Technical Data: Thyristor Control Unit - Compact Design
Technical Data: Thyristor Control Unit - Compact Design
3-phase control
Fully controlled
Phase-angle and burst control
(switchable)
Multi control signal
Industrial design
Technical data
1. Functions 8a. Control contact 2-7-8
Operation modes Function: set point adjustment (direct proportional
PH Phase-angle setting of firing angle)
SP Burst control Input impedance: 500Ω/50kΩ (switchable)
Actuation: potentiometer 2.5 to 47kΩ
2. Indicators (not included)
LED 1 green Ready for operation Line length: max. 10m, twisted pair
LED 1 red: General fault
LED 2 green: Device activated 8b. Control contact 7-8
LED2 orange: Device activated and working Function: set point adjustment (direct proportional
Subject to alterations and errors
Technical data
13. Power circuit 15. Ambient conditions
Supply voltage: 3~ 110 to 500V terminals L1-L2-L3 Ambient temperature: -25 to +55°C (according toIEC 68-1)
Tolerance: 10% Storage temperature: -25 to +75°C
Rated frequency: 48 to 63Hz Transport temperature: -25 to +75°C
Relative humidity: 5% to 95% not condensing
14. Power classes (according toIEC 721-3-3 class 3K3)
TST3 05 Rated current 3~ 5A Pollution degree: 2 (according toIEC 664-1)
TST3 15 Rated current 3~ 15A
TST3 25 Rated current 3~ 25A
TST3 35 Rated current 3~ 35A
TST3 50 Rated current 3~ 50A
Functions
The TST3 offers five types of setpoint adjustment.l Burst control:
For power control the device clocks the output voltage. Depending
Potentiometer actuation on the setting of the remote control potentiometer, the output of the
Direct or indirect (if inverse wired) setting of firing angle via potentio- device is disconnected from the power supply for short periods. Over
meter. a control period therefore, the power draw of the connected load
is reduced by the value set on the potentiometer. Since the load is
Signaling voltage 0-10V switched on and off only at zero crossing, the supply system is not
Direct setting of firing angle proportional to value of applied signaling subjected to additional reactive power components or harmonics by
voltage 0-10V the ESGT-SP(N). This power control can only be used for slow-acting
loads (such as heating elements) as the operation of loads such as
Inverted signaling voltage10-0V motors and lighting systems is disturbed by the off-times.
Indirect setting or firing angle indirect proportional to value applied at
signaling input.
Supply voltage
Signaling current 0-20mA
Direct proportional setting of firing angle via 0-20mA signaling current.
Phase-angle control:
A thyristor bridge is set by the remote control potentiometer so that
the thyristor switches the connected loads to the supply network in
every sinusoidal half-wave only when the selected voltage level is
reached. This produces a reduced rms voltage and therefore a small-
er power draw by the load. This type of power control is suitable for all
types of ohmic and inductive loads.
In three-wire systems (without a neutral conductor) the output power
can be infinitely regulated from around 20% to 100%; in four-wire sys-
tems (3~/N) it can be infinitely regulated from around 5% to 100%.
Supply voltage
Connections
Power circuits:
Phase-angle or burst control connection in 4-wire Burst control connection
supply systems in 3-wire supply systems
L1
L2
L1 L3
L2 N
L3 PE
N
PE
F 1-3 F 01
F 1-3 F 01
L1 L2 L3 PE 22 24
L1 L2 L3 PE 22 24
TST3
TST3
T1 T2 T3
T1 T2 T3
Subject to alterations and errors
L1 L2 L3 PE
L1 L2 L3 N PE
Load
3~400V
Load without neutral
wire connection
Activation
Fan Activation
TST3
Reset
Reset
not included
PTC or strap
not included
PTC or strap
Setpoint device
(SPC, controller etc.)
Setpoint device
(SPC, controller etc.)
Control circuit:
140mm
0 to +10V
Mass
55mm
Mass
+10 to 0V Device locked
Device locked
Dimensions
Connections
180mm
Master alarm
Signaling outputs
Device in operation
Signaling outputs
Device in operation
Actuation via signaling voltage 0-10VDC
Supply voltage
135mm
Supply voltage
www.tele-power-net.com
Activation
Activation
Reset
Reset
not included
PTC or strap
PTC or strap
Setpoint device
(SPC, controller etc.)
Mass
Device locked
Device locked
Signaling outputs
Device in operation
Signaling outputs
Device in operation
Actuation via potentiometer TELE R20
Actuation via signaling current 0-20mA