Jusco Gaurav Kumar
Jusco Gaurav Kumar
FOR
SUMMMER TRAINING
AT
JAMSHEDPUR UTILITIES AND SERVICES COMPANY
LTD. (JUSCO), JAMSHEDPUR.
SUBMITTED BY:
NAME: GAURAV KUMAR
SEMESTER: 5TH
The word substation comes from the days before the distribution
system became a grid. As central generation stations became larger,
smaller generating plants were converted to distribution stations,
receiving their energy supply from a larger plant instead of using their
own generators. The first substations were connected to only one
power station, where the generators were housed, and were
subsidiaries of that power station.
AN IMAGE OF A SUBSTATION
All the equipments have their own functions in a substation .Some equipments
such as transformer are used for changing the voltage levels. While circuit
breakers, relays ,fuses are used as protection devices.Other equipments such as
CT , PT are used for measurement of current and voltage respectively. Circuit
breakers and isolators are used as switches for turning the circuit on /off. A
detailed description of each of the equipments used in a substation is given in this
section.
TRANSFORMER
POWER TRANSFORMERS
Power transformers are generally used in stepping up or down the voltage for
transmitting power or receiving power. Power transformers generally operate at
full load and hence are designed to have maximum efficiency at near full load.
These transformers are of very high rating (generally more than 200 MVA).These
transformers operate at very high voltages such as 200 KV,133KV,400 KV.These
transformers have only one primary and one secondary. No tapping is provided
.Since power transformers generally operate at full load so their performance is
usually judged by full load efficiency.
DISTRIBUTION TRANSFORMERS
These transformers are used for distribution of power to the consumer end.
These transformers are generally designed to have maximum all day efficiency.
These operate on lower voltages such as 33 KV,6.6 KV,415 V etc .These
transformers may be provided with tap changing secondary. These transformers
operate at very low loads most of the times of the day. So to increase all day
efficiency distribution transformers are designed to have very low core loss. The
performance of these transformers is judged by all day efficiency.
CORE
MAIN TANK
Main tank of the transformer consists of core wound with windings immersed
in the oil. Oil acts like an insulating medium and is also important for cooling
of the transformer.
CONSERVATOR TANK
Whenever electrical distribution transformer is loaded, the temperature of the transformer
insulating oil increases, consequently the volume of the oil is increased. As the volume of the oil
is increased, the air above the oil level in conservator will come out. Again at low oil
temperature; the volume of the oil is decreased, which causes the volume of the oil to be
decreased which again causes air to enter into conservator tank. The natural air always
consists of more or less moisture in it and this moisture can be mixed up with oil if it is allowed
to enter into the transformer. The air moisture should be resisted during entering of the air
into the transformer, because moisture is very harmful for transformer insulation. A silica gel
breather is the most commonly used way of filtering air from moisture.
EXPLOSION VENT
This is nothing but a bent pipe with thin aluminum diaphragms at both ends. A wire mesh is
provided at lower end of the explosion vent to prevent the pieces of rutted diaphragm from
entering the tank. A wire mesh is also provided at upper end of vent pipe to protect mechanical
damages of upper diaphragm. Near the lower end, a small oil level indicator is provided to lower
diaphragm ruptures; transformer oil rises in the vent pipe and is visible through the indicator
indicating the failure of the lower diaphragm. If even after brushing the lower diaphragm, there is
enough pressure and is not reduced, the upper diaphragm then bursts out to give way to release
the inside pressure
RADIATOR UNIT
This cycle is repeated continuously till the load is connected to the transformer. Dissipation of heat
in the
transformer radiator; can be accelerated further by force air provided by means of fans. These fans
are fitted either on the radiator bank itself or fitted nearby the bank but all the fans must be faced
towards the radiator. Sometime, the cooling rate of convectional circulation of oil is not sufficient.
That time an oil pump may be used for speeding up oil circulation.
BUCHHOLZ RELAY
Buchholz relay in transformer is an oil container housed the connecting pipe from main tank to
conservator tank. It has mainly two elements. The upper element consists of a float. The float is
attached to a hinge in such a way that it can move up and down depending upon the oil level in the
Buchholz relay Container. One mercury switch is fixed on the float. The alignment of mercury
switch hence depends upon the position of the float. The lower element consists of a baffle plate and
mercury switch. This plate is fitted on a hinge just in front of the inlet (main tank side) of Buchholz
relay in transformer in such a way that when oil enters in the relay from that inlet in high pressure
the alignment of the baffle plate along with the mercury switch attached to it, will change.
TAP CHANGER
A tap changer on a transformer is the device that can connect different taps on the transformer
to the supply voltage. This device can regulate the output voltage on the transformer in steps
by connecting or disconnecting part of the windings on the transformer. The tap changer
basically allows you to fine tune the output voltage of the transformer, loading on the grid may
result in a drop in the line voltage at a substation and this may require you to change the
transformers winding ratio in order for the output to be within specification to your client.
Temperature indicators of transformer can also trip the circuit breakers associated with the
power transformer when the temperature of oil or winding reaches a predetermined
limit.These devices also control the cooling system of transformer. Switch on the cooling
equipment when the winding attains a preset high temperature and switch it off when the
temperature drops by an established differential.
This device measures the LV and HV winding temperature. A winding temperature indicator or
WTI is also used as protection of transformer.
LIGHTENING ARRESTER
TYPES OF LIGHTENING STROKES
STROKE B
INDIRECT STROKE
Indirect stroke occurs due to electrostatic charges induced on the
electrical equipments by the charged clouds. Suppose cloud P has
positive charge and it is above overhead wires .Then P induces
negative charge on top of the wire and positive on the side further
away from the cloud .Positive charge on wire flows to earth slowly
through the pole or leaks through insulator. Now if cloud P gets
discharged due to cloud to cloud or some other lightening. The
negative charge on the wire becomes free and it moves in both
directions like a travelling wave and ultimately goes to the earth
through the pole. Thus current through the wires increase
considerably due to indirect lightening strike.
WAVE TRAP
A transmission line carries mainly two types of signals which are
If communication signals being transmitted from generating stations and other substations
enter the bus it may damage the equipments .To prevent this power signals are separated
from communication signals using wave trap. A wave trap is parallel inductor capacitor
tuned circuit.It is designed to resonate at the frequency of the communication signals and
hence pose high impedance for them. So it blocks the communication signals from entering
the bus. It only sends power signals to the bus while communication signal is sent
separately to the control room. These communication signals help substations and
generating stations to communicate among themselves without the need of separate cable
for carrying these signals or any telecom company network.
CURRENT TRANSFORMER
A current transformer is generally used for measuring large currents. The
currents flowing in the bus and the transmission line is so large that directly
measuring it with an ammeter may damage the instrument. Current
transformers along with potential transformers are known as instrument
transformers. A current transformer lowers down the current to be measured
by transformer action and hence is used for measuring purpose and in
protective relays.The secondary winding of a current transformer should
never be kept open as a very large voltage may appear across the secondary
terminals damaging the insulation and increase the risk of an electric shock
The numbers inside the bracket indicate the error of the instrument
transformer. Hence a 5 CT has an error of +-5%.These transformers saturate
easily.
Fig: Current transformer for each of the three phases of power system
CIRCUIT BREAKER
A circuit breaker is like a electrical switch for switching on/off circuits
containing high amounts of flowing currents. It operates on the basis of signal
given by a relay in case of fault or when someone switches it on/off .A circuit
breaker also minimizes arc formation during change of state (on/off).A circuit
breaker also acts as an arc quenching device. Different medium are used for
arc quenching depending on voltage levels.
SF6 is used as arc quenching medium for voltages >33kV and less than 440
kV.The switching time of a circuit breaker should be as small as possible.
ISOLATOR
An isolator is a mechanical device used for isolating a part of the circuit which
has to be maintained .It is operated manually unlike circuit breakers which
can act on the basis of commands given by relay. An isolator also earths the
isolated part of circuit so that the charges stored in the circuits are completely
discharged before maintenance can begin also isolator are provided with pad
locks to prevent inadvertent operation. Also isolators are off load device
means that they can be switched on/off only when the devices to be isolated
are off or when no current is flowing through the branch to be isolated.
Special precautions should be taken to ensure that the branch to be isolated
carries no current before isolator is turned off to prevent arc. Isolators are not
used for normally controlling the circuit but are used only for isolating the
part of the circuit to be maintained.
USE OF SCADA IN SUBSTATIONS
SCADA stands for Supervisory Control And Data Acquisition. It is used in
automation of power distribution network. When we talk about automation of
power distribution network we mean that all the substations as well as switch
rooms associated with the power distribution can be controlled and
monitored from a central location. SCADA system is a industrial automation
system used to collect data from sensors and instruments located at remote
sites and process them and sends supervisory command to the circuit
breakers and other field devices located at remote sites accordingly .A SCADA
system has PLC’s,RTU’s,FRTU’s which acts as a device for converting analogue
output of the the circuit breakers to digital output which is sent to the cloud
storage through GPRS or fiber optics from here it goes to gateway server
which distributes data to warehouse server(for storage for future use), active
directory server defines the access rights of different users for example if any
user connects to the scada network then he will not be able to access the data
meant for administrator. From the field devices data goes to front end server
and from there it goes to application server which sends it to workstation
(computer which has ws500 SCADA software installed as well as connected
with HMI ) .A De server is used to modify Single Line Diagram of the various
substations in case the substation has to be modified. A SCADA network may
also have a thin client server , a thin client server can be accessed through
internet ,this server makes data related to the status of various circuit
breakers and other information accessible through internet.
Historian
A supervisory computer system: gathering (acquiring data) on the
process and sending commands (control) to the SCADA system.
Communication infrastructure involves connecting the supervisory
system to remote terminal unit.
APPLICATION SERVER
An application server is a component-based product that resides in the middle-
tier of a server centric architecture. It provides middleware services for security
and state maintenance, along with data access and persistence.
BACK UP SERVER
Server running Active Directory Domain Services (AD DS) is called a domain controller. It
authenticates and authorizes all users and computers in a Windows domain type network—
assigning and enforcing security policies for all computers and installing or updating software.
SCADA SYSTEM
Protection equipments such as Automation Equipments:
Relays, circuit breakers and
measuring instruments such as RTU’S, FRTU’S
Ammeter, voltmeters.
server
Gateway
server GPRS
HMI
Cloud (Tata
Communicati
on)
CONCLUSION
The project contains information about the various equipments
used in an electric substation. From this project we get to know the
importance of each of the components and their functions. Through
this project I gained practical knowledge about Lightening arresters,
relays, transformers and other equipments. It was very interesting
for me to see how SCADA system is used in JUSCO to monitor and
give commands to the remote substations. I also saw various types
of cables used in substations such as three core cables, single core
cables and other cables of different cross sections. As a whole, the
summer training at JUSCO was a wonderful experience and a great
opportunity for me to gain practical knowledge in my core subject.