Pump House Pool Fire

This document contains a piping and instrumentation diagram (P&ID) of a complex piping system with multiple tanks, pumps, valves and other equipment connected by pipes. The P&ID shows the piping layout, equipment details like dimensions, pressures and flows. Key components include storage tanks, pumps, heat exchangers and flow control valves connected in series and parallel configurations through various pipe segments of different diameters and lengths.

Uploaded by

Mohsin Raza
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
77 views15 pages

Pump House Pool Fire

This document contains a piping and instrumentation diagram (P&ID) of a complex piping system with multiple tanks, pumps, valves and other equipment connected by pipes. The P&ID shows the piping layout, equipment details like dimensions, pressures and flows. Key components include storage tanks, pumps, heat exchangers and flow control valves connected in series and parallel configurations through various pipe segments of different diameters and lengths.

Uploaded by

Mohsin Raza
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

L12

FW Tank T-678
P=0 R2 Wl=17.3
Pi=158 Wv=0 P=140
Po=158 Pi=158
Po=140
L7 V=3.3
L1 dP/L=0.6
Wl=17.3 D=3"
Wl=75.2 Wv=0 L=20
Wv=0 Pi=158
Pi=0.62 Po=158
Po=1.03 V=0.84
V=3.68 dP/L=0.0
dP/L=0.3 L2 L6
D=6"
D=6" Wl=75.2 Wl=47.9 L=90
T1 T3
L=17 P1 Wv=0 Wv=0 L12
P1=158 P1=158
Pi=1.03 Pi=159 P2=158 Pi=158 P2=158 Wl=11.4 Shed
J1
Po=159 Po=158 P3=158 Po=158 P3=158 Wv=0 P=158
P=158
V=3.68 V=2.34 Pi=158
dP/L=0.3 dP/L=0.1 Po=158
D=6" D=6" V=1.26
L=80 L=70 dP/L=0.1
D=4"
L=1

L11
Wl=27.3
Wv=0
Pi=158 L8
Po=158 Wl=30.6 L9
V=1.33 Wv=0 Wl=11.4 PumpHous
dP/L=0.0 Pi=158 Wv=0 P=157
D=6" Po=158 Pi=158
L=200 V=1.5 Po=158
dP/L=0.1 V=1.26
D=6" dP/L=0.1
L=70 D=4"
L=60
R3
Pi=158
Po=158

L10 L12
T4
P1=158 Wl=19.2 R1 Wl=19.2 TWGantry
L5 Wv=0 Pi=158 Wv=0 P=157
P2=158
Wl=27.3 P3=158 Pi=158 Po=158 Pi=158
Wv=0 Po=158 Po=157
Pi=158 V=0.94 V=2.13
Po=157 dP/L=0.0 dP/L=0.2
V=3.03 D=6" D=4"
dP/L=0.4 L=10 L=60
D=4"
L=25

PETROCHEMICAL ENGINEERING CONSULTANTS


Karachi-Pakistan
Hydraulic Simulation: Pump House Pool Fire
Technical Audit of Existing Fire Fighting System
at Bulawayo Depot
Vivo Energy - Zimbabwe
Eng Chkd Apvd Date Project Rev
Korf File Pump House Pool Fire.dat Units Custom;W=t/h; P=psig; L=m; dP/L=psi/100ft; v=ft/s SMR MZK SMS 16-09-2019 2901-001 0
======================================================================================================================================================
Hydraulic Simulation: Pump House Pool Fi This information is confidential, and shall Page: 1
Technical Audit of Existing Fire Fightin not be reproduced by any means without the Proj: 2901-001
at Bulawayo Depot written permission of PETROCHEMICAL ENGINEERING CONSULTANTS . By : SMR
Vivo Energy - Zimbabwe Chkd/Apvd: MZK / SMS
GENERAL Date: 16-09-2019
======================================================================================================================================================

Current file name = C:\Users\mohsi\OneDrive\Desktop\PEC\Bulawayo\Pump House Pool Fire.dat

Defaults : Compressible = Isothermal


Two phase flow = Homogeneous
Acceleration = Inverse
Elevation den = Homogeneous
Dukler hold-up = Dukler
Atmospheric pres = 14.696 psi abs

To view/print : Font = Courier, Size 7-8


Orientation = Landscape
Margins = 1-2 cm.

Run message = Problem solution reached after 16 iterations.

NOTE - Close before running and viewing next results.

======================================================================================================================================================
C:\Users\mohsi\OneDrive\Desktop\PEC\Bulawayo\Pump House Pool Fire.dat
======================================================================================================================================================
Hydraulic Simulation: Pump House Pool Fi This information is confidential, and shall Page: 2
Technical Audit of Existing Fire Fightin not be reproduced by any means without the Proj: 2901-001
at Bulawayo Depot written permission of PETROCHEMICAL ENGINEERING CONSULTANTS . By : SMR
Vivo Energy - Zimbabwe Chkd/Apvd: MZK / SMS
PRESSURE PROFILE REPORT Date: 16-09-2019
======================================================================================================================================================

Circuit Feed 1
-----------------
Number Description Flow Density Visc Dia Sch Length dP/L Velocity Elev dPelev dPin-out Pin Pout
t/h kg/m3 cP in m psi/100ft ft/s m psi psi psig psig
FW Tank Feed to Unit 0.6 0.711 -0.62 0 0.6204
L1 Pipe 75.18 1,000 1.0 6 40 17.0 0.325 3.68 0.854 -0.413 0.6204 1.033
P1 Pump 0 -158 1.033 159.4
L2 Pipe 75.18 1,000 1.0 6 40 80.0 0.325 3.68 0 1.27 159.4 158.2
T1 Tee piece 0 158.2

Circuit Junction 1 : 1
---------------------------
Number Description Flow Density Visc Dia Sch Length dP/L Velocity Elev dPelev dPin-out Pin Pout
t/h kg/m3 cP in m psi/100ft ft/s m psi psi psig psig
J1 Junction 0 157.5
L12 Pipe 11.4 1,000 1.0 4 40 1.0 0.0751 1.26 0 0.00246 157.5 157.5
Shed Product from Unit 0 0 0 157.5 157.5

Circuit T-Piece 1 : 2
-------------------------
Number Description Flow Density Visc Dia Sch Length dP/L Velocity Elev dPelev dPin-out Pin Pout
t/h kg/m3 cP in m psi/100ft ft/s m psi psi psig psig
T1 Tee piece 0 158.2
L11 Pipe 27.3 1,000 1.0 6 40 200 0.0499 1.33 0 0.358 158.2 157.8
R3 Expander/Reducer K = 1.44 0 0.0671 157.8 157.7
L5 Pipe 27.3 1,000 1.0 4 40 25.0 0.373 3.03 0 0.493 157.7 157.2
PumpHous Product from Unit 0 0 0 157.2 157.2

Circuit T-Piece 1 : 3
-------------------------
Number Description Flow Density Visc Dia Sch Length dP/L Velocity Elev dPelev dPin-out Pin Pout
t/h kg/m3 cP in m psi/100ft ft/s m psi psi psig psig
T1 Tee piece 0 158.2
L6 Pipe 47.88 1,000 1.0 6 40 70.0 0.14 2.34 0 0.366 158.2 157.9
T3 Tee piece 0 157.9

Circuit T-Piece 2 : 1
-------------------------
Number Description Flow Density Visc Dia Sch Length dP/L Velocity Elev dPelev dPin-out Pin Pout
t/h kg/m3 cP in m psi/100ft ft/s m psi psi psig psig
T4 Tee piece 0 157.7
L10 Pipe 19.2 1,000 1.0 6 40 10.0 0.0264 0.939 0 0.0387 157.7 157.7
R1 Expander/Reducer K = 1.44 0 0.0332 157.7 157.6
L12 Pipe 19.2 1,000 1.0 4 40 60.0 0.195 2.13 0 0.427 157.6 157.2
TWGantry Product from Unit 0 0 0 157.2 157.2

======================================================================================================================================================
C:\Users\mohsi\OneDrive\Desktop\PEC\Bulawayo\Pump House Pool Fire.dat
======================================================================================================================================================
Hydraulic Simulation: Pump House Pool Fi This information is confidential, and shall Page: 3
Technical Audit of Existing Fire Fightin not be reproduced by any means without the Proj: 2901-001
at Bulawayo Depot written permission of PETROCHEMICAL ENGINEERING CONSULTANTS . By : SMR
Vivo Energy - Zimbabwe Chkd/Apvd: MZK / SMS
PRESSURE PROFILE REPORT Date: 16-09-2019
======================================================================================================================================================

Circuit T-Piece 2 : 2
-------------------------
Number Description Flow Density Visc Dia Sch Length dP/L Velocity Elev dPelev dPin-out Pin Pout
t/h kg/m3 cP in m psi/100ft ft/s m psi psi psig psig
T4 Tee piece 0 157.7
L9 Pipe 11.4 1,000 1.0 4 40 60.0 0.0751 1.26 0 0.177 157.7 157.5
J1 Junction 0 157.5

Circuit T-Piece 3 : 1
-------------------------
Number Description Flow Density Visc Dia Sch Length dP/L Velocity Elev dPelev dPin-out Pin Pout
t/h kg/m3 cP in m psi/100ft ft/s m psi psi psig psig
T3 Tee piece 0 157.9
L7 Pipe 17.28 1,000 1.0 6 40 90.0 0.0218 0.845 0 0.0764 157.9 157.8
R2 Expander/Reducer K = 5.68 0 0.0959 157.8 157.7
L12 Pipe 17.28 1,000 1.0 3 40 20.0 0.613 3.3 -17.1 17.5 157.7 140.2
T-678 Product from Unit 12 0 0 140.2 140.2

Circuit T-Piece 3 : 3
-------------------------
Number Description Flow Density Visc Dia Sch Length dP/L Velocity Elev dPelev dPin-out Pin Pout
t/h kg/m3 cP in m psi/100ft ft/s m psi psi psig psig
T3 Tee piece 0 157.8
L8 Pipe 30.6 1,000 1.0 6 40 70.0 0.0615 1.5 0 0.152 157.8 157.7
T4 Tee piece 0 157.7

NOTES - (1) dPElev and dPin-out represent DRAWING Inlet - Outlet.


(2) dPfrictional + dPaccel = dPElev + dPin-out.
(3) Vessel/Tank dPElev represent effect of fluid levels inside vessel.
(4) Elev represent equipment or nozzle (vessel/tank) elevation.

======================================================================================================================================================
C:\Users\mohsi\OneDrive\Desktop\PEC\Bulawayo\Pump House Pool Fire.dat
======================================================================================================================================================
Hydraulic Simulation: Pump House Pool Fi This information is confidential, and shall Page: 4
Technical Audit of Existing Fire Fightin not be reproduced by any means without the Proj: 2901-001
at Bulawayo Depot written permission of PETROCHEMICAL ENGINEERING CONSULTANTS . By : SMR
Vivo Energy - Zimbabwe Chkd/Apvd: MZK / SMS
PIPE LINE REPORT Date: 16-09-2019
======================================================================================================================================================

-----------------------------------------------------------------------------------------------------------------------------------------------------
Line number | L1 | L2 | L12 | L11
Line name | Pipe | Pipe | Pipe | Pipe
-----------------------------------------------------------------------------------------------------------------------------------------------------
PROCESS DATA | AVG IN OUT | AVG IN OUT | AVG IN OUT | AVG IN OUT
Temperature C | 25.0 25.0 25.0 | 25.0 25.0 25.0 | 25.0 25.0 25.0 | 25.0 25.0 25.0
Pressure psig | 0.8267 0.6204 1.033 | 158.8 159.4 158.2 | 157.5 157.5 157.5 | 158.0 158.2 157.8
Liq Fraction wt | 1.0 1.0 1.0 | 1.0 1.0 1.0 | 1.0 1.0 1.0 | 1.0 1.0 1.0
Total-Flow t/h | 75.18 | 75.18 | 11.4 | 27.3
Dens-NS kg/m3 | 1,000 1,000 1,000 | 1,000 1,000 1,000 | 1,000 1,000 1,000 | 1,000 1,000 1,000
Elev kg/m3 | 1,000 | 1,000 | 1,000 | 1,000
Visc-NS cP | 1.0 | 1.0 | 1.0 | 1.0
Vapor-Flow t/h | 0 | 0 | 0 | 0
Density kg/m3 | 1.21 | 13.5 | 13.4 | 13.4
Visc cP | 0.010 | 0.010 | 0.010 | 0.010
Mol wt | 28.0 | 28.0 | 28.0 | 28.0
Z | 1.0 | 1.0 | 1.0 | 1.0
Cp/Cv | 1.4 | 1.4 | 1.4 | 1.4
Liquid-Flow (wt) t/h | 75.18 | 75.18 | 11.4 | 27.3
Flow (vol) m3/h | 75.18 | 75.18 | 11.4 | 27.3
Density kg/m3 | 1,000 | 1,000 | 1,000 | 1,000
Visc cP | 1.0 | 1.0 | 1.0 | 1.0
PIPE DATA | | | |
Size in | 6 | 6 | 4 | 6
Length m | 17.0 | 80.0 | 1.0 | 200
Schedule | 40 | 40 | 40 | 40
ID mm | 154 | 154 | 102 | 154
Roughness (E-3) mm | 45.7 | 45.7 | 45.7 | 45.7
Safety factor | 1.0 | 1.0 | 1.0 | 1.0
Sum of elev's m | 0 | 0 | 0 | 0
VELOCITY | | | |
Velocity ft/s | 3.68 3.68 3.68 | 3.68 3.68 3.68 | 1.26 1.26 1.26 | 1.33 1.33 1.33
Sonic-Vapor adia ft/s | 1,155 | 1,155 | 1,155 | 1,155
Vapor isoT ft/s | 976 | 976 | 976 | 976
PRESSURE DROP (In-Out) | | | |
Overall psi | -0.4125 | 1.266 | 0.002464 | 0.3576
Friction psi | 0.4412 | 1.266 | 0.002464 | 0.3576
Accel'n psi | 0 | 0 | 0 | 0
Static psi | -0.8537 | 0 | 0 | 0
dP/Length psi/100ft | 0.325 | 0.325 | 0.0751 | 0.0499
LINE SIZING | MAX/LARGER MIN/SMALLER | MAX/LARGER MIN/SMALLER | MAX/LARGER MIN/SMALLER | MAX/LARGER MIN/SMALLER
dP/Length psi/100ft | 0.999 | 0.999 | 0.999 | 0.999
Velocity ft/s | 328 0.984 | 328 0.984 | 328 0.984 | 328 0.984
VelCoef ft/s | 12.4 1.04 | 12.4 1.04 | 12.4 1.04 | 12.4 1.04
Size-Larger/Small in | 8 4 | 8 4 | 6 3 | 8 4
dP/Length psi/100ft | 0.0836 2.53 | 0.0836 2.53 | 0.0103 0.284 | 0.0132 0.373
Velocity ft/s | 2.12 8.34 | 2.12 8.34 | 0.557 2.18 | 0.771 3.03

======================================================================================================================================================
C:\Users\mohsi\OneDrive\Desktop\PEC\Bulawayo\Pump House Pool Fire.dat
======================================================================================================================================================
Hydraulic Simulation: Pump House Pool Fi This information is confidential, and shall Page: 5
Technical Audit of Existing Fire Fightin not be reproduced by any means without the Proj: 2901-001
at Bulawayo Depot written permission of PETROCHEMICAL ENGINEERING CONSULTANTS . By : SMR
Vivo Energy - Zimbabwe Chkd/Apvd: MZK / SMS
PIPE LINE REPORT Date: 16-09-2019
======================================================================================================================================================

-----------------------------------------------------------------------------------------------------------------------------------------------------
Line number | L1 | L2 | L12 | L11
Line name | Pipe | Pipe | Pipe | Pipe
-----------------------------------------------------------------------------------------------------------------------------------------------------
LIQUID HOLDUP | | | |
Liquid Fraction (vol) | 1.0 | 1.0 | 1.0 | 1.0
Liquid Holdup(dP) (vol) | 1.0 | 1.0 | 1.0 | 1.0
2-PHASE METHOD | Homogeneous | Homogeneous | Homogeneous | Homogeneous
FLOW REGIME | | | |
Horizontal | - | - | - | -
Vertical-Up | - | - | - | -
Vertical-Down | - | - | - | -
HOMOGENEOUS/DUKLER | | | |
Reynolds No | 172,606 | 172,606 | 39,431 | 62,681
Friction factor | 0.01802 | 0.01802 | 0.02338 | 0.02103
Friction factor (turb) | 0.01489 | 0.01489 | 0.01627 | 0.01489
Dukler-2phase factor | 1.00 | 1.00 | 1.00 | 1.00
density kg/m3 | 0 | 0 | 0 | 0
LOCKHART-M/CHENOWETH-M | | | |
Liquid-Re | 0 | 0 | 0 | 0
f | 0 | 0 | 0 | 0
Psi/Psi^2 | 0 | 0 | 0 | 0
Vapor-Re | 0 | 0 | 0 | 0
f | 0 | 0 | 0 | 0
Psi^2 | 0 | 0 | 0 | 0
X factor | 0 | 0 | 0 | 0
FITTINGS | TYPE No L/D K | TYPE No L/D K | TYPE No L/D K | TYPE No L/D K
| Entrance 0 0 0.5 | Entrance 0 0 0.5 | Entrance 0 0 0.5 | Entrance 0 0 0.5
| Exit 0 0 1 | Exit 0 0 1 | Exit 0 0 1 | Exit 0 0 1
| Gate valve 4 8 0 | Gate valve 2 8 0 | Gate valve 0 8 0 | Gate valve 1 8 0
| Globe valv 0 340 0 | Globe valv 0 340 0 | Globe valv 0 340 0 | Globe valv 0 340 0
| Check 0 50 0 | Check 1 50 0 | Check 0 50 0 | Check 0 50 0
| Stop-check 0 400 0 | Stop-check 0 400 0 | Stop-check 0 400 0 | Stop-check 0 400 0
| Elbow 6 20 0 | Elbow 8 20 0 | Elbow 0 20 0 | Elbow 5 20 0
| 180 Bend 0 50 0 | 180 Bend 0 50 0 | 180 Bend 0 50 0 | 180 Bend 0 50 0
| T-Straight 2 20 0 | T-Straight 4 20 0 | T-Straight 0 20 0 | T-Straight 3 20 0
| T-Branch 0 60 0 | T-Branch 0 60 0 | T-Branch 0 60 0 | T-Branch 0 60 0
| Other 0 0 | Other 0 0 | Other 0 0 | Other 0 0
Total K | 0 | 0 | 0 | 0
Total L/D | 192 | 306 | 0 | 168
Equiv Length m | 41.4 | 119 | 1.0 | 218

======================================================================================================================================================
C:\Users\mohsi\OneDrive\Desktop\PEC\Bulawayo\Pump House Pool Fire.dat
======================================================================================================================================================
Hydraulic Simulation: Pump House Pool Fi This information is confidential, and shall Page: 6
Technical Audit of Existing Fire Fightin not be reproduced by any means without the Proj: 2901-001
at Bulawayo Depot written permission of PETROCHEMICAL ENGINEERING CONSULTANTS . By : SMR
Vivo Energy - Zimbabwe Chkd/Apvd: MZK / SMS
PIPE LINE REPORT Date: 16-09-2019
======================================================================================================================================================

-----------------------------------------------------------------------------------------------------------------------------------------------------
Line number | L5 | L6 | L10 | L12
Line name | Pipe | Pipe | Pipe | Pipe
-----------------------------------------------------------------------------------------------------------------------------------------------------
PROCESS DATA | AVG IN OUT | AVG IN OUT | AVG IN OUT | AVG IN OUT
Temperature C | 25.0 25.0 25.0 | 25.0 25.0 25.0 | 25.0 25.0 25.0 | 25.0 25.0 25.0
Pressure psig | 157.5 157.7 157.2 | 158.1 158.2 157.9 | 157.7 157.7 157.7 | 157.4 157.6 157.2
Liq Fraction wt | 1.0 1.0 1.0 | 1.0 1.0 1.0 | 1.0 1.0 1.0 | 1.0 1.0 1.0
Total-Flow t/h | 27.3 | 47.88 | 19.2 | 19.2
Dens-NS kg/m3 | 1,000 1,000 1,000 | 1,000 1,000 1,000 | 1,000 1,000 1,000 | 1,000 1,000 1,000
Elev kg/m3 | 1,000 | 1,000 | 1,000 | 1,000
Visc-NS cP | 1.0 | 1.0 | 1.0 | 1.0
Vapor-Flow t/h | 0 | 0 | 0 | 0
Density kg/m3 | 13.4 | 13.5 | 13.4 | 13.4
Visc cP | 0.010 | 0.010 | 0.010 | 0.010
Mol wt | 28.0 | 28.0 | 28.0 | 28.0
Z | 1.0 | 1.0 | 1.0 | 1.0
Cp/Cv | 1.4 | 1.4 | 1.4 | 1.4
Liquid-Flow (wt) t/h | 27.3 | 47.88 | 19.2 | 19.2
Flow (vol) m3/h | 27.3 | 47.88 | 19.2 | 19.2
Density kg/m3 | 1,000 | 1,000 | 1,000 | 1,000
Visc cP | 1.0 | 1.0 | 1.0 | 1.0
PIPE DATA | | | |
Size in | 4 | 6 | 6 | 4
Length m | 25.0 | 70.0 | 10.0 | 60.0
Schedule | 40 | 40 | 40 | 40
ID mm | 102 | 154 | 154 | 102
Roughness (E-3) mm | 45.7 | 45.7 | 45.7 | 45.7
Safety factor | 1.0 | 1.0 | 1.0 | 1.0
Sum of elev's m | 0 | 0 | 0 | 0
VELOCITY | | | |
Velocity ft/s | 3.03 3.03 3.03 | 2.34 2.34 2.34 | 0.939 0.939 0.939 | 2.13 2.13 2.13
Sonic-Vapor adia ft/s | 1,155 | 1,155 | 1,155 | 1,155
Vapor isoT ft/s | 976 | 976 | 976 | 976
PRESSURE DROP (In-Out) | | | |
Overall psi | 0.4933 | 0.3656 | 0.0387 | 0.427
Friction psi | 0.4933 | 0.3656 | 0.0387 | 0.427
Accel'n psi | 0 | 0 | 0 | 0
Static psi | 0 | 0 | 0 | 0
dP/Length psi/100ft | 0.373 | 0.14 | 0.0264 | 0.195
LINE SIZING | MAX/LARGER MIN/SMALLER | MAX/LARGER MIN/SMALLER | MAX/LARGER MIN/SMALLER | MAX/LARGER MIN/SMALLER
dP/Length psi/100ft | 0.999 | 0.999 | 0.999 | 0.999
Velocity ft/s | 328 0.984 | 328 0.984 | 328 0.984 | 328 0.984
VelCoef ft/s | 12.4 1.04 | 12.4 1.04 | 12.4 1.04 | 12.4 1.04
Size-Larger/Small in | 6 3 | 8 4 | 8 4 | 6 3
dP/Length psi/100ft | 0.0499 1.45 | 0.0365 1.07 | 0.0070 0.195 | 0.0264 0.746
Velocity ft/s | 1.33 5.22 | 1.35 5.31 | 0.542 2.13 | 0.939 3.67

======================================================================================================================================================
C:\Users\mohsi\OneDrive\Desktop\PEC\Bulawayo\Pump House Pool Fire.dat
======================================================================================================================================================
Hydraulic Simulation: Pump House Pool Fi This information is confidential, and shall Page: 7
Technical Audit of Existing Fire Fightin not be reproduced by any means without the Proj: 2901-001
at Bulawayo Depot written permission of PETROCHEMICAL ENGINEERING CONSULTANTS . By : SMR
Vivo Energy - Zimbabwe Chkd/Apvd: MZK / SMS
PIPE LINE REPORT Date: 16-09-2019
======================================================================================================================================================

-----------------------------------------------------------------------------------------------------------------------------------------------------
Line number | L5 | L6 | L10 | L12
Line name | Pipe | Pipe | Pipe | Pipe
-----------------------------------------------------------------------------------------------------------------------------------------------------
LIQUID HOLDUP | | | |
Liquid Fraction (vol) | 1.0 | 1.0 | 1.0 | 1.0
Liquid Holdup(dP) (vol) | 1.0 | 1.0 | 1.0 | 1.0
2-PHASE METHOD | Homogeneous | Homogeneous | Homogeneous | Homogeneous
FLOW REGIME | | | |
Horizontal | - | - | - | -
Vertical-Up | - | - | - | -
Vertical-Down | - | - | - | -
HOMOGENEOUS/DUKLER | | | |
Reynolds No | 94,426 | 109,929 | 44,083 | 66,409
Friction factor | 0.02027 | 0.01918 | 0.02245 | 0.02136
Friction factor (turb) | 0.01627 | 0.01489 | 0.01489 | 0.01627
Dukler-2phase factor | 1.00 | 1.00 | 1.00 | 1.00
density kg/m3 | 0 | 0 | 0 | 0
LOCKHART-M/CHENOWETH-M | | | |
Liquid-Re | 0 | 0 | 0 | 0
f | 0 | 0 | 0 | 0
Psi/Psi^2 | 0 | 0 | 0 | 0
Vapor-Re | 0 | 0 | 0 | 0
f | 0 | 0 | 0 | 0
Psi^2 | 0 | 0 | 0 | 0
X factor | 0 | 0 | 0 | 0
FITTINGS | TYPE No L/D K | TYPE No L/D K | TYPE No L/D K | TYPE No L/D K
| Entrance 0 0 0.5 | Entrance 0 0 0.5 | Entrance 0 0 0.5 | Entrance 0 0 0.5
| Exit 0 0 1 | Exit 0 0 1 | Exit 0 0 1 | Exit 0 0 1
| Gate valve 2 8 0 | Gate valve 0 8 0 | Gate valve 0 8 0 | Gate valve 1 8 0
| Globe valv 0 340 0 | Globe valv 0 340 0 | Globe valv 1 340 0 | Globe valv 0 340 0
| Check 1 50 0 | Check 0 50 0 | Check 0 50 0 | Check 0 50 0
| Stop-check 0 400 0 | Stop-check 0 400 0 | Stop-check 0 400 0 | Stop-check 0 400 0
| Elbow 5 20 0 | Elbow 4 20 0 | Elbow 0 20 0 | Elbow 3 20 0
| 180 Bend 0 50 0 | 180 Bend 0 50 0 | 180 Bend 0 50 0 | 180 Bend 0 50 0
| T-Straight 1 20 0 | T-Straight 0 20 0 | T-Straight 0 20 0 | T-Straight 1 20 0
| T-Branch 0 60 0 | T-Branch 0 60 0 | T-Branch 0 60 0 | T-Branch 0 60 0
| Other 0 0 | Other 0 0 | Other 0 0 | Other 0 0
Total K | 0 | 0 | 0 | 0
Total L/D | 186 | 80 | 340 | 88
Equiv Length m | 40.3 | 79.6 | 44.7 | 66.9

======================================================================================================================================================
C:\Users\mohsi\OneDrive\Desktop\PEC\Bulawayo\Pump House Pool Fire.dat
======================================================================================================================================================
Hydraulic Simulation: Pump House Pool Fi This information is confidential, and shall Page: 8
Technical Audit of Existing Fire Fightin not be reproduced by any means without the Proj: 2901-001
at Bulawayo Depot written permission of PETROCHEMICAL ENGINEERING CONSULTANTS . By : SMR
Vivo Energy - Zimbabwe Chkd/Apvd: MZK / SMS
PIPE LINE REPORT Date: 16-09-2019
======================================================================================================================================================

-----------------------------------------------------------------------------------------------------------------------------------------------------
Line number | L9 | L7 | L12 | L8
Line name | Pipe | Pipe | Pipe | Pipe
-----------------------------------------------------------------------------------------------------------------------------------------------------
PROCESS DATA | AVG IN OUT | AVG IN OUT | AVG IN OUT | AVG IN OUT
Temperature C | 25.0 25.0 25.0 | 25.0 25.0 25.0 | 25.0 25.0 25.0 | 25.0 25.0 25.0
Pressure psig | 157.6 157.7 157.5 | 157.8 157.9 157.8 | 149.0 157.7 140.2 | 157.8 157.8 157.7
Liq Fraction wt | 1.0 1.0 1.0 | 1.0 1.0 1.0 | 1.0 1.0 1.0 | 1.0 1.0 1.0
Total-Flow t/h | 11.4 | 17.28 | 17.28 | 30.6
Dens-NS kg/m3 | 1,000 1,000 1,000 | 1,000 1,000 1,000 | 1,000 1,000 1,000 | 1,000 1,000 1,000
Elev kg/m3 | 1,000 | 1,000 | 1,000 | 1,000
Visc-NS cP | 1.0 | 1.0 | 1.0 | 1.0
Vapor-Flow t/h | 0 | 0 | 0 | 0
Density kg/m3 | 13.4 | 13.4 | 12.7 | 13.4
Visc cP | 0.010 | 0.010 | 0.010 | 0.010
Mol wt | 28.0 | 28.0 | 28.0 | 28.0
Z | 1.0 | 1.0 | 1.0 | 1.0
Cp/Cv | 1.4 | 1.4 | 1.4 | 1.4
Liquid-Flow (wt) t/h | 11.4 | 17.28 | 17.28 | 30.6
Flow (vol) m3/h | 11.4 | 17.28 | 17.28 | 30.6
Density kg/m3 | 1,000 | 1,000 | 1,000 | 1,000
Visc cP | 1.0 | 1.0 | 1.0 | 1.0
PIPE DATA | | | |
Size in | 4 | 6 | 3 | 6
Length m | 60.0 | 90.0 | 20.0 | 70.0
Schedule | 40 | 40 | 40 | 40
ID mm | 102 | 154 | 77.9 | 154
Roughness (E-3) mm | 45.7 | 45.7 | 45.7 | 45.7
Safety factor | 1.0 | 1.0 | 1.0 | 1.0
Sum of elev's m | 0 | 0 | 0 | 0
VELOCITY | | | |
Velocity ft/s | 1.26 1.26 1.26 | 0.845 0.845 0.845 | 3.3 3.3 3.3 | 1.5 1.5 1.5
Sonic-Vapor adia ft/s | 1,155 | 1,155 | 1,155 | 1,155
Vapor isoT ft/s | 976 | 976 | 976 | 976
PRESSURE DROP (In-Out) | | | |
Overall psi | 0.1773 | 0.07641 | 17.48 | 0.152
Friction psi | 0.1773 | 0.07641 | 0.4021 | 0.152
Accel'n psi | 0 | 0 | 0 | 0
Static psi | 0 | 0 | 17.07 | 0
dP/Length psi/100ft | 0.0751 | 0.0218 | 0.613 | 0.0615
LINE SIZING | MAX/LARGER MIN/SMALLER | MAX/LARGER MIN/SMALLER | MAX/LARGER MIN/SMALLER | MAX/LARGER MIN/SMALLER
dP/Length psi/100ft | 0.999 | 0.999 | 0.999 | 0.999
Velocity ft/s | 328 0.984 | 328 0.984 | 328 0.984 | 328 0.984
VelCoef ft/s | 12.4 1.04 | 12.4 1.04 | 12.4 1.04 | 12.4 1.04
Size-Larger/Small in | 6 3 | 8 4 | 4 2 | 8 4
dP/Length psi/100ft | 0.0103 0.284 | 0.0058 0.16 | 0.16 4.43 | 0.0162 0.462
Velocity ft/s | 0.557 2.18 | 0.488 1.92 | 1.92 7.27 | 0.864 3.4

======================================================================================================================================================
C:\Users\mohsi\OneDrive\Desktop\PEC\Bulawayo\Pump House Pool Fire.dat
======================================================================================================================================================
Hydraulic Simulation: Pump House Pool Fi This information is confidential, and shall Page: 9
Technical Audit of Existing Fire Fightin not be reproduced by any means without the Proj: 2901-001
at Bulawayo Depot written permission of PETROCHEMICAL ENGINEERING CONSULTANTS . By : SMR
Vivo Energy - Zimbabwe Chkd/Apvd: MZK / SMS
PIPE LINE REPORT Date: 16-09-2019
======================================================================================================================================================

-----------------------------------------------------------------------------------------------------------------------------------------------------
Line number | L9 | L7 | L12 | L8
Line name | Pipe | Pipe | Pipe | Pipe
-----------------------------------------------------------------------------------------------------------------------------------------------------
LIQUID HOLDUP | | | |
Liquid Fraction (vol) | 1.0 | 1.0 | 1.0 | 1.0
Liquid Holdup(dP) (vol) | 1.0 | 1.0 | 1.0 | 1.0
2-PHASE METHOD | Homogeneous | Homogeneous | Homogeneous | Homogeneous
FLOW REGIME | | | |
Horizontal | - | - | - | -
Vertical-Up | - | - | - | -
Vertical-Down | - | - | - | -
HOMOGENEOUS/DUKLER | | | |
Reynolds No | 39,431 | 39,675 | 78,431 | 70,256
Friction factor | 0.02338 | 0.02292 | 0.02134 | 0.02061
Friction factor (turb) | 0.01627 | 0.01489 | 0.0173 | 0.01489
Dukler-2phase factor | 1.00 | 1.00 | 1.00 | 1.00
density kg/m3 | 0 | 0 | 0 | 0
LOCKHART-M/CHENOWETH-M | | | |
Liquid-Re | 0 | 0 | 0 | 0
f | 0 | 0 | 0 | 0
Psi/Psi^2 | 0 | 0 | 0 | 0
Vapor-Re | 0 | 0 | 0 | 0
f | 0 | 0 | 0 | 0
Psi^2 | 0 | 0 | 0 | 0
X factor | 0 | 0 | 0 | 0
FITTINGS | TYPE No L/D K | TYPE No L/D K | TYPE No L/D K | TYPE No L/D K
| Entrance 0 0 0.5 | Entrance 0 0 0.5 | Entrance 0 0 0.5 | Entrance 0 0 0.5
| Exit 0 0 1 | Exit 0 0 1 | Exit 0 0 1 | Exit 0 0 1
| Gate valve 1 8 0 | Gate valve 1 8 0 | Gate valve 0 8 0 | Gate valve 1 8 0
| Globe valv 0 340 0 | Globe valv 0 340 0 | Globe valv 0 340 0 | Globe valv 0 340 0
| Check 0 50 0 | Check 0 50 0 | Check 0 50 0 | Check 0 50 0
| Stop-check 0 400 0 | Stop-check 0 400 0 | Stop-check 0 400 0 | Stop-check 0 400 0
| Elbow 7 20 0 | Elbow 7 20 0 | Elbow 0 20 0 | Elbow 1 20 0
| 180 Bend 0 50 0 | 180 Bend 0 50 0 | 180 Bend 0 50 0 | 180 Bend 0 50 0
| T-Straight 1 20 0 | T-Straight 1 20 0 | T-Straight 0 20 0 | T-Straight 1 20 0
| T-Branch 0 60 0 | T-Branch 0 60 0 | T-Branch 0 60 0 | T-Branch 0 60 0
| Other 0 0 | Other 0 0 | Other 0 0 | Other 0 0
Total K | 0 | 0 | 0 | 0
Total L/D | 168 | 168 | 0 | 48
Equiv Length m | 72.0 | 107 | 20.0 | 75.3

NOTES - (1) dPoverall = dPfrictional + dPaccel + dPstatic


(2) NS = No slip or homogenous

======================================================================================================================================================
C:\Users\mohsi\OneDrive\Desktop\PEC\Bulawayo\Pump House Pool Fire.dat
======================================================================================================================================================
Hydraulic Simulation: Pump House Pool Fi This information is confidential, and shall Page: 10
Technical Audit of Existing Fire Fightin not be reproduced by any means without the Proj: 2901-001
at Bulawayo Depot written permission of PETROCHEMICAL ENGINEERING CONSULTANTS . By : SMR
Vivo Energy - Zimbabwe Chkd/Apvd: MZK / SMS
FEED SUMMARY Date: 16-09-2019
======================================================================================================================================================

Number Description Elevation Density Level Rel Elev Rel Pres dP Level dP Inlet Pres
m kg/m3 m m psi psi psi psig

FW Tank Feed to Unit 0.60 1,000 0.50 0 - 0.711 0.091 0

======================================================================================================================================================
C:\Users\mohsi\OneDrive\Desktop\PEC\Bulawayo\Pump House Pool Fire.dat
======================================================================================================================================================
Hydraulic Simulation: Pump House Pool Fi This information is confidential, and shall Page: 11
Technical Audit of Existing Fire Fightin not be reproduced by any means without the Proj: 2901-001
at Bulawayo Depot written permission of PETROCHEMICAL ENGINEERING CONSULTANTS . By : SMR
Vivo Energy - Zimbabwe Chkd/Apvd: MZK / SMS
PRODUCT SUMMARY Date: 16-09-2019
======================================================================================================================================================

Number Description Elevation Density Level Rel Elev Rel Pres dP Level dP Inlet Pres
m kg/m3 m m psi psi psi psig

PumpHous Product from Unit 0 1,000 0 0 - 0 0 157


T-678 Product from Unit 12.0 1,000 0 0 - 0 0 140
Shed Product from Unit 0 1,000 0 0 - 0 0 158
TWGantry Product from Unit 0 1,000 0 0 - 0 0 157

======================================================================================================================================================
C:\Users\mohsi\OneDrive\Desktop\PEC\Bulawayo\Pump House Pool Fire.dat
======================================================================================================================================================
Hydraulic Simulation: Pump House Pool Fi This information is confidential, and shall Page: 12
Technical Audit of Existing Fire Fightin not be reproduced by any means without the Proj: 2901-001
at Bulawayo Depot written permission of PETROCHEMICAL ENGINEERING CONSULTANTS . By : SMR
Vivo Energy - Zimbabwe Chkd/Apvd: MZK / SMS
PUMP SUMMARY Date: 16-09-2019
======================================================================================================================================================

Number Description Eff Power Flow Density Vol Flow Head Pout-Pin PresIn PresOut
kW t/h kg/m3 m3/h m psi psig psig

P1 Pump 1.0 22.8 75.2 1,000 75.2 111 158 1.03 159

======================================================================================================================================================
C:\Users\mohsi\OneDrive\Desktop\PEC\Bulawayo\Pump House Pool Fire.dat
======================================================================================================================================================
Hydraulic Simulation: Pump House Pool Fi This information is confidential, and shall Page: 13
Technical Audit of Existing Fire Fightin not be reproduced by any means without the Proj: 2901-001
at Bulawayo Depot written permission of PETROCHEMICAL ENGINEERING CONSULTANTS . By : SMR
Vivo Energy - Zimbabwe Chkd/Apvd: MZK / SMS
T-PIECE SUMMARY Date: 16-09-2019
======================================================================================================================================================

Number Description Service Line Spacing Kc Q/Qc A/Ac Pressure


L/ID psig

T1 Tee piece Combined L2 1.0 1.0 158


Manifold L6 0 -0.0027 0.637 1.0 158
Branch L11 1.07 0.363 1.0 158

T4 Tee piece Combined L8 1.0 1.0 158


Manifold L10 0 0 0.627 1.0 158
Branch L9 1.36 0.373 0.441 158

T3 Tee piece Combined L6 1.0 1.0 158


Manifold L7 0 1.04 0.361 1.0 158
Branch L8 1.12 0.639 1.0 158

NOTES - (1) dP Inlet for Feed, Products and Vessels represent pressure to velocity conversion only, not friction.

======================================================================================================================================================
C:\Users\mohsi\OneDrive\Desktop\PEC\Bulawayo\Pump House Pool Fire.dat
======================================================================================================================================================
Hydraulic Simulation: Pump House Pool Fi This information is confidential, and shall Page: 14
Technical Audit of Existing Fire Fightin not be reproduced by any means without the Proj: 2901-001
at Bulawayo Depot written permission of PETROCHEMICAL ENGINEERING CONSULTANTS . By : SMR
Vivo Energy - Zimbabwe Chkd/Apvd: MZK / SMS
WARNINGS & ERRORS Date: 16-09-2019
======================================================================================================================================================

Warning! Line L7 velocity coef less than minimum (m/s) = 0.3162


Warning! Line L10 velocity coef less than minimum (m/s) = 0.3162

======================================================================================================================================================
C:\Users\mohsi\OneDrive\Desktop\PEC\Bulawayo\Pump House Pool Fire.dat