EPSY (Earthfault Protection On the other hand, devices and of earth faults for the operators
System) is the comprehensive systems of traditional earth of medium-voltage networks.
earth fault protection system fault protection engineering It performs for both high and
from Trench Austria, designed can not meet these stringent low impedance faults to earth,
specifically for compensated requirements. including difficult intermittent
networks. Compared with faults where frequent
other methods of power system The protection system EPSY restrikes occur.
earthing, earth fault com- consists of:
pensation offers major ad- The electronic components of
vantages for the safety of per- - an arc suppression coil EPSY and their configuration
sonnel, the security of supply (ASC, continuously possibilities are summarised
and the reduction in conse- adjustable type), in the following pages.
quential damage during earth - an automatic compen-
faults. sation controller and
However, compared to alter- - an earth fault detection
native earthing methods, earth device (selective, highly
fault compensation demands sensitive type).
the highest requirements on
the capability and reliability of The enhanced approach for the
the protection devices for de- selective detection of high-
tecting and locating earth impedance earth faults, which
faults. These standards are met is integrated in the EFD20
by Trench Austria’s EPSY system. device, offers reliable detection
Fig. 2 Earthfault Compensation Controller EFC20i with 19‘‘-rack mounted Current Injection Device ECI
The Earthfault Compensation Controller • The operation mode EFC20i requires the
EFC20i uses a current injection into the installation of the current injection device
zero-sequence system for determination of ECI (see also page 10).
the resonance point. Therefore a detuning • For details see EFC20/EFC20i brochure.
of the Arc Suppression Coil is no longer
necessary for the calculation procedure.
3
Earthfault Detection Device EFD20 / EFD20c
4
Device concept EFD20 / EFD20c
5
Operating
• easy operating by
means of
- integrated display
- scroll wheel
- clearly arranged
function keys
Fig. 4 Operating panel of compact device EFD20c
• clear menu guide with
„help“ – text
• automatic, adaptive
menu according to
activated software options
Fig. 5 EFDTerm
6
Software Software Options
• software-update via
serial interface
7
Technical Data EFD20 / EFD20c
Expansion
Basic device
unit
Hardware
operation
24 line display, 53 symbols per line, 6 keys, scroll wheel x x -
digital inputs
potential free contacts, 24 ... 230 V AC/DC 16 ... 1123 16 ... 1123 16 ... 1443
digital outputs
potential free contacts, 230 V AC/DC, max 5 A continuous 16 ... 1123 16 ... 1123 16 ... 1443
max contact current closing rating 1000 VA
max contact interrupting rating 30 VA
auxiliary voltage
230 V AC/DC x x x
110 V DC (x)* (x)* (x)*
(other voltages upon request)
1
current inputs allocateable via menu for zero sequence current measurement resp. for current injection (max. 3 pcs.)
2
in steps of 4 available (8, 12, 16, ... 32)
2
depending on the system configuration; in steps of 16
*optional
8
Basic device Software options
Software
detection of low- and high-impedance earth faults x x
automatic earth fault compensation control of stepless x
adjustable plunger core coils
terminal program EFDTerm for Windows x x
automatic adaptive menu x x
non-volatile measurement buffer x x
3 menu access levels for users x x
software-update via serial interface x x
implemented PLC-functionality x x
fault location at loop configuration x x
automatic reclosing unit x x
SCADA x x
predefined coil position1 x
automatic resistor control 1
x
fix coil control 1
x
ideal compensation (v=0)1 during earth fault condition x
automatic switching if Vo exceeds Vmax 1
x
Mechanical data
dimensions width 483.0 mm
height 266.0 mm
depth 350.0 mm
weight approx. 13 kg
temperatures operating 0°C ... +40°C
storage -25°C ... +55°C
transport -25°C ... +70°C
humidity class G acc. to DIN 40040
protection class IP20
1
for details see EFC20/EFC20i brochure
9
Current Injection Device ECI
The Current Injection Device The current injection into the Following designs are available:
ECI is used to produce zero-sequence system is usually
differential measurement done via a suitable power • cubicle for indoor or
values by means of the current auxiliary winding of the arc outdoor design
injection into the zero- suppression coil. • mounting plate for
sequence system. This approach The Current Injection Device installation in an
is used by both the Earthfault ECI essentially consists of a existing cubicle
Compensation Controller transformer, capacitors for • 19‘‘-rack mounted (3U)
EFC20i and the Earthfault current limiting, relays, control-
Detection Device EFD20. and signal contacts.
Fig. 6 ECI in conventional design (indoor design, Fig. 7 ECI 19‘‘-rack mounted
outdoor design and design on mounting
plate available )
10
Examples for System Configurations
Single-busbar configuration
14
Trench Austria GmbH
Paschinger Straße 49, Postfach 36
A-4060 Linz-Leonding/Austria
Phone +43.732.6793-0
Fax +43.732.67 13 41
email [email protected]
Trench Limited
Instrument Transformer Division
390 Midwest Road, Scarborough
Ontario, Canada M1P 3B5
Phone +1.416.751-8570
Fax +1.416.751-6952
email [email protected]
Trench Limited
Coil Product Division
71 Maybrook Drive, Scarborough
Ontario, Canada M1V 4B6
Phone +1.416.298-8108
Fax +1.416.298-2209
email [email protected]
Trench France S.A.
16, rue du Général Cassagnou
B.P. 70
F- 68302 St-Louis/France
Phone +33.3.89 70 23 23
Fax +33.3.89 67 26 63
email [email protected]
Trench Germany GmbH
Nürnberger Straße 199
D-96050 Bamberg/Germany
Phone +49.951.1803-0
Fax +49.951.1803-224
email [email protected]
Trench Switzerland AG
Lehenmattstraße 353
CH - 4028 Basel/Switzerland
Phone +41.61.315 51 11
Fax +41.61.315 59 00
email [email protected]
Trench (UK) Limited
South Drive
Hebburn
Tyne & Wear
NE 31 1 UW
Phone +44-191-483-4711
Fax +44-191-430-0633
www.trenchgroup.com email [email protected]
Trench Brasil LTDA
Via Expressa de Contagem, 2685
CEP 32370-485
Contagem, Minas Gerais/Brasil
Phone +55.31.391-5959
Fax +55.31.391-1828
email [email protected]
Trench China Limited
3658 Jiang Cheng Road
Minhang, Shanghai 200245
P.R. China
Subject to change without notice Phone +86.21.64630088
09.05
Fax +86.21.64637828
E 667 email [email protected]