Switchyard Earthing Design Calculations-Pile 20 Ohm
Switchyard Earthing Design Calculations-Pile 20 Ohm
1.Nomenclature
Page 1
PROJECT: 110.4 MW DNPUCL HFO POWER PLANT
2. Input parameters
3. Ampacity calculation
Estep50=((1000+6*Cs*ρs)*0.116)/sqrt(ts)
Page 2
PROJECT: 110.4 MW DNPUCL HFO POWER PLANT
4. Grid configuration
Formula used:
Em=ρ*IG*Km*Ki/LM
Es=ρ*IG*Ks*Ki/Ls
IG = S f * I f IG = 24 kA
Km = 1/2*3.14(ln((D2/16*h*d)+((D+2*h)2/8*D*d)-(h/4*d))+
((Kii/Kh)ln(8/3.14*(2*n-1)))
For grids with ground rods along the perimeter and throughout the
grid area.
Kii = 1 No unit
Kh = sqrt(1+(h/h0))
h0 = 1m (grid reference depth) h0 = 1 m
n=na*nb*nc*nd
na = 2*LC/Lp na = 8.7897853 No unit
Km = 1/2*3.14(ln((D2/16*h*d)+((D+2*h)2/8*D*d)-(h/4*d))+
((Kii/Kh)ln(8/3.14*(2*n-1))) Km = 0.8324904
LM = Lc+(1.55+1.22*(Lr/sqrt(Lx^2+Ly^2)))*LR LM = 1330.3855 m
Em = ρ*IG*Km*Ki/LM Em = 588.00433 V
Ls = (0.75*Lc)+(0.85*LR) Ls = 967.125 m
Es=ρ*IG*Ks*Ki/Ls Es = 317.73246 V
Page 3
PROJECT: 110.4 MW DNPUCL HFO POWER PLANT
7. Safety check
For the safe earthing design, Attainable Step & Touch voltages
should be less than the Tolerable values respectively.
Attainable Tolerable
Touch Voltage in V 588.0043 946.35784369
Step Voltage in V 317.7325 3150.0732081
Page 4
EARTH RESISTIVITY CALCULATIONS
Average Resistivity,
DIRECTION ohm-m
ERT - 02
Avg N-S 2454.98
Avg E-W 2198.25
Average Resistivity,
ohm-m 2326.615
ρ = 2326.615 Ω-m
2326.615 Ω-m
Note: - 1. Earth Resistivity values are taken from GEOTECHNICAL INVESTIGATION REPORT furnished by
MAGNUS POWER PVT LTD.
2. Bentonite treatment has been recommended since the soil resistivity is on very higher side. Hence the
earthing design shall be carried out by considering soil resistivity of 20 Ω - m instead of 2326.615 Ω - m.
DOC: Earthing grid configuration
54.47 m
80.56 m
10
Average spacing D= 10 m
= 10 No
= 7 No