Appendix L Electrical Method of Procedure: University of Nevada, Reno Campus Design & Construction Standards
Appendix L Electrical Method of Procedure: University of Nevada, Reno Campus Design & Construction Standards
APPENDIX L
ELECTRICAL METHOD OF
PROCEDURE
The following appendix includes information and standard drawings
that are diagrammatic and are used only to convey intent.
Work to be performed: UNR to replace wire to main switch gear for new water heater,
tighten and clean gear and panels in Ross Hall and Jones Center.
Proper PPE
Category 2 and 4 / 8 cal. and 40 cal.
Fluke volt meter
Lock out tag out, lock out tag out tree
Equipment
LED lights
Socket sets
Rags
5-point sockets
Torque Wrenches
Portable Generators
Cords
Vacuums
Torque specs.
Hot Sticks
Rope with a hook
Morning meeting at 6:30 am in Electric shop Saturday 7-23-2016
Review Project with UNR MOP
Verify Rotation at 120/208 volt disconnect on main transformer with Category 2/8
cal2 gear (James and Steve).
Power shut down 7:00 am with Joe from Contractor X on site in case switch does
not work
UNR Open Main breakers in Ross and Jones and LOTO (Steve and James).
UNR open PB- 13, open, close, open 4160-volt switch to Ross and Jones with
Category 4/40 cal2 gear (Steve and James).
Close vault lid, LOTO PB-13.
UNR Verify power is de-energized to Ross and Jones with Category 2/8 cal2 gear
(Steve and James).
If PB- 13 switches correctly, Joe from Contractor X can leave.
7:00 to 3:00 pm.
UNR to pull wire for water heater @ Ross Hall (Brent and Cimothy).
UNR torque and cleaning switch gear @ Ross Hall (Brent and Cimothy).
Check all Emergency lights in Ross and Jones (James, Steve).
UNR to torque and clean panels @ Ross Hall and Jones (James, Steve, Brent,
and Cimothy).
UNR clean and torque transformer (not the porcelain bushings) T- RHJV.
UNR exercise all breakers in both buildings.
Make drawing of conduits in PB-13 for FS Electrical Engineer.
Re-energize power 3:30 pm or sooner
UNR contact control shop (997-9652) before we re-energize
UNR remove LOTO from PB-13
UNR close switch at PB-13 with Category 4/40 cal2 gear (James and Steve)
UNR Verify three phase power Ross and Jones with Category 2/8 cal2 gear
(James and Steve).
UNR close Main breakers @ Ross and Jones with Category 2/8 cal2 gear (James
and Steve).
UNR confirms power is restored to both buildings.