Relay

This document summarizes an undervoltage relay called the BA 9043, AA 9943, and VARIMETER. It is a 3-phase undervoltage relay that monitors nominal voltages from 100/57V to 690/400V. It measures the arithmetic mean value of voltage across the three phases and has adjustable operate and release values. It has LED indicators, is insensitive to harmonics, and works with frequencies up to 400Hz.

Uploaded by

Uni uni
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
98 views4 pages

Relay

This document summarizes an undervoltage relay called the BA 9043, AA 9943, and VARIMETER. It is a 3-phase undervoltage relay that monitors nominal voltages from 100/57V to 690/400V. It measures the arithmetic mean value of voltage across the three phases and has adjustable operate and release values. It has LED indicators, is insensitive to harmonics, and works with frequencies up to 400Hz.

Uploaded by

Uni uni
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Monitoring technique

Undervoltage relay BA 9043, AA 9943


VARIMETER

• According to IEC 255, EN 60 255, VDE 0435 part 303


• 3-phase
• For nominal voltage of 3 AC 100 / 57 to 690 / 400 V

0221539

Measures arithmetic mean value


• Adjustable operate and release value
• For 3p3w or 3p4w systems
• BA 9043 optionally with adjustable time delay
• Closed circuit operation
• LED indicator for operation and state of contact
• Insensitive to harmonics
• Frequency up to 400 Hz
• Width 45 mm

BA 9043 AA 9943

Function diagram Approvals and marking

operate value
0,4-0,6UN Application
hysteresis
3 phases L1, L2, L3 Undervoltage detection in 3 phase systems
t
Indicators
BA9043 11-14 upper LED: on, when voltage connected
BA9043/001
AA9943 11-12 (only BA 9043)
lower LED: on, when output contact activated

BA9043/002 11-14 Notes


BA9043/003
11-12
tv
For determination of the arithmetic mean value of the voltage the 3
M6864_a
tv phases are measured against N.
The variants without N ( /001 and /003) measure L1 and L2 against L3.
delay the delay is only active at U ≥ 0,6 UN . At < 0.4 UN the relay switches
off without delay.

Circuit diagram Technical Data

Input
L1 L2 L3 11 21 L1 L2 L3 11 21

L1 L1 Nominal voltage UN
11 21 11 21 BA 9043, BA 9043/002
N L2 AA 9943: 3/N AC 100/57 V; 220/127 V; 400/230 V
L2 415/240 V; 440/254 V; 500/290 V
L3 12 14 22 24 12 14 22 24
L3 BA 9043, BA 9043/002: 3 AC 690/400 V
BA 9043/001, BA 9043/003
12 14 22 24 N 12 14 22 24
M7520 M7521 AA 9943/001: 3 AC 100 V; 220 V; 400 V; 415 V, 440 V;
500 V
BA 9043, BA 9043/002 BA 9043/001, BA 9043/003
BA 9043/001, BA 9043/003: 3 AC 690 V
AA 9943 AA 9943/001
Max. overload
BA 9043: 1.2 UN continuously
AA 9943: 1.1 UN continuously
Nominal consumption: AC 4 VA
Nominal frequency: 50 ... 400 Hz
Frequency range: ±5%
Temperature influence: < 0.05 % / K

Setting ranges

Response value: 0.85 ... 1.05 UN, infinite variable with


upper potentiometer
Hysteresis: 0.75 ... 0.95 of operate value
Setting accuracy: ≤ ± 10 %
Switching delay tM: see diagram switching delay
Time delay tv: infinite variable from 0.5 ... 10 sec for
BA 9043/002, BA 9043/003
Between 0.4 and 0.6 UN the contacts
fall back according to the diagram
without additional delay

All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time. 1 06.12.10 e / 082
Technical Data Variants

Output AA 9943/001: without neutral


AA 9943/175: for nuclear power plants
Contacts BA 9043/001: without neutral
BA 9043: 2 changeover contacts BA 9043/002: with neutral, adjustable time delay
AA 9943.11: 1 changeover contact tv = 0.5 ... 10 sec
AA 9943.12: 2 changeover contacts BA 9043/003: without neutral, adjustable time delay
Thermal current Ith: 6 A; see diagramm tv = 0.5 ... 10 sec
Continuous current limit curve Ordering example for Variants
Switching capacity
to AC 15
BA 9043 /_ _ _ 3/N AC 400/230 V 50 ... 400 Hz
NO contact: 3 A / AC 230 V IEC/EN 60 947-5-1
NC contact: 1 A / AC 230 V IEC/EN 60 947-5-1
to DC 13 Nominal frequency
NO contact: 1 A / DC 24 V IEC/EN 60 947-5-1 Nominal voltage
NC contact: 1 A / DC 24 V IEC/EN 60 947-5-1 Variant, if required
Electrical life IEC/EN 60 947-5-1 Type
to AC 15 at 3 A, AC 230 V: 3 x 105 switching cycles
Short circuit strength AA 9943 .11 /_ _ _ 3/N AC 400/230 V 50 ... 400 Hz
max. fuse rating: 4 A gL IEC/EN 60 947-5-1
Mechanical life: > 30 x 106 switching cycles Nominal frequency
Nominal voltage
General Data Variant, if required
Contact
Operating mode: Continuous operation Type
Temperature range: - 20 ... + 60°C
Clearance and creepage
distances Accessories
rated impuls voltage /
AA 9943:
pollution degree: 4 kV / 2 IEC 60 664-1
K 70-34 Cover
EMC
Electrostatic discharge: 8 kV (air) IEC/EN 61 000-4-2
HF irradiation: 10 V/m IEC/EN 61 000-4-3
Fast transients: 2 kV IEC/EN 61 000-4-4
Surge voltages
between
wires for power supply: 1 kV IEC/EN 61 000-4-5
between wire and ground: 2 kV IEC/EN 61 000-4-5
HF wire guided: 10 V IEC/EN 61 000-4-6
Interference suppression: Limit value class B EN 55 011
Degree of protection
Housing: IP 40 IEC/EN 60 529
Terminals: IP 20 IEC/EN 60 529
Housing: Thermoplastic with V0 behaviour
according to UL subject 94
Vibration resistance: Amplitude 0.35 mm IEC/EN 60 068-2-6
frequency 10 ... 55 Hz
Climate resistance: 20 / 060 / 04 IEC/EN 60 068-1
Terminal designation: DIN EN 50 005
Wire connection: 2 x 2.5 mm2 solid or
2 x 1.5 mm2 stranded wire with sleeve
DIN 46 228-1/-2/-3/-4
Wire fixing: Flat terminals with self-lifting
clamping piece IEC/EN 60 999-1
Mounting: DIN rail IEC/EN 60 715
Weight
BA 9043: 310 g
AA 9943: 300 g

Dimensions

Width x height x depth


BA 9043: 45 x 73 x 132 mm
AA 9943: 45 x 77 x 127 mm

Standard type

BA 9043 3/N AC 400 / 230 V 50 ... 400 Hz


Article number: 0039676 stock item
• for 3p4w systems
• Nominal voltage UN: 3/N AC 400 / 230 V
• Output: 2 changeover contacts
• Width: 45 mm

2 06.12.10 e / 082
Characteristics Specification for tender for BA 9043

I (A) Undervoltage relay according to IEC 255, VDE 0435 for nominal voltage
A of 3 AC 100/57 to 500/290 V. Adjustable operate and release value, for
contact current
6
3p4w systems
Width 45 mm
5 B Type BA 9043
Manufactured by E. DOLD & SÖHNE KG
4
Undervoltage relay according to IEC 255, VDE 0435 for nominal voltage of
3 AC 100/57 to 500/290 V. Adjustable operate and release value, for 3p4w
3
systems, adjustable time delay up to 10 s.
Width 45 mm
2 Type BA 9043/002
Manufactured by E. DOLD & SÖHNE KG
1
Undervoltage relay according to IEC 255, VDE 0435 for nominal voltage
of 3 AC 100/57 to 500/290 V. Adjustable operate and release value, for
-20 0 20 40 60 T (°C) 3p3w systems
M6865_a ambient temperature Width 45 mm
Type BA 9043/001
Continuous current limit curve Manufactured by E. DOLD & SÖHNE KG

A = Devices mounted with 2 cm distance Undervoltage relay according to IEC 255, VDE 0435 for nominal voltage of
B = Devices mounted without distance 3 AC 100/57 to 500/290 V. Adjustable operate and release value, for 3p3w
systems, adjustable time delay up to 10 s.
F
x off Width 45 mm
2,0 Type BA 9043/003
1,8 Manufactured by E. DOLD & SÖHNE KG
x on
1,6
1,4
1,2
1,0
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2
t [s]
M6866_a

Diagram switching delay

Switching delay tM:

When the voltage changes fast on the measuring input, the arithmetic mean
value can only adjust after a short delay.

Example:
U applied 240 V
F= F= = 1.26
U setting 190 V

U setting = 190 V
U applied = 240 V

according to diagram:
tMon = approx. 800 ms
tMoff = approx. 100 ms

3 06.12.10 e / 082
E. DOLD & SÖHNE KG • D-78114 Furtwangen • PO Box 1251 • Telephone (+49) 77 23 / 654-0 • Telefax (+49) 77 23 / 654-356
e-mail: [email protected] • internet: http://www.dold.com 4 06.12.10 e / 082