Calculate Size of Contactor, Fuse, C.B, Over Load Relay of DOL Starter
Calculate Size of Contactor, Fuse, C.B, Over Load Relay of DOL Starter
Calculate Size of Contactor, Fuse, C.B, Over Load Relay of DOL Starter
Calculate Size of each Part of DOL starter for The System Voltage 415V ,5HP Three Phase House
hold Application Induction Motor ,Code A, Motor efficiency 80%,Motor RPM 750 ,Power Factor 0.8 ,
Overload Relay of Starter is Put before Motor.
Basic Calculation of Motor Torque & Current:
A 1 3.14
B 3.15 3.54
C 3.55 3.99
D 4 4.49
E 4.5 4.99
F 5 2.59
G 2.6 6.29
H 6.3 7.09
I 7.1 7.99
K 8 8.99
L 9 9.99
M 10 11.19
N 11.2 12.49
P 12.5 13.99
R 14 15.99
S 16 17.99
T 18 19.99
U 20 22.39
V 22.4
As per above chart Minimum Locked Rotor Current =1000x5x1/1.732×415=7 Amp
Maximum Locked Rotor Current =1000x5x3.14/1.732×415=22 Amp.
Motor Full Load Current (Line) =KWx1000/1.732×415
Motor Full Load Current (Line) = (5×0.746)x1000/1.732×415=6 Amp.
Motor Full Load Current (Phase)=Motor Full Load Current (Line)/1.732
Motor Full Load Current (Phase)==6/1.732=4Amp
Motor Starting Current =6 to 7xFull Load Current.
Motor Starting Current (Line)=7×6=45 Amp
(1) Size of Fuse:
Type of
Motor Time Delay Fuse Non-Time Delay Fuse
Wound
Rotor 150% 150%
Direct
Current 150% 150%
Maximum Size of Time Delay Fuse =300% x Full Load Line Current.
Maximum Size of Time Delay Fuse =300%x6= 19 Amp.
Maximum Size of Non Time Delay Fuse =1.75% x Full Load Line Current.
Maximum Size of Non Time Delay Fuse=1.75%6=11 Amp.
(2) Size of Circuit Breaker:
Type of
Motor Instantaneous Trip Inverse Time
Wound
Rotor 800% 150%
Direct
Current 200% 150%
Maximum Size of Instantaneous Trip Circuit Breaker =800% x Full Load Line Current.
Maximum Size of Instantaneous Trip Circuit Breaker =800%x6= 52 Amp.
Maximum Size of Inverse Trip Circuit Breaker =250% x Full Load Line Current.
Maximum Size of Inverse Trip Circuit Breaker =250%x6= 16 Amp.
(3) Thermal over Load Relay:
Switching of
Electrical Discharge
Lamp
AC5a 3
Switching of
Electrical
Incandescent Lamp
AC5b 1.5
Switching of
Transformer
AC6a 12
Switching of
Capacitor Bank
AC6b 12
Slightly Inductive
Load in Household
or same type load
AC7a 1.5
Motor Load in
Household
Application
AC7b 8
Hermetic
refrigerant
Compressor Motor
with Manual O/L
Reset
AC8a 6
Hermetic
refrigerant AC8b 6
Compressor Motor
with Auto O/L Reset
Control of Restive
Load and Solid State
with T/C Isolation
AC13 10
Control of Small
Electro Magnetic
Load ( <72VA)
AC14 6
Control of Small
Electro Magnetic
Load ( >72VA)
AC15 10
As per above Chart
Type of Contactor= AC7b
Size of Main Contactor = 100%X Full Load Current (Line).
Size of Main Contactor =100%x6 = 6 Amp.
Making/Breaking Capacity of Contactor= Value above Chart x Full Load Current (Line).
Making/Breaking Capacity of Contactor=8×6= 52 Amp.