Distribution Arrester Ac Rating Calculator

This document uses a calculator to determine the appropriate AC rating for an arrester based on the characteristics of an electrical distribution system. It provides the nominal system voltage, maximum line to ground voltage during a fault, overvoltage duration, and recommends a 15kV rated arrester to withstand potential overvoltages in the system. The calculator overlays the system overvoltage curve with the arrester's withstand capability to determine the proper rating.

Uploaded by

Ooi Ban Juan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
168 views4 pages

Distribution Arrester Ac Rating Calculator

This document uses a calculator to determine the appropriate AC rating for an arrester based on the characteristics of an electrical distribution system. It provides the nominal system voltage, maximum line to ground voltage during a fault, overvoltage duration, and recommends a 15kV rated arrester to withstand potential overvoltages in the system. The calculator overlays the system overvoltage curve with the arrester's withstand capability to determine the proper rating.

Uploaded by

Ooi Ban Juan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 4

ANSI Distribution Arrester AC Rating Calculator by

Displaying
Mouse over for Help
Nominal System
11 kV
Voltage (kV)

Overvoltage Amplitude (kV rms)


System Regulation
5.0 %
Error (%) Selected Arrester's Overvoltage Withstand Curves an
Max System Line to
6.68 kV 60
Ground Voltage
System Neutral Worst case system volta
Configuration Three Wire Impedance Grounded Examples and after a fault on unfa
phases
50
Arrester
OB Elbow Arrester
Type
40
Overvoltage Several days Sec
Duration
1000000
30
Max L-G Voltage
11.55 kV
during a fault
20
Recommended kV Rated/
Arrester AC Rating 15(12.7) (MCOV) 1
10

About This Calculator


Conti
ArresterWorks 2017 R1 0 Volta
0.01 0.1 1 10
Overvoltage 100
Duration 1000 10000
(seconds) 100000 100
g Calculator by ArresterWorks
OB Elbow Arrester

Overvoltage Withstand Curves and Potential System Overvoltage from a Fault

Worst case system voltage during


and after a fault on unfaulted
phases
Arrester ACRatings

Continuous
Voltage
0rvoltage Duration
100 1000 10000
(seconds) 100000 1000000
Back

Compound System Grounded Wye for MOV 1


Delta for MOV 2

Back