Heat Load Calculation

This document summarizes the heat load calculations for the Seminar Hall No. 1 at the Indira Gandhi Institute. The area of the hall is 935 square feet with a height of 22 feet. The calculated cooling load is 107,527 BTU/hour with a required 12.13 tons of cooling and 4,753 CFM of dehumidified air. The number of occupants is estimated to be 90 people with equipment load of 750 watts.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
546 views

Heat Load Calculation

This document summarizes the heat load calculations for the Seminar Hall No. 1 at the Indira Gandhi Institute. The area of the hall is 935 square feet with a height of 22 feet. The calculated cooling load is 107,527 BTU/hour with a required 12.13 tons of cooling and 4,753 CFM of dehumidified air. The number of occupants is estimated to be 90 people with equipment load of 750 watts.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 6

Name of Project: INDIRA GANDHI INSTITUTE Job ref./ Enquiry No.

:
Address: GOREGAON Estimated by:
Space used for: SEMINAR HALL No 1 Peak load at:
Area in sq.ft = 935 Length in Ft. Height in ft.= 22.0
Volume in cu.ft 20570 Width in Ft. Contact factor : 0.88 (British Units)
Bypass factor : 0.12 Btu/hour Outside
Area x Temp.diffFactor Sensible Load Latent Load Inside
SOLAR GAIN-GLASS Difference
Glass (N) 0 11 0.56 0 - Eq. Temp.correction facto
Glass (E) 38 11 0.56 231 -
Glass (S) 0 11 0.56 0 - 90
Glass (W) 0 165 0.56 0 - 1
Glass (NE) 0 11 0.56 0 - Selected Outdoor Air C
Glass (SW) 0 113 0.56 0 -
Glass (NW) 0 118 0.56 0 -
Glass (SE) 0 11 0.56 0 -
SOLAR & TRANSMISSION GAIN-WALLS & ROOF Effective Sens. Heat Facto
Wall (N) 585.2 14 0.35 2867 -
Wall (E) 1326.5 28 0.35 13000 - INDICATED ADP =
Wall (S) 0 26 0.35 0 -
Wall (W) 0 22 0.35 0 -
Wall (NE) 0 20 0.35 0 -
Wall (SW) 0 24 0.35 0 - Dehum. Rise = Contact Fa
Wall (NW) 0 16 0.35 0 - Dehum. CFM = ERSH/1.08
Wall (SE) 0 28 0.35 0 -
Exposed Roof 935 45 0.48 20196 - U-factors:
TRANSMISSION GAIN-EXCEPT WALLS & ROOF Exposed Walls
All Glass 38 22 1.13 932 - Partition Walls
Partition Wall 0 17 0.40 0 Partition Glass
Partition Glass 0 17 0.43 0 - Factors for Glass:
Ceiling 0 17 0.48 0 -
Floor 0 17 0.48 0 - Some typical inside desig
INTERNAL HEAT
People 90 276 224 24840 20160
Lights (I) - W 1870 3.41 1.0 6377 -
Lights (F) - W 0 3.41 1.25 0 -

DESIGN CONDITIONS
Equip.Load -W 750 3.41 1.0 2558 -
-do- in HP 0 2545 1.0 0 -
Others 0 0
Subtotals 71001 20160
Safety Factors (12.5% & 5% respectively) 8875 1008
Room Sensible & Latent Loads 79876 21168

Outdoor Air cfm = 506.1 1443 3386


Effective Room Sensible Heat (ERSH) 81319 -
Effective Room Latent Heat (ERLH) - 24554
Effective Room Total Heat (ERTH) 105873
OUTDOOR AIR (O.A.)
Sensible Load 10582 - Air on Coil in deg F:
Latent Load - 24834 DBT :
Effective Room Total Heat + O.A Heat 141289 WBT :
Other Heat Gains @ 3% 4239
GRAND TOTAL HEAT 145527 TMBH =
TR 12.13 SMBH =
Enquiry No.:
GDK Heat load for: Summer
4.00 PM
DESIGN CONDITIONS
DBT % RH WBT Gr/lb
95 60 83 151
73 55 62 69
22 xxxx xxxx 82
p.correction factor 10
OUTDOOR AIR (CFM)
People x 5.6233333333 CFM/Person = 506.1
No. of air changes/hr = 342.8333
d Outdoor Air CFM = 506.1

APPARATUS DEW POINT

Sens. Heat Factor (ESHF) = ERSH/ERTH = 0.77

ED ADP = 55 SELECT.ADP= 55

DEHUMIDIFIED AIR QUANTITY

Rise = Contact Factor x (Rm Temp. - ADP)= 15.8


CFM = ERSH/1.08/Dehum. Rise = 4753
Dehum CFM /400 = 11.88
Roof Insl 0.12
0.35 Roof Non Insl 0.48
0.40 Ceiling 0.48
0.43 Floor 0.48
ors for Glass: Solar gain 0.56
Transm. Gain 1.13
pical inside design conditions:
DBT % RH WBT Gr/lb
70 50 58.5 54.8
70 55 59.7 60.1
72 50 60.1 58.8
72 55 61.4 64.4
74 50 61.8 62.0
74 55 63.0 68.0
75 50 62.6 65.0
75 55 64.0 71.5
76 55 64.9 74.0
77 55 65.6 76.6
90 88 86 184.0
104 45 83 138.0
105 40 83 136.0
110 25 78 94.0

oil in deg F: Check figures:


75 sq.ft/TR = 77
64 cfm/sq.ft = 5.1
cfm/TR = 392
145.5
91.9 Sheet No.
SUMMARY OF HEATLOAD FOR INDIRA GAHDI INSTITUTE.
DATE : 09.04.2014
Area in sq.ft = 935 TR 12.13
Height in ft.= 22.00 Dehum CFM 4753.48
SEMINAR HALL No 1 12.13
People 90 Dehum CFM /400 = 11.88
Equip.Load -W 750
Area in sq.ft = 935 TR 12.13
TOTAL People 90 Dehum CFM 4753.48 12.13
Equip.Load -W 750 Dehum CFM /400 = 11.88
AREA / TR

77.10

77.10