0% found this document useful (0 votes)
1K views2 pages

H Series - GES203H Manual

The H series is an online three phase UPS that provides reliable power for IT infrastructure from 15-30kVA. It has dual mains input and a manual bypass switch for maintenance. Models include 3p-3p or 3p-1p configurations. It offers high input power factor, flexible connectivity options, and low total cost of ownership through energy savings modes.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views2 pages

H Series - GES203H Manual

The H series is an online three phase UPS that provides reliable power for IT infrastructure from 15-30kVA. It has dual mains input and a manual bypass switch for maintenance. Models include 3p-3p or 3p-1p configurations. It offers high input power factor, flexible connectivity options, and low total cost of ownership through energy savings modes.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

H series

Three Phase 15-30kVA

Uninterruptible Power Supply

The H series is an on-line three phase UPS which provides


quality power for IT rooms, SMBs, telecommunications, banking
and industry. With dual mains input, it guarantees higher reliability
for your mission critical applications.

The H series has an inbuilt manual bypass switch to keep power


uninterrupted during maintenance. It is available in 3p-3p or 3p-1p
models depending on your power needs.

Availability Flexibility Lowest Total Cost Of Ownership


• Wide input voltage range reduces the • SNMP/RS232/AS400/Dry contact • High input power factor (pf > 0.95). Savings
chance of using the battery. connectivity with power management in installation costs.
• Hot-standby installation capability. software. • Economy mode for energy and operation
• Built-in maintenance and static bypass • EPO (Emergency Power Off) function. cost savings.
switch. • Optional extended battery cabinet for longer
• 3p-3p and 3p-1p models are available. backup time.

Industry

Data Center Telecom Industry Network

Security Labs Medical Metro


H series
Three Phase 15-30kVA

Technical Specifications
GES153H GES153H GES203H GES203H GES303H
Model
3/1 3/3 3/1 3/3 3/3
Power Rating 15kVA / 12kW 20kVA / 16kW 30kVA / 24kW
Rating Voltage V 380/220, 400/230, 415/240 (3phase, 4-wire plus ground)
Voltage Range V 270 ~ 485 (line-line) / 156 ~ 280 (line-neutral)
Input
Power Factor > 0.95
Control and LCD Display Panel
Frequency Hz 50 or 60 ± 3
3/3 model : 220/380, 230/400, 240/415 (3phase, 4-wire plus ground)
Voltage V
3/1 model : 220/230/240 (single phase)
Voltage Harmonic % ≤ 3 (linear load)

Output Voltage Regulation % ±2


Frequency Hz 50 or 60 ± 0.1
≤102% : Continuous ; 102~125% : 1 minute ;
Overload
125~150% : 0.5 minute ; >150% : 2 seconds
Rating Voltage V 240Vdc
Built-in : 2.6 Amp ; Built-in : 5.2 Amp ;
Battery Recharging Capability Optional extra charger : 5 Amp Optional extra charger : 5 Amp
(external installation) (external installation)
Electrical Connection Cable
LED UPS status : Mains input, Bypass input, AC-DC, DC-AC, Backup, Bypass, Output
Display Input/Output, Bypass, Inverter, Frequency, Loading and battery voltage,
LCD
Abnormal message and intelligent self diagnosis
Standard RS232 x 1, SNMP slot x 1, AS400 x 1, Dry contact x 1
Interface
Optional Accessories SNMP card, Modbus card, Relay I/O control card, EnviroProbe, SNMP+5 ports hub

Safety CE, EN62040-1-1 Extended Battery Cabinet


Conformance
EMC CISPR 22 ClassA
Emergency Power Off Local and remote

Maintenance Bypass Switch Built-in


Others
Extended Battery Cabinet Optional (Two types : 26Ah or 40Ah)

Battery-Start Yes
3/3 model : 90 (full load)
Normal (AC-AC) %
3/1 model : 87 (full load)
Efficiency
3/3 model : 97 (full load)
Economic %
3/1 model : 95 (full load)
Temperature ºC 0 ~ 40

Overall Relative Humidity % 5 ~ 95% (non-condensing)


Noise (one meter) dBA < 60
Dimensions (WxDxH) mm 380 x 650 x 860 (UPS and battery cabinet are the same)
3/3 Model 108
Weight kg Power Management Software
3/1 Model 210 220 240

All specifications are subject to change without prior notice.

Delta offers full-scale UPS solutions from


0.6kVA to 4000kVA to fulfill all your power security needs.

091116