An Introduction To Vibration Control in Buildings
An Introduction To Vibration Control in Buildings
in Buildings
P: (877) 322-5800
F: (877) 322-4774
[email protected]
An Introduction to
Vibration Control
in Buildings
1. VIBRATION CRITERIA
2. VIBRATION ISOLATION ELEMENTS
3. VIBRATION CONTROL
4. TABLES OF RECOMMENDED VIBRATION ISOLATION DETAILS
5. VIBRATION ISOLATION – MISCELLANEOUS
(This publication is adapted from the Unified Facilities Criteria of the United States government which are
in the public domain, have been authorized for unlimited distribution, and are not copyrighted.)
(Figures, tables and formulas in this publication may at times be a little difficult to read, but they are the
best available. DO NOT PURCHASE THIS PUBLICATION IF THIS LIMITATION IS NOT
ACCEPTABLE TO YOU.)
2.1 STEEL SPRING ISOLATORS. Steel springs are used to support heavy equipment
and to provide isolation for the typical low-frequency range of about 3 to 60 Hz (180- to
3600-rpm shaft speed). Steel springs have natural frequencies that fall in the range of
about 1 Hz (for approximately 1-inch static deflection) to about 6 Hz (for approximately
1/4-inch static deflection). Springs transmit high frequency structure borne noise, so
they should be supplemented with a high-frequency pad-type isolator when used to
support equipment directly over critical locations in a building. Unhoused “stable” steel
springs are preferred over housed unstable or stable springs. Unstable springs tend to
tilt over when they are loaded and to become short-circuited when they bind against the
inside walls of the spring housing. Stable steel springs have a diameter that is about 0.8
to 1.2 times their compressed height. They have a horizontal stiffness that is
approximately equal to their vertical stiffness; therefore, they do not have a tendency to
tilt sideways when a vertical load is applied. The free-standing unhoused spring can
easily be inspected to determine if the spring is compressed correctly, is not overloaded
to the point that adjacent coils are solid against one another, and is not binding against
its mounting bracket, and to ensure that all springs of a total installation are uniformly
compressed and that the equipment is not tilting on its base. For reasons of safety, steel
springs are always used in compression, not in tension.
3.2 VIBRATION ISOLATION ELEMENTS. Table 1 lists the principal types of vibration
isolators and their general range of applications. This table may be used as a general
guide for comparing isolators and their range of static deflections and natural
frequencies as applied to two equipment categories (rotary and reciprocating) and two
equipment locations (noncritical and critical). Additional details are required for actual
selections of mounts. Vibration isolator types are discussed in this paragraph, and
equipment installations are discussed in the remaining paragraphs of this chapter.
3.2.1 STEEL SPRING ISOLATORS. Steel springs are used to support heavy
equipment and to provide isolation for the typical low-frequency range of about 3 to 60
Hz (180- to 3600-rpm shaft speed). Steel springs have natural frequencies that fall in
the range of about 1 Hz (for approximately 1-inch static deflection) to about 6 Hz (for
approximately 1/4-inch static deflection). Springs transmit high frequency structure
borne noise, so they should be supplemented with a high-frequency pad-type isolator
when used to support equipment directly over critical locations in a building. Unhoused
“stable” steel springs are preferred over housed unstable or stable springs. Unstable
springs tend to tilt over when they are loaded and to become short-circuited when they
bind against the inside walls of the spring housing. Stable steel springs have a diameter
that is about 0.8 to 1.2 times their compressed height. They have a horizontal stiffness
that is approximately equal to their vertical stiffness; therefore, they do not have a
tendency to tilt sideways when a vertical load is applied. The free-standing unhoused
Table 1
General Types and Applications of Vibration Isolators
3.2.5 FELT PADS. Felt strips or pads are effective for reducing structureborne sound
transmission in the mounting of piping and vibrating conduit. One or more layers of 1/8
or 1/4 inch thick strips should be wrapped around the pipe under the pipe clamps that
attach the piping to building structures. Felt pads will compress under long time and
high load application and should not be used alone to isolate vibration of heavy
equipment.
3.2.6 CORK PADS. Cork pads, strips, or blocks may be used to isolate high frequency
structureborne noise, but they are not recommended for high load bearing applications
because cork gradually compresses under load and loses its resilience. High density
construction cork is sometimes used to support one wall of a double wall. In this
application, the cork will compress slightly with time, and it will continue to serve as a
high frequency isolator (say, for structureborne noise above about 100 to 200 Hz), but it
will not provide good low frequency isolation at equipment driving frequencies of about
10 to 60 Hz. Years ago, before other resilient materials came into widespread use, cork
was often misused under heavy vibrating equipment mounts; full area cork pads were
frequently loaded at rates of 1 to 5 lb/in2. This is such a low loading rate that the cork
appears stiff and does not provide the desired resilience. If cork is to be used for
vibration isolation, a load deflection curve should be obtained from the supplier, and the
cork should be used in the central linear region of the curve (possibly loaded at about
3.2.7 AIR SPRINGS. Air springs are the only practical vibration isolators for very low
frequencies, down to about 1 Hz or even lower for special problems. An air mount
consists of pressurized air enclosed in a resilient reinforced neoprene chamber. The air
is pumped up to the necessary pressure to carry its load. Since the chamber is subject
to very slow leakage, a system of air mounts usually includes a pressure sensing
monitor and an air supply (either a pump or a pressurized air tank). A group of air
mounts can be arranged to maintain very precise leveling of a base by automatic
adjustment of the pressure in the various mounts. If air mounts are used in a design, an
active air supply is required. Operational data should be obtained from the
manufacturer.
3.1.1 BUILDING USES. Isolation recommendations are given for three general
equipment locations: on grade slabs, on upper floors above noncritical areas, and on
upper floors above critical areas. It is assumed that the building under consideration is
an occupied building involving many spaces that would require or deserve the low noise
and vibration environments of such buildings as hotels, hospitals, office buildings, and
the like, as characterized by categories 1 through 4 in Table 2. Hence, the
recommendations are aimed at providing low vibration levels throughout the building. If
a building is intended to serve entirely such uses as those of categories 5 and 6 of
Table 2, the recommendations given here are too severe and can be simplified at the
user’s discretion. An on-grade slab usually represents a more rigid base than is
provided by a framed upper floor, so the vibration isolation recommendations can be
relaxed for on-grade installations. Of course, vibration isolation treatments must be the
very best when a high-quality occupied area is located immediately under the MER, as
compared with the case where a “buffer zone” or noncritical area is located between the
MER and the critical area.
3.1.2.1 ELECTRICAL CONDUIT should be long and “floppy” so that it does not offer
any resistance or constraint to the free movement of the equipment. Piping should be
resiliently supported. Limit stops, shipping bolts, and leveling bolts on spring isolators
3.1.2.2 ALL BUILDING TRASH should be removed from under the isolated base of the
equipment. Loose pieces of grout, 2x4s, nuts, bolts, soft drink bottles, beer cans,
welding rods, pipes, and pipe couplings left under an equipment base can shortcircuit
the isolation mounts. It is recommended that a 2-inch to 4-inch clearances be provided
under all isolated equipment in order to facilitate inspection and removal of trash from
under the base.
3.1.2.3 FOR MANY EQUIPMENT INSTALLATIONS, there is no need to bolt down the
isolation mounts to the floor because the smooth operation of the machine and the
weight of the complete assembly keep the system from moving. For some systems,
however, it may be necessary to restrain the equipment from “creeping” across the
floor. In these situations, it is imperative that the hold-down bolts not short circuit the
pads. A suggested restraining arrangement is illustrated in Figure 5. Simpler versions
can be devised.
(1) The length and the width of the inertia block should be at least 30 percent greater
than the length and width of the supported equipment.
(3) Floor slab thickness. It is assumed that MER upper floor slabs will be constructed of
dense concrete of 140-150 lb/ft.3 density, or, if lighter concrete is used, the thickness
will be increased to provide the equivalent total mass of the specified floor. For large
MERs containing arrays of large and heavy equipment, it is assumed that the floor slab
thickness will be in the range of 8 to 12 inches, with the greater thicknesses required by
the greater floor loads. For smaller MERs containing smaller collections of lighter weight
but typical equipment, floor slab thicknesses of 6 to 10 inches are assumed. For
occasional locations of one or a very few pieces of small high-speed equipment (say
1800 rpm or higher) having no reciprocating action, floor slabs of 4 to 6 inches may be
used with reasonable expectation of satisfactory results. However, for reciprocating-
action machines operating at the lower speeds (say, under 1200 rpm), any floor slab
thicknesses reduced from those listed above begin to invite problems. There is no clear
crossover from “acceptable” to “unacceptable” in terms of floor slab thickness, but each
reduction in thickness increases the probability of later difficulties due to vibration. The
thicknesses mentioned here are based on experience with the “acoustics” of equipment
installations. These statements on thicknesses are in no way intended to represent
structural specifications for a building. “Housekeeping pads” under the equipment are
assumed, but the height of these pads is not to be used in calculating the thickness of
the floor slab.
(4) The ratio of the weight of the concrete block to the total weight of all the supported
equipment (including the weight of any attached filled piping up to the point of the first
pipe hanger) shall be in accordance with the recommendations given in the paragraph
and table for the particular equipment requiring this mounting assembly. The inertia
block adds stability to the system and reduces motion of the system in the vicinity of the
driving frequency. For reciprocating machines or for units involving large starting
torques, the inertia block provides much-needed stability.
(5) The static deflection of the free-standing stable steel springs shall be in accordance
with the recommendations given in the paragraph and table for the particular
equipment. There shall be adequate clearance all around the springs to assure no
contact between any spring and any part of the mounted assembly for any possible
alignment or position of the installed inertia block.
3.3 . TYPE II MOUNTING ASSEMBLY. This mount is the same as the Type I mount in
all respects except that the mounting brackets and the top of the steel springs shall be
(1) If necessary, the steel springs can be recessed into pockets in the concrete block,
but clearances around the springs should be large enough to assure no contact
between any spring and any part of the mounted assembly for any possible alignment
or position of the installed inertia block. Provision must be made to allow positive visual
inspection of the spring clearance in its recessed mounting.
(2) When this type of mounting is used for a pump, the concrete inertia block can be
given a T-shape plan, and the pipes to and from the pump can be supported rigidly with
the pump onto the wings of the T. In this way, the pipe elbows will not be placed under
undue stress.
(3) The weight of the inertia block and the static deflection of the mounts shall be in
accordance with the recommendations given in the table for the particular equipment.
3.4 TYPE III MOUNTING ASSEMBLY. The equipment or the assembly of equipment
should be mounted on a steel frame that is stiff enough to allow the entire assembly to
be supported on flexible point supports without fear of distortion of the frame or
misalignment of the equipment. The frame should then be mounted on resilient mounts-
steel springs or neoprene-in-shear mounts or isolation pads, as the static deflection
would require. If the equipment frame itself already has adequate stiffness, no additional
framing is required, and the isolation mounts may be applied directly to the base of the
equipment.
(1) The vibration-isolation assembly should have enough clearance under and all
around the equipment to prohibit contact with any structural part of the building during
operation.
(1) The floor should be grouted or shimmed to assure a level base for the equipment
and therefore a predictable uniform loading on the isolation pads.
(2) The pads should be loaded in accordance with the loading rates recommended by
the pad manufacturer for the particular densities or durometers involved. In general,
most of these pads are intended for load rates of 30 to 60 psi, and if they are
underloaded (for example, at less than about 10 psi), they will not be performing at their
maximum effectiveness.
(1) It is recommended that the motor, drive shaft, gear reducer, and propeller be
mounted as rigidly as possible on a “unitized” structural support and that this entire
assembly be isolated from the remainder of the tower with stable steel springs in
(2) In addition, where the cooling tower is located on a roof deck directly over an
acoustically critical area, the structureborne waterfall noise may be objectionable. It can
be reduced by locating three layers of ribbed or waffle-pattern neoprene between the
base of the cooling tower and the supporting structure of the building. This treatment is
usually not necessary if there is a noncritical area immediately under the cooling tower.
(3) A single-treatment alternate to the combined two treatments of (1) and (2) above is
the isolation of the entire cooling tower assembly on stable steel springs, also in
accordance with Table 10. The springs should be in series with at least two layers of
ribbed or waffle-pattern neoprene if there is an acoustically critical area immediately
below the cooling tower (or within about 25 feet horizontally on the floor immediately
under the tower). It is necessary to provide limit stops on these springs to limit
movement of the tower when it is emptied and to provide limited movement under wind
load.
(4) Pad materials, when used, should not be short-circuited by bolts or rigid
connections. A schematic of an acceptable clamping arrangement for pad mounts is
shown in Figure 7. Cooling tower piping should be vibration-isolated in accordance with
suggestions given for piping.
4.1 TABLE FORMAT. A common format is used for all the tables that summarize the
recommended vibration isolation details for the various types of equipment. A brief
description of the format is given here.
4.1.1 EQUIPMENT CONDITIONS. The three columns on the left of the table (location,
rating, and speed of the equipment) define the equipment conditions covered by the
recommendations. The rating is given by a power range for some equipment, cooling
capacity for some, and heating capacity for some. The rating and speed ranges
generally cover the range of equipment that might be encountered in a typical building.
Subdivisions in rating and speed are made to accommodate variations in the isolation. If
vibrating equipment is supported or hung from an overhead floor slab, immediately
beneath an acoustically critical area, the same degree of vibration isolation should be
provided as is recommended for the location designated as “on upper floor above
critical area”. Similarly, if the vibrating equipment is hung from an overhead floor slab
beneath a noncritical area, the same vibration isolation should be provided as is
recommended for the location designated as “on upper floor above noncritical area”.
Figure 6
Schematic of Vibration Isolation Mounting for Fan and
Drive-Assembly of Propeller-Type Cooling Tower
4.1.2 MOUNTING RECOMMENDATIONS. The three columns on the right of the table
summarize three basic groups of recommendations: Column 1, the type of mounting;
Column 2, the suggested minimum ratio of the weight of the inertia block (when
required) to the total weight of all the equipment mounted on the inertia block; and
Column 3, the suggested minimum static deflection of the isolator to be used.
(a) When the weight of the inertia block is being considered, the larger weight of the
range given should be applied where the nearby critical area is very critical, or where
the speed of the equipment is near the lower limit of the speed range given, or the rating
of the equipment is near the upper limit of the rating range. Conversely, the lower end of
the weight range may be applied where the nearby critical area is less critical, or where
the speed is near the upper limit of the speed range, or the rating is near the lower limit
of the rating range.
(b) When the static deflection of the isolators is being considered, these minimum
values are keyed to the approximate span of the floor beams; that is, as the floor span
increases, the floor deflection increases, and therefore the isolator deflection must
increase. The specific minimum deflection in effect specifies the type of isolator that can
(c) The recommendations given here assume that a moderate amount of large
equipment (say, more than five or six pieces) totaling more than this equipment are
given in Table 4. These recommendations apply also to the drive unit used for a single
piece of equipment remote from other equipment. The recommendations can be
relaxed, either by decreasing the static deflection of the mount or by decreasing the
weight of the inertia block, or even by eliminating the inertia block where a critical area
is not involved.
Table 3
Vibration Isolation Mounting for Centrifugal and Axial-Flow Fans
4.7 BOILERS. The recommended vibration isolation for boilers are given in Table 8.
These apply for boilers with integrally attached blowers. Table 3 should be followed for
the support of blowers that are not directly mounted on the boiler. A flexible connection
or a thermal expansion joint should be installed in the exhaust breaching between the
boiler and the exhaust stack.
4.8 STEAM VALVES. Steam valves are usually supported entirely on their pipes;
recommendations herein should be applied to the resilient support of steam piping,
including steam valves.
4.12 GEARS. When a gear is involved in a drive system, vibration isolation should be
provided in accordance with recommendations given for either the main power drive unit
or the driven unit, whichever imposes the more stringent isolation conditions.
5.1 RESILIENT PIPE SUPPORTS. All piping in the MER that is connected to vibrating
equipment should be supported from resilient ceiling hangers or from floor-mounted
resilient supports.
(1) As a general rule, the first three pipe supports nearest the vibrating equipment
should have a static deflection of at least one-half the static deflection of the mounting
system used with that equipment. Beyond the third pipe support, the static deflection
can be reduced to 1/4 inch or ½ inch for the remainder of the pipe run in the MER.
(2) When a pipe passes through the MER wall, a minimum 1-inch clearance should be
provided between the pipe and the hole in the wall. The pipe should be supported on
either side of the hole, so that the pipe does not rest on the wall. The clearance space
should then be stuffed with fibrous filler material and sealed with a nonhardening
caulking compound at both wall surfaces.
(3) Vertical pipe chases through a building should not be located beside acoustically
critical areas. If they are located beside critical areas, pipes should be resiliently
mounted from the walls of the pipe chase for a distance of at least 10 feet beyond each
such area, using both low-frequency and high-frequency isolation materials.
(4) Pipes to and from the cooling tower should be resiliently supported for their full
length between the cooling tower and the associated MER. Steam pipes should be
resiliently supported for their entire length of run inside the building. Resilient mounts
should have a static deflection of at least 1/2 inch.
(5) In highly critical areas, domestic water pipes and waste lines can be isolated with the
use of 1/4-inch- to 1/2-inch-thick wrappings of felt pads under the pipe strap or pipe
clamp.
(7) During inspection, the hanger rods should be checked to ensure they are not
touching the sides of the isolator housing and thereby shorting out the spring.
5.3 SUMMARY. In this publication, fairly complete vibration isolation mountings are laid
out for most of the equipment included in an MER. Most of these have been developed