Test Report: Request No. 14-01L-0719-TP

This test report summarizes the results of testing 101 electricity meters in Lot 1. The meters were of the GE I210 FM2S type with 3 wires and single phase. Each meter was tested for accuracy at full load, light load, and 50% power factor. The test results showed errors between -0.110% to 0.025% for all meters, within the acceptable criteria. The inspection found no non-conforming meters, so the entire lot of 101 meters was accepted.

Uploaded by

Robert Quiambao
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
349 views

Test Report: Request No. 14-01L-0719-TP

This test report summarizes the results of testing 101 electricity meters in Lot 1. The meters were of the GE I210 FM2S type with 3 wires and single phase. Each meter was tested for accuracy at full load, light load, and 50% power factor. The test results showed errors between -0.110% to 0.025% for all meters, within the acceptable criteria. The inspection found no non-conforming meters, so the entire lot of 101 meters was accepted.

Uploaded by

Robert Quiambao
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

Request No.

14-01L-0719-TP

TEST REPORT
INFORMATION ABOUT THE LOT
LOT NUMBER NUMBER OF METERS
1 101
OWNER OF LOT
NAME ADDRESS

DESCRIPTION OF METERS
BRAND TYPE WIRE PHASE TEST DIAL
AMPHERE VOLTAGE KH CONSTANT
G.E I210 FM2S 3 1 30 240 1.0 0000

CONDITION OF METERS
NEW REHABILITATED RECONDITIONED IF RECONDITIONED OR REPAIRED, INDICATE
OR REPAIRED ANY MODIFICATION MADE

WORKING STANDARD USED


BRAND TYPE OR MODEL SERIAL NUMBER
Scientific Columbus SC-10V 051005
TEST CALIBRATION REPORT INSPECTOR FINDINGS

% Error at %Error % Error at


Meter no./ Meter Serial Full Load. at Light Full Load, ERC’s ERC Seal &
Lot. No. Number or Unity PF Load. 50%PF Findings Sticker Serial
Company Number Unity PF (applicable Number
only to
singlephase
Meters)
1/1 40587461 -0.025 -0.086 PASSED 16A0966802
2/1 98062324 -0.073 -0.050 PASSED 16A0966800
3/1 71070360 -0.041 -0.288 PASSED 16A0966801
4/1 10804668 -0.084 -0.014 PASSED 16A0966793
5/1 11811710 -0.017 -0.287 PASSED 16A0966796
6/1 10804043 -0.024 -0.057 PASSED 16A0966794
7/1 10807766 -0.066 -0.086 PASSED 16A0966795
8/1 97031677 -0.054 -0.288 PASSED 16A0966230
9/1 65145666 -0.110 -0.317 PASSED 16A0966245
10/1 65010809 -0.054 -0.086 PASSED 16A0966246
LOT SIZE SAMPLE NO.OFNON-CONFORMING NO. OF NON- NO. OF NON-
SIZE METERS ACCEPTANCE CONFORMING METERS CONFORMITIE
CRITERIA REJECTION CRITERIA S
10 10 0 1 0

TYPE OF INSPECTION USED: LOT IS ACCEPTED: LOT IS REJECTED:


NORMAL √
CERTIFIED BY:

GLENN DJ DE JESUS/ January 15,2018


Signature over printed name / date