Data Sheet 3LD2122-0TK11: Model
Data Sheet 3LD2122-0TK11: Model
Model
Product brand name SENTRON
Product designation 3LD Switch disconnector
Design of the product Main switch
Display version / for switch position indicator manual 1 ON - 0 OFF
operation
Design of the operating mechanism selector switch
Design of handle knob-operated mechanism, black
Type of the driving mechanism / motor drive No
Voltage
Insulation voltage / rated value 690 V
Surge voltage resistance / rated value 6 kV
Protection class
Protection class IP IP65
Protection class IP / on the front IP65
Dissipation
Power loss [W] / for rated value of the current / at AC 1.1 W
/ in hot operating state / per pole
Electricity
Continuous current / rated value 25 A
Continuous current / of upstream fuse / rated value 25 A
Short-time current resistance (Icw) / at 690 V / limited 640 A
to 1 s / rated value
Main circuit
Operating frequency
● initial value 50 Hz
● Full-scale value 60 Hz
Operating power
● at AC-23 A / at 400 V / rated value 9.5 kW
● at AC-23 A / at 690 V / rated value 9.5 kW
● at AC-3 / at 400 V / rated value 7.5 kW
● at AC-3 / at 690 V / rated value 7.5 kW
Operating voltage
● at AC / at 50/60 Hz / rated value 690 V
Auxiliary circuit
Number of CO contacts / for auxiliary contacts 0
Number of NC contacts / for auxiliary contacts 0
Number of NO contacts / for auxiliary contacts 0
Operating voltage / of auxiliary contacts / at AC / 500 V
maximum
Continuous current / of the auxiliary contact / rated 10 A
value
Insulation voltage / of the auxiliary switch / rated 500 V
value
Suitability
Suitability for use
● Main switch Yes
● switch disconnector Yes
● EMERGENCY OFF switch No
● safety switch Yes
● maintenance/repair switch Yes
Short circuit
Conditional short-circuit current / with line-side fuse
protection
● at 690 V / by gG fuse / rated value 50 kA
Connections
Type of connectable conductor cross-sections
● for copper conductor / solid 1x (1,5...16mm²)
● for copper conductor / finely stranded / with 1x (1,5...10mm²)
core end processing
● for copper conductor / stranded 1x (1,5...16mm²)
● for auxiliary contacts / solid 2x (0.75 ... 2.5 mm²), 1x 4 mm²
● for auxiliary contacts / finely stranded / with 2x (0.75 ... 1.5 mm²), 1x 2.5 mm²
core end processing
● for auxiliary contacts / stranded 2x (0.75 ... 2.5 mm2), 1x 4 mm2
Type of electrical connection
● for main current circuit box terminal
● for auxiliary contacts connection terminals
Requirements
Design of the fuse link
● for short-circuit protection of the main circuit / fuse gL/gG: 25 A
required
● for short-circuit protection of the auxiliary switch fuse gL/gG: 10 A
/ required
Mechanical Design
Height 71 mm
Width 49 mm
Depth 85.5 mm
Mounting type Built-in unit fixed-mounted version
Mounting type
● front mounting with 4-hole attachment Yes
● front mounting with central attachment No
● rail mounting Yes
Net weight 186 g
Certificates
Reference code
● acc. to DIN EN 61346-2 S
● acc. to DIN EN 81346-2 SF
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/lowvoltage/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3LD2122-0TK11
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3LD2122-0TK11
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3LD2122-0TK11
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications
36
10
44
48
55
36
5
46
-Q1
2 4 6
1 2
L1
3 4
L2
5 6
L3