Voltage Drop Calculation 1

The document contains calculations for voltage drop in multiple circuits connected to panel PB NO.3. It provides information on the circuit number, wire size and length, load type and current, and calculates the voltage drop based on resistance and reactance values from tables. The calculations show voltage drops between 0.042% to 0.313%, below the allowed 5% limit.

Uploaded by

Honnie Mae Padua
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views

Voltage Drop Calculation 1

The document contains calculations for voltage drop in multiple circuits connected to panel PB NO.3. It provides information on the circuit number, wire size and length, load type and current, and calculates the voltage drop based on resistance and reactance values from tables. The calculations show voltage drops between 0.042% to 0.313%, below the allowed 5% limit.

Uploaded by

Honnie Mae Padua
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 8

VOLTAGE DROP CALCULATION

GENERAL INFORMATION:
PANEL: PB NO.3
CIRCUIT NO.: 1 TO 6
DISTANCE FROM THE PANEL BOARD: 30 METERS
SIZE OF WIRE USED: 2-5.5mm2 + 1-3.5mm2 THHN Cu. WIRE

LOAD DESCRIPTION:
TYPE OF LOAD: SPLIT TYPE, INVERTER ACU
NUMBER OF PHASE: 1Ø
HP RATING: 2.5HP
FULL LOAD CURRENT: 7.4A
OPERATING VOLTAGE: 230V
OPERATING FREQUENCY: 60HZ
POWER FACTOR: 0.8 LAGGING

FROM THE TABLE APPROXIMATE R, X AND ZOF 600V CABLES IN MAGNETIC DUCTS
RESISTANCE = 3.9 OHM/Km
REACTANCE = 0.207 OHM/Km

FOR THE GIVEN LENGTH OF THE LINE


RL = (3.9 OHM/Km) (0.025Km) = 0.117 OHM
XL = (0.207 OHM/Km) (0.025Km) = 0.00621 OHM
ZL = 0.117 + j0.00621 OHM
STEADY STATE CONDITION, PERCENT VOLTAGE DROP MUST NOT EXCEED 5%.

POWER FACTOR = O.8 LAGGING


Ɵ = 36.87°
IFL = 7.4 <-36.87° A

VLD = (IFL) (ZL)


VLD = (7.4 <-36.87°) (0.117 + j0.00621)
VLD = 0.867 <-33.83° V

VR = VS - VLD
VR =230 <0 - 0.867 <-33.83°
VR = 229.28 <0.1° V

%VD = [(VS – VR)/ VR] [100%]

%VD = [(230 – 229.28)/230] [100%]

%VD = 0.313%
VOLTAGE DROP CALCULATION

GENERAL INFORMATION:
PANEL: PB NO.3
CIRCUIT NO.: 7 & 8
DISTANCE FROM THE PANEL BOARD: 10 METERS
SIZE OF WIRE USED: 2-3.5mm2 + 1-3.5mm2 THHN Cu. WIRE

LOAD DESCRIPTION:
TYPE OF LOAD: DOCK LEVELLER
NUMBER OF PHASE: 1Ø
HP RATING: 2.5HP
FULL LOAD CURRENT: 8.15A
OPERATING VOLTAGE: 230V
OPERATING FREQUENCY: 60HZ
POWER FACTOR: 0.8 LAGGING

FROM THE TABLE APPROXIMATE R, X AND ZOF 600V CABLES IN MAGNETIC DUCTS
RESISTANCE = 6.6 OHM/Km
REACTANCE = 0.224 OHM/Km

FOR THE GIVEN LENGTH OF THE LINE


RL = (6.6 OHM/Km) (0.010Km) = 0.066 OHM
XL = (0.224 OHM/Km) (0.010Km) = 0.00224 OHM
ZL = 0.066 + j0.00224 OHM
STEADY STATE CONDITION, PERCENT VOLTAGE DROP MUST NOT EXCEED 5%.

POWER FACTOR = O.8 LAGGING


Ɵ = 36.87°
IFL = 8.15 <-36.87° A

VLD = (IFL) (ZL)


VLD = (8.15<-36.87°) (0.066 + j0.00224)
VLD = 0.538 <-34.93° V

VR = VS - VLD
VR =230 <0 – 0.538<-34.93°
VR = 229.559<0.08° V

%VD = [(VS – VR)/ VR] [100%]

%VD = [(230 – 229.559)/ 230] [100%]

%VD = 0.192%
VOLTAGE DROP CALCULATION

GENERAL INFORMATION:
PANEL: PB NO.3
CIRCUIT NO.: 10
DISTANCE FROM THE PANEL BOARD: 1.5 METERS
SIZE OF WIRE USED: 2-3.5mm2 + 1-3.5mm2 THHN Cu. WIRE

LOAD DESCRIPTION:
TYPE OF LOAD: WATER PUMP
NUMBER OF PHASE: 1Ø
HP RATING: 2HP
FULL LOAD CURRENT: 12A
OPERATING VOLTAGE: 230V
OPERATING FREQUENCY: 60HZ
POWER FACTOR: 0.8 LAGGING

FROM THE TABLE APPROXIMATE R, X AND ZOF 600V CABLES IN MAGNETIC DUCTS
RESISTANCE = 6.6 OHM/Km
REACTANCE = 0.224 OHM/Km

FOR THE GIVEN LENGTH OF THE LINE


RL = (6.6 OHM/Km) (0.0015Km) = 0.0099 OHM
XL = (0.224 OHM/Km) (0.0015Km) = 0.0003 OHM
ZL = 0.0099 + j0.0003 OHM
STEADY STATE CONDITION, PERCENT VOLTAGE DROP MUST NOT EXCEED 5%.

POWER FACTOR = O.8 LAGGING


Ɵ = 36.87°
IFL = 12 <-36.87° A

VLD = (IFL) (ZL)


VLD = (12<-36.87°) (0.0099 + j0.0003)
VLD = 0.1189<-35.13° V

VR = VS - VLD
VR =230 <0 - 0.1189<-35.13°
VR = 229.903<0.02° V

%VD = [(VS – VR)/ VR] [100%]

%VD = [(230 – 229.903)/ 230] [100%]

%VD = 0.042%
VOLTAGE DROP CALCULATION

GENERAL INFORMATION:
PANEL: PB NO.3
CIRCUIT NO.: 11 &12
DISTANCE FROM THE PANEL BOARD: 6 METERS
SIZE OF WIRE USED: 2-3.5mm2 + 1-3.5mm2 THHN Cu. WIRE

LOAD DESCRIPTION:
TYPE OF LOAD: FUEL PUMP
NUMBER OF PHASE: 1Ø
HP RATING: 2HP
FULL LOAD CURRENT: 12A
OPERATING VOLTAGE: 230V
OPERATING FREQUENCY: 60HZ
POWER FACTOR: 0.8 LAGGING

FROM THE TABLE APPROXIMATE R, X AND ZOF 600V CABLES IN MAGNETIC DUCTS
RESISTANCE = 6.6 OHM/Km
REACTANCE = 0.224 OHM/Km

FOR THE GIVEN LENGTH OF THE LINE


RL = (6.6 OHM/Km) (0.006Km) = 0.0396 OHM
XL = (0.224 OHM/Km) (0.006Km) = 0.0013 OHM
ZL = 0.0396 + j0.0013 OHM
STEADY STATE CONDITION, PERCENT VOLTAGE DROP MUST NOT EXCEED 5%.

POWER FACTOR = O.8 LAGGING


Ɵ = 36.87°
IFL = 12 <-36.87° A

VLD = (IFL) (ZL)


VLD = (12<-36.87°) (0.0396 + j0.0013)
VLD = 0.476<-34.99° V

VR = VS - VLD
VR =230 <0 - 0.476<-34.99°
VR = 229.611<0.07° V

%VD = [(VS – VR)/ VR] [100%]

%VD = [(230 – 229.611)/ 230] [100%]

%VD = 0.169%