Structural Design Basic Report
Structural Design Basic Report
PROJECT BRIEF
This report sets out the basic parameters used for the structural design of the
proposed construction of Ground plus one proposed villa ‘HAVEN’ at Ayanambakkam,
Thiruverkadu. This has been updated to incorporate the current information on the
structure.
STRUCTURAL SYSTEM
The foundation System comprises of deep foundation (pile) is adopted as per soil
Test report.
LOAD DATA
On the basis of intended occupancy and uses, the loading shall be base on
IS: 875 (PART II)
Wind loads for design of structures shall be based on the design wind
speeds arrived on IS: 875 (PART III)
The parameters for calculation of design wind speed as per IS: 875
(PART III) are as follows.
Risk coefficient, K1
: 0.6 x 33.52
: 0.673 kN/m2
IS 1893-2002.
Zone : III
Importance factor : 1
The proposed building is designed using the limit state method with
appropriate factors as per IS: 456-2000.
Load Combination
1.0 (DL+LL)
1.0(DL+WLX)
1.0(DL-WLX)
1.0(DL+WLZ)
1.0(DL-WLZ)
1.0(DL+SLX)
1.0(DL-SLX)
1.0(DL+SLZ)
1.0(DL-SLZ)
1.0DL+0.8LL+0.8WLX
1.0DL+0.8LL-0.8WLX
1.0DL+0.8LL+0.8WLZ
1.0DL+0.8LL-0.8WLZ
1.0DL+0.8LL+0.8SLX
1.0DL+0.8LL-0.8SLX
1.0DL+0.8LL+0.8SLZ
1.0DL+0.8LL-0.8SLZ
Where
DL - Dead load
LL - Live load
ADDITIONAL CRITERIA
2. The lateral loads include wind loads and earthquake loads, seismic loads of medium
And moderate intensity of Zone III is considered for analysis and design puropose.
4. The super structure members are designed for actual flexure, shear and forces.
5. The structure is analyzed for specific loads (Dead and live loads) and for the load