12.primary Pump Head Calculation

This document provides information about primary pump head calculations for a piping system. It includes a table with pipe section descriptions, sizes, flow rates, and lengths. It then shows calculations for head loss through different pipe fittings and valves. The total head loss is calculated to be 35.14 feet or 10.71 meters of water. Based on this, the required pump horsepower is calculated to be 1.60 HP.

Uploaded by

Zain Shariff
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
410 views4 pages

12.primary Pump Head Calculation

This document provides information about primary pump head calculations for a piping system. It includes a table with pipe section descriptions, sizes, flow rates, and lengths. It then shows calculations for head loss through different pipe fittings and valves. The total head loss is calculated to be 35.14 feet or 10.71 meters of water. Based on this, the required pump horsepower is calculated to be 1.60 HP.

Uploaded by

Zain Shariff
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

PRIMARY PUMP HEAD CALCULAT

SIZE(DIA) FLOW STRAIGHT LENGTH


DESCRIPTION OF THE PIPE
SECTION RUN
INCH LPS GPM MT FT

A-B PUMP DISCHARGE LINE 4 9.7 153.6 0.91 3

B-C PUMP DISCHARGE HEADER 4 9.7 153.6 1.11 3.6

C-D CHILLER SUCTION HEADER 4 9.7 153.6 5.96 19.6

D-E CHILLER SUCTION LINE 4 9.7 153.6 0.91 3

CHILLER

E-F CHILLER DISCHARGE LINE 4 9.7 153.6 0.91 3

F-G CHILLER DISCHARGE HEADER 4 9.7 153.6 5.87 19.3

G-H BYPASS LINE 4 9.7 153.6 6.63 21.7


H-I PUMP SUCTION HEADER 4 9.7 153.6 0.90 2.9

I-J PUMP SUCTION LINE 4 9.7 153.6 0.91 3


HP=((GPM X HEAD IN FT. O
P HEAD CALCULATION
EQT. HEAD LOSS FRICTION LOSS
TOTAL EQT. TOTAL EQT.
LENGTH OF LENGTH
VALVES & FITTINGS QTY OF LENGTH (FT)
FITTINGS FITTING (FT)
(FT) FT. OF H2O/100 IN FT. OF H2O

90° ELBOW 1 10
FLEXIBLE CONNECTOR 1 20
190 193 1.89 3.64
SWING CHECK VALVE 1 40
DOUBLE REG. VALVE 1 120
TEE JOINT 3 21 63 66.6 1.89 1.26
TEE JOINT 2 21
52 71.6 1.89 1.35
90° ELBOW 1 10
GATE VALVE 1 4.5
M.B.V 1 4.5
39 42 1.89 0.79
90° ELBOW 1 10
FLEXIBLE CONNECTOR 1 20
15.00
FLEXIBLE CONNECTOR 1 20
90° ELBOW 1 10 150 153 1.89 2.89
DOUBLE REG. VALVE 1 120
TEE JOINT 4 21
94 113.3 1.89 2.14
90° ELBOW 1 10
TEE JOINT 1 21 21 42.7 1.89 0.81
TEE JOINT 2 21 42 44.9 1.89 0.85
ISOLATING VALVE 1 4.5
STRAINER 1 60
94.5 97.5 1.89 1.84
FLEXIBLE CONNECTOR 1 20
90° ELBOW 1 10
HEAD LOSS IN FT OF WG 30.56
SAFETY FACTOR 15% 4.58
TOTAL HEAD LOSS IN FT OF WG 35.14
TOTAL HEAD LOSS IN METER 10.71
HP=((GPM X HEAD IN FT. OF WG) X SP. GRAVITY OF WATER)/(3960 X % OF EFFICIENCY) 1.60