The document provides details on three power system analysis problems involving calculations for line and load impedances, voltages, currents, and power in balanced and unbalanced three-phase systems. The problems include conversions between wye and delta connections and determining values at different points in the system.

Uploaded by

Rodrigo Babijis
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
223 views

ECE 476 - Power System Analysis Fall 2017: Homework 2

The document provides details on three power system analysis problems involving calculations for line and load impedances, voltages, currents, and power in balanced and unbalanced three-phase systems. The problems include conversions between wye and delta connections and determining values at different points in the system.

Uploaded by

Rodrigo Babijis
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

ECE 476 – Power System Analysis Fall 2017

Homework 2

In-class quiz: Thursday, September 14, 2017

Problem 1. A three-phase line, which has an impedance of (2 + j4) Ω per phase, feeds two balanced three-phase
loads that are connected in parallel. One of the loads is Y-connected with an impedance of (30 + j40) Ω per phase,
and the other is ∆-connected with an impedance of (60 – √ j45) Ω per phase. The line is energized at the sending end
from a 60-Hz, three-phase, balanced voltage source of 120 3 V (rms, line-to-line). Determine:
First, convert the ∆-connected load to its Y -connected equivalent:
60 − j45
Z̄2 = = 20 − j15 Ω
3
1. The current, real power, and reactive power delivered by the sending-end source.
The per-phase total impedances of the line and loads is
 −1
1 1
Z̄ = Z̄line + Z̄1 ||Z̄2 = 2 + j4 + + = 24∠0◦ Ω.
(30 + j40) (20 − j15)
Then, the source current is
V̄ 120∠0◦
I¯s = = = 5∠0◦ A.
Z̄ 24◦
The complex power delivered by the source is
S̄s = 3V̄ I¯∗ = 3(120∠0◦ )(5∠0◦ ) = 1800∠0◦ VA,
with Ps = 1800 W and Qs = 0 MVar.
2. The line-to-line voltage at the load.
The phase voltage at the load is
V̄L = V̄s − Z̄line I¯s∗ = 120∠0◦ − (2 + j4)(5∠0◦ ) = 110 − j20 V = 111.80∠ − 10.3◦ V.
Therefore the line-to-line voltage at the load is
√ √
V̄L,L−L = 3V̄L ∠30◦ = 3111.80∠ − 10.3◦ + 30◦ = 193.65∠19.7◦ V

3. The current per phase in each load.


The per-phase current through the Y -connected load is
V̄L 111.80∠ − 10.3◦
I¯1 = = = 2.236∠ − 63.4◦ A.
Z̄1 30 + j40
The per-phase current through the Y -connected equivalent of the ∆-connected load is
V̄L 111.80∠ − 10.3◦
I¯2,φ = = = 4.472∠26.57◦ A.
Z̄2 20 − j15
So the per-phase current of the ∆-connected load is
I¯2,φ 4.472
I¯2,∆ = √ ∠30◦ = √ ∠26.57◦ + 30◦ = 2.582∠56.57◦ A.
3 3

1
4. The total three-phase real and reactive powers absorbed by each load and by the line.
The 3φ complex power absorbed by the Y -connected load is
S̄1 = 3V̄L I¯1∗ = 3(111.80∠ − 10.3◦ )(2.236∠ − 63.4◦ )∗ = 450.3 + j599.7 VA.
The 3φ complex power absorbed by the ∆-connected load is
S̄2 = 3V̄L,L−L I¯2,∆

= 3(193.65∠19.7◦ )(2.582∠56.57◦ )∗ = 1200 − j900 VA.
The complex power absorbed by the line impedance is
S̄line = 3Z̄line I 2 = 3(2 + j4)52 = 150 + j300 VA.
The sum of the three quantities above is 1800 + j0 VA, which matches the value obtained in Part 1.
Check that the total three-phase complex power delivered by the source equals the total three-phase
power absorbed by the line and loads.

Problem 2. Two three-phase generators supply a three-phase load through separate three-phase lines. The load
absorbs 30 kW at 0.8 power factor lagging. The line impedance is (1.4 + j1.6) Ω per phase between generator G1
and the load, and (0.8 + j1) Ω per phase between generator G2 and the load. If generator G1 supplies 15 kW at 0.8
power factor lagging, with a terminal voltage of 460 V line-to-line, determine:
1. The voltage at the load terminals.
The complex power supplied by G1 is
15
S̄1,3φ = ∠ cos−1 0.8 = 18.75∠36.87◦ kVA.
0.8
The current supplied by G1 is
 ∗
 ∗ ◦
S̄1,3φ 18.75∠36.87 
I¯G1 = =   = 23.53∠ − 36.87◦ A.
3V̄G1 460
3 √3 ∠0 ◦

So the phase voltage at the load is


 
460
V̄L = V̄G1 − Z̄l1 I¯G1 = √ ∠0◦ − (1.4 + j1.6)(23.53∠ − 36.87◦ ) = 216.9∠ − 2.74◦ V,
3
and the line-to-line voltage at the load is

V̄L,L−L = 3(216.9)∠27.26◦ V,

2. The voltage at the terminals of generator G2.


The complex power absorbed by the load is
30
S̄L,3φ = ∠ cos−1 0.8 = 37.5∠36.87◦ kVA.
0.8
The current into the load is
∗  ∗
37.5∠36.87◦

¯ S̄L,3φ
IL = = = 57.63∠ − 39.61◦ A.
3V̄L 3(216.9∠ − 2.74◦ )
The current into the load is the sum of the currents supplied by the two generators, so
I¯G2 = I¯L − I¯G1 = 57.63∠ − 39.61◦ − 23.53∠ − 36.87◦ = 34.15∠ − 41.5◦ A.
And finally the voltage at the terminal of G2 is the sum of the voltage drop across the load and Z̄l2 :
V̄G2 = V̄L + Z̄l2 I¯G2 = 216.9∠ − 2.74◦ + (0.8 + j1)(34.15∠ − 41.5◦ ) = 259.8∠ − 0.638◦ V.
And the line-to-line voltage at the terminal of G2 is

V̄G2 ,L−L = 3(259.8)∠29.36◦ V.
3. The real and reactive power supplied by generator G2. The complex power supplied by G2 is

S̄G2 ,3φ = 3V̄G2 I¯G



2
= 3(259.8∠ − 0.638◦ )(34.15∠41.5◦ ) = 20.1 + j17.4 kVA.

Hence, the real power supplied is PG2 ,3φ = 20.1 kW and the reactive power supplied is QG2 ,3φ = 17.4 kVar.

Problem 3. An unbalanced three-phase, Y -connected power system is shown in the figure below. The three phases
have voltages V a = 100∠0◦ V, V b = 100∠ − 120◦ V, V c = 100∠120◦ V. The impedances of loads A, B, C are
Z a = 10 Ω, Z b = −j10 Ω, Z c = j10 Ω.

1. What are the currents of each phase I a , I b , I c ?


Va 100∠0◦ Vb 100∠0◦ Vc 100∠0◦
Ia = Za
= 10 = 10∠0◦ A, I b = Zb
= −j10 = 10∠ − 30◦ A, I c = Zc
= j10 = 10∠30◦ A

2. What is the current on the neutral line I n ?



I n = I a + I b + I c = 10∠0◦ + 10∠ − 30◦ + 10∠30◦ = (10 + 10 3)∠0◦ = 27.3∠0◦ A
3. What are the line voltages V ab , V bc , V ca ?
√ √ √
V ab = 100 3∠30◦ = 173∠30◦ V, V bc = 100 3∠ − 90◦ = 173∠ − 90◦ V, V ca = 100 3∠150◦ = 173∠150◦ V

4. Provide the phasor diagram of the phasors including the phase voltages, line voltages, phase currents and the
current on the neutral line.

Figure 1: phasor diagram