RC Two-Way Slab Design (Aci318-05) : Long Span To Short Span Ratio Less Than 2, Hence Two-Way Slab

This document summarizes the design of a two-way concrete slab according to ACI 318-05 code provisions. Key details include: - The slab has dimensions of 10 ft x 10 ft and a thickness of 5 in. - Reinforcement requirements are calculated for column and middle strips in both x and y directions. - Required flexural strengths and reinforcement amounts are determined based on factored moments from load and geometry. - No. 4 bars spaced at 6 in are provided as reinforcement in both positive and negative directions for the column strip.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
55 views6 pages

RC Two-Way Slab Design (Aci318-05) : Long Span To Short Span Ratio Less Than 2, Hence Two-Way Slab

This document summarizes the design of a two-way concrete slab according to ACI 318-05 code provisions. Key details include: - The slab has dimensions of 10 ft x 10 ft and a thickness of 5 in. - Reinforcement requirements are calculated for column and middle strips in both x and y directions. - Required flexural strengths and reinforcement amounts are determined based on factored moments from load and geometry. - No. 4 bars spaced at 6 in are provided as reinforcement in both positive and negative directions for the column strip.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 6

RC TWO-WAY SLAB DESIGN (ACI318-05)

lx x

½ Column strip
Middle strip
ly

½ Column strip
½ Column strip Middle strip ½ Column strip

TWO-WAY SLAB PANEL

Slab definition
Slab thickness; h = 5.00 in
Span along x - dir; lx = 10.000 ft
Span along y - dir; ly = 10.000 ft
Long span to Short span ratio less than 2, hence two-way slab.
Clear cover to positive reinforcement; cc = 0.75 in
Clear cover to negative reinforcement; c’c = 0.75 in
Column section
Column width along x - dir; hcx = 12.000 in
Column width along y - dir; hcy = 12.000 in
Materials
Specified compressive strength of concrete; f’c = 3000 psi
Specified yield strength of reinforcement; fy = 40000 psi
Modulus of elasticity; ESACI = 29000000psi
Concrete type; Normal weight
Concrete modification factor;  = 1.00
Loads
Total factored ultimate load on slab; wu = 100.000 psf
Check for the depth of slab provided
Clear span x – dir – cl. 13.6.2.5; lnx = max(0.65  lx, (lx – hcx / 2 – hcx / 2)) = 9.000 ft
Clear span y – dir – cl. 13.6.2.5; lny = max(0.65  ly, (ly – hcy / 2 – hcy / 2)) = 9.000 ft
Ratio;  = max(lnx, lny) / min(lnx, lny) = 1.000
Moment of inertia of beam; Ib = 0 in4
Isx = h3 / 12 × ly
Isy = h3 / 12 × lx
Moment of inertia of slab along x – axis; Isx = in4
Moment of inertia of slab along y – axis; Isy = 1250.000 in4
Flexural stiffness ratio along x – axis; fx = Ib / Isx = 0
Flexural stiffness ratio along y – axis; fy = Ib / Isy = 0
Average flexural stiffness ratio; fm = ( fx × 2 + fy × 2 ) / 4 = 0
Minimum depth required – cl. 9.5.3; hmin = 5.000 in
PASS - Slab thickness provided is sufficient for deflection
Moment computation ( x – direction)
Width of column strip (half) – cl. 13.2.1; lcol_stp = min( 0.25 × lx, 0.25 × ly ) = 2.500 ft
Width of middle strip – cl. 13.2.2; lmid_stp_x = ly – 2 × lcol_stp = 5.000 ft
Factored moment - eqn. 13-4; Mox = wu × ly × lnx2 / 8 = 10.125 kip_ft
Moment distribution for int. panel – cl. 13.6.3.2; M’ux = 0.65 × Mox = 6.581 kip_ft
Mux = 0.35 × Mox = 3.544 kip_ft
Moment distribution in column and middle strips:
ly / lx = 1.00
fx × ly / lx = 0.00
Moment distribution factors; fx_neg = 0.75
fx_pos = 0.60
Total column strip design moments; M’x_col_stp = fx_neg × M’ux = 4.936 kip_ft
Mx_col_stp = fx_pos × Mux = 2.126 kip_ft
Total middle strip design moments; M’x_mid_stp = (1 - fx_neg) × M’ux = 1.645 kip_ft
Mx_mid_stp = (1 - fx_pos) × Mux = 1.417 kip_ft
Required flexural nominal strength in column strip per 12 in width of slab;
M’nx_col = M’x_col_stp / ( 0.9 × (2 × lcol_stp)) = 1.097 kip_ft/ft
Mnx_col = Mx_col_stp / ( 0.9 × (2 × lcol_stp)) = 0.472 kip_ft/ft
Required flexural nominal strength in middle strip per 12 in width of slab;
M’nx_mid = M’x_mid_stp / (0.9 × lmid_stp_x) = 0.366 kip_ft/ft
Mnx_mid = Mx_mid_stp / (0.9 × lmid_stp_x) = 0.315 kip_ft/ft
Moment computation ( y – direction)
Width of column strip (half) – cl. 13.2.1; lcol_stp = min( 0.25 × lx, 0.25 × ly) = 2.500 ft
Width of middle strip – cl. 13.2.2; lmid_stp_y = lx – 2 ×lcol_stp = 5.000 ft
Factored moment - eqn. 13-4; Moy = wu × lx × lny2 / 8 = 10.125 kip_ft
Moment distribution for int. panel – cl. 13.6.3.2; M’uy = 0.65 × Moy = 6.581 kip_ft
Muy = 0.35 × Moy = 3.544 kip_ft
Moment distribution in column and middle strips:
lx / ly = 1.00
fy × lx / ly = 0.00
Moment distribution factors; fy_neg = 0.75
fy_pos = 0.60
Total column strip design moment; M’y_col_stp = fy_neg × M’uy = 4.936 kip_ft
My_col_stp = fy_pos × Muy = 2.126 kip_ft
Total middle strip design moment; M’y_mid_stp = (1 - fy_neg) × M’uy = 1.645 kip_ft
My_mid_stp = (1 - fy_pos) × Muy = 1.417 kip_ft
Required flexural nominal strength in column strip per 12 in width of slab;
M’ny_col = M’y_col_stp / ( 0.9 × (2 × lcol_stp)) = 1.097 kip_ft/ft
Mny_col = My_col_stp / ( 0.9 × (2 × lcol_stp)) = 0.472 kip_ft/ft
Required flexural nominal strength in middle strip per 12 in width of slab;
M’ny_mid = M’y_mid_stp / (0.9 × lmid_stp_y) = 0.366 kip_ft/ft
Mny_mid = My_mid_stp / (0.9 × lmid_stp_y) = 0.315 kip_ft/ft
Reinforcement calculations
Stress block depth factor; 1 = 0.85
Reinforcement percentage at strain of 0.004; b = 0.85  1  f’c / fy  (0.003 / (0.003 + 0.004)) = 0.023
Maximum reinforcement percentage; max = b = 0.023
Minimum area of steel required; Amin = min  h = 0.12 in2/ft
Maximum allowable spacing – cl. 13.3.2; smax = min (2 × h, 18 in) = 10.0 in
Column strip (x – direction)
Negative Reinforcement:
Depth to negative steel; d’x_col = h – c’c – D’col_x / 2 = 4.00 in
Flexural resistance factor; R’ux_col = M’nx_col / d’x_col2 = 0.069 ksi
Reinforcement required; ’reqx_col =0.85f’c/fy×[1–(abs(1–2×R’ux_col /(0.85×f’c)))]=
0.00174
Outer compression steel not required
Area of tension steel required; A’sx_req_col = ’reqx_col × d’x_col = 0.083 in2/ft
Maximum area of tension steel; A’sx_max_col = max × d’x_col = 1.115 in2/ft
Reinforcement provided (negative), No. 4 @ 6.0 in centers
Area of tension steel provided; A’sx_col = 0.393 in2/ft
PASS - Area of steel provided is OK
Actual tensile bar spacing provided; s’x_col = 6.0 in
PASS - Spacing of bars less than allowable
Positive reinforcement
Depth to positive steel; dx_col = h – cc - Dcol_x / 2 = 4.00 in
Flexural resistance factor; Rux_col = Mnx_col / dx_col2 = 0.030 ksi
Reinforcement required; reqx_col =0.85f’c/fy×[1–(abs(1–2×Rux_ col/(0.85×f’c)))] =
0.00074
Outer compression steel not required
Area of tension steel required; Asx_req_col = reqx_col × dx_col = 0.036 in2/ft
Maximum area of tension steel; Asx_max_col = max × dx_col = 1.115 in2/ft
Reinforcement provided (positive), No. 4 @ 6.0 in centers
Area of tension steel provided; Asx_col= 0.393 in2/ft
PASS - Area of steel provided is OK
Actual tensile bar spacing provided; sx_col = 6.0 in
PASS - Spacing of bars less than allowable
Middle strip (x – direction)
Negative Reinforcement:
Depth to negative steel; d’x_mid = h – c’c – D’mid_x / 2 = 4.00 in
Flexural resistance factor; R’ux_mid = M’nx_mid / d’x_mid2 = 0.023 ksi
Reinforcement required; ’reqx_mid = 0.85f’c/fy×[1–(abs(1–2×R’ux_mid/(0.85×f’c)))]
=0.00057
Outer compression steel not required
Area of tension steel required; A’sx_req_mid = ’reqx_mid × d’x_mid = 0.028 in2/ft
Maximum area of tension steel; A’sx_max_mid = max × d’x_mid = 1.115 in2/ft
Reinforcement provided (negative), No. 4 @ 6.0 in centers
Area of tension steel provided; A’sx_mid = 0.393 in2/ft
PASS - Area of steel provided is OK
Actual tensile bar spacing provided; s’x_mid = 6.0 in
PASS - Spacing of bars less than allowable
Positive reinforcement
Depth to positive steel; dx_mid = h – cc - Dmid_x / 2 = 4.00 in
Flexural resistance factor; Rux_mid = Mnx_mid / ( dx_mid2) = 0.020 ksi
Reinforcement required; reqx_mid = 0.85  f’c/fy×[1–(abs(1–2×Rux_mid/(0.85×f’c)))]
=0.00049
Outer compression steel not required
Area of tension steel required; Asx_req_mid = reqx_mid × dx_mid = 0.024 in2/ft
Maximum area of tension steel; Asx_max_mid = max × dx_mid = 1.115 in2/ft
Reinforcement provided (positive), No. 4 @ 6.0 in centers
Area of tension steel provided; Asx_mid= 0.393 in2/ft
PASS - Area of steel provided is OK
Actual tensile bar spacing provided; sx_mid = 6.0 in
PASS - Spacing of bars less than allowable
Column strip (y – direction)
Negative Reinforcement:
Depth to negative steel; d’y_col = h – c’c – D’col_x - D’col_y / 2 = 3.50 in
Flexural resistance factor; R’uy_col = M’ny_col / d’y_col2 = 0.090 ksi
Reinforcement required; ’reqy_col =0.85f’c/fy× [1 –(abs(1–2×R’uy_col/(0.85×f’c)))]=
0.00228
Outer compression steel not required
Area of tension steel required; A’sy_req_col = ’reqy_col × d’y_col = 0.096 in2/ft
Maximum area of tension steel; A’sy_max_col = max × d’y_col = 0.975 in2/ft
Reinforcement provided (negative), No. 4 @ 6.0 in centers
Area of tension steel provided; A’sy_col = 0.393 in2/ft
PASS - Area of steel provided is OK
Actual tensile bar spacing provided; s’y_col = 6.0 in
PASS - Spacing of bars less than allowable
Positive reinforcement
Depth to positive steel; dy_col = h – cc - Dcol_x - Dcol_y / 2 = 3.50 in
Flexural resistance factor; Ruy_col = Mny_col / dy_col2 = 0.039 ksi
Reinforcement required; reqy_col =0.85f’c/fy×[1–(abs(1–2×Ruy_col/(0.85 × f’c)))] =
0.00097
Outer compression steel not required
Area of tension steel required; Asy_req_col = reqy_col × dy_col = 0.041 in2/ft
Maximum area of tension steel; Asy_max_col = max × dy_col = 0.975 in2/ft
Reinforcement provided (positive), No. 4 @ 6.0 in centers
Area of tension steel provided; Asy_col= 0.393 in2/ft
PASS - Area of steel provided is OK
Actual tensile bar spacing provided; sy_col = 6.0 in
PASS - Spacing of bars less than allowable
Middle strip (y – direction)
Negative Reinforcement:
Depth to negative steel; d’y_mid = h – c’c – D’mid_x - D’mid_y / 2 = 3.50 in
Flexural resistance factor; R’uy_mid = M’ny_mid / d’y_mid2 = 0.030 ksi
Reinforcement required; ’reqy_mid = 0.85f’c/fy×[1–(abs(1–2×R’uy_mid/(0.85×f’c)))]
=0.00075
Outer compression steel not required
Area of tension steel required; A’sy_req_mid = ’reqy_mid × d’y_mid = 0.032 in2/ft
Maximum area of tension steel; A’sy_max_mid = max × d’y_mid = 0.975 in2/ft
Reinforcement provided (negative), No. 4 @ 6.0 in centers
Area of tension steel provided; A’sy_mid = 0.393 in2/ft
PASS - Area of steel provided is OK
Actual tensile bar spacing provided; s’y_mid = 6.0 in
PASS - Spacing of bars less than allowable
Positive reinforcement
Depth to positive steel; dy_mid = h – cc - Dmid_x - Dmid_y / 2 = 3.50 in
Flexural resistance factor; Ruy_mid = Mny_mid / dy_mid2 = 0.026 ksi
Reinforcement required; reqy_mid = 0.85  f’c/fy×[1–(abs(1–2×Ruy_mid/(0.85×f’c)))]
=0.00065
Outer compression steel not required
Area of tension steel required; Asy_req_mid = reqy_mid × dy_mid = 0.027 in2/ft
Maximum area of tension steel; Asy_max_mid = max × dy_mid = 0.975 in2/ft
Reinforcement provided, No. (positive) 4 @ 6.0 in centers
Area of tension steel provided; Asy_mid= 0.393 in2/ft
PASS - Area of steel provided is OK
Actual tensile bar spacing provided; sy_mid = 6.0 in
PASS - Spacing of bars less than allowable
Distribution reinforcement - (for shrinkage and temperature)
Minimum ratio of distribution reinforcement; t =0.0020
Minimum area of distribution reinforcement required; At_req = t × h = 0.120 in2/ft
Maximum allowable spacing of bars; smax_t = min ( 5 × h, 18 in) = 18.000 in
Distribution steel provided , No. 4 @ 6.0 in centers
Distribution reinforcement provided; At_prov = 0.393 in2/ft
PASS - Area of inner steel provided (Distribution) OK
Actual bar spacing provided; st = 6.000 in
PASS - Spacing of distribution bars is less than allowable
Check for shear
Ratio 2;  = Max(hcx,hcy) / Min(hcx,hcy) = 1.000
Ratio s for interior column; s = 40
Strength reduction factor for shear – cl. 9.3.2.3;  = 0.75
Slab depth for shear design; d = (d'x_col + d'y_col) / 2 = 3.75 in
Perimeter of critical section – cl. 11.11.1.2; bo = 2  (hcx + d + hcy + d)= 63.00 in
Vc as per eqn. 11-31; Vc1 = (2 + 4 /  Min(100psi,(f'c  1 psi))  bo  d =
77.640 kips
Vc as per eqn. 11-32; Vc2 = (s  d / bo + 2)   Min(100psi,(f'c  1 psi))  bo  d
= 56.689 kips
Vc as per eqn. 11-33; Vc3 = 4   Min(100psi,(f'c  1 psi))  bo  d = 51.760 kips
Nominal concrete shear strength – cl. 11.11.2.1; Vc = Min(Vc1,Vc2,Vc3) = 51.760 kips
Design shear strength of slab; Vc = Vc = 38.820 kips
Shear at d/2 from column face; Vu = wu × [( lx  ly) – ((hcx + d) × ( hcy + d))] = 9.828 kips
PASS - Shear capacity
Check for clear cover (ACI 318 cl. 7.7.1)
Permissible min nominal cover to all reinforcement; cmin = 0.75 in
Clear cover to tension reinforcement (negative); cc_neg =0.750 in
PASS - Cover to steel resisting hogging exceeds allowable minimum cover
Clear cover to tension reinforcement (positive); cc_pos = 0.750 in
PASS - Cover to steel resisting sagging exceeds allowable minimum cover
Schematic reinforcement distribution.
y

lx
½ Column strip x

A'sy_col
Asx_col A'sx_col

Asy_mid
Middle strip
ly

Asx_mid A'sx_mid
Asy_col
½ Column strip

A'sy_mid

½ Column strip Middle strip ½ Column strip

TWO-WAY SLAB PANEL Legend -


Top reinf.
(Reinforcement layout)
Bottom reinf.