work done in a refrigeration system is called as
290 The fo Following function cannot be achieved with automatic power factor controllers
292 The electronic ballast in lighting application does not have one of the following
characteristics
a) requiring a starter
b) tuned circuit to deliver power at 28-32 KHz
c) lower operational losses than magnetic ballast
d) low temperature rise
d) None of the above
293 Which method uses infrared, acoustic, ultrasonic or microwave sensors for lighting
control?
a) Time-based control
b) Daylight-linked control
c) Occupancy-linked control
d) Localized switching
294 In a DG set, the generator is consuming 90 litre per hour diesel oil. If the specific fuel
consumption of this DG set is 0.25 litres/ kWh at that load, then what is the kVA loading
of the set at 0.72 PF?
295 For assembly line, inspection areas, painting shops, where colour critical applications
and higher illumination levels are required, the following type of lamps will be most
suitable
a) lower slip b) lower shaft speed c) higher starting torque d) all of the above
297 If a 100 W,230 Volt rated incandescent lamp is operated at 200 Volt, the power drawn by
the lamp will be ( assume lamp filament resistance remains same)
a) 75W b) 87W c) 100W d)none of the above
298 Select the Correct statement: Operating power factor of a DG set running in isolation
from the grid supply
a) shall always be maintained at 0.8 at all the load
b) shall always be maintained at unity at all the load
c) shall always be the same as maintained for the grid supply
d) shall be decided based on the engine shaft power(kW), alternator losses(kW), exciter
power requiremetns and load on the alternator(kVA)
299 In a driven equipment connected with motor through a variable speed fluid coupling
a) The luminous efficacy is the ratio of light output in lumens to power input to lamp in
watts.
b) The minimum illuminance for all non-working interiors, has been mentioned as 20 Lux
(as per IS 3646).
c) The efficacy of Halogen lamps and incandescent lamps is almost same
d) One lux is equal to one lumen per square feet.
303 A bulk power factor correction system which is left connected to an installation where the load
has reduced considerably may result in
304 The total loss for a transformer loading at 60% and with no load and full load losses of 3 kW
and 25 kW respectively, is
a) 3 kW b) 12 kW c) 18 kW d) 25 kW
305 A pure resistive load in an alternating current (AC) circuit draws only
306 The nearest kVAr compensation required for improving the power factor of a 1000 kW load
from 0.95 leading power factor to unity power factor is
307 The ratings of the PF correction capacitors at motor terminals for a 37 kW induction motor at
3000 rpm synchronous speed will be---------------------in comparison to the same sized
induction motor at 1500 rpm synchronous speed
308 The largest potential for electricity savings with variable speed drives is generally in
309 A 7.5 kW, 415 V, 15 A, 970 RPM, 3 phase rated induction motor with full load efficiency of
86% draws 7.5 A and 3.23 kW of input power. The percentage loading of the motor is about
311 A two pole induction motor operating at 50 Hz, with 1% slip will run at an actual speed of
a) low speed Squirrel cage induction motors are normally less efficient than high speed
Squirrel cage induction motors
b) the capacitor requirement for PF improvement at induction motor terminals
decreases with decrease in rated speed of the induction motors of the same sizes
c) induction motor efficiency increases with increase in its rated capacity
d) totally-enclosed, fan cooled (TEFC) motors are more efficient than Screen–protected, drip-
proof (SPDP) induction motors
a) compressor efficiency will be reduced by about 2 percent for every 250 mm WC pressure
drop across the air inlet filters.
b) every 40C rise in inlet air temperature results in a higher energy consumption by 1 % to
achieve equivalent output
c) an increase of 5.50C in the inlet air temperature to the second stage results in a 2 %
increase in the specific energy consumption.
d) compressed air receiver volume should be 100% of the rated hourly free air output
317 Which of the following is not a part of the vapour compression refrigeration system
319 The COP of a vapour compression refrigeration system is 3.0. If the power input to compressor
is 100 kW , the tonnage of refrigeration system is given by
320 The refrigeration load in TR when 30 m3/hr of water is cooled from a 14 o C to 6.5 o C is about
2 3
P N P N P N
a) 1 = 1 b) 1 = 1 2 c) 1 = 1 3 d) none of the above
P2 N 2 P2 N 2 P2 N 2
323 Friction loss in a piping system carrying fluid is proportional to
d) 1
a) fluid flow b) (fluid flow)2 1 c) (fluid
fluid flow)2
flow
324 _____ fans are known as “non-overloading“ because change in static pressure do not overload
the motor
326 The value, by which the pressure in the pump suction exceeds the liquid vapour pressure, is
expressed as
327 When the local static pressure in a fluid reaches a level below the vapor pressure of the liquid at
the actual temperature, ____________ may occur in a pump.
a) "Voltage" fluctuations in lighting circuit can be minimized by isolating from the power
feeders.
b)This will reduce the voltage related problems, which in turn increases the efficiency of the
lighting system.
c) With proper control device “over voltage” that might occur during lean load or off-peak can
be avoided, in turn excess energy consumption and improved lamp life
d)all the above
329 Parallel operation of two identical fans in a ducted system
a) will double the flow b) will double the fan static pressure
c) will not double the flow d) will increase flow by more than two times
330 Normally the guaranteed best approach a cooling tower can achieve is
a) for a given heat rejection duty, a higher range will reduce the circulating water flow rate
b) when the cycle of concentration is left at one, all water left in the cooling tower after
evaporation needs to be removed as blowdown.
c) a better indicators for cooling tower performance is Range
d) a cooling tower size will be greater for 20oC Wet bulb temperature (WBT) than for a 30oC
WBT, for the same circulation, range and approach
332 Which of the following ambient conditions will evaporate minimum amount of water in a
cooling tower
a) 35oC DBT and 30oC WBT b) 38oC DBT and 31oC WBT
c) 38oC DBT and 37oC WBT d) 35oC DBT and 29oC WBT
333 Input power to the motor driving a pump is 30 kW. The motor efficiency is 0.9. The power
transmitted to the water is 16.2 kW. The pump efficiency is
334 A 500 cfm reciprocating compressor is operating to meet a constant demand of 300 cfm. The
least cost energy efficient solution will be
337 The inputs required for an automatic power factor controller using kVAR control
340 The flow output of which of the following changes with the discharge pressure
341 A fan is operating at 970 RPM developing a flow of 3000 Nm3/hr. at a static pressure of 650
mmWC. If the speed is reduced to 700 RPM, the static pressure (mmWC) developed will be
344 An engineering industry which was operating with a maximum demand of 500 kVA at 0.9
power factor improved its power factor to 0.99 by installing power factor correction capacitors
near the load centres. The percentage reduction in distribution losses within the plant will be
346 The main precaution to be taken care by the waste heat recovery device manufacturer to
prevent the problem in a DG set during operation is:
348 Which of the following refrigeration systems uses vacuum for operation ?
353 A bulk power factor correction system which is left connected to an installation where the load
has reduced considerably may result in
a) 3 kW b) 12 kW c) 18 kW d) 25 kW
355 A pure resistive load in an alternating current (AC) circuit draws only
356 The nearest kVAr compensation required for improving the power factor of a 1000 kW load
from 0.95 leading power factor to unity power factor is
357 The ratings of the PF correction capacitors at motor terminals for a 37 kW induction motor at
3000 rpm synchronous speed will be---------------------in comparison to the same sized
induction motor at 1500 rpm synchronous speed
358 The largest potential for electricity savings with variable speed drives is generally in
359 A 7.5 kW, 415 V, 15 A, 970 RPM, 3 phase rated induction motor with full load efficiency of
86% draws 7.5 A and 3.23 kW of input power. The percentage loading of the motor is about
a) low speed Squirrel cage induction motors are normally less efficient than high speed
Squirrel cage induction motors
b) the capacitor requirement for PF improvement at induction motor terminals
decreases with decrease in rated speed of the induction motors of the same sizes
c) induction motor efficiency increases with increase in its rated capacity
d) totally-enclosed, fan cooled (TEFC) motors are more efficient than Screen–protected, drip-
proof (SPDP) induction motors
a) compressor efficiency will be reduced by about 2 percent for every 250 mm WC pressure
drop across the air inlet filters.
b) every 40C rise in inlet air temperature results in a higher energy consumption by 1 % to
achieve equivalent output
c) an increase of 5.50C in the inlet air temperature to the second stage results in a 2 %
increase in the specific energy consumption.
d) compressed air receiver volume should be 100% of the rated hourly free air output
367 Which of the following is not a part of the vapour compression refrigeration system
369 The COP of a vapour compression refrigeration system is 3.0. If the power input to compressor
is 100 kW , the tonnage of refrigeration system is given by
370 The refrigeration load in TR when 30 m3/hr of water is cooled from a 14 o C to 6.5 o C is about
2 3
P N P N P N
a) 1 = 1 b) 1 = 1 2 c) 1 = 1 3 d) none of the above
P2 N 2 P2 N 2 P2 N 2
374 _____ fans are known as “non-overloading“ because change in static pressure do not overload
the motor
a) radial b) forward- curved c) backward-inclined d) tube- axial
376 The value, by which the pressure in the pump suction exceeds the liquid vapour pressure, is
expressed as
377 When the local static pressure in a fluid reaches a level below the vapor pressure of the liquid at
the actual temperature, ____________ may occur in a pump.
e) "Voltage" fluctuations in lighting circuit can be minimized by isolating from the power
feeders.
f) This will reduce the voltage related problems, which in turn increases the efficiency of the
lighting system.
g)With proper control device “over voltage” that might occur during lean load or off-peak can
be avoided, in turn excess energy consumption and improved lamp life
h)all the above
a) will double the flow b) will double the fan static pressure
c) will not double the flow d) will increase flow by more than two times
380 Normally the guaranteed best approach a cooling tower can achieve is
a) for a given heat rejection duty, a higher range will reduce the circulating water flow rate
b) when the cycle of concentration is left at one, all water left in the cooling tower after
evaporation needs to be removed as blowdown.
c) a better indicators for cooling tower performance is Range
d) a cooling tower size will be greater for 20oC Wet bulb temperature (WBT) than for a 30oC
WBT, for the same circulation, range and approach
382 Which of the following ambient conditions will evaporate minimum amount of water in a
cooling tower
a) 35oC DBT and 30oC WBT b) 38oC DBT and 31oC WBT
c) 38oC DBT and 37oC WBT d) 35oC DBT and 29oC WBT
383 Input power to the motor driving a pump is 30 kW. The motor efficiency is 0.9. The power
transmitted to the water is 16.2 kW. The pump efficiency is
384 A 500 cfm reciprocating compressor is operating to meet a constant demand of 300 cfm. The
least cost energy efficient solution will be
390 The flow output of which of the following changes with the discharge pressure
391 A fan is operating at 970 RPM developing a flow of 3000 Nm3/hr. at a static pressure of 650
mmWC. If the speed is reduced to 700 RPM, the static pressure (mmWC) developed will be
394 An engineering industry which was operating with a maximum demand of 500 kVA at 0.9
power factor improved its power factor to 0.99 by installing power factor correction capacitors
near the load centres. The percentage reduction in distribution losses within the plant will be
a) 17.35% b) 1.21% c) 86.75% d) none of the above
396 The main precaution to be taken care by the waste heat recovery device manufacturer to
prevent the problem in a DG set during operation is:
398 Which of the following refrigeration systems uses vacuum for operation ?
399 Which of the following electrical equipment has the highest efficiency ?
401 In the city electrical distribution scheme, a proposal is being prepared to upgrade 33 kV
network to 66 kV. The distribution loss, corresponding to the same quantum of load in the
proposed upgraded system will be
402 Rating of power factor correction capacitors at induction motor terminals should be
b) the power factor indicated in the monthly electricity bill is the lowest power factor
recorded at any time during the billing month
c) PF capacitors operating at lower voltage then their rated values have higher operating
kVArs then their rated values
d) the power factor of an induction motor decreases with decrease in percentage motor
loading
404 If the efficiencies of a power plant, transmission and distribution systems are 30%, 95% &
85% respectively, the cascade efficiency of power generation, and transmission system is
given by
a) 24.23% b) 28.5 % c) 80.75% d) 95%
405 Which of the following is not likely to create harmonics in an electrical system?
406 What is the % slip of a 4 pole induction motor if the shaft speed at 49.5 Hz supply
frequency is 1460 rpm?
408 An induction motor rated for 7.5 kW and 90 % efficiency at full load, was drawing 5 kW.
The percentage loading on the motor is
409 If the apparent power drawn over a recording cycle of 30 minutes is 3000kVA for 10
minutes, 2400kVA for 15 minutes and 2900 for 5 minutes, the MD recorder will commute
MD as
410 The performance of rewinding of an induction motor can be assessed by which of the
following factors?
412 The Free Air Delivery capacity of a reciprocating compressor is directly proportional to
413 The inlet air temperature to a two stage reciprocating air compressor is 35oC. At which of
the following 2nd stage inlet temperatures the compressor will consume least power?
414 At which of the following discharge pressures, the reciprocating air compressor will
consume maximum power
416 A 1.5 ton air conditioner installed in a room and working continuously for two hours will
remove heat of
417 Which of the following can be used as refrigerant both in vapour compressor and vapour
absorption systems
418 Chilled water enters evaporator at 120C and leaves at 60C. The flow rate of chilled water
was measured as 300 m3/hr. The tons of refrigeration capacity is
a) 0.595 b) 595.24 c) 35.7 d) none of the above
419 Centrifugal compressors are most efficient when they are operating at_____.
420 The Coefficient of Performance (COP) of Vapour Absorption Refrigeration System (VAR)
421 Backward-inclined fans are known as _____ because change in static pressure does not
overload the motor
a) overloading b) non-overloading
c) radial d) axial
423 A fan is drawing 16 kW at 800 RPM. If the speed is reduced to 600 RPM then the power
drawn by the fan would be
424 The hydraulic power of a motor pump set is 8.5 kW. If the power drawn by the motor is
15.5 kW at a 89% efficiency, the pump efficiency is given by
426 If inlet and outlet water temperatures of a cooling tower are 44oC and 38oC respectively and
atmospheric DBT and WBT are 40 oC and 35 oC respectively, then the effectiveness of
cooling tower is
427 In which of the following fans air enters and leaves the fan with no change in direction
428 The motor efficiency is 0.9 and the pump efficiency is 0.6.The input power to the motor
driving the pump is 28 kW. The power transmitted to the water is
429 A water pump is delivering 200 m3/hr at ambient conditions. The impeller diameter is
trimmed by 10%. The water flow at the changed conditions is
431 Increasing the Cycles of Concentration (C.O.C) in circulating water in a cooling tower, the
blow down quantity will
a) 26oC b) 28 oC c) 29 oC d) 25 oC
433 Which of the following ambient conditions will not evaporate maximum amount of water
in a cooling tower
434 If inlet and outlet water temperatures of a cooling tower are 39oC and 33oC respectively and
atmospheric DBT and WBT are 35 oC and 28 oC respectively then the approach of cooling
tower is
435 If flow rate is 100m3/hr and the range is 8oC for a cooling tower, then its heat load in
kCal/hr will be.
436 Which method uses infrared, acoustic, ultrasonic or microwave sensors for lighting control?
437 If voltage is increased from 230 V to 250 V for a fluorescent tube light, it will result in
th th
438 The 5 and 7 harmonic in a 50 Hz power supply system will have:
440 The COP of a vapour compression system is 3.0. If the motor draws power of 11 kW at
90% motor efficiency, the cooling effect of vapour compression system will be
a) 29.7 kW b) 37.8 kW
c) 0.36 kW d) none of the above as cooling effect is always measured in
TR
442 A slide valve is used for capacity control in which of the following refrigeration
compressors?
443 In a DG set, a 3 phase alternator is supplying on an average 100 A at 420 V and 0.9 pf to a
load. If the specific fuel consumption of this DG set is 0.30 lts/ kWh at that load, then how
much fuel is consumed while delivering generated power for one hour?
444 The largest potential for electricity savings with variable speed drives is generally for:
445 The electronic ballast fitted in a tube light fitting does not have one of the following
characteristics
448 In a "V" belt coupled fan drive, the measured speed at motor end 6" diameter pulley is 1480
rpm and that at fan end 10" diameter pulley is 820 RPM. What is the slippage loss in %?
a) slip ring induction motors are normally less efficient than squirrel cage induction motors
b) high speed squirrel cage induction motors are normally less efficient than low speed
Squirrel cage induction motors
a) kW/TR
b) power input to compressor (kW) / cooling effect (kW)
c) cooling effect (kW) / Power input to compressor (kW)
d) none of the above
451 For the same quantity of power handled by a distribution line, the lower the voltage
i) the higher the current drawn and higher the distribution loss
j) the lower the current drawn and lower the distribution loss
k) the lower the voltage drop and lower the distribution loss
l) the higher the voltage drop and lower the distribution loss
452 The ratio of overall maximum demand of the plant to the sum of individual maximum
demand of various equipment is ______.
453 Maximum demand charges for a billing cycle is calculated by the Utility based on:
454 The total amount of harmonics present in the system is expressed using ___.
455 The gross efficiency of a coal based power plant with an operating gross heat rate of 2450
kCal/kWh is
456 The efficiency at various stages from power plant to end-use is given below: Efficiency of
power generation in a power plant is 30 %, T & D losses are 23 %, distribution loss within
the factory is 6 %, and equipment end use efficiency is 65 %. The overall cascade system
efficiency from fuel input in power generation to end-use in this case will be
a) 2.69% b) 14.11% c) 4.21 d) none of the above
457 A 3 phase, 7.5 kW, 415 V, 15 A, 1480 RPM rated induction motor with full load efficiency
of 90% draws 5 A at rated voltage and 0.5 power factor. The percentage loading of the
motor is about
458 An induction motor installed with static PF correction capacitors across the motor terminals
got damaged along with capacitors once it was disconnected from the supply. The possible
reason among the following was
a) charging current of the capacitor was only 80% of the motor magnitising current
b) motor PF was over corrected or critically corrected (unity power factor)
c) motor was oversized
d) motor was undersized
459 A 4-pole squirrel cage induction motor operates with 1% slip at full load. What is the
approximate full load RPM of motor you may expect at a grid frequency of 49.5 Hz ?
a) increases with increase in motor loading b) decreases with increase in motor loading
c) is independent of motor loading d) increases with decrease in motor
loading
461 Which of the following pipe fittings used in compressed air pipe line offers maximum
resistance
a) Gate Valve in open condition b) Return bend c) Elbow d) Tee 90o long
bend
462 An induction motor rated for 15 kW and 93% efficiency, operating at full load at the rated
parameters condition, will
463 Modest flow variation, from 100% to 80%, in a centrifugal fan is achieved more efficiently
with which of the following flow control methods
a) inlet damper b) outlet damper c) inlet guide vanes d) none of the above
464 A 200 cfm compressor has a loading and unloading period of 10 seconds and 20 seconds
respectively during a compressed air leakage test. The air leakage in the compressed air
system would be
465 Select the correct Statement: The advantage of PF improvement by capacitor addition in an
electric network is
466 A 500 cfm reciprocating compressor was earlier operating at load - unload pressure setting
of 6.0 kg/cm2g and 7.5 kg/cm2g which was changed to 6.0 to 6.5. kg/cm2g respectively for
the same end use conditions. This change with respect to previous situation will result in
467 If the energy efficiency ratio (Watt/Watt) of a split air conditioner is 2.3, then power
consumed by it per ton of refrigeration will be
469 The refrigeration load in TR when 84 litre/minute of water is cooled from 21oC to 15 oC is
about
470 The COP of a vapour compression refrigeration system is 3.5. If the motor delivers power
of 10.8 kW at its shaft with a 90% motor efficiency, the cooling effect of vapour
compression system will be
a) 34 kW b) 37.8 kW
c) 0.36 kW d) none of the above as cooling effect is always measured in TR
472 A fan with 30 cm pulley diameter is driven by a 1480 rpm motor through a v-belt system. If
the motor pulley is reduced from 20 cm to 18 cm at the same motor rpm and fan pulley
diameter, the fan speed will reduced by
474 As per the fan laws, by reducing the fan RPM by 10% , the fan power requirement:
a) suction heads b) discharge heads c) closed valve heads d) none of the above
478 Small diameter by-pass lines are installed in pumps some times to _____.
479 There are four pumps working against the same friction heads. For which of the following
static heads, the variable speed drive will be most economical. (assume magnitude of flow
variation and the number of time it varies is same for all the situations and VSD application
can be considered)
480 A pump with 200 mm impeller is delivering a flow of 120 m3/hr. If the flow is to be
reduced to 100 m3/hr by trimming the impeller, what should be the approximate impeller
size?
482 When you do a walk through energy audit of a cooling tower which salient parameter will
you quickly spot check for its water cooling performance?
a) makeup water tap is on or off b) hot water entry temperature to the cooling tower
c) cooling tower fan is on or off d) cold well and ambient wet bulb temperature
484 Which of the following is correct statement in the case of cooling towers:
a)"Range" is the difference between the cooling tower water inlet and ambient wet bulb
temperature.
b) "Approach" is the difference between the cooling tower outlet cold water temperature
and hot inlet water temperature.
c) "Range" is the only indicator of cooling tower performance.
d) Cooling tower capacity is expressed as heat rejected in Ton of Refrigeration (TR)
486 Name the fan which is more suitable for high pressure application
a) to stabilize the gas discharge b) to supply power to the lamp at supply frequency
c) to ignite the tube light d) to supply power to the lamp at very high frequency
488 Energy savings potential of variable torque applications compared to constant torque
application is:
489 In a DG set, a 3 phase alternator is loaded at 450 A, at 415 volts and 0.85 PF. If the specific
fuel consumption of this DG set is 0.25 lts/ kWh at that load, then how much fuel is
consumed while delivering generated power for one hour.
490 Slip ring induction motors, in general, have a …… design efficiency in comparison with
the squirrel cage induction motors for similar ratings
491 A power factor capacitor designed for 10 kVAr at 415 V was found to be operating at 405
V. The effective capacity of the capacitor would be
492 Which combination of readings as indicated by the panel mounted instruments of a DG set
would give the indications of proper capacity utilisation of diesel engine and generator?
a) kW & Voltage b) kVA & kVAr c) kW & kVA d) none of the above
493 Among the following electrical equipment _______ has the highest design efficiency
495 How many units per liter will be available from a DG set if the operating efficiency is
40%? The calorific value of diesel is 10,000 kCal per liter
a) 3.50 b) 6.98
c) cannot be worked out as DG set loading is not indicated d) 4.65
th th
496 The 5 and 7 harmonic in a 50 Hz power environment will have:
497 The source of maximum harmonics among the following in a plant power system could be:
498 Which of the following are emerging technological solutions in electric power distribution
system?
a) Intelligent meters for improved system operation and customer relationship management
b) Intelligent or “smart meters” to replace older systems to allow customers a clear picture
of their energy use profile,
c) SCADA system to control and data acquisition for complete T&D system
d) all the above
499 Which of the following options reduces the electricity consumption in lighting system in a
wide spread plant?
500 Capacitors with automatic power factor controller when installed in a plant
a) reduces active power drawn from grid b) reduces the reactive power drawn from grid
c) reduces the voltage of the plant d) increases the load current of the plant
a) lower the heat rate of a power generating unit, higher is the generation efficiency.
b) one kilo Watt hour of electrical energy being equivalent to 3600 kilo Joules of thermal
energy
c) „Heat Rate‟ is directly proportional to the efficiency of power generation.
d) design „Heat Rate‟ of a 210 MW thermal generating unit is higher than that of a 110
MW thermal generating unit.
502 If power factor is improved from PF1 to PF2 then the reduction in distribution losses in an
electric network is proportional to :
503 In the BEE labeling programme for distribution transformers, the total transformer losses at
504 A 5 kVAr, 415 V rated power factor capacitor was found to be having 5.5 kVAr operating
capacity. The operating supply voltage at the same supply frequency would approximately
be
507 The synchronous speed (rpm) of a 2 pole induction motor at 49.5 Hz supply frequency is :
a) rated input of the motor b) maximum input power which the motor can draw
c) rated output of the motor d) maximum instantaneous input power of the motor
509 A 7.5 kW, 415 V, 14.0 A, 1480 RPM, three phase rated squirrel cage induction motor, after
decoupling from the driven equipment, was found to be drawing 3.5 A at no load. The
current drawn by the motor at no load is high because of
a) very high supply frequency at the time of no load test b) faulty ammeter reading
c) very poor power factor as the load is almost inductive d) loose motor terminal
connections
510 A six pole induction motor operating at 49.6 Hz, with 980 RPM actual speed , will have
operating % slip of
a) 3 kW b) 12 kW c) 18 kW d) 25 kW
a) required PF capacitor kVAr at induction motor terminal increases with decrease in speed
of the motor
b) PF capacitor improves power factor from the point of installation back to the load side.
c) induction motor efficiency increases with increase in its rated capacity
d) The largest potential for electricity savings with variable speed drives is generally in
variable torque applications
515 In a textile mill, two 150 cfm belt driven reciprocating compressors are seen to be working
constantly with a loading time of 20 seconds and unloading time of 30 seconds. The best
economic option for energy savings would be:
516 Which of the following pipe fittings used in compressed air pipeline offers maximum
resistance
519 In a vapour compression refrigeration system, the component where the refrigerant fluid
experiences no heat loss or gain is
520 The refrigeration load in TR when 20 m3/hr of water is cooled from 13 oC to 8 oC is about
521 In an engine room 15 m long, 10 m wide and 4 m high, ventilation requirement in m 3/hr for
20 air changes/hr is:
522 The specific ratio as defined by ASME and used in differentiating fans, blowers and
compressors, is given by
525 For centrifugal fans, the relation between shaft input Power (kW) and Speed (N) is given
by
2 3
kW1 N kW1 N kW1 N
a) = 1 b) = 12 c) = 13 d) none of the above
kW2 N 2 kW2 N 2 kW2 N 2
526 The value, by which the pressure in the pump suction exceeds the liquid vapour pressure, is
expressed as
a) static head b) dynamic head c)suction head d) net positive suction head
available
527 In a pumping system the static head is 10 m and the dynamic head is 15 m. If the pump
speed is doubled, then the total head will be
528 The advantage of installing a dedicated servo transformer for lighting feeders is;
i) "Voltage" fluctuations in lighting circuit can be minimized by isolating from the power
feeders.
j) reduction of voltage related problems, which in turn increases the efficiency of the
lighting system.
k)with proper control device “over voltage” that might occur during lean load or off-peak
can be avoided, in turn less energy consumption and improved lamp life can be
achieved
l) all the above
a) will double the flow b) will double the fan static pressure
c) will increase flow by more than two times d) will not double the flow
530 The COP of a vapour compression refrigeration system is 3.0. If the compressor motor
output is 9.555 kW, the tonnage (TR) of the refrigeration system is
532 A process fluid at 40 m3/hr, with a density of 0.95, is flowing in a heat exchanger and is to
be cooled from 35 oC to 29 oC. The fluid specific heat is 0.78 kCal/kg. If the chilled water
range across the heat exchanger is 4 oC, the chilled water flow rate is
533 Input power to the motor driving a pump is 30 kW. The motor efficiency is 0.9. The power
transmitted to the water is 16.2 kW. The pump efficiency is
535 The illuminance is 10 lm/m² from a lamp at 1 meter distance. The illuminance at half the
distance will be
539 The electronic ballast in lighting application does not have one of the following
characteristics
540 The lumens output varies from _______ Lumens/Watt in case of White LED lamps.
541 A fan is operating at 970 RPM developing a flow of 3000 Nm3/hr. at a static pressure of
650 mmWC. If the speed is reduced to 700 RPM, the static pressure (mmWC) developed
will be
544 A DG set is generating 900 kVA at 0.8 PF. If the specific fuel consumption of this DG set
is 0.3 lts/ kWh at that load, then how much fuel is consumed while delivering generated
power for one hour.
547 Two most important electrical parameters, which are to be monitored on generator panel,
among the following, for safe operation of a Diesel generator set are:
a) voltage and ampere b) kVA and ampere c) power factor and voltage d) kW and
kVA
548 Which of the following is not a climate zone as per ECBC classification?
549 The T2,T5,T8 and T12 fluorescent tube light are categorized based on
550 Select the feature which does not apply to energy efficient motors by design:
551 In a 22 kV feeder, if the voltage is raised from 22 kV to 66 kV for the same loading
conditions, the voltage drop in the same feeder system would be lowered to
552 Normally, the efficiency of distribution transformer at full load varies anywhere between
553 What is the reduction in distribution loss if the current flowing through the distribution
line is reduced by 10%?
a) kVAr/kW b) (kW2+kVAr2)1/2/kW
555 The electricity bill shows an average power factor of 0.72 with an average kW demand of
627. How much kVAr is required to improve the power factor to 0.95? (Given Data: tan 01
= 0.964,tan 02 = 0.329)
556 Where transformer loading is known, the actual transformer loss at a given load can
be computed as:
a) high torque starting or where smooth acceleration over a broad speed range is required.
b) low torque starting or where steady acceleration over a narrow speed range is required.
c) normal torque starting or where high acceleration over a broad speed range is required.
d) low torque starting or where smooth acceleration over a broad speed range is required.
558 A 3-phase, 415 volts, 50 Hz, 100 kW, 6 pole squirrel cage induction motor with a rated
slip of 2% will have a full load rotor speed of
(a) 1470 rpm (b) 980 rpm (c) 1020 rpm (d) none of the above
a) I2R loss of stator b) I2R loss of rotor c) friction and windage loss d) all of the above
560 Rewinding can affect which of the following factors that contribute to deterioration in
motor efficiency:
561 If measured Line Current of a 3 phase induction motor is 25.98 A, what will be the
Phase Current?
a) 15 A b) 45 A c) 8.96 A d) 30 A
564
Select the correct statement for reciprocating air compressors:
o
a) for every 4 C drop in the inlet air temperature, the increase in energy consumption is by
1%.
b) for every 4
oC rise in the inlet air temperature, the decrease in energy consumption is by
1%
c) for every 4
oC rise in the inlet air temperature, the increase in energy consumption is by
1%
d) the energy consumption remains same irrespective of inlet air temperature
565
Which of the following parameters is not required for evaluating volumetric efficiency
of the compressor?
a) FAD b) Cylinder bore diameter c) Stroke length d) Power input
566
Which of the following will not occur if a reciprocating compressor is operated at a
lower discharge pressure?
a) lower power consumption
b) less load on the piston rods and hence reduced maintenance costs
c) lower leakage losses
d) lower free air delivery than rated
567 Which type of energy efficient dryer can be opted if a user in a plant requires compressed
air at a dew point of -40°C ?
569 Identify the wrong statement from the following regarding Vapour Compression
Refrigeration system
a)"Range" is the difference between the cooling tower water inlet and outlet temperature.
b) "Approach" is the difference between the cooling tower outlet cold water temperature
and ambient wet bulb temperature.
d)'Range' is a better indicator of cooling tower performance.
e) Cooling capacity is the heat rejected in kCal/hr or TR
573 Decreasing the rpm of a fan at partial loading by 10% results in:
576 For the same flow, through which of the following diameter pipes, the pump will work with
maximum pressure?
578 Input power to the motor driving a pump is 20 kW. The motor efficiency is 0.9 and
pump efficiency is 0.7. The power transmitted to the water is
580 The refrigeration load in TR when 10 m3/hr of water is cooled from a 15 oC to 7 oC is about
584 If the evaporation loss is 16 m3 /hr per cell and Cycles of Concentration is 3, the blow
down requirement in m3 /hr per cell of a cooling tower:
a) 8 b) 5.33 c) 4 d) 2
586 The Solar Heat Gain Coefficient (SHGC) of window of a building is 0.30. This means:
a) That the window allows 70 % of the sun's heat to pass through into interior of the
buildings
b) That the window allows 30 % of the sun's heat to pass through into the building
interior
c) That 70 % of the sun's heat is incident on the window
That the window reflects back to exterior a minimum of 30 % of the sun's heat
587 FRP fans consume less energy than aluminium fans because
589 The most energy intensive heat transfer loop of a Vapour Compression Refrigeration
System is:
a) more than the induction motor b) less than the induction motor
c) zero d) load dependent
593 In BEE Star labeled distribution transformers, which of following losses are defined?
595 Which one of the following device will help to eliminate the hunting problems normally
associated with capacitor switching?
597 A 2500 MW super thermal power station generated 15786 million units in the year 2011-
12. Its Plant Load Factor (PLF) is:
598 Which of the following statements is not true of maximum demand controller
599 The main reason for using Variable Frequency Drive (VFD) for capacity control in
electrical motor driven centrifugal fans with fluctuating load is :
a) harmonics occur as spikes at intervals which are multiples of the supply frequency
b) harmonics are multiples of the fundamental frequency
c) induction motors are the major sources of harmonics
d) transformers operating near saturation level create harmonics
601 The gross efficiency of a coal based power generating unit with a gross heat rate of
2490 kcal/kWh is
602 The efficiencies of a power plant and transmission systems are 40%, and 97% respectively.
The percentage loss of the distribution system of the same network is 23% . The
cascade efficiency of generation ,transmission and distribution system is given by
603 The rating of power factor correction capacitors at induction motor terminals should be
605 The Energy Performance Index (EPI) of a building as per Energy Conservation Building
Code (ECBC) and as defined in the Energy Conservation Act,2001 is:
a) kWh per square meter per year b) kWh per square meter
c) kW per square meter d) kWh per year
606 If the maximum demand is 3500 kVA at 0.88 p.f., the maximum demand will reduce
by kVA if PF is improved to 0.98 :
607 The performance of rewinding of an induction motor can be assessed by which of the
following factors?
608 For a synchronous speed of 1500 rpm, at a given mains frequency of 50 Hz, the
induction motor will have number of poles.
a) 8 b) 6 c) 4 d) 2
609 A 7.5 kW, 415 V, 14.5 A, 1460 RPM rated 3 phase induction motor with full load
efficiency of 90%, draws 9.1 A and 4.6 kW of input power. The percentage loading of the
motor is about
610 The power input to a rotor of three phase induction motor is 42.3 kW. If the induction
motor is operating at a slip of 1.30 % the total mechanical power developed will be :
611 If the apparent power drawn over a recording cycle of 30 minutes is 5000 kVA for 0.5
minutes, 3400 kVA for 20 minutes and 1800 for 9.5 minutes, the MD recorder will
compute MD as
612 The rating of the p.f correction capacitors at motor terminals for a 37 kW, 2 poles
induction motor will be in comparison to the same sized induction motor of 6
poles
a) more b) less c) same d) sometime less or more
613 Which parameters need to be measured to assess the percentage loading of a motor by slip
method neglecting voltage correction?
615 Reduction in the delivery pressure of an air compressor working at 7 bar, by 1 bar would
reduce the power consumption by
a) for every 5.5oC drop in the inlet air temperature, the increase in energy
consumption is by 2%
b) for every 4oC rise in the inlet air temperature, the increase in energy
consumption is by 1%
c) for every 4oC rise in the inlet air temperature, the decrease in energy
consumption is by 1%
d) the energy consumption remains same irrespective of inlet air temperature
617 The Free Air Delivery of a reciprocating air compressor is directly proportional to
620 The COP of a vapour compression refrigeration system is 3.1 If the motor draws power of
9.3 kW at an operating efficiency of 88%, the tonnage of refrigeration system is about
621 Chilled water enters an evaporator at 100C and leaves at 60C. The flow rate of chilled
water was measured as 200 m3/hr. The tons of refrigeration capacity is
622 In an air conditioning system analysis which one temperature is sufficient to determine
the enthalpy of air?
624 The driving force for refrigeration in a vapour absorption refrigeration system is
626 The relation between COP and kW/TR for a refrigeration system is given by
627 In which of the following fans the air does not change flow direction from suction to
discharge?
a) tube axial fan b) vane axial fan c) propeller fan d) all of the above
628 The parameter used by ASME to classify fans, blowers and compressors is
629 The pressure to be considered for calculating the power required for centrifugal fans is
630 The inclined manometer connected to a pitot tube is used for measuring which pressure in a
gas stream?
631 If the power drawn by the motor driving a pump is 20 kW at a 91% efficiency, and the
hydraulic power of a motor pump set is 12.5 kW, the pump efficiency will be
634 The preferred method of flow control for reducing pump flow permanently in a pumping
system is-------
635
A water pump is delivering 20 m3/hr at ambient conditions. The impeller diameter is
trimmed by 10%. This will reduce the pump discharge by
637
The range of a cooling tower with inlet and outlet temperature as 41o C and 32o C
respectively and wet bulb temperature as 29o is
638 Find the correct equation, if M = makeup water (from the mains water supply), E =
losses due to evaporation, B = losses due to blow-down and D = drift losses of a cooling
tower:
a) M = E + B + D b) M = E + B - D c) M = E - B + D d) M = E - B - D
639
If the wet bulb temperature of air is 380C, then its relative humidity in % is
640
For a cooling tower if blowdown is 10 m3 /hour and Cycles of Concentration (CoC) is 2.5
the evaporation loss is equal to:
641 If the metered kWh is 95, kVAh is 100 and kVARh is 31, the power factor will be:
644 A refrigeration system using which of the following compressors is likely to be most
efficient?
645 Which of the following is not true for a fluorescent lamp with electronic ballast
647 The refrigerant which can be used both in vapour compression chillers and vapour
absorption chiller is
649 In a transformer on load, if the secondary voltage is one-fourth the primary voltage,
then the secondary current will be
650 If V1 is actual supply voltage and V2 is the rated voltage of a capacitor, the reactive
KVAr produced would be in the ratio of
651 Which loss is considered the most unreliable or complicated to measure in electric motor
efficiency testing?
654 “Heat Rate” of a thermal power station is the heat input in kilo Calories or kilo Joules, for
generating
656 For a 6 pole induction motor operating at 49.5 Hz, the percentage slip at a shaft speed of
950 RPM will be
657 A plant had installed three phase shunt capacitors to improve power factor at Motor
Control Circuit (MCC). Busbar three phase Voltages at the main electrical panel of a plant
were balanced but at the Motor Control Circuit (MCC),receiving three phase power from
busbars, the line voltages were found to be unbalanced. The main reason for this
unbalanced voltage at MCC among the following could be
659 A 75 kW rated squirrel cage induction motor installed with static PF correction capacitors
across the motor terminals got damaged along with capacitors once supply was switched
off due to power failure. The possible reason for the motor burn out among the following
could be
a) motor was oversized
b) motor was undersized
c) charging current of the capacitors was more than the magnetizing current of the motor
d) charging current of the capacitor was only 85% of the motor magnetizing current
660 An induction motor rated for 75 kW and 94 % efficiency, operating at full load, will
662 Increase in the delivery pressure of a compressor by 1 bar would reduce the power
consumption by
a) 1 to 5 % b) 6 to 10 % c) 11 to 15 % d) none of the above
663
The FAD of a reciprocating compressor is directly proportional to
a) pressure b) volume c) speed d) all of the above
664 Which of the following is not true of air receivers in a compressed air system?
665 Typical acceptable pressure drop in mains header at the farthest point of an industrial
compressed air network is
666 All other conditions remaining the same in a refrigeration system, at which of the following
condenser temperatures, the power consumption will be the least:
668 A 1.5 ton air conditioner installed in a room and working continuously for one hour
will remove heat of
669 If the power consumed by a 1.5 TR refrigeration compressor is 2.5 kW , what is the energy
efficiency ratio?
670 In the performance assessment of a refrigeration system, which performance ratio (energy
efficiency) does not follow the trend “a higher ratio means a more efficient refrigeration
system”?
672 A fan with 25 cm pulley diameter is driven by a 2940 rpm motor through a V-belt system.
If the motor pulley is reduced from 20 cm to 15 cm keeping the motor rpm and fan
pulley diameter the same, the fan speed will reduce by
674 The hydraulic power of a motor pump set is 8 kW. If the power drawn by the motor is 16
kW at 90% efficiency, the pump efficiency will be
675 The energy saving with variable speed drives in a pumping system will be maximum for
systems with
676 A process fluid at 50 m3/hr, with a density of 0.96, is flowing in a heat exchanger and is to
be cooled from 36oC to 29oC. The fluid specific heat is 0.78 kcal/kg. If the chilled water
range across the heat exchanger is 5oC,the chilled water flow rate is
677 The inner tube of an L-type pitot tube is used to measure …… in the air duct
679 In case of increased suction lift from open wells, the pump delivered flow rate
a) increases b) decreases c) remains same d) none of the above
680 In pumping systems where static head is a high proportion of the total, the appropriate
solution is
681
A Plant wants to replace the existing 100 TR water cooled vapour compression
refrigeration system with a waste heat driven vapour absorption chiller. The capacity of
the existing cooling tower
a) needs no change b) is to be doubled
c) is to be raised to 1.2 times d) none of the above
682 Shaft power of the motor driving a pump is 30 kW. The motor efficiency is 0.92 and pump
efficiency is 0.5. The power drawn by the motor will be
a) 65.2 kW b) 15 kW c) 30 kW d) 32.6 kW
683
If water is flowing through a cooling tower at 120 m3/h with 5oC range, the load on
cooling tower at an ambient wet bulb ambient temperature of 33 oC is
a) 198.4 TR b) 357 TR c) 158 TR d) none of the above
684 In a plant, the loading on a transformer was 1000 kVA with the power factor of 0.88. The
plant improved the power factor to 0.99 by adding capacitors on the load side. The release
in transformer loading( kVA) will be
a) 111 b) 889 c) 999 d) none of the above
685
The wet bulb temperature normally chosen for designing of cooling tower is
a) average maximum wet bulb for rainy months
b) average maximum wet bulb for summer months
c) average minimum wet bulb for summer months
d) average maximum wet bulb for winter months
686 Which one from the following types of cooling towers consumes least power for the same
operating conditions?
a) counter flow film fill cooling tower b) cross-flow splash fill cooling tow
c) counter flow splash fill cooling tower d) none of the above
a) ratio of luminous flux emitted by a lamp to the power consumed by the lamp
b) one lumen per square meter
c) one lumen per square feet
d) none of the above
688 Which among the following is the most energy efficient lamp for the same wattage rating?
689
is a measure of effect of light on the perceived colour of objects
a) lux b) lumens c) CRI d) lamp circuit efficacy
691 Two most important electrical parameters, which are to be monitored, among the following
for safe operation of Diesel Generator set are:
692 In a DG set, the generator capacity is 1000 kVA with a rated power factor 0.8. It is
consuming 150 litre per hour diesel oil. If the specific fuel consumption of this DG set is
0.25 litres/ kWh at that load, then what is the kVA loading of the set at 0.88 PF?
693 The maximum unbalanced load between phases should not exceed % of the
capacity of the DG set
694 The capacity of largest motor that can be started in the given DG set is…… of kVA rating
of DG set
695 The jacket cooling water in a diesel engine flows at 12.9 m3/hr with a range of 10oC and
accounts for 30% of the engine input energy. What will be the hourly Diesel consumption
in kg with a calorific value of 10,000 kcal/kg
a) harmonics occur as spikes at intervals which are multiples of the supply frequency
b) harmonics are not multiples of the fundamental frequency
c) induction motors are not the major sources of harmonics
d) transformers operating near saturation level create harmonics
697 If the speed of centrifugal fan is reduced to 80% of its rated speed then the power drawn
will % of its rated power:
a) 80% b) 51.2 % c) 40 % d) 64 %
699 Which one of the following device will help to eliminate the hunting problems normally
associated with capacitor switching?
a) Maximum Demand Controller b) Intelligent Power Factor Controller (IPFC)
c) Soft Starter d) Eddy Current Drives
700 The occupancy sensors in a lighting installation are best suited for
701 Which of the following is not a part of vapour compression refrigeration cycle:
702 Which of the following can be attributed to commercial loss in electrical distribution system
a) maximize water and air contact b) capture water droplets escaping with air stream
c) enables entry of air to the cooling tower d) eliminates uneven distribution of water into
the cooling tower
a) active, reactive and maximum demand b) active, power factor and apparent power
c) active, harmonics and maximum demand d) active, reactive and apparent power
a) reduce the peak demand of the distribution company b) increase the revenue of the
distribution company
c) increase the peak demand d) increase the maximum
demand in a industry
711 The nomenclature T2,T5,T8 and T12 for fluorescent lamps are categorized based on
712 The inexpensive way to improving energy efficiency of a motor which operates
consistently at below 40% of rated capacity is by .
714 The illuminance of a lamp at one meter distance is 10 Lm/m2. What will be the
corresponding value at
0.7 meter distance
716 The cooling tower size is _ with the entering WBT when heat load, range and
approach are constant.
a) one part for capacity(or demand) drawn and second part for actual energy drawn
b) one part for actual Power Factor and second part for actual energy drawn
c) one part for capacity(or demand) drawn and second part for actual reactive energy drawn
d) one part for actual apparent energy drawn and second part for actual reactive energy
drawn
718 The adsorption material used in an adsorption air dryer for compressed air is
a) calcium chloride b) magnesium chloride c) activated alumina d) potassium chloride
719 The actual measured load of 1000 k VA transformer is 400 k VA. Find out the total
transformer loss corresponding to this load if no load loss is 1500 Watts and full load
Copper Loss is 12,000 Watts
720 The percentage imbalance when line-line voltages are 415 V, 418 V and 408 V is
a) squirrel cage induction motor. b) wound rotor motor c) synchronous motor d) DC shunt
motor
723 Rotating magnetic field is produced in a
731 In a no load test of a poly-phase induction motor, the measured power by the wattmeter
consists of:
732 In a large compressed air system, about 70% to 80% of moisture in the compressed air is
removed at the
734 If two identical pumps operate in series, then the combined shutoff head is
a) it does not affect head b) more than double c) doubled d) less than
736 If the observed temperature in air receiver is higher than ambient air temperature the
correction factor for free air delivery will be:
a) less than one b) greater than one c) equal to one d)equal to zero
737 If the COP of a vapour compression system is 3.5 and the motor draws power of 10.8
kW at 90% motor efficiency, the cooling effect of vapour compression system will
be:
738 If EER of One Ton Split AC is 3.5, what is its power rating?
743 Find the Total Harmonic Distortion (THD) for current for the following current readings.
Current at 50 Hz fundamental frequency = 250 A, Third harmonic current = 50 A, fifth
harmonic current = 35 A
a) 58 % b) 48 % c) 24% d) 34 %
744 Calculate the density of air at 11400 mmWC absolute pressure and 650C. (Molecular weight
of air:
28.92 kg/kg mole and Gas constant:847.84 mmWC m3/kg mole K)
745 A spark ignition engine is used for firing which type of fuels:
a) high speed diesel b) light diesel oil c) natural gas d) furnace oil
746 A hotel building has four floors each of 1000 m2 area. If the interior lighting power
allowance for the hotel building is 43000W, the Lighting Power Density (LPD) is:
747 A DG set consumes 70 litres per hour of diesel oil. If the specific fuel consumption of
this DG set is
0.33 litres/ kWh at that load, then what is the kVA loading of the set at 0.8 PF?
748 A company installed a 130 kVAr, 600 Volt capacitor but the power meter indicates
that it is only operating at 119 kVAr. The reason out of the following could be
749 A 50 hp motor with a full load efficiency rating of 90 percent was metered and found to be
operating at 25 kW. The percent motor load is
a) 75% b) 50% c) 60% d) 25%
750 A 22 kW, 415 kV, 45A, 0.8 PF, 1475 RPM, 4 pole 3 phase induction motor operating at
420 V, 40 A and 0.8 PF. What will be the rated efficiency
751 Which of the following is the most comfortable conditions for an office room?
DBT = Dry bulb temperature, and RH = Relative humidity
752 Energy Star Label Rating scheme for Fluorescent lamp is based on:
753 The effect of increasing the air gap in an induction motor will increase:
a) power factor
b) speed
c) capacity
d) magnetizing current
756 Which of the following is wrong with respect to Color Rendering Index (CRI)?
757 Which of the following is wrong with reference to heat rate of a coal fired thermal power
plant
?
758 Installing larger diameter pipe in pumping system results in reduction in:
a) Static head
b) Dynamic head
c) Both (a) and (b)
d) None of the above
760 Which of the following is wrong statement with reference to LED lamps?
761 In no load test of a poly-phase induction motor, the measured power by the
wattmeter consists of:
a) core loss
b) copper loss
c) core loss, windage & friction loss
d) stator copper loss, iron loss, windage & friction loss
762 A 10 MVA generator has power factor 0.86 lagging. The reactive power produced will be
a) 10 MVAr
b) 8 MVAr
c) 5 MVAr
d) 1.34 MVAr.
763 The no-load loss and copper loss of a 500 kVA transformer is 900 watts and 6400
watts respectively. What is the total loss at 50% of transformer loading?
a) 4100 watts
b) 6850 watts
c) 2500 watts
d) 3650 watts
a) impeller diameter
b) specific ratio
c) speed
d) volume delivered
769 As per the building area method given in Energy Conservation Building Code (ECBC)
compute the lighting power allowance; given that : the allowed LPD is 12 watt per
square meter and enclosed office area is 500 square meter
a) 6 kW
b) 4.16 kW
c) 6 W
d)
4.16 W
a) Improves with increase in excitation and may even become leading at high
excitations
b) Decreases with increase in excitation
c) Is independent of its excitation
771 A 4 pole 50 Hz induction motor is running at 1470 rpm. What is the slip value?
a) 0.2
b) 0.02
c) 0.04
d) 0.4
772 As per Energy Conservation Building Code compute the Effective Aperture (EA); given
that Window Wall Ratio (WWR) is 0.40 and Visible Light Transmittance(VLT) is 0.25
a) 0.10
b) 0.65
c) 0.33
d) 0.15
774 The percentage reduction in distribution loses when tail end power factor is raised from 0.8
to
0.95 is:
a) 29% b) 15.8% c) 71% d) 84%
775
In a Three Phase Transformer, the secondary side line current is 139.1A, and
secondary voltage is 415V. The rating of the transformer would be .
a. 50 kVA
b. 150 kVA
c. 100 kVA
d. 63 kVA
d. Incandescent lamps
778 A company installed a new 100 kVAr, 415Volt capacitor but the power analyzer indicates
that it is operating at 93 kVAr. The reason could be
779 The kVA reduction by improving the power factor of a plant operating at 400 kW load from
1.85 to 0.95 is
a) 40 b) 49 c) 72 d) None of the above
780 For a supply end Voltage of 10.6 kV and receiving end Voltage of 9.8 kV, the
percentage regulation works out to:
a) 0.80 b) 8.16 c) 7.55 d) None of these.
781 Which of the following can be attributed to Commercial Loss in Electrical Distribution
System?
a) Lengthy Low Voltage Lines b) Low Load side power factor
c) Faulty consumer service meters d) Undersized conductors
784 A DG set has a 300 HP engine drive and is connected to a 300 kVA alternator with
95% efficiency. When a plant load of 290 amps at 415 Volts and 0.76 power factor is
connected, the engine loading works out to
786 At which of the following discharge pressures, the same reciprocating air compressor will
consume maximum power
787 In a DG set, the generator is consuming 70 litre per hour diesel oil. If the specific
fuel consumption of this DG set is 0.33litres/ kWh at that load, what is the kVA
loading of the set at 0.8 PF?
788 If EER of One Ton Split AC unit is 3.51, what is its power rating?
a) 1.0 kW
b) 1.5 kW
c) 0.8 kW
d) 2.0 kW
789 As per the Inverse Square Law of illumination what will be the illuminance at
half the distance?
790 Find the air density at 35oC temperature at one atmospheric pressure. It is given that at
one atmospheric pressure the air density at 20 oC is 1.2041 kg/m3
791 A spark ignition engine is used for firing which type of fuels:
792 The blow down requirement in m3/hr of a cooling tower with evaporation rate of 16 m3/hr
and CoC of 3 is
a) 4 b) 2 c) 8 d ) 16
794 Which of the following power plants has the highest efficiency
a. Combined cycle gas turbine
b. Diesel Engine
c. Conventional coal plants
d. Open cycle Gas Turbine
795 The voltage unbalance in three phase supply is 1.5 %. If the motor is operating at 100 oC,
the additional temperature rise in oC due to voltage unbalance is
a. 4.5 b. 9 c. 0 d none of the above
796 Which of the following cannot be controlled by automatic power factor controllers
798 The refrigeration load in TR when 30 m3/hr of water is cooled from a 14 o C to 6.5 o C is
about
d. none of these
800 A good DG set waste heat recovery device manufacturer will take precautions to prevent
which of the following problem while DG set is in
operation
a) 0.5
b) 0.75
c) 0.6
d) 0.2
802 Which of the following is not likely to create harmonics in an electrical system?
804 A 10 HP/7.5 kW, 415 V, 14.5 A, 1460 RPM, 3 phase rated induction motor, after
decoupling from the driven equipment, was found to be drawing 3 A at no load. The
current drawn by the
motor at no load is high because of
806
The percentage reduction in distribution losses when tail end power factor is raised from 0.8
to
0.95 is .
a) 29%
b) 15.8%
c) 71%
d) none of the above
807 The correction factor for actual free air discharge in a compressor capacity test will be -------
--
---, when the compressed air discharge temperature is 15 0C higher than ambient air of 40
0C.
808 If we increase the temperature of air without changing specific humidity, dew
point temperature of air will
a) increase b) decrease
c) remain constant d) can‟t say
809 Which of the following happens to air when it is cooled through evaporation process in
an air washer?
811 In a vapor compression refrigeration system, the component across which the
enthalpy remains constant
a) compressor b) condenser c) expansion valve d) evaporator
812 If 30,000 kcal of heat is removed from a room every hour then the refrigeration tonnage
will be nearly equal to
a) 30 TR b) 15 TR c) 10 TR d) 100 TR
813 In a no load test of a 3-phase induction motor, the measured power by the wattmeter
consists of:
a) core loss
b) copper loss
c) core loss, windage & friction loss
814 In an engine room 15 m long, 10 m wide and 4 m high, ventilation requirement in m3/hr
for 20 air changes/hr is:
816 The inner tube of a L-type Pitot tube facing the flow is measures in the fan
system
817 A pump discharge has to be reduced from 120 m3/hr to 100 m3/hr by trimming the
impeller. What should be the percentage reduction in impeller size?
822 Which among the following inlet air conditions would result in the best cooling
tower performance?
a) air with lowest wet bulb temperature and high relative humidity
b) air with lowest wet bulb temperature and low relative humidity
c) air with same dry bulb and wet bulb temperature
d) air with high dry bulb temperature and high moisture.
823 As the „approach‟ increases while other parameters remain constant, the effectiveness
of a cooling tower:
a) increases
b) remains unchanged
c) decreases
d) none of the above
824 What is the reduction in distribution loss if the current flowing through the distribution
line is reduced by 10%?
825
Which among the following types of fans is predominantly used in cooling towers ?
826 Which of the following type of lamps is most suitable for color critical applications ?
827 Which of the following factors does not affect waste heat recovery in a DG Set ?
828 The blow down requirement in m3/hr of a cooling tower for site Cycle of Concentration
of 2.5 and approach of 4oC is:
a) 10
b) 0.63
c) 1.6
d) Data not sufficient to calculate
829 Which of the following is not a climate zone as per ECBC classification?
831 Which of the following statements is not true regarding centrifugal pumps?
832 Which of the following is not true regarding system characteristic curve in a pumping
system with large dynamic head ?
a) System curve represents a relationship between discharge and head loss in a system
of pipes
b) System curve is dependent on the pump characteristic curve
c) The basic shape of system curve is parabolic
d) System curve will start at zero flow and zero head if there is no static lift
833 In a DG set, the generator is generating 1000 kVA, at 0.7 PF. If the specific fuel
consumption of this DG set is 0.25 lts/ kWh at that load, then how much fuel is consumed
while delivering generated power for one hour.
a) 230 litre
b) 250 litre
c) 175 litre
d) none of the above
834 The T2,T5,T8 and T12 fluorescent tube light are categorized based on
835 For an air compressor with displacement of 100 CFM and system leakage of 10%,
free air delivery is .
a) 111.11 CFM
b) 90 CFM
c) 100 CFM
d) None of the above
836 The source of maximum harmonics among the following, in a plant power system is
837 The lamp based on high frequency electromagnetic field from outside, exciting the
mercury gas sealed in the bulb, to produce UV radiation and light is
a) Induction lamp
b) Fluorescent lamp
a) for a given fan operating at a constant temperature, the power input to fan increases
by 4 times when the fan speed becomes double
b) for a given fan operating at a constant temperature, the power input to fan increases by 8
times when the fan speed becomes double
c) for a given fan operating at a constant flow rate, the power input increases as the air
temperature increases
d) for a given fan operating at a constant static pressure rise, the flow rate reduces as the
air temperature increases
840 One tonne of refrigeration has the ability to remove kcal of heat in a 24-hour period.
841 In pumping systems where static head is a high proportion of the total, the appropriate
solution is
846 If the COP of a vapour compression system is 3.5 and the motor draws a power of 10.8
kW at 90% motor efficiency, the cooling effect of vapour compression system will be
c) lux d) lumens
a) dimmers
b) timers
c) photosensors
d) daylight harvesting
849 Which of the following flow controls in a fan system will change the system resistance
curve:
850 When the dew point temperature is equal to the air temperature then the relative humidity is
a) 0%
b) 50%
c) 100%
d) Unpredictable
Short Answer Questions
Each question carries Five marks
1 Calculate the transformer total losses for an average loading of 60%. Assume no load
and full load losses as 3 kW and 25 kW respectively
3 How does power factor of an induction motor reduce with the reduction of the applied
load on the motor? Draw a curve depicting power factor vs percentage loading on the
motor.
4 What are the parameters required to be measured while estimating the chiller
performance in kW/TR?
5 A fan is operating at 900 RPM developing a flow of 3000 Nm3/hr. at a static pressure
of 600 mmWC. What will be the flow and static pressure if the speed is reduced to 600
RPM.
7 In a cooling tower, the Cycle of Concentration (C.O.C.) is 3 and evaporation losses are
1%. The circulation rate is 1200 m3 /min. Find out the blow down quantity required
for maintaining the desired level of dissolved solids in the cooling water.
9 A 5 MW DG set with an average load of 3 MW running in parallel with the grid was
found to be exporting 100 kVAr. Without calculating, explain what could be the
possible reasons for the export of reactive power to the grid. List
advantages/disadvantages of the above situation.
10 How are energy savings achieved through electronic ballast in a fluorescent tube light
in comparison to the conventional magnetic ballast?
11 A maximum demand recorder for a plant will record the following loads over a period
of 30 minutes. Compute the MD as the recorder would do
12 How does the power factor of a motor reduce with the reduction in the applied load on
the motor?
14 Chilled water enters evaporator at 110C and leaves at 80C. The flow rate of chilled
water was measured as 350 m3/hr. Calculate the tons of refrigeration capacity.
15 A fan is delivering 10,000 Nm3/hr of air at static pressure rise of 60 mm WC. If the fan
static efficiency is 70%, find out the shaft power of the fan.
16 What do you mean by the term cavitation and describe its undesirable effects on the
pumping system.
17 How size of cooling tower and wet bulb temperature are related? What Cooling Tower
approach value is normally used by Cooling Tower manufacturers.
20 Briefly describe the principle of variable frequency drives used along with squirrel cage
induction motors.
21 Compute the maximum demand recorded for a plant where the recorded load is as
mentioned below in the recording cycle of 30 minutes.
- 100 kVA for 10 minutes
- 200 kVA for 5 minutes
- 50 kVA for 10 minutes
-150 kVA for 5 minutes
22 Why is it beneficial to operate motors in star mode for induction motors loaded less
than 50%?
24 What is the main difference between vapor compression refrigeration (VCR) and
Vapour Absorption Refrigeration (VAR) system?
25 How the heat is absorbed, or removed from a low temperature source and transferred to
a high temperature source in a vapour compression system ?
26 Find out the blow down rate from the following data. Cooling Water Flow Rate is 500
m3/hr. The operating range is 8oC. The TDS concentration in circulating water is 1800
ppm and TDS in make up water is 300 ppm
28 Explain how stator and rotor I2R losses are reduced in an energy efficient motor.
30 A genset is operating at 800 kW loading with 480oC exhaust gas temperature. The DG
set generates 8 kg gas/ kWh generated, and specific heat of gas at 0.25 kCal/ kg oC. A
heat recovery boiler is installed after which the exhaust gas temperature reduces to 180
o
C. How much steam will be generated at 3 kg/ cm2 with enthalpy of 650.57 kCal/ kg.
Assume boiler feed water temperature as 80oC.
31 Calculate the transformer total losses for a 100 kVA transformer for an average loading
of 40%. Assume no load and full load losses as 1.70 kW and 10.50 kW respectively.
32 Fill in the blanks
a) Slip ring induction motors are normally___ efficient than squirrel cage
induction motors
b) Low speed Squirrel cage induction motors are normally _____efficient than
high speed Squirrel cage induction motors
33 Calculate the free air delivery (FAD) capacity of a compressor in m3/hr for the
following observed data:
34 The COP of a vapour compression refrigeration system is 3.0. If the compressor motor
draws power of 10.5 kW at 91% motor efficiency, find out the tonnage of the
refrigeration system.
35 Estimate the cooling tower capacity (TR) and approach with the following parameters
36 How do you calculate the velocity of air/gas in a duct using the average differential
pressure and density of the air/gas?
37 Briefly explain the benefit of installing servo stabilizer for lighting feeder
38 A 180 kVA, 0.80 PF rated DG set has diesel engine rating of 220 BHP. What is the
maximum power factor which can be maintained at full load on the alternator without
overloading the DG set? (Assume alternator losses and exciter power requirement as
5.60 kW and there is no derating of DG set)
40 What are the technical aspects of energy efficient motors with respect to insulation life,
slip and starting torque?
41 For any electrical distribution system, list any 5 options for distribution loss
optimization
42 Draw a typical curve for efficiency and power factor Vs load for a 3-phase induction
motor between 0% and 100% (Note: Explanation not required)
43 A 7.5kW, 3 phase, 415 V induction motor draws 10.5 A and 5 kW input power at 410
V . What is the Apparent and Reactive Power drawn by the motor at the operating load?
44 In an air-handling unit (AHU), the actual airflow rate is 10350 m3/h and the inlet air has
16 kcal/kg of enthalpy. At the outlet of AHU, air has enthalpy of 13.45 kcal/kg. The
density of air of 1.15 kg/ m3. Estimate the TR of the air-handling unit?
46 A process fluid at 40m3/hr, with a density of 0.95, is flowing in a heat exchanger and is
to be cooled from 35oC to 29oC. The fluid specific heat is 0.78 kCal/kg. Find out the
chilled water flow rate if the chilled water range across the heat exchanger is 4oC.
48 A DG set is operating at 750 kW loading with 440oC exhaust gas temperature. The DG
set generates 8 kg gas/ kWh generated, and specific heat of gas at 0.25 kCal/ kg oC. A
heat recovery boiler is installed after which the exhaust gas temperature reduces to
190oC. How much steam will be generated at 3 kg/ cm2 with enthalpy of 650.57 kCal/
kg. Assume boiler feed water temperature as 70oC.
49 An engineering industry which was operating with a maximum demand of 1000 kVA at
0.9 power factor brought down its demand to 900 kVA by power factor improvement.
Find out the percentage reduction in distribution losses within the plant
50 A cast iron foundry has a load of 450 kVA. It has installed two transformers of 500
kVA each. The no load loss and full load copper loss are 760 W and 5400 W
respectively. From the energy efficiency point of view the foundry management wants
to take a decision on whether to operate a single transformer on full load or two
transformers equally sharing the load. What is your recommendation? Why?
51 A no load test conducted on a three phase delta connected induction motor gave the
following values:
53 Air at 25,200 m3/hr and at 1.2 kg/m3 density is flowing into an air handling unit of an
inspection room. The enthalpy difference between the inlet and outlet air is 10 kJ/kg.
If the motor draw a power of 25 kW at an efficiency of 90%, find out the kW/TR of
the refrigeration system. (1 J = 4.18 Cal.)
54 Air flow measurements using the pitot tube, in the primary air fan of a coal fired boiler
gave the following data
55 In a cooling tower, the cooling water circulation rate is 1200 m3/hr. The operating
range is 8oC. If the blowdown rate of the cooling tower is 1 % of the circulation rate,
calculate the evaporation loss and COC
56 A system has a static head of 45 meters and friction head of 10 meters. The pump is
operating at 1440 RPM. For reducing the flow, the pump speed is reduced to 1100
RPM. What is likely to happen as a result of this ?
57 The hot water temperature entering the cooling tower is 38oC. If the wet bulb
temperature is 26 oC and the range is twice the approach, find out the cold water
temperature and effectiveness of the cooling tower.
58 A jockey pump of a fire hydrant system is analysed for efficiency and following data is
collected:
59
List any five problems that can arise due to harmonics in a system.
60 Why does the power factor of a induction motor decreases with the decrease in the
applied load on the motor?
61 A water pump is delivering 300 m3/hr flow at 40 meter head at ambient conditions.
The pump shaft power is 52kW. The impeller diameter is trimmed by 8%. Find out the
new water flow, head and pump shaft power at the changed condition
62 If inlet and outlet water temperatures of a cooling tower are 42oC and 36oC
respectively and atmospheric DBT and WBT are 39 oC and 32 oC respectively, find
out the range, approach and the effectiveness of cooling tower.
63 Draw a sketch of a typical centrifugal fan characteristic curve along with system
resistance. (Note: No explanation is required)
64 The COP of a vapour compression refrigeration system is 3.0. If the compressor motor
draws power of 15 kW at 90% motor efficiency, find out the tonnage of the
refrigeration system.
67 Briefly explain transformer losses and how the total transformer losses at any load
level can be computed.
68 The power input to a three phase induction motor is 45 kW. If the induction motor is
operating at a slip of 2% and with total stator losses of 1.80 kW, find the total
mechanical power developed.
70 Name any five methods of capacity controls for fans (Note: no explanation is required)
71 A genset is operating at 700 kW loading with 450OC exhaust gas temperature: The
DG set generates 8 kg gas/ kWh generated, and specific heat of gas at 0.25 kCal/ kg
OC. A heat recovery boiler is installed after which the exhaust temperature drops by
260oC. How much steam will be generated at 3 kg/ cm2 with enthalpy of 650.57 kCal/
kg. Assume boiler feed water temperature as 60oC
72 An energy audit of a fan was carried out. It was observed that fan was delivering
15,000 Nm3/hr of air at static pressure rise of 60 mm WC. The power measurement of
the 3-phase induction motor coupled with the fan recorded 1.92 kW/ phase on an
average. The motor operating efficiency was assessed as 0.88 from the motor
performance curves. What would be the fan static efficiency ?.
73 Discuss in brief any three methods by which energy can be saved in an air conditioning
system.
74 a) A 10 kVAr, 415 V rated power factor capacitor was found to be having terminal
supply voltage of 440 V. Calculate the capacity of the power factor capacitor at the
operating supply voltage.
b) What would be the nearest kVAr compensation required for changing the power
factor of a 500 kW load from 0.9 lead to unity power factor ?
77 Define one „Ton of Refrigeration (TR)‟. How do you calculate TR across the Air
Handling Units?
78 Estimate the cooling tower capacity (TR) and approach with the following parameters
80 a) Briefly explain the difference between a „filament lamp‟ and a „gas discharge
lamp‟?
b) State any 3 best practices in a lighting system for energy savings?
81 Calculate the free air delivery (FAD) capacity of a compressor in m3/min for the
following observed data:
a) If the reactive power drawn by a particular load is zero, it means the load is
operating at__ power factor
a) input power in kW
b) current drawn by the motor
c) RPM at a full load slip of 1%
84 In an air-handling unit (AHU), the actual airflow rate is 9300 m3/hr and the inlet air
has 16.12 kCal/kg of enthalpy. At the outlet of AHU, air has enthalpy of 13.33
kCal/kg. The density of air is 1.15 kg/m3. Estimate the TR of the air-handling unit?
86 Find out the blow down rate of a cooling tower from the following data:
Cooling water flow rate is 600 m3/hr. The operating range is 8 oC. The TDS
concentration in circulating water is 1500 ppm and TDS in make up water is 300 ppm.
87 In a throttle valve-controlled pumping system with oversized pump, list any five best
methods to improve energy efficiency? (Note: Name only methods, no explanation
required)
88 Compute AT & C (Aggregate Technical and Commercial) losses for the following data:
Annual
Description
Data
Input energy = (import - export), MU 10
Energy billed (metered), MU 6
Energy billed (Un-metered), MU 1
Amount billed (Rs. lakhs ) 400
Gross amount collected (Rs. lakhs) 410
Arrears collected (Rs. lakhs) 40
89 Match the following load-shape objectives of any Demand Side Management (DSM)
programme of a utility.
Peak Clipping
i a
ii
Valley filling b
Load shifting
iii c
Conservation
iv d
Load building
v e
90 The power input to a three phase induction motor is 52 kW. If the induction motor is
operating at a slip of 1.9% and with total stator losses of 1.30 kW, find the total
mechanical power developed.
Existing EER
AC No 1 2.05
AC No 2 2.19
AC No 3 2.30
AC No 4 2.40
AC No 5 2.17
Calculate the total kW saving potential if all the existing ACs are replaced with 3 star
labeled ACs of same capacity?
92 The following data of a water pump of a process plant have been collected
Flow: 70 m3/hr, Total head: 24 meters, Power drawn by motor– 7.2 kW, Motor
efficiency – 89%. Determine the pump efficiency
94 An induced draft-cooling tower is designed for a range of 8 °C. The energy auditor
finds the operating range as 2 °C during the conduct of energy audit. In your opinion
what could be the reasons for this situation
95 Briefly explain transformer losses and how the total transformer losses at any load level
can be computed.
96 A 15 kW, 3 phase, 415 V induction motor draws 25 A and 12 kW input power at 410
V. Calculate the Apparent and Reactive Power drawn by the motor at the operating
load?
97 A water pump of a process plant is analysed for efficiency and following data is
collected:
Flow - 50 m3/hr, Suction head -3 meters, Discharge head - 27 meter, meters, Power
drawn by motor – 7.5 kW, Motor efficiency – 88%
98 Distinguish between NPSH available and NPSH required in case of a centrifugal pump
?
99 A DG set is operating at 600 kW load with 450OC exhaust gas temperature. The DG set
generates 8 kg of exhaust gas/ kWh generated. The specific heat of gas at 450 oC is 0.25
kCal/ kgOC. A heat recovery boiler is installed after which the exhaust temperature
drops to 230OC. How much steam will be generated at 3 kg/ cm2 with enthalpy of
650.57 kCal/ kg. Assume boiler feed water temperature as 80oC.
100 An energy audit of a fan was carried out. It was observed that the fan was delivering
16,000 Nm3/hr of air with static pressure rise of 55 mm WC. The power measurement
of the 3-phase induction motor coupled with the fan recorded 2.1 kW/ phase on an
average. The motor operating efficiency was assessed as 86% from the motor
performance curves. What would be the fan static efficiency?.
101 Discuss in brief any three methods by which energy can be saved in a building air
conditioning system
102 A pump is delivering 64 m3/hr of water with a discharge head of 26 metres. The water
is drawn from a sump where water level is 3 metres below the pump centerline. The
power drawn by the motor is 8.89 kW at 88% motor efficiency. Find out the pump
efficiency
103 How do the Time-Of-Day (TOD) metering and billing benefit the utilities as well as
consumers?
104 Explain briefly the difference between static and dynamic head of a centrifugal
pumping system.
105 A DG set is operating at 700 kW load with 450OC exhaust gas temperature. The DG set
generates 7.8 kg of exhaust gas/ kWh generated. The specific heat of gas at 430oC is
0.25 kCal/ kgOC. A heat recovery boiler is installed after which the exhaust
temperature drops to 220OC. How much steam will be generated at 3 kg/ cm2 with
enthalpy of 650.57 kcal/ kg. Assume boiler feed water temperature as 65oC.
106 An energy audit of a fan was carried out. It was observed that the fan was delivering
18,500Nm3/hr of air with static pressure rise of 45 mm WC. The power measurement of
the 3-phase induction motor coupled with the fan recorded 2.9 kW/ phase on an average.
The motor operating efficiency was assessed as 88% from the motor performance
curves. What would be the fan static efficiency?
107 Compute AT & C (Aggregate Technical and Commercial) Losses for the following
data:
S. No. Description Annual
Data
1 Input Energy = (Import-Export), MU 11
2a Energy Billed (Metered), MU 7
2b Energy Billed (Un-Metered), MU 1
2c Total Energy Billed 8
3 Amount Billed (Rs. lakhs ) 450
4a Gross Amount Collected (Rs. lakhs) 460
4b Arrears Collected (Rs. lakhs) 40
108 List down any 5 energy conservation opportunities in compressed air system
109 A 15 kW, 415 V, 4 pole, 50 Hz, 3 Phase squirrel cage induction motor has a full
load efficiency of 92% and power factor of 0.89. Find the following if the motor
operates at full load rated values.
a) input power in kW
b) current drawn by the motor
c) RPM at a full load slip of 0.8%
111 Air flow measurements using the pitot tube, in the primary air fan of a coal fired
boiler gave the following data
112 Estimate the cooling tower capacity (TR) and approach with the following parameters
Water flow rate through CT = 2 m3/min
Specific heat of water = 1 kcal/kg °C
Inlet water temperature = 43 °C
Outlet water temperature = 35 °C
Ambient WBT = 30°C
113 A 37 kW, 3 phase, 415 V induction motor draws 56 A and 33 kW power at 410 V .
What is the Apparent and Reactive Power drawn by the motor at the operating load?
114 An energy audit of a fan was carried out. It was observed that the fan was delivering
18,500 Nm3/hr of air with static pressure rise of 52 mm WC. The power measurement
of the 3-phase induction motor coupled with the fan recorded 3.1 kW/ phase on an
average. The motor operating efficiency was assessed as 88% from the motor
performance curves. What would be the fan static efficiency?.
115 State any three major differences between vapor compression refrigeration (VCR) and
Vapour Absorption Refrigeration (VAR) system?
116 A 180 kVA, 0.80 PF rated DG set has diesel engine rating of 210 BHP. What is the
maximum power factor which can be maintained at full load on the alternator without
overloading the DG set? (Assume alternator losses and exciter power requirement
as 5.66 kW and there is no derating of DG set)
Long Answer Questions
Each question carries Ten marks
1 A plant has 2 identical 500 kVA transformers, each with a no load loss of 0.84 kW and full
load copper loss of 5.7 kW. The plant average load is 300 kVA and has never exceeded 450
kVA in the past.
(a) Compare the transformer losses when single transformer is in operation and when
both transformers are in parallel operation.
2 A compressed air leakage test was conducted in an engineering industry, which employs a
500 cfm reciprocating compressor. The compressed air system is maintained at the normal
loading-unloading settings of 6.5 kg/cm2g and 7 kg/ cm2g respectively. The following was
observed for a period of 15 minutes trial:
Subsequently some of the air leakage points were attended and the leakage test was
repeated. The following was observed while maintaining the same loading &
unloading pressure settings and trial period:
The average power drawn during the above 2 trials was observed as 70 kW during load and
15 kW during unload condition. Calculate the annual cost savings for 5000 hr/ year of
compressor operation. Assume energy charge of Rs. 5.00 per kWh
4 Briefly explain the step by step approach for the conduct of energy audit of vapour
compression refrigeration plants.
7 A 10 HP, 415 V, 4 pole, 50 Hz, 3 Phase squirrel cage induction motor has a full load
efficiency of 90% and power factor of 0.88. Find the following if the motor operates at full
load rated values.
c) compressor unload timings and loading pressure are 40 seconds and 6.5
kg/cm2 g respectively.
9 A water pump is delivering 300 m3/hr at ambient conditions. The impeller diameter is
trimmed by 10% and its speed is reduced by 10%. Find out the water flow at the changed
conditions.
(b) A process plant consumes of 125,000 kWh per month at 0.9 Power Factor (PF).
What is the percentage reduction in distribution losses per month if PF is improved
up to 0.96 at load end?
11 a) A V-belt driven reciprocating instrument air compressor was found to be maintaining a
distribution system pressure of 7 kg/cm2g. 20% of the instrument air was used for control
valves installed in a boiler house and requiring 6.5 kg/cm2g, whereas balance 80% of the
instrument air was used for other application requiring
4 kg/cm2g. What would you like to advise in this situation?
b) An energy auditor observes the following load unload condition on two similar
reciprocating air compressor installed in two separate industrial locations (A & B)
A B
The energy auditor concludes that at location B, the compressed air system in operation is
inefficient. Do you agree with his observation. Justify your reply with atleast two reasons in
support of your argument
13 In an air conditioning duct of 0.6 m x 0.6 m size, the average velocity of air measured by
vane anemometer is 30 m/s. The static pressure at inlet of the fan is 25 mm WC and at the
outlet is 35 mm WC. The motor coupled with fan through belt drive draws 19 A at 410 V at
a power factor of 0.8. Find out the efficiency of the fan. Assume motor efficiency = 90%
and belt transmission efficiency of 98% (density correction can be neglected).
14 An efficiency assessment test was carried out for a standard squirrel cage induction motor
in a process plant. The motor specifications are as under.
Motor rated specification: 50 HP/ 415 Volt, 60 Amps, 1475 rpm, 3 phase,
delta connected
The following data was collected during the no load test on the motor.
15 The contract demand of a process plant is 5000 kVA with the electricity supply utility
company. The average monthly recorded maximum demand of the process plant is 4600
kVA at a power factor of 0.80. The utility bill analysis provides the following tariff
structure.
a) Minimum monthly billing demand is 75% of the contract demand or the actual
recorded maximum demand whichever is higher.
Find out the optimum limit of power factor capacitor requirement entirely from the
view of reducing maximum demand so that no excess demand charges are paid to the
supply company. Also work out the simple payback period, assuming cost of power
factor capacitor installation along with automatic power factor correction controller
is as Rs. 500 per kVAr.
16 A 7.5 kW, 415 V, 14.5 A, 4 pole, 50 Hz, 3 phase rated squirrel cage induction motor has a
full load efficiency and power factor of 89% and 0.88 respectively.
1. Power input in kW
2. % motor loading
3. % slip
17 (a) A fan is delivering 20,000 Nm3/hr. of air at static pressure difference of 70 mm WC.
If the fan static efficiency is 55%, find out the shaft power of the fan.
(b) Explain briefly the difference between static and dynamic head of a centrifugal
pumping system.
19 Briefly explain the step-by-step approach for conducting Energy Performance Assessment
of DG set on shopfloor.
20 A plant has 2 identical 500 kVA transformers, each with a no load loss of 0.80kW and full
load copper loss of 5.7 kW. The plant average load is 420 kVA and has never exceeded 460
kVA in the past. An energy auditor while conducting the energy audit founds that only
single transformer is kept in operation and second transformer is switched off. The plant
management was of the view that since the plant load is well within the reach of one
transformer, therefore there is no need of keeping the second transformer in parallel
operation. As claimed by the management, plant would be saving no load loss of
transformer, which is 0.80kW.
a) In your opinion, whether energy auditor would agree with the stand taken by the
management.
b) If not, what he would like to like to advise to the plant‟s management on
transformers operation keeping in view the energy saving potential, reliability
and safety of the system
21 An energy auditor works out the percentage loading of a particular induction motor as a
ratio of current drawn to the rated current of the motor.
a) Do you agree with the above methodology adopted by the consultant?
Justify your answer with reasons.
b) In your opinion what is the right approach for working out the motor
loading?
c) List any other method ,which is also an indicator of motor loading
22 The management of an industrial plant retains the services of an energy auditor to undertake
the performance evaluation of a large fan handling gases. The auditor measures the
following data:
x) Efficiency of motor at the operating load (from the performance curve): 94%.
After analyzing the operating data, the energy auditor concludes that the static fan
efficiency has fallen to around 50% and there is a need to replace the fan impeller after
undertaking a detailed financial analysis. However, plant personnel insist that static
efficiency of the plant is still better and is around 85% and there is no need of fan impeller
replacement.
a) In your opinion who is correct, assuming that the measurement of data is correct.
Justify your answer.
b) Can you catch the mistake committed by either of them in the analysis of
electrical parameters?
23 a) An energy auditor while conducting the energy audit of a DG set in a plant founds that a 3
MW DG set with an average load of 2.5 MW running in parallel with the grid was exporting
50 kVAr. In your opinion, what electrical parameters should be checked by the auditor?
List the disadvantages of the above situation.
b) An energy auditor observes the following load unload condition on two similar
reciprocating air compressor and compressed air system installed in two separate
industrial plant locations (A & B)
Location A Location B
The energy auditor concludes that at location B, the compressed air system has
become inefficient. Do you agree with his observation? Justify your answer with at
least two reasons in support of your argument
24 The management of a building facility retains the services of an energy auditor to asses the
refrigeration load of each floor of the building and efficiency of the chilled water pump. The
auditor measures the chilled water flow of each AHU by non contact flow meter and
measures the temperature at the inlet and outlet of AHUs, as per the details given below. The
discharge pressure gauge of the chilled water pump shows 3.5 kg/cm2 and the refrigeration
tank water level is 1 metre above the pump centerline. The power drawn by the refrigeration
compressor and pump motor was found to be 89kW and 17.58 kW respectively.
25 1st Floor
3 o
3.5kg/cm2 20m /hr, 7 C 10oC
Refrigera-
tion Plant
30m3/hr, 7oC 11oC
26 A chemical plant has a contract demand of 2500 kVA with the power supply company. The
average maximum demand of the plant is 2000 kVA at a power factor of 0.95. The
maximum demand is billed at the rate of Rs.300/kVA. The minimum billable maximum
demand is 75 % of the contract demand. An incentive of 0.5 % reduction in energy charges
component of electricity bill are provided for every 0.01 increase in power factor over and
above 0.95. The average energy charge component of the electricity bill per month for the
company is Rs.10 lakhs.
The plant decides to improve the power factor to unity. Determine the power factor
capacitor kVAr required, annual reduction in maximum demand charges and energy charge
component. What will be the simple payback period if the cost of power factor capacitors is
Rs.800/kVAr.
27 A cooling tower is operating at a capacity of 32,40,000 kcal/hr and a range of 6oC. The
cooling tower pump has a positive suction of 1 m and the discharge pressure shows 3.8
kg/cm2. The measured motor power is 71 kW and the operating efficiency of the motor is
92%. Find out the efficiency of the pump.
28 A fan is driven by a motor through a belt pulley system. The input power to the fan is 36 kW
for a 2500 Nm3/hr fluid flow. The motor speed is 2990 RPM and its pulley diameter is 200
mm. The fan pulley diameter is 300 mm. If the flow is to be reduced by 20% by changing
the fan pulley size, what should be the diameter of the fan pulley and what will be the power
input to the fan?
29 Draw a sketch of centrifugal pump (head vs flow) characteristic curve incorporating the
following. (Draw separate sketches for each of the conditions)
a) System resistance curve (with static and dynamic head) and show the operating
point
b) Effect of throttling the pump on head and flow
c) Effect of pump speed reduction on head and flow
d) Effect of impeller diameter reduction on head and flow
A 7.5 kW, 415 V, 14.5 Amp,4 pole, 50 Hz rated, 3 phase squirrel cage induction motor has
a half load efficiency of 84% and power factor of 0.7. Find the following if the motor
operates at 50% of its rated output.