Cooling Load Calculations: Temperatures Summer Outdoor Coldest Outdoor Coldest Indoor
Cooling Load Calculations: Temperatures Summer Outdoor Coldest Outdoor Coldest Indoor
TEMPERATURES
Summer Outdoor Coldest 20 o
F
Outdoor
Dry Bulb 93 o
F
Coldest 70 o
F
Summer Indoor Indoor
Dry Bulb 68 o
F Daily Range 25 o
F
*SHR = Sensible Load/Total Load, Use: 0.65 for Tropic, 0.70 Humid, 0.75 Avg., 0.80
Dry, 0.85 Arid
WALLS
U CLTD Area(sq. ft) C. Load
North 0.055 15.5 193 0.16
NE 0.055 21.5 0.00
East 0.055 25.5 193 0.27
SE 0.055 23.5 0.00
South 0.055 18.5 193 0.20
SW 0.055 23.5 0.00
West 0.055 25.5 193 0.27
NW 0.055 21.5 0.00
DOORS
U CLTD Area(sq. ft) C. Load
North 0.25 15.5 0.00
NE 0.25 21.5 0.00
East 0.25 25.5 22 0.14
SE 0.25 23.5 0.00
South 0.25 18.5 0.00
SW 0.25 23.5 0.00
West 0.25 25.5 20 0.13
NW 0.25 21.5 0.00
PEOPLE
Number Btu/hr-person Cooling Load
5 230 1.15
COMPUTED VALUES
Sensible Cooling Load, Mbtu/h 15.24
Net Cooling Load, Mbtu/h 23.44
Windows
U SC GLF Area (sq.ft) Cooling Load
North 0.55 0.45 25.06 14 0.35
NE 0.55 0.55 43.20 10 0.43
East 0.55 0.55 56.95 40 2.28
SE 0.55 0.55 39.79 11 0.44
South 0.55 0.55 24.17 14 0.34
SW 0.55 0.55 39.79 21 0.84
West 0.55 0.3 37.31 64 2.39
NW 0.55 0.55 93.83 12 1.13
Drapes, Venetian
None Blind, or Translucent Opaque Roller Shade
Roller Shade
Glass Type SC U SC U SC U
Single 1.00 1.04 0.50 0.81 0.38 0.81
Double 0.88 0.61 0.45 0.55 0.36 0.55
Heat Absorbin 0.58 0.45 0.37 0.44 0.33 0.44
Triple 0.80 0.44 0.44 0.40 0.36 0.40
ROOF
U CLTD Area (sq. ft) C. Load
0.033 49.5 390 0.64
INFILTRATION
cfm C. Load
Summer 0 0.00
SENSIBLE
Total Sensible Load 15.24