TC515
TC515
Description of Operation
The Basics of ON/OFF Control temperatures. Unfortunately, the process temperature only settles at the setpoint if
In this simple form of control, the controller output switches off when the process the heat source (heater) matches the heat load of the process EXACTLY. Heaters
temperature reaches the setpoint. The process cools until the recovery level is and processes are rarely matched and therefore the process temperature usually
reached and power is re-applied to the process. The resulting process temperature settles at a value offset from the setpoint as shown in Fig. 3.
oscillates through this hysteresis band (the band between setpoint and recovery
levels) as illustrated in Fig. 1. On/Off Control is ideal for large capacity processes Proportional and Integral Control (PI)
(processes that have slow temperature changes and are insensitive to To compensate for the offset resulting in proportional only control, a second control
disturbances) because the hysteresis band can be set very narrow, minimising term known as Integral Action is introduced. Integral Action eliminates the offset by
temperature oscillations. responding to duration of the error signal (through integration) and automatically
Example: The thermostat of a household heater uses On/Off control. When the forcing the process temperature to settle exactly at the setpoint after a period of time
room temperature reaches the setpoint, a switch opens and turns the heater off. The (as shown in fig. 4). This is achieved by small adjustments in the proportional output.
switch remains off until the room temperature drops below the setpoint causing the
switch to close, turning the heater on again. The heater is either ON or OFF. Proportional, Integral and Derivative Control (PID)
In many small capacity processes, the controller must respond quickly to large and
The Basics of Trip & Recovery Control rapid changes in temperature caused by disturbances. Derivative action provides
Trip and Recovery mode facilitates control of two independent setpoints. In heating, additional temperature stability by reacting to the rate of change of the process
each trip point represents the temperature above which the relay is de-energised temperature.
and the heating mechanism is de-activated. The recovery points represent a Example: An injection moulding machine benefits from PID control. Proportional
temperature below which the relay is re-energised and the heating mechanism is control ensures that the plastic temperature is stable and does not oscillate. Integral
turned on. This feature can also be used in cooling applications. Each trip point will control maintains accuracy by keeping the temperature exactly at the setpoint over
then represent the temperature below which the relay is de-energised and the long periods. Derivative action forces the temperature back to the setpoint quickly
cooling mechanism is de-activated. The recovery points represent the temperature when the cold plastic pellets enter the melting chamber.
above which the relay is re-energised and the cooling mechanism is turned on.
Example: A typical application where two fans are used to control a process is Autotune Function
shown in Fig. 2 above. The first fan is activated at 300° and remains on until the For optimum PID control, the controller parameters (P, I and D values) should be
temp. falls below 250°, while the second switches on at 350° and switches off at tuned for each temperature process. This can be performed manually or
280°. automatically by activating the Autotune function. PID control facilitates precision
control at the setpoint temperature (as shown in fig. 5) and the Autotune function
The Basics of PID Control makes the unit easy to set up.
In applications where precision control is required, including small capacity
processes that react quickly to disturbances, it is necessary to provide a more Anti-Reset Wind-Up
sophisticated method of temperature regulation than that of ON/OFF control. For Anti-reset wind-up, sometimes referred to as manual reset, is automatically
example, ON/OFF control would be ineffective in controlling the temperature of a calculated during the Autotune function but can also be manually set, if required. It is
bathroom shower as the person would be subjected to alternative bursts of HOT and used in conjunction with proportional, integral and derivative terms to speed up the
COLD water, neither of which is desirable. It is necessary to establish a proportion of time it takes a process to reach its setpoint temperature while minimising overshoot.
hot to cold water to maintain the required temperature. This term represents the percentage power that a proportional only system would
require to maintain its setpoint temperature.
Proportional Control (P)
Proportional control provides added temperature stability by eliminating Example: A user would set the anti-reset term to 30 for a system requiring 30%
temperature fluctuations by setting the proportion of power supplied to the process power to maintain its setpoint temperature.
depending on the difference between process and setpoint
REC2 350°
SETPOINT REC1 300°
TEMPERATURE
} } OFFSET SETPOINT
TEMPERATURE
TEMPERATURE
TEMPERATURE
TRIP2 280°
SETPOINT SETPOINT
TRIP1 250°
HYSTERESIS
TIME
RELAY 1
TIME TIME TIME
TIME
RELAY 2
Figure 1 Figure 2 Figure 3 Figure 4 Figure 5
Precision Measures Perfection
THERMOLINE
1. Process Value Display: 3 digit display of process temperature or function name.
L L
Fast-Blow
Fuse See Note**
Fast-Blow
Fuse 1 4
+
+ -
Heater Thermocouple Controlled -
Alarm SSR 230V System 3
220V AC/DC 2
Relay 230V 8A 3-Wire PT100 Heater Solid State
AC/DC Sensor Input 220V Relay 25A
Sensor
Sensor Input Controlled Alarm 20A
TC515
+ -
System 220V 5A
TC515
N N
Example 1: Controller with Relay Output, no alarm required. Example 2: Controller with Solid State Relay (SSR)
Input is from a thermocouple. Output and Relay Output for Alarm.
Input is from a PT-100 RTD.
** Note: It is recommended that a Slave Relay/Contactor be installed when switching large inductive/ resistive loads
Technical Specifications
Controller Specifications EMC Protection Rating General Specifications
Setting Accuracy ± 1% Radiated Susceptibility IEC 801-3, Class 3 Operating Temperature 0 - 50°C
Linearisation Accuracy ± 0.3% Radiated Emission CISPR11, Class B Humidity 5-85% non-condensing
Cold Junction Tracking 0.05°C per °C Conducted Susceptibility IEC 255-22-1, Class II Storage Temperature -20°C to 70°C
Sampling Period 70ms Conducted Emission CISPR11, Class B Protection Class (Front) IP54
Protection Class (Rear) IP30
Control Method PID, On/Off or Trip & Rec.
PID Relay Cycle Period 1-240secs
Control Output Options Connection Plug-connector
Relay 250V AC, 8A, SPDT Weight 250g
On/Off Control Hysteresis 0-99.9°
SSR Drive 8-28V DC at 10mA Standards CE Mark
Proportional Band 0,5°-999º Creepage Distance VDE 0110 (Group C 250V)
Integral Time 0-999 seconds IEC 664/664A
VDE 0435
Derivative Time 0-999 seconds
Timer Range 1-999 minutes Alarm Output Options Power Supply
Timer Accuracy 0.1% of preset time Relay 250V AC, 8A, SPST (N.O) Power Supply 21-53V AC/DC
SSR Drive 8-28V DC at 10mA 85-265V AC/DC
Timer Resolution 1 minute
Power Consumption Less than 3VA