0% found this document useful (0 votes)
175 views2 pages

ClimaSys NSYCU2K3P4 PDF

(1) This document provides specifications for the ClimaSys CU2000 cooling unit that provides 2000W of cooling at 400V. (2) Key specifications include its dimensions of 999mm x 405mm x 237mm, a weight of 54kg, and cooling powered by a 0.59kg R134a refrigerant circuit. (3) It has a rated current of 2.5A, inrush current of 10A, and power consumption of 970W at 50/60Hz which provides an energy efficiency ratio of 2.1.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
175 views2 pages

ClimaSys NSYCU2K3P4 PDF

(1) This document provides specifications for the ClimaSys CU2000 cooling unit that provides 2000W of cooling at 400V. (2) Key specifications include its dimensions of 999mm x 405mm x 237mm, a weight of 54kg, and cooling powered by a 0.59kg R134a refrigerant circuit. (3) It has a rated current of 2.5A, inrush current of 10A, and power consumption of 970W at 50/60Hz which provides an energy efficiency ratio of 2.1.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Product data sheet NSYCU2K3P4

Characteristics ClimaSys standard cooling unit side of


enclosure - 2000W at 400 V

Main
Range ClimaSys
Product name CU
Category Cooling unit
Mounting type Side
Type of installation Indoor
Product destination For enclosure
Mounting mode By screws
Input voltage 400 V 50/60 Hz
Network number of 3 phases
phases
Cooling power 2000 W 50/60 Hz L35-L35
1510 W 50/60 Hz L35-L50

It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Complementary
Height 999 mm
Width 405 mm
Depth 237 mm
[In] rated current 2.5 A

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Inrush current 10 A

Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Power consumption in W 970 W at 50/60 Hz, L35-L35
1150 W at 50/60 Hz, L35-L50
Energy efficiency ratio 2.1
Control type Electronic controller
Temperature setting range 20...50 °C
Ambient air temperature for operation 20...46 °C, inside the enclosure
20...50 °C, outside the enclosure
55 °C, maximum
Noise level 65 dB conforming to EN/ISO 3746
Pressure 25 bar
Flow rate Internal circuit : 860 m3/h at 50/60 Hz
External circuit : 1050 m3/h at 50/60 Hz
Product weight 54 kg
Cooling gas type R134a (0.59 kg)
Type of filter Optional external circuit filter
Protection type Thermal protection : T 6 A
Short-circuit protection (magnetic) :
Material Steel
Colour Grey RAL 7035

Environment
Product certifications CE
Directives 2004/108/EC - electromagnetic compatibility
2006/42/EC - machinery
2006/95/EC - low voltage directive
Standards EN 60204-1
EN/ISO 12100
EN 60335-1
EN 378
EN 60335-2-40
IP degree of protection IP34 on the external circuit conforming to IEC 60529
IP55 on the internal circuit conforming to IEC 60529