Design Analysis
Design Analysis
General Lighting
Total m2 of habiltable living area: 168 x 24 VA/m2
Load: (See Table 2.20.2.3 PEC 2017)
Provide atleast two (2) 15A Lighting circuits
Air Conditioning Load
2Hp Air Conditioning Units @ 2760 VA 4 x 2760 VA
Load: For 2Hp Single Phase Motors @ 230V, use 12A FLA (See Table 4.30.14.2 P
Provide four (4) 30A ACU circuits
TOTAL
(A) Total Load Demand @ 100% (See Section 2.20.3.23 PEC 2017)
Small Appliance Load
Two small appliance circuits 2 - 1500VA each: 2 x 1500 VA
Provide two (2) 20A Small Appliance/Convenience Receptacle circuits
Additional appliance circuit @ 1000VA (Spare): 1 x 1500 VA
Provide atleast one (1) 20A Spare circuit
Laundry Load
Laundry circuit (washing machine) @ 1500VA 1 x 1500 VA
Provide one (1) 20A Laundry circuit
TOTAL
(B) Tota Load Demand @ 40% (See Section 2.20.3.23 PEC 2017)
TOTAL RESIDENTIAL LOAD (A+B)
Service Entrance Conductors
Total Full Load Current (See Sections 4.30.2.4 and 4.40.1.7)
6.63V
= x 100
230V
%VD = 2.88
(See FPN No. 2 of 2.15.1.2(a)(3) for v
Use: 2 - 22mm2 + 1 - 8.0mm2 (G) THWN Cu. Cable
Service Equipment
a. Maximum Current Rating of Protective Device (See Section: 4.30.4.2 and Table 4.30.4.2 PEC
Inverse Time Circuit Breaker
ICB = 250% IHRML + Total Full Load Current - IHRML
= 250% x 12A + 78.96A - 12VA
ICB = 96.96 A
b. Service Equipment Rating
Use: 100A, 2-Pole, 230V, 60Hz Moulded Case Circuit Breaker
= 4032 VA
= 11040 VA
e Table 4.30.14.2 PEC 2017
= 15072 VA
= 15072 VA
= 3000 VA
tacle circuits
= 1500 VA
= 1500 VA
= 6000 VA
= 2400 VA
= 17472 VA
e: L = 30m
0.3Ω/305m) x 0.6] x 30m
Current - IHRML
uit Breaker
Single Phase Short Circuit Calculation
Available Utility
Infinite Bus Assumption
Assume: Transformer
25kVA, 13.2/0.23 -kV, 1Ø
X/R = 1.1
%Z = 1.5
ISC = 4774A
Load:
Lighting & Small Appliance = 10032VA
ACU = 11040VA
p.f. = 0.8
100
Multiplier =
1.5 x 0.9
= 74.07
Fault X3
2 x 30m x 8051.41A
f=
4774A x 2 x 230V
= 0.22
1
Multiplier =
Multiplier =
1+0.220
= 0.82
100
Multiplier =
1.5 x 0.9
= 74.07
Fault X3
2 x 30 x 12227.45
f=
4774 x 2 x 230 733647
= 0.557 2196040
0.334077
1 0.749582
Multiplier =
1+0.334 9165.159
= 0.75
Therefore, use Service Equipment Rating with kAIC higher than 12227.45A
Say, 100A, 2-Pole, 230V, 18kAIC, 60Hz Moulded Case Circuit Breaker