Mechanical Measurements and Control System PDF
Mechanical Measurements and Control System PDF
& TECHNOLOGY
(Autonomous Institution – UGC, Govt. of India)
Recognized under 2(f) and 12 (B) of UGC ACT 1956
(Affiliated to JNTUH, Hyderabad, Approved by AICTE - Accredited by NBA & NAAC –
‘A’ Grade - ISO 9001:2015 Certified)
Maisammaguda, Dhulapally (Post Via. Kompally), Secunderabad – 500100,
Telangana State, India
For
B.Tech – IV YEAR – I sem
Prepared by
Mr. K .Bicha
Mrs.Prasuna Lilly
DIGITAL NOTES
MALLA REDDY COLLEGE OF ENGINEERING & TECHNOLOGY
IV Year B. Tech, ME-I Sem L T/P/D C
3 0 3
Objectives:
To impart knowledge of architecture of the measurement system.
To deliver working principle of mechanical measurement system.
To study concept of mathematical modeling of the control system. To analyse control
system under different time domain
UNIT –I
Definition – Basic principles of measurement – Measurement systems, generalized
configuration and functional descriptions of measuring instruments – examples. Dynamic
performance characteristics – sources of error, Classification and elimination of error.
Measurement of Displacement: Theory and construction of various transducers to
measure displacement – Piezo electric, Inductive, capacitance, resistance, ionization and
Photo electric transducers, Calibration procedures.
UNIT –II
Measurement of Temperature: Classification – Ranges – Various Principles of measurement –
Expansion, Electrical Resistance – Thermistor – Thermocouple – Pyrometers – Temperature
Indicators.
Measurement of Pressure: Units – classification – different principles used. Manometers,
Piston, Bourdon pressure gauges, Bellows – Diaphragm gauges. Low pressure measurement –
Thermal conductivity gauges – ionization pressure gauges, Mcleod pressure gauge.
Measurement of Level: Direct method – Indirect methods – capacitative, ultrasonic,
magnetic, cryogenic fuel level indicators – Bubler level indicators.
UNIT –III
Flow Measurement: Rotameter, magnetic, Ultrasonic, Turbine flow meter, Hot – wire
anemometer, Laser Doppler Anemometer (LDA).
Measurement of Speed: Mechanical Tachometers – Electrical tachometers –
Stroboscope, Noncontact type of tachometer
Measurement of Acceleration and Vibration: Different simple instruments – Principles of
Seismic instruments – Vibrometer and accelerometer using this principle.
UNIT –IV
Stress Strain Measurements: Various types of stress and strain measurements – electrical
strain gauge – gauge factor – method of usage of resistance strain gauge for bending
compressive and tensile strains – usage for measuring torque, Strain gauge Rosettes.
Measurement of Humidity – Moisture content of gases, sling psychrometer, Absorption
psychrometer, Dew point meter.
UNIT –V
Measurement of Force, Torque And Power- Elastic force meters, load cells, Torsion meters,
Dynamometers.
Elements of Control Systems: Introduction, Importance – Classification – Open and closed
systems Servomechanisms– Examples with block diagrams–Temperature, speed & position
control systems.
TEXT BOOKS:
1. Mechanical Measurements / Beck With, Marangoni, Linehar/ PHI Publisher
2. Measurement Systems: Applications & design / D.S Kumar/McGraw Hill Publishers
3. Mechanical Measurements /Shawney/McGraw Hill Publishers
REFERENCE BOOKS:
1. Experimental Methods for Engineers / Holman/ McGraw-Hill Education
2. Mechanical and Industrial Measurements / R.K. Jain/ Khanna Publishers.
3. Instrumentation and Mechanical Measurements / A.K. Tayal / Galgotia Publications.
OUTCOMES:
Learner should be able to Identify and select proper measuring instrument for specific
application Illustrate working principle of measuring instruments.
Explain calibration methodology and error analysis related to measuring instruments
Mathematically model and analyze.
UNIT- I
Measurement:-
The old measurement is used to tell us length, weight and temperature are a change of these
physical measurement is the result of an opinion formed by one (or) more observes about the
relative size (or) intensity of some physical quantities.
Definition:
The word measurement is used to tell us the length, the weight, the temperature, the colour or a
change in one of these physical entities of a material. Measurement provides us with means for
describing the various physical and chemical parameters of materials in quantitative terms. For example
10 cm length of and object implies that the object is 10 times as large as 1 cm; the unit employed in
expressing length.
These are two requirements which are to be satisfied to get good result from the measurement.
1. The standard must be accurately known and internationally accepted.
2. The apparatus and experimental procedure adopted for comparison must be provable.
Instrumentation:-
Definition:
The human senses cannot provide exact quantitative information about the knowledge of events
occurring in our environments. The stringent requirements of precise and accurate measurements in the
technological fields have, therefore, led to the development of mechanical aids called instruments.
Or
Definition: the technology of using instruments to measure and control physical and
chemical properties of materials is called instrumentation.
In the measuring and controlling instruments are combined so that measurements provide
impulses for remote automatic action, the result is called control system.
Uses:
-> study the function of different components and determine the cause of all functioning of the system,
to formulate certain empirical relations.
-> to test a product on materials for quality control.
-> to discover effective components.
-> to develop new theories.
-> monitor a data in the interest of health and safety.
Ex:- fore casting weather it predicting in the earth case.
Methods of measurement:-
1. Direct and indirect measurement.
2. Primary and secondary & tertiary measurement.
3. Contact and non-contact type of measurement.
Measurement is a process of comparison of the physical quantity with a standard depending upon
requirement and based upon the standard employed, these are the two basic methods of
measurement.
Direct measurement:
The value of the physical parameter is determined by comparing it directly with
different standards. The physical standards like mass, length and time are measured by direct
measurement.
Indirect measurement:
The value of the physical parameter is more generally determined by indirect
comparison with the secondary standards through calibration.
The measurement is convert into an analogous signal which subsequently process
and fed to the end device at present the result of measurement.
Ex:
The convergent of pressure into displacement by means of be allows and the convergent of
force into displacement.
Pressure measurement by manometer and the temperature measurement by mercury in
glass tube thermometer.
The measurement of static pressure by boundary tube pressure gauge is a typical example of tertiary
measurement.
3. Contact and non-contact type of measurements:
Contact type:
Where the sensing element of measuring device as a contact with medium whose characteristics
are being measured.
Non-contact type:
Where the sense doesn't communicate physically with the medium.
Ex:
The optical, radioactive and some of the electrical/electronic measurement belong to this category.
Objectives of instrumentation:-
1. The major objective of instrumentation is to measure and control the field parameters to increase
safety and efficiency of the process.
2. To achieve good quality.
3. To achieve auto machine and automatic control of process there by reducing human.
4. To maintain the operation of the plan within the design exportations and to achieve good quantity
product.
Generalised measurement system and its functional elements:-
3) Manipulation of element.
The principal functions of an instrument is the acquisition of information by Sensing and perception, the
process of that information and its final presentation to a Human observer. For the purpose of analysis
and synthesis, the instrument s are considered as systems (or) assembly of inter connected components
organised to perform a specified function. The different components are called elements.
An element that is sensitive to the measured variable .The sensing element sense the condition , state
(or) value of the process variable by extracting a small part of energy from the measurement and
produces an output which is proportional to the input. Because of the energy expansion, the measured
quantity is always disturb. Good instruments are designed to minimise this loading effect.
An element that converts the signal from one physical for to Another without changing the
information content of the signal.
Example:
It modifies the direct signal by amplification, filtering etc., so that a desired output is produced.
[input]× constant = Output
An element that transmits the signal from one location to another without changing the information
content. Data may by transmitted over long distances (from one location to another) or short
distances (from a test centre to a nearby computer).
An element that modifies data before it is displayed or finally recorded. Data processing may be used for
such purposes as:
Corrections to the measured physical variables to compensate for scaling, non-linearity, zero
offset, temperature error etc.
useful form, e.g., calculation of engine efficiency from speed, power input and
Covert the data into
torque developed.
Collect information regarding average, statistical and logarithmic values.
An element that provides record or indication of the output from the data processing element. Ina
measuring system using electrical instrumentation, an exciter and an amplifier are also incorporated
into the circuit.
a) Input Stage
b) Intermediate Stage
i. Signal Amplifications
c) Output Stage
a) Input Stage:
Input stage (Detector-transducer) which is acted upon by the input signal (a variable to be measured)
such as length, pressure, temperature, angle etc. and which transforms this signal in some other physical
form. When the dimensional units for the input and output signals are same, this functional
element/stage is referred to as the transformer.
b) Intermediate Stage:
i. signal amplification to increase the power or amplitude of the signal without affecting its
waveform. The output from the detector-transducer element' is generally too small to operate an
indicator or a recorder and its amplification is necessary. Depending upon the type of transducer
signal, the amplification device may be of mechanical, hydraulic/pneumatic, optical and electrical
type.
ii. Signal filtration to extract the desired information from extraneous data. Signal filtration removes the
unwanted noise signals that tend to obscure the transducer signal. Depending upon nature of the signal
and situation, one may use mechanical, pneumatic or electrical filters.
iii. Signal modification to provide a digital signal from an analog signal or vice versa, or change the form
of output from voltage to frequency or from voltage to current.
Iv. Data transmission to telemeter the data for remote reading and recording.
c) Output Stage:
which constitutes the data display record or control. The data presentation stage collects the
output from the signal-conditioning element and presents the same to be read or seen and noted
by the experimenter for analysis. This element may be of:-
visual
display type such as the height of liquid in a manometer or the position of pointer on a
scale
numerical readout on an electrical instrument
Graphic record on some kind of paper chart or a magnetic tape.
The manual instruments require the services of an operator while the automatic types donot. For
example, the temperature measurement by mercury-in-glass thermometer is automatic as the
instrument indicates the temperature without requiring any manual assistance. However, the
measurement of temperature by a resistance thermometer incorporating; Wheatstone brigde in its
circuit is manual in operation as it needs an operator for obtaining the null position.
Self-generated instruments are the output is supplied entirely by the input signal. The
instrument does not require any out side power in performing its function
Example: mercury in glass thermometer, bourdon pressure gauge, pitot tube for measuring velocity
So instruments require same auxillary source of power such as compound air, electricity, hydraulic
supply for these operations and hence are called externally powered instruments (or) passive
instruments.
Example:
The different elements of a self-contained instrument are contained in one physical assembly. In a
remote indicating instrument, the primary sensing element may be located at a sufficiently long distance
from the secondary indicating element. In the modern instrumentation technology, there is a trend to
instalremote indicating instruments where the important indications can be displayed in the central
control rooms.
4) Deflection and null output instruments:
In null-type instruments, the physical effect caused by the quantity being measured is nullified
(deflection maintained at zero) by generating an equivalent opposing effect. The equivalent null
causing effect then provides a measure of the unknown quantity. A deflection type instrument is that in
which the physical effect generated by the measuring quantity (measurand) is noted and correlated to
the measurand.
The signals of an analog unit vary in a continuous fashion and can take on infinite number of values in
a given range. Wrist watch speedometer of an automobile, fuel gauge, ammeters and voltmeters are
examples of analog instruments.
Accordingly based upon the service rendered, the instruments may also be classified as indicating
instruments, recording instruments and controlling instruments.
o=G i
i) Desired input:
A quantity that the instrument is specifically intended to measure. The desired input produces an
output component according to an input-output relation symbolised by ; here represents the
mathematical operation necessary to obtain the output from the input.
ii) Interfering input:
A quantity to which the instrument is unintentionally sensitive. The interfering input would produce
an output component according to input-output relation symbolised by
A quantity that modifies the input-6utput relationship for both the desired and interfering inputs. The
modifying input would cause a change in and/or . The specific manner in which affects and G, is
represented by the symbols and , respectively.
Example:
Consider a deferential manometer which consists of an u-tube filled with mercury and with its ends
connected to the two points between which the pressure differentia is to be measured .The pressure
differential 1- 2 is worked out from the hydro static (Equilibrium) equation:
( 1- 2)=g h ( − )
and are the mass densities of mercury and fluid respectively, and h is the scale reading. lf the fluid
flowing in the pipeline is a gas, then << accordingly the above identity can be re-written as
( 1- 2)=g h
Here differential pressure is 1- 2 is the desired input; Scale reading ‘h’ is the output and is the
parameter which relates the output and the input.
A) The manometer is placed on a wheel which is subjected to acceleration and scale indicates a reading
even through the pressures 1& 2 at the two ends are equal.
The acceleration that constitutes the interference input. The manometer has an angular tilt i.e., is
not properly align with the direction of the gravitational force.
An output will result even when there is no pressure difference. Here the angular tilt acts as
the interfering input.
Here scale factor establishes the input - output relation and this gets modified due to
1) Signal filtering
3) Output correction.
1. Static characteristics
2. Dynamic characteristics
The performance characteristics of an instrument system is conclusion by low accurately the
system measures the requires input and how absolutely it reject the undesirable inputs.
Error = measured value ( ) – true value (( )
Correction = ( - ).
1. Static characteristics:
The region between the limits with in which as instrument is designed to operate for measuring,
indicating (or) recording a physical quantity is called the range of instrument. The range is expressed
by standing the lower and upper values. Span represents the algebraic difference between the upper
and lower range values of the instruments.
Ex: -
o o o
Range - 10 C to 80 C Span=90 c
No instrument gives an exact value of what is being measured, there is always some uncertainty in the
measured values. This uncertainty express in terms of accuracy and error.
= -
c) Calibration:
The magnitude of the error and consequently the correction to be applied is determined by making
a periodic comparison of the instrument with standards which are known to be constant. The entire
procedure laid down for making, adjusting or checking a scale so that readings of an instrument or
measurement system conform to an Accepted standard is called the calibration. The graphical
representation of the calibration record is called calibration curve and this curve relates standard values
of input or measurand to actual values of output throughout the operating range of the instrument. A
comparison of the instrument reading may be made with
The following points and observations need consideration while calibrating an instrument:-
(a) Calibration of the instrument is out with the instrument in the same (upright, horizontal etc.) and
subjected same temperature and other environmental conditions under which it is to operate while in
service.
(b) The instrument is calibrated with values of the measuring impressed both in the increasing and in the
decreasing order. The results are then expressed graphically, typically the output is plotted as the
ordinate and the input or measuring as the abscissa.
(c) Output readings for a series of impressed values going up the scale may not agree with the output
readings for the same input values when going down.
(d) Lines or curves plotted in the graphs may not close to form a loop.
d) Repeatability:
Repeatability describes the closeness of the output readings, when the same input is applied
repeatability over a short period of time with the same measurement conditions, same instrument
and observer, same location and same conditions of use maintained throughout.
e) Reproductability: Reproductability describes the closeness of output readings for the same input.
When are changes in the method of measurement, observer, measuring instrument, location, conditions
of use and time of measurement.
f) Precision:
The instrument ability to reproduce a certain group of the readings with a given accuracy is known as
precision i.e., if a no of measurements are made on the same true value then the degree of closeness of
these measurements is called precision.
It refers to the ability of an instrument to give its readings again and again in the same manner
for constant input signals.
g) Sensitivity:
Sensitivity of an instrument is the ratio of magnitude of response (output signal) to the magnitude of the
quantity being measured (input signal) i.e.,
Threshold defines the minimum value of input which is necessary to cause detectable change from zero
output.
When the input to an instrument is gradually increased from zero, then the input must reach to a certain
minimum value, so that the change in the output can be detected. The minimum value of input refers to
threshold.
i) Resolution:
It is defines as the increment in the input of the instrument for which input remains constant i.e., when
the input given to the instrument is slowly increased for which the output remains same until the
increment exceeds a different value.
j) Drift:
The slow variation of the output signal of a measuring instrument is known as draft.
The variation of the output signal is not due to any changes in the input quantity, but to the changes in
the working conditions of the components inside the measuring instruments.
Hysteresis is the maximum difference for the same measuring quantity (input signal) between the up
scale and down scale reading during a full range measure in each direction.
Dead zone is the largest range through which an input signal can be varied without initiating
any response from the indicating instrument it is due to the friction.
2. Dynamic characteristics:
a) Speed of response and measuring lag, b) Fidelity and dynamic error, c) Over shoot, d) Dead time and
dead zone, e) Frequency response.
In a measuring instrument the speed of response (or) responsiveness is defined as the rapidity
with which an instrument responds to a change in the value of the quantity being measured.
Measuring lag refers to delay in the responds of an instrument to a change in the input signal.
The lag is caused by conditions such as inertia, or resistance.
Fidelity of an instrumentation system is defined as the degree of closeness with which the system
indicates (or) records the signal which is upon its. It refers to the ability of the system to reproduce the
output in the same form as the input. If the input is a sine wave then for 100% fidelity the output
should also be a sine wave.
The difference between the indicated quantity and the true value of the time quantity is the
dynamic error. Here the static error of instrument is assumed to be zero.
c) Over shoot:
Because of maximum and inertia. A moving part i.e., the pointer of the instrument does not
immediately came to reset in the find deflected position. The pointer goes find deflected position. The
pointer goes beyond the steady state i.e., it over shoots.
The over shoot is defined as the maximum amount by which the pointer moves beyond the steady
state.
Dead time is defined as the time required for an instrument to begin to respond to a change in the
measured quantity it represent the time before the instrument begins to respond after the
measured quantity has been altered.
Dead zone define the largest change of the measured to which the instrument does not respond.
Dead zone is the result as friction backlash in the instrument.
e) Frequency response:
(The dynamic performance of both measuring and control system is determine by applying some known
and predetermined input signal to its primary sensing element and them)
Maximum frequency of the measured variable that an instrument is capable of following with
error. The usual requirement is that the frequencies of the measured should not exceed 60% of the
natural frequency measuring instrument.
The dynamic performance of both measuring and control system is determined by applying some
known and predetermined input signal to its primary sensing element and then studying the behaviour
of the output signals.
i. Step functions
ii. Linear (or) ramp functions
iii. Sinusoidal (or) sine wave functions
i. Step function:
Which is a sudden change from one steady value to another the step input is
mathematically represented by
Where 0 ℎ .
The input varies linearly with time. The ramp input is mathematical represented as
=0 <0
=Ω ≥0
Here the input has a cycle variation, the input varies sinusoidal with a constant
amplitude mathematically it may be represented as
Zero, first and second order systems:-
The behaviour of a first order system is represented by a first order differential equation of the form.
Sources of error:
1. Calibration of Instrument
2. Instrument reproducibility
3. Measuring arrangement
4. Work piece
5. Environmental condition
6. Observes skill
1. Calibration of Instrument:
For any instrument calibration` is necessary before starting the process of measurement. When the
instrument is load frequently for long time, the calibration of instrument is used frequently for long
time, the calibration of instrument may get disturbed. The instrument which is gone out of b ration
cannot give actual value of the measured. Therefore the output produced by such an instrument have
error. The error due to improper calibration of instrument is known as systematic instrumental error,
and it occurs regularly.
Therefore this error can be eliminated by, properly calibrating the instrument at frequent intervals.
2. Instrument reproducibility:
Though an instrument is calibrated perfectly under group of conditions, the output produced by that
instrument contains error. This occurs if the instrument is used under those set of conditions which are
not identical to the conditions existing during calibration. i.e., the instrument should be used under
those set of conditions at which -.the instrument is calibrated. This type of error may occur
systematically or accidentally.
3. Measuring arrangement:
The process of measurement itself acts as a source of error if the arrangement of different
components of a measuring instrument is not proper.
Example:
While measuring length, the comparator law of Abbe should be followed. According to this, actual value
of length is obtained when measuring instrument and scale axes are collinear, and any misalignment of
these will give error value. Hence this type of error can be eliminated by having proper arrangement of
measuring instrument.
4. Work piece:
The physical nature of object (work piece) i.e., roughness, softness and hardness of the object acts as
a source of error. Many optomechanical and mechanical type of instruments contact the. Object
under certain fixed pressure conditions. Since the response of soft and hard objects under these fixed
conditions is different the output of measurement will be in error.
5. Environmental condition:
Changes in the environmental conditions is also a major source of error. The environmental conditions
such as temperature, humidity, pressure, magnetic or electrostatic field surrounding the instrument
may affect the instrumental characteristics. Due to this the result produced by the measurement may
contain error.
There errors are undesirable and can be reduced by the following ways,
(b) Employing hermetically sealing to certain components in the instrument, which eliminate the effects
of the humidity, dust, etc.
6. Observes skill:
It is a well-known fact that the output of measurement of a physical quantity is different from operator
to operator and sometimes even for the same operator the result may vary with sentimental and
physical states. One of the examples of error produced by the operator is parallax error in reading a
meter scale. To minimize parallax errors modern electrical instruments have digital display of output.
No measurement can be made with perfect accuracy but it is important to find out what accuracy is
and how different errors have entered into the measurement. A steady of errors is a first step in finding
ways to reduce them. Errors may arise from different sources and are usually classified as under.
1. Gross errors
2. Systematic (or) instrumental errors
3. Random (or) environmental errors
1. gross errors:
This cause of errors mainly covers human mistakes in reading instruments and recording and
calculating measurement result. The responsibility of the mistake normally lies with the experimental.
0 0
Ex: The temperature is 31.5 c, but it will write as 21.5 c its an error how ever they can be avoided
by adopting two means
2. systematic errors:
a. Instrumental errors
b. Environmental errors
c. Observational errors
a. Instrumentation errors:
b. Environmental errors:
These errors are caused due to changes in the environmental conditions in the area surrounding the
instrument, that may affect the instrument characteristics, such as the affects of changes in
temperature, humidity, barometric pressure or if magnetic field or electrostatic field.
(ii) Employing hermetically sealing to certain components in the instrument, which eliminate the effects
of the humidity dust, etc.
c. Observational errors:
These errors are produced by the experiment. Enter. The most frequent error is the parallax
error introduced in reading a meter scale.
These errors are caused by the habits of individual observers To minimize parallax errors
modern electrical instruments have digital display of output.
The causes of such errors is unknown (or) not determinable in the ordinary process making
measurements. Such errors are normally small and follow the law of chance. Random errors they
may be treated mathematically according to the law of probability.
These errors occur due to inconsistency in estimating successive readings from the instrument by an
experimenter. To reduce these errors it is necessary to exercise extreme care with mature and
considered judgement in recording the observations.
Precision errors in the instrument may arise from the outside disturbances to the measuring system.
These disturbances may be variations or mechanical vibrations. Poorly controlled processes also lead to
random errors.
These errors are caused due to some uncontrolled, disturbances which influence the instrument output.
Line voltage fluctuations, vibrations of the instrument supports, etc., are common examples of this type.
Measurement of
displacement:-
Introduction:
The direct measurements of displacement, force, torque and speed are very important in industrial
processes. Also. Many other quantities such as pressure, temperature, level, flow, etc. are often
measured by transducers them to displacement. Motion, or force, and then measuring these
parameters which give the required value of a particular quantity. In this chapter some of the methods
for measuring displacement, force, torque and speed have been discussed.
Measurement of displacement:
Generally, displacement is thought of in terms of motion of a few millimeters (mm) or less. The
measurement of displacement is made frequently to relate to some other measurement and hence
displacement transducers are fundamental components of any instrumentation system Displacement is
closely associated with motion (from one point to another) and position (i.e. a change from one position
to the next). Displacement can be measured by both mechanical and electrical methods, but only
electrical methods which are common in industrial use will be described here.
Definition of a Transducer:
Strain gauge is a positive-type resistance transducer which converts a mechanical displacement into a
change of resistance. It is the most commonly used transducer for the measurement of displacement.
The resistance gauge is essentially a fine wire which changes its resistance, when mechanically strained.
Due to physical effects. Its length and cross-sectional area vary and a change of electrical resistivity
also occurs.
i. detects or senses the present and changes in physical quantity being measured.
The strain Range is mounted to the measured surface so that it elongates or contracts with that surface.
This deformation of the sensing materials causes it to undergo a change in resistance.
Classification of transducers:-
Active transducers are self-generating type. They do not required electric energy. They work on the
principle of conservation of energy. The energy required for production of an output signal is
obtained from the input or physical phenomenon being measured.
Passive transducers are externally powered type. Passive transducers are based on principle of energy
controlling and they required a secondary electrical source for operation.
Examples: LVDT (Linear variable differential transformer), Thermistors, resistance thermometers, strain
gauge devices.
b) Analog Transducer
c) Digital Transducer
1. Analog Transducer:
These transducers convert the input physical phenomenon into an analog output (analog form) which is
continuous function of time.
These transducers convert the input physical phenomenon into an electrical output (digital form) which
may be in the form of pulses.
LVDT
Reluctance pickup
Pressure gauge
Di electric gauge
Thermo couple
Photo conductive
Photo voltaic
Photo emissive
Limitations:-
f) Instrument electrical properties may change the actual reading of the variable which is to be
measured.
A typical mode of operation of a piezo electric device for measuring varying force applied to a simple
plate is shown in Fig. Metal electrodes are attached to the selected faces of a crystal in order to detect
the electrical charge developed The magnitude and Polarity of the induced charge on the crystal surface
is proportional to the magnitude and direction of the applied force and is given by :
Q=KF
Where Q is the charge in coulomb, F is the impressed force in newtons and K is the crystal sensitivity in
C/N; it is constant for particular crystals and the manner in which they are cut. The relationship between
the force F and the change t in the crystal thickness t is given by the stress-strain relationship.
There are two main groups of piezo-electric crystals: (i) natural crystals such as quartz and tourmaline,
b) synthetic crystals such as Rochelle salts, lithium sulphate (LS), ammonia hydrogen phosphate (ADP),
ethylene diamine tartrate (EDT), potassium tartrate (DKT) etc. The advantages vary from crystal to
crystal and one is chosen on the basis of a particular application. Tourmaline `is the least active
chemically while tartaric acid is most active electrically.
iv. Natural crystals have a very low electrical leakage when used with very high input impedance
amplifiers and permit the measurement of a slowly varying parameter. They are, therefore, capable
of withstanding higher temperatures; operating at low frequencies and sustaining shocks.
v. Synthetic crystals exhibit a much high output for an applied stress and are about thousand times more
sensitive than natural crystals. However, they are usually unable to withstand high mechanical strain
without fracture. Further, the synthetic crystals have an accelerated rate of deterioration over the
natural ones.
3 High output,
4 Rugged construction
6 Small size. The small size of the transducer is especially useful for accelerometers where
added mass will mechanically load a system.
Applications: Piezo-electric transducers are most often used for accelerometers, pressure cells and
force cells in that order.
Resistance Transducers:-
In terms of physical quantities, the equation for electrical resistance of a metal conductor is
=
Variable inductance transducers:-
(d) Synchros
(e) Resolvers
1. LVDT (Linear variable differential Transducer):
The linear variable-differential transformer (LVDT) is the most widely used inductive transducer to
translate linear motion into electrical signal.
Construction: A differential transformer consists of a primary winding and two secondary windings.
The windings are arranged concentrically and next to each other. They are wound over a hollow bobbin
which is usually of a non-magnetic and insulating material, as shown in Fig.
Working: Any physical displacement of the core causes the voltage of one secondary winding to increase
while simultaneously, reducing the voltage in the other secondary winding. The difference of the two
voltages appears across the output terminals of the transducer and gives a measure of the physical
position of the core and hence the displacement.
When the core is in the neutral or zero position, voltages induced in the secondary windings are equal
and opposite and the net output is negligible. As the core is moved in one direction from the null
position, the differential voltage, i.e. the difference of the secondary voltages, will increase while
maintaining an in-phase relationship with the voltage from the input source. In the other direction
from the null position, the differential voltage will again increase, but will be 180' out of phase with the
voltage from the input source. By comparing the magnitude and phase of the output (differential)
voltage with the input source. The amount and direction of movement of the core and hence of
displacement may be determined. Variation of output voltage with core position is shown in Fig.
4. The output voltage of these transducer is practically linear for displacements upto 5 mm.
7. These transducers can usually tolerate a high degree of shock and vibration without any adverse
effects.
8. They are simple, light in weight, and easy to align and maintain.
Following are the disadvantages of LVDT:
A RVDT is used to convert rectangular displacement into electrical signal. The construction and
working of RVDT is same as that of LVDT except that is employs a cam shaped core. This core rotates
between the primary and two secondary windings with the help of shaft.
3. Synchros:
The devices by which the angular position of shaft is converted into electrical signal are known as synchros. The synchros are electromagnetic
transducers. The construction of synchro is same as a three phase alternator. It has a stator and a rotor. The stator consists of 3 identical
stationary windings which are separated by 120° in space. These stationary windings are connected in star (Y) configuration.
The rotor is dumb-bell shaped rotor to which an AC excitation voltage is applied through slip rings. The
rotor acts as primary winding of single phase transformer where as the stationary windings act as
secondary winding of single phase & transformer. There are two basic parts m a synchro system
namely synchro transmitter and synchro receiver.
4. Resolvers:
It is an electromagnetic device which consists of two stator windings and two rotor windings. Resolving
is nothing but converting from one co-ordinate system to another coordinate system. The resolvers
converts the shafts angular position into Cartesian coordinates i.e., the angular rotor position is
converted into those signals which are proportional to the sine and cosine of the rotor position and
this is carried out with respect to the position of the stators.
Photo-electric Transducers:-
These transducers operate on the principle that when light strikes special combination of materials, a
voltage may be generated, a resistance change may take place, or electrons may flow. Photoelectric
cells are used for a wide variety of purposes in control engineering for precision measuring devices, in
exposure meters used in photography. They are also used in solar batteries as sources of electrical
power for rockets and satellites used in space research.
Based on the principle of rotation photo electric transducers are classified into the 3 types. They are,
3. Photo-emissive cell: These transducers operate on the photo-emissive effect, i.e., when certain types
of materials are exposed to light, electrons readmitted and a current flow is produced. Light sensitive
photo-cathode may consist of a very thin film of cesium deposited by isotonic onto an oxidised silver
base. Light strikes the cathode, causing the emission electrons which are attracted towards the anode.
This phenomenon produces flow of it current in the external circuit; the current being a function of
radiant energy striking the cathode.
Light information ------------------ current information
b Photo-conductive cell: These are the variable resistance transducers. They on the principle of photo
conductive effect, i.e., some special type of semiconductor oils change their resistance when exposed
to light.
Light information ------------------ resistance information
Figure shows schematically the construction and electrical circuit of a photoconductive cell. The
sensitive material usually employed is cadmium selenide, germanium etc in the form of thin coating
between the two electrodes on a glass. Further, the cells are used in the circuit as a variable resistance
and are put in .series an ammeter and a voltage source. When the light strikes the semiconductor
material, is a decrease in the cell resistance thereby producing an increase in the current indicated the
ammeter.
d. Photo-voltaic cell: These transducers operate on the photo-valtaic effect, i.e., when light's trikes a
junction of certain dissimilar metals, a potential difference is built up.
Light information ------------------ emf information
The cell consists of a metal base plate, a non-metal semiconductor and a thin transparent metallic layer.
Typical examples of the layers are the copper oxide on copper and iron oxide on iron combination. The
transparent layer may be in the form of a sprayed conducting lacquer. Light strikes the coating and
generates an electric potential. The output is, however, low and is non-linear function of the light
intensity. In contrasted photo-tube and photo-conductive cells, the photo-voltaic unit is self-gene, rated
and requires no voltage source to operate it.
Capacitive Transducers:-
UNIT-II
Measurement of Temperature
Temperature is probably, most widely measured and frequently controlled variable encountered in
industrial processing of all kinds measurement of temperature is involved in thermo dynamics, heat
transfer and many chemical operations. Basically all the properties of matter such as size, colour,
electrical and magnetic characteristics and the physical states (solid, liquid, gas) change with changing
temperature.
Definition:
Temperature may be defined as the degree of hotness and coldness of a body are an environmental
measured on a definite scale.
The temperature of a substance is a measure of the hotness, or coldness, of that substance. It is the
thermal site of a body or a substance which determines whether it will give heat to, or receive heat
from, other bodies. If two bodies are placed in contact then heat tends to flow from a body at a
higher temperature to a body at a lower temperature, just as water flows from higher to lower levels.
The terms, heat and temperature, are closely related Temperature may be defined as "degree of heat"
but heat is usually taken to mean "quantity of heat” Temperature and heat flow are related
quantitatively by the second law of thermodynamics, which states that heat flows. Of its own accord,
from a body at a higher temperature to a body at a lower temperature. It is therefore important to
remember that in temperature measurement, two bodies in intimate contact are at the same
temperature only if there is no heat flow between them.
Temperature scales:
Temperature scales are based upon some recognized fixed points. At least two fixed points are
required which are constant in temperature and can be easily reproduced as:
On both these scales the freezing point and boiling point of water are used as fixed point. The freezing
0 0 0
point. The centigrade scale abbreviated as c, assigns 0 c to the ice point and 100 c to the steam point
and the intervals between these points is divided into 100 equal points. The corresponding values of the
0 0 0
Fahrenheit scale deviated F are 32 F and 212 F with the interval divided into 180 equal parts.
The efficiency of an ideal engine operating up on the control cycle between any two temperatures
is given by
4. International temperature scale:-
This scale has been established and adopted provide an experimental basis for the calibration of specific
thermometers to indicate temperatures as close as possible to the Kelvin thermodynamic scale. The
International temperature scale covers the range from the boiling point of oxygen to the highest
temperatures of incandescent bodies and names. The main features of this scale, adopted in 1948 at the
Ninth General Conference on Weights and Measures are:
4. Temperatures are to be designated as of and denoted by the symbol t. The name Celsius was
officially adopted to replace the name Centigrade.
5. The scale is based upon a number of fixed and reproducible equilibrium temperatures to which
numerical values are assigned.
Fundamental fixed points and their numerical values (at standard atmospheric pressure of 1013250
dynes/ )
Classification:-
The instruments for measuring temperature have been classified in the first place according to the
nature of change produced in the testing body by the change of temperature. The following four
broad categories have been proposed.
Bimetaliic thermometer
Expansion of liquids
Thermistors.
Ranges:-
1.Glass thermometers
(a) mercury filled -39 to 400 0.3 to 1.0
(b) + 2 -39 TO 540 0.3 TO5.5
(C) Alcohol filled -70 to 65 0.5 to 1.0
2.Pressure gauge thermometer.
(a) vapour pressure type 11 to 200 1 to 5.5
(b) liquid (or) gas type filled -150 to 600 1 to 5.5
3.Bimetallic thermometer -74 to 540 0.3 to 14.0
4.Resistance thermometer -240 to 980 0.003 to 3.0
5.Thermo couples
(a) base metals -185 to 1150 0.3 to 11.0
(b) Percious metals -185 to 1150 0.3 to 11.0
6.Thermistors -100 to 260 Depends up on ageing
7.pyrometers
(a) optical 760 and above 11 for black body
(b) radiation 540 and above 11-16 for black body
8.fusion 590 to 3600 As low as 20-30 under optimum
conditions.
Construction:-
A bimetallic strip consists of two pieces of different materials firmly bonded together by bending. For a
bi-metal in the form of a straight cantilever beam temp changes cause the free end to deflect because of
the different expansion rates of the components. This deflection can be correlated quantitatively to the
temp change.
Normally the two expansion material is invar and the high expansion material is brass. The
respective coefficient of expansion for invar and brass.
When bimetallic strip in the form of cantilever is assumed to bend to a circular are than
Bimetallic elements can be arranged in the flat spiral the single helix and the multiple
helix configuration.
Characteristics:-
6) Low cost.
Applications:-
The liquid in gas thermometers is one of the most common types of temp measuring devices. The
unit consists of glass envelope, responsive liquid and indicating scale.
Liquid range℃
Salient features/characteristics:-
Portable
7) Complete immersion
8) Total immersion
9) Partial immersion
Correction factor = 0.00018N(T1-T2)
1. The glass is very fragile and hence care should be taken in handling these thermometers.
The position of the thermometer for accurate temp measurement is not always the best
position for reading the scale of the thermometer
Both of these disadvantages are overcome in mercury in steel thermometer. The principle of operation
is again the differential expansion of liquid which is used.
i. a pressure or volume sensitive device such as Bourdon tube, bellows or diaphragms, and
ii. a device for indicating or recording a signal related to the measured temperature.
v.Quite rugged construction, minimum possibility of, damage or failure in shipment, installation and use
vii. Remote indication upto about 100 m possible with capillary lines.
Gas Thermometer:-
This system is defined as "a thermal system with a gas and operating on the principle of pressure change
with temperature change". The expansion, of a gas is governed by the ideal gas law:
PV = RT; P = (RT/V)
Gas: Nitrogen gas
Range: -130°to 540°
The volume of gas required in the bulb is determined by the gas expansion and by the temperature
range of the instrument.
−
V=R(2 1)
2− 2
Where subscripts 1, 2 refer to the conditions at the lowest and highest points of the scale.
Electrical Methods:-
In electrical methods of measuring temperature, the temperature signal is converted into electrical
signal either through a change in resistance or voltage development of emf.
7) Resistance Thermometers
8) Thermistors
9) Thermo couples
1. Resistance Thermometers:
The thermometer comprises a resistance element or bulb, suitable electrical leads and an indicating -
recording or resistance measuring instrument. The resistance element is, usually in the form of a coil of
very fine platinum, nickel or copper wound non -conductively. Onto an insulating ceramic former which
is protected externally by a metal sheath. A laboratory type of resistance thermometer is often wound
on a crossed mica former and enclosed in a pyrex tube. The tube may be evacuated or filled with an
inert gas to protect the metal wire. Care is to be taken to ensure that the resistance wire is free from m
mechanical stresses. A metal which has been strained will suffer a change in the resistance
characteristics; the metal is therefore usually annealed at a temperature higher than that at which it is
so operate.
4) Physically stable (i.e., relatively indifferent to its environment, resists corrosion and chemical
attack and is not readily oxidised) and has high electrical resistance characteristics.
5) Accuracy attainable with a platinum resistance thermometer is of the order of ± 0.01 of upto 500° and within ± 0. 1° of upto 1200 ° .
Advantages:-
2. Thermistors:
Thermistors is a contraction of term Thermal Resistor. They are essentially semi-conductors which
behave as resistors with a high negative temperature coefficient. As -the temperature increases, the
resistance goes down, and as the temperature decreases, the resistance goes up. This is just opposite to
the effect of temperature changes on metals.
Thermistors are composed of sintered mixture of metallic oxides such as manganese. Nickel, cobalt,
copper, iron and uranium. These metallic oxides are milled, mixed in appropriate proportions, are
pressed into the desired shape with appropriate binders and finally sintered the electrical terminals are
either embedded before sintering or baked afterwards. The electrical characteristics of thermistors are
controlled by varying the type of oxide used and physical size and configuration of the thermistor.
Thermistors may be shaped in the form of beads, disks, washers, rods and `these standard forms are
shown in Fig.
The mathematical expression for the relation- ship between the resistance of a thermistor and
absolute temperature of thermistor is
3. Thermo couples:
Experimentally it has been found that -the magnitude of the current is directly related to the two materials
M1 and M2, and the temperature difference (T1 – T2 ). In the practical application of the effect, a suitable
device is incorporated in the circuit to indicate any electromotive force or Bower current. For convenience
of measurement and standardization, one of the two junctions is usually maintained at some constant
known temperature. The output voltage of the circuit then indicates the temperature difference relative to
the reference temperature. Most tabulations set the reference value to the triple point of water (O° ).
iii) a potential difference always exists between two dissimilar metals in contact with each other
(Peltier effect)
iv) a potential gradient exists even in a single conductor having & temperature gradient (Thomson
effect)
In commercial instruments, the thermocouple materials are so chosen that the Peltier and Thomson
emfs act in such a manner that the combined value is maximum and that varies directly with
temperature.
Measurement of pressure:
Pressure definition:-
OR
OR
Units:-
1 torr = 1 mm of Hg.
1 bar = 1 dyne/ 2
Pa = N/ . 2
Terminology:-
Following terms are generally associated with pressure and its measurement.
Atmospheric pressure ( ):-
This is the pressure exerted by the envelope of air surrounding the earth surface. Atmospheric pressure
is usually determined by a mercury column barometer shown in fig. A long clean thick glass tube closed
at one end is filled with pure mercury. The tube diameter is such that capillary effects are minimum.
The open end is stoppered and the tube is inserted into a mercury container; the stoppered end kept
well beneath the mercury surface. When the stopper is removed, mercury runs out of the tube into the
container and eventually mercury level in the tube settles at height h above mercury level in the
container. Atmospheric pressure acts at the mercury surface in the container, and the mercury vapour
pressure exits at the top of mercury column in the tube. From hydrostatic equation,= ℎ……………………………..(i)
Mercury has a low vapour pressure (≈1.6 × 10−6bar at 20 °C) and thus for all intents and purposes it
can be neglected in comparison to which is about 1.0 bar at mean sea level. Then
= ℎ ……………………………..(ii)
Atmospheric pressure varies with altitude, because the air nearer the earth’s surface is compressed by
air above. At sea level, value of atmospheric pressure is close to 1.01325 bar or 760 mm of Hg column (=
10.33 m of water column).
Absolute pressure ( ):-
It is defined as the force per unit area due to the interaction of fluid particles amongst themselves. A
zero pressure intensity will occur when molecular momentum is zero. Such a situation can occur only
when there is a perfect vacuum, i.e., a vanishingly small population of gas molecules or of molecular
velocity. Pressure intensity measured from this state of vacuum or zero pressure is called absolute
pressure.
GAUGE PRESSURE ( ) AND VACUUM PRESSURE ( ):-
Instruments and gauges used to measure fluid pressure generally measures the difference between the
unknown pressure ‘P’ and the existing atmospheric pressure ‘ ’. When the unknown pressure is more
than the atmospheric pressure the pressure is recorded by the instrument is called gauge pressure ( ). A
pressure reading below the atmospheric pressure is known as vacuum pressure or negative
pressure. Actual absolute pressure is the sum of gauge pressure indication and the atmospheric
pressure.
= +
= -
Static pressure is defined as the force per unit area acting on a wall by a fluid at rest or flowing parallel
to the wall in a pipe line.
Static pressure of a moving fluid is measured with an instrument which is at rest relative to the fluid. The
instrument should theoretically move with same speed as that of the fluid particle itself. As it is not
possible to move a pressure transducer along in a flowing fluid; static pressure is measured by inserting
a tube into the pipe line at right angles to the flow path. Care is taken to ensure that the tube does not
protrude into the pipe line and cause errors due to impact and eddy formation. When the tube
protrudes into the stream, there would be local speeding up of the flow due to its deflection around the
tube; hence an erroneous reading of the static pressure would be observed.
A. Instruments for measuring low pressure (below 1 mm of Hg): - manometers and low pressure gauges.
B. Instruments for medium and low pressures (below 1 mm of Hg to 1000 atmospheres):- Bourdon tube
and diaphragm gauges.
C. Instruments for measuring low vacuum and ultra high vacuum (760 torr to 10−9 torr and beyond):-McLeod thermal conductivity and ionization gauges.
D. Instruments for measuring very high pressure (1000 atmospheres and above):- bourdon tube,
diaphragm and electrical resistance pressure gauges.
E. Instruments for measuring varying pressure:- engine Indicator and CRO ( cathode ray oscilloscope).
3. Gravitational transducer.
A dead weight tester.
Manometer.
4. Electrical transducers.
Bourdon tube pressure gauges.
Elastic diaphragm pressure.
Bellows gauges.
5. Strain gauge pressure cells.
Pinched tubes.
Cylindrical tube pressure cell.
6. McLeod gauge.
7. Thermal conductivity gauges.
Thermocouple gauge
Pirani gauge
8. Ionization gauge.
9. Electrical resistance pressure gauge.
6. Pressure can be measured by balancing a column of liquid against the pressure which has to be
measured. The height of the column which is balanced becomes a measure of the applied pressure
when calibrated.
Ex: - manometer.
vii. When the pressure is applied to the elastic elements the shape of the elastic element changes
which intern the pointer moves with respect to the scale. The pointer readings become a measure of
applied pressure.
Ex: - bourdon tube pressure gauge, diaphragm, bellows.
g) When electric current flows through a conducting wire it gets heated. Depending up on the
conductivity of the surrounding media the heat is dissipated from the wire. The rate of change in the
temperature of the wire becomes a measure of the pressure.
The dead weight tester is a primary standard for pressure measurement, and it offers a good calibration facility over a wide pressure range (700 N/ 2 to 70 MN/ 2 gauge in
steps as small as 0.01% of range with a calibration uncertainly of 0.01-0.05% of the reading).
A typical gauge is schematically shown in Fig. It consists of an accurately machined, bored and finished
piston which is inserted into a close fitting cylinder; both of known cross- section areas. A platform is
attached to the top of the piston and it serves to hold standard weights of known accuracy. The chamber
and the cylinder are filled with a clean oil; the oil being supplied from an oil reservoir provide with a check
valve at its bottom. The oil withdrawn from the reservoir when the pump plunger executes an outward
stroke and forced into the space below the piston during inward motion of the pump plunger. For calibrating
a gauge, an appropriate amount of weight is placed on the platform and the fluid pressure is applied until
enough upward force is developed to lift the piston-weight combination. When this occurs, the piston-
weight combination begins to float freely within the cylinder.
Under the equilibrium condition the pressure force is balanced against the gravity force on the mass ‘m’
of the calibrated masses, plus the piston and flat form and a frictional force. If ‘A’ is the equivalent area
of the piston cylinder combination then:
PA = mg + frictional drag.
The effective or equivalent area depends on such factors as piston cylinder clearance, pressure level,
temperature, and is normally taken as the mean of the cylinder and piston areas.
Manometers:-
Manometers measure pressure by balancing a column of liquid against the pressure to measured.
Height of column so balanced is noted and then converted to the desired units. Manometers may be
vertical, inclined, open, differential or compound. Choice of any type depends on its sensitivity of
measurement, ease of operation and the magnitude of pressure being measured. Manometers can
be used to measure gauge, differential, atmospheric, and absolute pressure.
i. Piezo meter
7. U- tube manometer
i. Piezo meter:
lt is a vertical transparent glass tube, the upper end of which is open to atmosphere and the lower end is
in communication with the gauge point ; a point in the fluid container at which pressure is to be
measured. Rise of fluid in the tube above a certain gauge point is a measure of the pressure at that
point.
Fluid pressure at gauge point A = atmospheric pressure pu at the free surface + pressure due to a liquid column of height ℎ1
1= + ℎ1
This simplest and useful pressure measuring consists of a transparent tube bent in the form of letter U and
filled with a particular liquid whose density is known. The choice of a particular manometric liquid
upon the pressure range and nature of the fluid whose pressure is sought. For high mercury (specific
gravity 13.6) is the manometric/balancing liquid. For low pressure liquids like carbon tetrachloride
(specific gravity 1.59) or acetylene tetrabromide (specific gravity 2.59) are employed. Quite often, some
colours are added to the balancing so as to get clear readings.
Pressure in the two legs at the same level 1 and 2 are equal; 1 = 2 and therefore, Gauge pressure in the container, = −( 1 ℎ1 = 2 ℎ2)
Single column manometer is modified form of manometer in which a reservoir having a large cross sectional
area as compared to the area of the tube, is connected to one of the limbs (say left limb) of the reservoir. The
other limb may be vertical or inclined. There are two types of single column manometers.
To start with, let both limbs of the manometer be exposed to atmospheric pressure. Then the liquid
level in the wider limb (also called reservoir well basin) and narrow limbs will correspond to position 0-
0.
ℎ1 = height of center of pipe above 0-0
ℎ2 = rise of heavy liquid in right limb
For the left limb, gauge pressure at point 1 is: 1= + 1 ℎ1 + 1 h
For the right limb, the gauge pressure at point 2 is: 2= 0 + 2 ℎ2 + 2 h
Points 1 and 2 are at the same horizontal plane: 1 = 2 and therefore
Gauge pressure in the container is: = ( 2 ℎ2 - 1 ℎ1 ) + h ( 2 - 1 )
This manometer is more sensitive. Due to inclination the distance moved by heavy liquid in the
right limb will be more.
= 2 (sin + / )
14) sensitivity can be altered easily by affecting a change in the quantity of manometric
liquid in the manometer
15) generally large and bulky, fragile and gets easily broken
17) measured medium has to be compatible with the manometric fluid used
19) surface tension of manometric fluid creates a capillary affect and possible hysteresis
20) meniscus height, has to be determined by accurate means to ensure improved accuracy.
Mechanical Gauges: - Elastic Pressure Transducer:-
For measuring pressures in excess of two atmosphere elastic mechanical type transducers are used. The
actions of these gauges are based on the deflection of the hollow tube, diaphragm and bellows caused
by the applied pressure difference. The resulting deflection made directly accurate a pointer. Scale read
out through suitable linkages and gears are the motion may be transmitted through and electrical
signal. Bellows and diaphragm gauges are generally suitable up to 28 to 56 bars. Where as bourdon
tubes are very high pressure gauges.
Bellow gauges:
The bellows is a longitudinally expansible and collapsible member consisting of several convolutions
or folds. The general acceptable methods of fabrication are:
turning from a solid stock of metal, (ii) soldering or welding stamped annular rings, (iii) rolling
a tubing, and (iv) hydraulically forming a drawn tube. Material selection is generally based on
considerations like strength or the pressure range, hysteresis and fatigue.
In the differential pressure arrangement (Fig) two bellows are connected to the ends of an equal arm
lever. If equal pressures are applied to the two bellows, they would extend by the same amount. The
connecting lever would then rotate but no movement would result in the movement sector. Under a
differential pressure, the deflections of the bellow would be unequal and the differential displacement
of the connecting levers would be indicated by the movement of the pointer on a scale.
Advantages:
f) Simple in construction.
g) Good for low to moderate pressures.
h) Available for gauge, differential and absolute pressure measurements.
i) Moderate cost.
Limitations:
BOURDON GAUGE:-
The pressure responsive element of a bourdon gauge consists essentially of metal tube (called bourdon
tube or spring), oval in cross section and bent to from a circular segment of, approximately 200 to 300
degrees. The tube is fixed but open at one end and it is through this fixed end that the pressure to be
measured is applied. The other end is closed but free to allow displacement under deforming action of the
pressure difference across the tube walls. When a pressure (greater than atmosphere) is applied to the
inside of the tube, its cross-section tends to become circular. This makes the tube straighten itself out with
a consequent increase in its radius of curvature, i. e., the free end would collapse and curve.
Type travel:
The motion of the free end commonly called tip travel is a function of tube length wall thickness, cross sectional geometry and modulus of
the tube material. For a bourdon tube a deflection ∆a of the elemental tip can be expressed as
∆a = 0.05 ( ) ( ) ( )
Where ‘a’ is the total angle subtended by the tube before pressurization, P is the applied
pressure difference and ‘E’ is the modulus of elasticity of the tube material.
Errors and their rectification: in general 3 types of error are found in bourdon gauges:
Zero error or constant error which remains constant over the entire pressure range.
Multiplication error where in the gauge may tend to give progressively a higher or low reading.
Angularity error: quite often it is seen that a one– to–one correspondence does not occur.
The C-type bourdon tube has a small tip travel and this necessitates amplification by a lever,
quadrant, pinion and pointer arrangement. Increased sensitivity can be obtained by using a very long
length of tubing in the form of a helix, and a flat spiral as indicated in Fig.
Materials:
Advantages:
Limitations:
(vi) So response.
(vii) Susceptibility to sharp and vibration.
(viii) Mutually required geared movement for application.
DIAPHRAGM GAUGES:-
In its elementary form, a diaphragm is a thin plate of circular shape clamped firmly around its edges.
The diaphragm gets deflected in accordance with the pressure differential across the side; deflection
being towards the low pressure side. The pressure to be measured is applied to diaphragm causing it to
deflect the deflection being proportional to applied pressure. The movement of diaphragm depends on
its thickness and diameter. The pressure deflection relation for a flat diaphragm with adjustable
clamped is given by
Where, P=pressure difference across the diaphragm, E=modulus of elasticity, t= diaphragm thickness
D) Non-metallic or slack diaphragm which employs a soft, flexible material with no elastic characteristic.
Diaphragm types: The diaphragms can be in the form of flat, corrugated or dished plates; the choice
depending on the strength and amount of deflection desired. Most common types of diaphragms are
shown in Fig.
Diaphragm material, pressure ranges and applications: Metallic diaphragms are generally fabricated
form a full hard, cold-rolled nickel, chromium or iron alloy which can have an elastic limit up to 560
MN/ml. Typical pressure ranges are 0 - 50 mm water gauge, 0-2800 kN/ 2 pressure and 0 - 50 mm
water gauge vacuum.
Typical applications are low pressure absolute pressure gauges, draft gauges, liquid level gauges and
many types of recorders and controllers operating in the low range of direct or differential pressures.
Non-metallic slack diaphragms are made a variety of materials such as gold beaters, skill , animal
membranes, impregnated silk clothes and synthetic materials like Teflon, neoprene, polythene …Etc.
Advantages:
Limitations:-
Low vacuum =760 torr to 25 torr, Medium vacuum =25 torr to 10^-3 torr,
High vacuum =10 −3 torr to 10 −6 torr, Very high vacuum =10 −6 torr to 10 −9torr, Ultra high vacuum =10 −9 torr and beyond.
Low pressure gauges are grouped into two types. They are
5. Direct measurement: wherein displacement deflection caused by the pressure is measured and is
correlated to the applied pressure. This principle is incorporated in bellows, diaphragm, bourdon tube,
manometer.
6. Indirect type measurements: wherein the low pressure is detected through measurement of a
pressure controlled property such as volume, thermal conductivity etc. the inferential gauges include
Thermal conductivity gauges, Ionization gauge, McLeod gauge.
These gauges measure pressure through a change in the thermal conductivity of the gas. Their operation
is based on the thermodynamic principle that “at low pressures there is a relationship between the
pressure and thermal conductivity i.e., the heat conductivity decreases with decrease in pressure”.
There are two types of thermal gauges.
d) Thermocouple gauge.
e) Pirani gauge.
1. Thermocouple gauge:
The schematic diagram of a thermocouple type conductivity gauge is shown in figure (1). The pressure
to be measured admitted to a chamber. A constant current is passed through the thin metal strip in
the chamber.
Due to this current, the metal strip gets heated and acts as hot surface. The temperature of this hot
surface is sensed by a thermocouple which is attached to the metal strip. The glass tube acts as the cold
surface. Whose temperature is nearly equal room temperature. The conductivity of the metal strip
changes due to the applied pressure. This change in conductivity causes a change in the temperature,
which is sensed by the thermocouple. The thermocouple produces current corresponding to the
thermocouple output which is then indicated by a mm. This indicated current becomes a measure of the
applied pressure when calibrated.
2. Pirani gauge:
It consists of two identical tubes, platinum/tungsten Wire and a compensating element. A constant
current is passed through the platinum wire which is mounted along the axis of the glass tube. The wire
gets heated due to this current and its resistance is measured using a resistance bridge. The gas whose
pressure to be measured is admitted to the glass tube. The conductivity of the Wire changes due to this
applied pressure. This change in conductivity causes a change in temperature of the wire which in turn
causes, a change in the resistance of the wire. This change in resistance is measured using the
resistance bridge. The other tube present in the gauge is evaluated to a very low pressure and it acts as
a compensating element to minimize the variations caused by ambient temperature changes.
IONIZATION GAUGE:-
The hot filament ionization gauge consists of a heated filament (cathode) to furnish electrons, a grid,
and an anode plate. These elements are housed in an envelop which communicates with the vacuum
system under test. The grid is maintained at a positive potential of 100-350 V while the anode plate is
maintained at negative potential of about 3-50 V with respect to cathode. The cathode is thus a
positive ion collector and the anode plate is an electron collector.
The rate of ion production is proportional to the number of electrons available to ionize the gas and
the amount of gas present. Thus the ratio of + ve ions, i. e., the anode current 1 to -ve ions and
electrons, ie., grid current 2 is a measure of the gas pressure P. The following approximate relation
holds:
=11
2
Where the proportionality constant S is called the sensitivity of the gauge. Sensitivity is a function of the
tube geometry, nature of the gas, and the operating voltages. Its value is determined by calibration of
the particular gauge.
Advantages:-
l) Wide pressure range 10−3 torr to 10−11 torr.
m) Constant sensitivity.
n) Possibility of process control and remote indication.
o) Fast response to pressure changes.
p) High cost and complex electrical circuit.
q) Calibration varies with gases.
r) Filament burns out if exposed to air by hot.
s) Decomposition of some gases by the hot filament.
t) Contamination of gas due to heat.
MCLEOD GAUGE:-
The unit comprises the system of glass tubes in which a known volume of gas at unknown pressure is
trapped and then isothermally compressed by a rising mercury column. Its operation involves the
following steps:
(x)Plunger is withdrawn and the mercury level is lowered to the cut off position, there by admitting gas
at unknown pressure ‘ 0’ in to the system. let ‘ 0′ be the volume of the gas admitted into the measuring
capillary, the bulb and into the tube down to the cutoff points.
(i) The plunger is push in and the mercury level goes up. The plunger motion is continued until
the mercury level in the reference capillary reaches the zero mark. Let height ‘h’ is the measure of
the compressed gas volume sealed into the measuring capillary. This height also represents rise in
gas pressure in terms of height of mercury column.
If ‘a’ denotes the area of the measuring capillary then the final volume ‘ ′=a.h and the final monomeric
pressure = 0+h. the unknown pressure is then calculated using boil’s law as follows:
This an one type of manometer. This is used for calibration of pirani and thermocouple gauges.
UNIT -III
Measurement of Liquid and Flow
Measurement of Liquid Level:-
Liquid level refers to the position or height of a liquid surface above a datum line.
Level measurements are made to a certain quantity of the liquid held with in a container.
Level offers both the pressure and rate of flow in and out of the container and as such its measurement
and control is an important function in a variety of processes. The task of liquid level measurement
may be accomplished by direct methods and indirect methods.
This is the simplest method of measuring liquid level. In this method, the level of liquid is measured
directly by means of the following level indicators:
8. Sight Glass
9. Float-type
When the level of liquid in an open tank is measured directly on a scale (the scale may be in the liquid
or outside it), it is sometimes difficult to read the level accurately because of parallax error. In this case
a hook type of level indicator is used.
Construction:
Hook-type level indicator consists of a wire of corrosion resisting alloy (such as stainless steel) about ¼ in (0.063 mm) diameter.
Bent into U-Shane with one arm longer than the other as shown in Fig. The shorter arm is pointed with a °60 tater. While the
longer one is attached to a slider having a Vernier scale. Which moves over the main scale and indicates the level.
Working:
In hook-type level indicator, the hook is pushed below the surface of liquid whose level is to be
measured and gradually raised until the point is just about to break through the surface. It is then
clamped, and the level is read on the scale. This principle is further utilized in the measuring point
manometer in which the measuring point consists of a steel point fixed with the point upwards
underneath the water surface.
A sight glass (also called a gauge glass) is another method of liquid level measurement. It is used for the
continuous indication of liquid level within, tank or vessel.
A sight glass instrument consists of a graduated tube of toughened glass which is connected to the
interior of the tank at the bottom in which the water level is required. Figure shows a simple sight glass
for an open tank in which the liquid level in the sight glass matches the level of liquid in the tank, As the
Ievel of liquid in the tank rises and falls, the level in the sight glass also rises and falls accordingly. Thus,
by measuring the level in the sight glass, the level of liquid in the tank is measured. In sight glass, it is
not necessary to use the same liquid as in the tank. Any other desired liquid also can be used.
(iii) Float-type:
FIoat-Type Level Indicator moat operated level indicator is used to measure liquid levels in a tank in
which a float rests on the surface of liquid and follows the changing level of liquid. The movement of the
float is transmitted to a pointer through a suitable mechanism which indicates the level on a calibrated
scale. Various types of floats are used such as hollow mewl spheres, cylindrical-shaped floats and disc-
shaped floats.
Figure shows the simplest form of float operated mechanism for the continuous liquid level
measurement. In this case, the movement of the float is transmitted to the pointer by stainless steel or
phosphor-bronze flexible cable wound around a pulley, and the pointer indicates liquid level in the
tank. The float is made of corrosion resisting material (such as stainless steel) and rests on liquid level
surface between two grids to avoid error due to turbulence, With this type of instrument, liquid level
from ½ ft. (152 mm) to 60, ft. (1.52 m) can be easily measured.
Indirect methods liquid level measurements converts the changes in liquid level into some other form
such as resistive, capacitive or inductive beyond force, hydrostatic pressure … Etc. and measures them.
Thus the change occurred in these parameters gives the measures of liquid level.
The principle of operation of capacitance level indicator is based upon the familiar capacitance
equation of a parallel plate capacitor given by:
=
K = Dielectric constant
A = area of plate, in 2
D= Distance between two plates. in m
Therefore, it is seen from the above elation that if A and D are constant, then the capacitance of
a capacitor is directly proportional to the dielectric constant, and this principle is utilized in the
capacitance level indicator.
Figure shows a capacitance type Liquid level indicator. It consists of an insulated capacitance probe
(which is a metal electrode) firmly fixed near and parallel to the maul wall of the tank If liquid in the tank
is non-inductive, the capacitance probe and the tank wall form the plates of a parallel plate capacitor
and liquid in between them acts as the dielectric. If liquid is conductive, the capacitance probe and liquid
form the plates of the capacitor and the insulation of the probe acts as the dielectric. A capacitance
measuring device is connected with the probe and the tank wall, which is calibrated in terms of the level
of liquid in the tank.
Ultrasonic liquid level works on the principle of reflection of the sound wave from the surface of the
liquid. The schematic arrangement of liquid level measurement by ultrasonic liquid level gauge is
illustrated above.
The transmitter ‘T’ sends the ultrasonic wave towards the free surface of the liquid. The wave gets
reflected from the surface. The reflected waves received by the receiver ‘R’. The time taken by the
transmitted wave to travel to the surface of the liquid and then back to the receives gives the level of
the liquid. As the level of the liquid reaches the time taken to reach the surface of the liquid and then
back to receiver also changes. Thus the change in the level of the liquid are determined accurately.
Advantages:-
Disadvantages:-
Very expensive.
Very experienced and skilled operator is required for measurement.
These are used for measuring the toxic and corrosive liquids. It is used to measure the level of liquids
which contain corrosive and toxic materials.
It contains a float in which a magnet is arranged and is placed in the chamber, whose liquid level is to be
determined. The float moves up and down with the increase and decrease in the level of liquid respectively.
A magnetic shielding device and an indicator containing small wafers arranged in series and attached to the
sealed chamber. These wafers are coated with luminous paint and rotate 180*. As the level changes the float
moves (along with the magnet) up and down. Due to this movement of magnet, wafers rotate and present a
black coloured surface for the movement of float in opposite direction.
A gas which changes its state (gaseous state into liquid state). When cooled to very low temperatures is
known as cryogenic fluid. A cryogenic fluid exists in liquid state at very low temperatures, which are
usually less than the temperature levels at which a superconductor exhibits zero resistance
characteristic.
(v) Bubbler level indicator:
The Bubbler type level indicator is also known as purge type of liquid level meter.
In this technique of level measurement, the air pressure in the pneumatic pipeline is adjusted and
maintained slightly greater than the hydrostatic pressure at the lower end of the bubbler tube. The
bubbler tube is dipped in the tank such that its lower end is at zero level i.e., reference level, and the
other end is attached to a pressure regulator and a pressure gauge. Now the supply of air through the
bubbler tube is adjusted so that the air pressure is slightly higher than the pressure exerted by the
liquid column in the vessel or tank. This is accomplished by adjusting the air pressure regulator until a
slow discharge of air takes place i.e., bubbles are seen leaving the lower end of the bubbler tube. (In
some cases a small air flow meter is arranged to control an excessive air flow if any). When there is a
small flow of air and the fluid has uniform density, the pressure indicated by the pressure gauge is
directly
proportional to the height of the level in the tank provided the gauge is calibrated properly in unit of
liquid level.
FLOW MEASUREMENT:-
Introduction: Measurement of fluid velocity, flow rate and flow quantity with varying degree of
accuracy or a fundamental necessity in almost all the flow situations of engineering. Studying ocean or
air currents, monitoring gas input into a vacuum chamber, measuring blood movement in a vein. The
scientist or engineer is faced with choosing a method to measure flow. For experiment procedures, it
may be necessary to measure the rates of flow either into or out of the engines. “Pumps, compressors
and turbines”. In industrial organizations flow measurement is needed for providing the basis for
controlling processes and operations. That is for determining the proportions of materials entering or
leaving, a continuous manufacturing process. Flow measurements are also made for the purpose of cost
accounting in distribution of water and gas to domestic consumers, and in the gasoline pumping
stations.
8) Quantity meters.
9) Flow meters.
Quantity meters:-
In this class of instruments actual flow rate is measured. Flow rate measurement devices
frequently required accurate. Pressure and temperature measurements in order to calculate the
output of the instrument. The overall accuracy of the instrument depends upon the accuracy of
pressure and temperature measurements.
ROTAMETER:-
The rotameter is the most extensively used form of the variable area flow meter. It consists of a vertical
tapered tube with a float which is free to move up or down within the tube as shown in Fig. The tube is
made tapered so that there is a linear relationship between the flow rate and position in the float within
the tube. The free area between float and inside wall of the tube forms an annular orifice. The tube is
mounted vertically with the small end at the bottom. The fluid to be measured enters the tube from the
boom and passes upward around the float and exit at the top. When there is no flow through the
rotameter, the float rests at the bottom of the metering tube where the maximum diameter of the float
is approximately the same as the bore of the tube. When fluid enters the metering tube, the float
moves up, and the flow area of the annular orifice increases. The pressure differential across the
annular orifice is paranormal to the square of its flow area and to the square of the flow rate. The float
is pushed upward until the `limns force produced by the pressure differential across its upper and lower
surface is equal to the weight of the float If the flow rate rises, the pressure differential and hence the
lining force increases temporarily, and the float then rises, widening the annular orifice until the force
cawed by the pressure differential is again equal to the weight of the Boat.
Thus, the pressure differential remains constant and the area of the annular orifice (i.e., free area
between float and inside wall of the tube) to which the float moves. Changes in proportion to the flow
rate. Any decrease in flow rate causes the float to drop to a lower position. Every float position
corresponds to one particular flow rate for a quid of a given density and viscosity. A calibration scale
printed on the tube or near it. Provides a direct medication of flow rate. The tube materials of rotameter
may be of glass or metal.
Advantages:-
j) Simplicity of operation.
k) Ease of reading and installation.
l) Relatively low cost.
m) Handles wide variety of corrosive fluids.
n) Easily equipped with data transmission, indicating and recording devices.
Disadvantages:-
Principle: - the permanent magnet attached to the body of rotor is polarized at 90° to the axis of rotation.
When the rotor rotates due to the velocity of the fluid (V), the permanent magnet also rotates along with
the rotor. Therefore, a rotating magnetic field will be generated which is then cut by the pickup coil. Due to
this ac-voltage pulses are generated whose frequency is directly proportional to the flow rate.
Q=
By minimizing the bearing friction and other losses that device can be designed to give linear output.
Advantages:-
Disadvantages:-
Applications:-
Principle:- When a fluid flows over an electrically heated surface, heat transfer takes place from the
surface or wire to the fluid. Hence, the temperature of the heated wire decreases which causes
variations in the resistance. The change that occurred in the resistance of the wire is related to the
flow rate.
The sensor is a 5 micron diameter platinum tungsten wire welded between the two prongs of the probe
and heated electrically as a part of Wheat stone bridge circuit. When the probe is introduced into the
fluid flowing, it tends to be cooled by the instantaneous velocity and consequently there is a tendency
for the electrical resistance to change. The rate of cooling depends up on the dimensions and physical
properties of the wire. Difference of the temperature between the wire and fluid, physical properties of
the fluid, string velocity under measurement.
Depending on the associated electronic equipment, the hot wire may be operated in two modes:
Here the voltage across the bridge circuit is kept constant. Initially the circuit is adjusted such that the
galvanometer reads zero, when the heated wire lies in stationary. Air when the air flows the hot wire
cools, the resistance changes and the galvanometer deflects. The galvanometer deflections
are amplified measured in terms of air velocity or liquid velocity or gas velocity.
Here the resistance of the wire and its temperature is maintained constant in the event of the tendency
of the hot wire to cool by the flowing fluid, the external bridge voltage is applied to the wire to maintain
a constant temperature. The reading on the voltmeter is recorded and correlated with air velocity.
MAGNETIC FLOWMETER: -
Magnetic flow meter depends up on the faradays law of electromagnetic induction. These meters utilize
the principles of faradays law of electromagnetic induction for making a flow measurement. It states
that whenever a conductor moves through a magnet field of given field strength; a voltage is induced in
the conductor, which is proportional to the relative between the conductor and the magnetic field. In
case of magnetic flow meters electrically conductive flowing liquid works as the conductor the induced
voltage.
e= × 10−8
Where, e=induced voltage, B=magnetic flux density in gauss, L=length of the conductor in cm,
V=velocity of the conductor in m/sec.
The equation of continuity, to convert a velocity measurement to volumetric flow rate is given by
Q=AV
Where, Q=volumetric flow rate, A=cross sectional area of flow meter, V=fluid velocity.
Construction and Working:
Fig illustrates the basic operating principle of a magnetic flowmeter in which the flowing liquid acts as
the conductor. The length L of which is the distance between the electrodes and equals the pipe
diameter. As the liquid passes through the pipe section, it also passes through the magnetic field set up
by the magnet coils, thus inducing the voltage in the liquid which is detected by the pair of electrodes
mounted in the pipe wall. The amplitude of the induced voltage is proportional to the velocity of the
flowing liquid. The magnetic coils may energized either by AC or DC voltage, but the recent development
is the pulsed DC-type in which the magnetic coils are periodically energized.
Advantages:-
Disadvantages:-
7) Cost is more.
8) Heavy and larger in sizes.
9) Explosion proof when installed in hazardous electrical areas.
10) It must be full at all times.
Applications:-
7. Corrosive acids.
8. Cement slurries.
9. Paper bulb.
10. Detergents.
f) Bear … Etc.
The velocity of propagation of ultrasonic sound waves in a fluid is changed when the velocity of the flow
of fluid changes. The arrangement of flow rate measurement using ultrasonic transducer contains two
piezo-electric crystals placed in the fluid whose flow rate is to be measured of these two crystals one
acts as a transmitting transducer and the other acts as a receiving transducer. The transmitter and
receiver are separated by some distance say “L”. Generally the transmitting transducer is placed in the
upstream and it transmits ultrasonic pulses. These ultrasonic pulses are then received by the receiving
transducer placed at the downstream flow. Let the time taken by the ultrasonic pulsed to travel from
the transmitter and received at the receiver is “delta”. If the direction of propagation of the signal is
same as the direction of flow then the transit time can be given by:
∆1= −
Where L=distance between the transmitter and receiver, Vs =velocity of sound in the fluid, V=velocity
of flow in the pipe.
If the direction of the signal is opposite with the direction of the flow then the transit time is given by:
∆2= −
∆ =∆2−∆1
2
∆ = 2− 2
Compared to the velocity of the sound the velocity of the flowing fluid is very very less. So,
2
∆ = 2
Therefore the change in time is directly proportional to the velocity of fluid flow
∴∆ ∝
The optical flow visualization methods offer the advantage that they do not disturb the flow during the
measurement process. The LDA is a device that offers the non-disturbance advantages of optical
methods while affording a very precise quantitate measurement of flow velocity. This instrument is the
most recent development in the area of flow measurement, especially measurement of high frequency
turbulence fluctuation. The operating principle of this instrument involves the focusing of laser beams at
a point, where the velocity is to be measured and then sensing with a photo detector. The light
scattered by then particles carried along with the fluid as it passes though the laser focal point. The
velocity of the particles which is assumed to be equal to the fluid velocity causes a Doppler shift of the
frequency of the scattered light and produces a photo detector signal related to the velocity.
2 sin( )
f= 2
Speed is a rate variable defined as the time-rate of motion. Common forms and units of speed
measurement include: linear speed expressed in meters per second (m/s), and the angular speed of a
rotating machine usually expressed in radians per second (rad/s) or revolutions per minute (rpm).
Measurement of rotational speed has acquired prominence compared to the measurement of linear
speed.
Angular measurements are made with a device called tachometer. The dictionary definitions of a
tachometer are:
11. “an instrument used to measure angular velocity as of shaft, either by registering the number of
rotations during the period of contact, or by indicating directly the number of rotations per minutes”
12. “an instrument which either continuously indicates the value of rotary speed, or continuously
displays a reading of average speed over rapidly operated short intervals of time”
Mechanical tachometers:
These tachometers employ only mechanical parts and mechanical movements for the measurement
of speed.
The revolution counter, sometimes called a speed counter, consists of a worm gear which is also the
shaft attachment and is driven by the speed source. The worm drives the spur gear which in turn
actuates the pointer on a calibrated dial. The pointer indicates the number of revolutions turned by the
input shaft in a certain length of time. The unit requires a separate timer to measure the time interval.
The revolution counter, thus, gives an average rotational speed rather than an instantaneous
rotational speed. Such speed counters are limited to low speed engines which permit reading the
counter at definite time intervals. A properly designed and manufactured revolution counter would
give a satisfactory speed measure upto 2000-3000 rpm.
2. Tachoscope:
The difficulty of starting a counter and a watch at exactly the same time led to the development of
tachoscope, which consists of a revolution counter incorporating a built-in timing device. The two
components are integrally mounted, and start simultaneously when the contact point is pressed
against the rotating shaft. The instrument runs until the contact point is disengaged from the shaft. The
rotational speed is computed from the readings of the counter and timer. Tachoscopes have been used
to measure speeds upto 5000 rpm.
The indicator has an integral stop watch and counter with automatic disconnect. The spindle operates
when brought in contact with the shaft, but the counter does not function until the start and wind
button is pressed to start the watch and engage the automatic clutch. Depressing of the starting button
also serves to wind the starting watch. After a fixed time-interval (usually 3 or 6 seconds), the revolution
counter automatically gets disengaged. The instrument indicates the average speed over the short
interval, and the dial is designed to indicate the rotational speed directly in rpm. These speed measuring
units have an accuracy of about 1% of the full scale and have been used for speeds within the range
20,000 to 30,000 rpm.
The rotating shaft drives an indicating shaft through at slipping clutch. A pointer attached to the
indicator shaft moves over a calibrated scale against the torque of a spring. The pointer position gives a
measure of the shaft speed.
5. Centrifugal force tachometers:
The device operates on the principle that centrifugal force is proportional to the speed of rotation. Two
flyballs (small weights) are arranged about a central spindle. Centrifugal force developed by these
rotating balls works to compress the spring as a function of rotational speed. A grooved collar or sleeve
attached to the free end of the spring then slides on the spindle and its position can be calibrated in
terms of the shaft speed. Through a series of linkages, the motion of the sleeve is usually amplified and
communicated to the pointer of the instrument to indicate speed. Certain attachments can be mounted
onto the spindle to use these tachometers for the measurement of linear speed.
Tachometers of the vibrating reed type utilize the fact that speed and vibration in a body are
interrelated. The instrument consists of a set of vertical reeds, each having its own natural frequency
of vibration. The reeds are lined up in order of their natural frequency and are fastened to a base plate
at one end, with the other end free to vibrate. When the tachometer base plate is placed in mechanical
contact with the frame of a rotating machine, a reed tuned to resonance with the machine vibrations
responds most frequently. The indicated reed vibration frequency can be calibrated to indicate the
speed of the rotating machine.
Electrical tachometers:
An electrical tachometer depends for its indications upon an electrical' signal generated in proportion to
the rotational speed of the shaft. Depending on the type of the transducer, electrical tachometers have
been constructed in a variety of different designs.
In an eddy current or drag type tachometer, the test shaft rotates a permanent magnet and this induces
eddy currents in a drag cup or disc held close to the magnet. The eddy currents produce a torque which
rotates the cup against the torque of a spiral spring. The disc tums in the direction of the rotating
magnetic field until the torque developed equals that of the spring. A pointer attached to the cup
indicates the rotational speed on a calibrated scale. The automobile speedometers operate on this
principle and measure the angular speed of the wheels. The rotational measurement is subsequently
converted into linear measurement by assuming some average diameter of the wheel, and the scale is
directly calibrated in linear speed units.
Eddy current tachometers are used for measuring rotational speeds upto 12,000 rpm with an accuracy of ±3%.
The operation of this tachometer is based on alternately charging and discharging a capacitor. These
operations are controlled by the speed of the machine under test. The instrument essentially consists of:
h) Tachometer head containing a reversing switch, operated by a spindle which reverses twice with each
revolution.
10.Indicating unit containing a voltage source, a capacitor, milliammeter and a calibrating circuit. When
the switch is closed in one direction, the capacitor gets charged from d-c supply and the current starts
flowing through the ammeter. When the spindle operates the reversing switch to close it in opposite
direction, capacitor discharges through the ammeter with the current flow direction remaining the
same. The instrument is so designed that the indicator responds to the average current. Thus, the
indications are proportional to the rate of reversal of contacts, which in turn are proportional to speed
of the shaft. The meter scale is graduated to read in rpm rather than in milliamperes. The tachometer is
used within the range 200 - 10000 rpm.
10) Tachogenerators: These tachometers employ small magnet type d.c or a.c generators which
translate the rotational speeds into d.c. or a.c voltage signal. The operating principle of such
tachometers is illustrated in Fig. Relative perpendicular motion between a magnetic field and conductor
results in voltage generation in the conductor.
10) D. C. tachometergenerator: This is an accurately made dc. generator with a permanent magnet
of horse-shoe type. With rotation of the shaft, a pulsating dc. Voltage proportional to the shaft speed is
produced, and measured with the help of a moving coil voltmeter having uniform scale and calibrated
directly in terms of speed. The tachometer is sensitive to the direction of rotation and thus can be used
to indicate this direction by the use of an indicator with its zero point at mid-scale. For greater accuracy,
air gap of the magnetic paths must be maintained as uniform as possible. Further, the instrument
requires some form of commutation which presents the problem of brush maintenance.
11) A.C. tachometer generator: The unit embodies a stator surrounding a rotating permanent
magnet. The stator consists of a multiple pole piece (generally four), and the permanent magnet is
installed in the shaft whose speed is being measured. When the magnet rotates, an a.c. voltage is
induced in the stator coil. The output voltage is rectified and measured with a permanent magnet
moving coil instrument. The instrument can also be used to measure a difference in speed of two
sources by differentially connecting the stator coils.
Tachogenerators have been successfully employed for continuous measurement of speeds upto 500
rpm with an accuracy of ±1%.
4. Contactless electrical tachometers:
Tachometers of this type produce pulse from a rotating shaft without any physical contact between
the speed transducer and the shaft. This aspect has the distinct advantage in that no load is applied to
the machine.
Inductive pick-up tachometer: The unit consists of a small permanent magnet with a coil round it. This
magnetic pick up is placed near a metallic toothed rotor whose speed is to be measured. As the shaft
rotates, the teeth pass in front of the pick-up and produce a change in the reluctance of the magnetic
circuit. The field expands or collapses and a voltage is induced in the coil. The frequency of the pulses
depends upon the number of teeth on the wheel and its speed of rotation. Since the number of teeth is
known, the speed of rotation can be determined by measuring the pulse frequency. To accomplish this
task, pulse is amplified and squared, and fed into a counter of frequency measuring unit.
If the rotor has 60 teeth, and if the counter counts the pulses in one second, then me counter will
directly display the speed in revolutions per minute.
The device consists of a vane attached to one end of the rotating machine shaft. When the shaft
rotates between the fixed capacitive plates, there occurs a change in the capacitance. The capacitor
forms a part of an oscillator tank so that number of frequency changes per unit of time is a measure of
the shaft speed. The pulses thus produced are amplified, and squared, and may then be fed to
frequency measuring unit or to a digital counter so as to provide a digital analog of the shaft rotation.
23) Photo-electric tachometer: These pick-ups utilize a rotating shaft to intercept a beam of light falling
on a photo-electric or photo conductive cell. The shalt has an intermittent reflecting (white) and non-
reflecting (black) surface. When a bean) of light hits the reflecting surface on the rotating shaft, light
pulses are obtained and the reflected light is focused onto the photo-electric cell. The frequency of light
pulses is proportional to the shaft speed, and so will be the frequency of electrical output pulses from
the photo-electric cell.
(iv)Stroboscope:
The stroboscope utilises the phenomenon of vision when an object is viewed intermittently. The human
sense of vision is so slow to react to light stimuli that it is unable to separate two different light impulses
reaching the eye within a very short Period of time (less than 0.1second). A succession of impulses
following one another at brief intervals are observed by the eye as a continuous unbroken sequence. A
mechanical disk type stroboscope consists essentially of a whirling disk attached to motor whose speed
can be varied and measured. A reference mark on the rotating shaft on the shaft appears to be
stationary. For this condition, the shaft speed equals that of rotating disk, or some even multiple of this
speed and is given by:
Vibration amplitude and acceleration
Vibration refers to the repeated cyclic oscillations of a system; the oscillatory motions may be simple
harmonic (sinusoidal) or complex (non-sinusoidal). The oscillations are caused when acceleration is
applied to the machine alternately in two directions
The excessive vibration level in a machine is an indication of the following troubles it can cause:
p) Excessive wear because of failure to compensate for vibration to which a product is subjected or
which is created by the product
q) Faulty production
Measurement of acceleration:
There are two types of accelerometers generally used for measurement of acceleration:
(i)Piezo-electric accelerometer: The unit is perhaps the simplest and most commonly used transducer
employed for measuring acceleration. The sensor consists of a piezo-electric crystal sandwitched,
between two electrodes and has a mass placed on it. The unit is fastened to the base whose
acceleration characteristics are to be obtained. The can threaded to the base acts as a 'spring and
squeezes the mass against the crystal. Mass exerts a force on the crystal and a certain output voltage is
generated. If the base is now accelerated downward, inertial reaction force on the base acts upward
against the top of the can. This relieves stress on the crystal. From Newton's second law
force = mass × acceleration
Advantages and limitations
12. a = dL / L ≈ (L2 − L1 ) / L1 = ∆L / L
εa = axial strain
L1 = linear dimension or gage length
L2 = final strained linear dimension
D1 D2
L1 L2 – L1
L2
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
σ
13. = a
a
E = Young’s modulus
σa = uniaxial stress
−ε
= L
a
xii. = Poisson’s ratio
εL = lateral strain
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
σ −νσ
εx= x y ε = σ y −νσ x
y
E E
E(ε x +νε y ) E(ε y +νε x )
σx= σy=
1 −ν 2 1−ν
2
σy
εy οy
E
οx
−ν
E
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Strain Measurement
Extensometer
Optical
Mechanical
Electrical strain gage
Resistive – the most common
Capacitive
Inductive
Photoelectric
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Foil-Type Gage
During the 1950s the foil-type
gage replaced the the wire gage
The common form consists of a metal
foil element on a thin epoxy support
Manufactured using printed-circuit techniques
Major advantage – almost unlimited
pane configurations are possible
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
ρL ρL
R= = 2
A CD
The gage factor
F = dR / R = dR / R = 1 + 2ν + dρ / ρ
dL / L εa dL / L
i) = 1 ∆R
F R
The values of F and R are supplied by the gage
manufacturer, and the user determines ∆R corresponding to
the input situation being measured.
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Desirable Properties of
Grid Material
High gage factor, F
High sensitivity, ρ
Low temperature sensitivity
High electrical stability
High yield strength
High endurance limit
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Good workability
Good solderability or weldability
Low hysteresis
Low thermal emf when joined to
other materials
Good corrosion resistance
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Temperature Sensitivity
In many applications, compensation is
provided in the electrical circuitry – this
does not always eliminate the problem
Two factors are involved:
The differential expansion existing between the
grid support and the grid proper, resulting in a
strain that the gage is unable to distinguish
from load strain
The change in resistivity ρ with temperature
change
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
*Trade names
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Temperature Compensation
The adjacent-arm compensating gage –
bridge circuitry
Self-temperature compensation
Selected-melt gage
11. Through proper manipulation of alloy and processing,
grid materials may be prepared to show very low apparent
strain versus temperature change
Dual-element gage
11) Use two wire elements connected in series in one
gage assembly
12) The two elements have different temperature
characteristics and are selected so that the net temperature-
induced strain is minimized
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Strain-Measuring Systems
Basic strain indicator, useful for static:
single-channel readings
Single-channel system either external to
or an integral part of a cathode-ray
oscilloscope
Oscillographic systems incorporating either
12) stylus-and-paper or lightbeam
and phtographic paper readout
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Stress-Strain Relationships
Simple uniaxial stress situation
Biaxial stress situation
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Measurement of Force
Mechanical weighing systems
Balance, multiple-lever system, pendulum
force-measuring mechanism
Elastic transducers
Proving ring
Strain-gage load cells
Piezoelectric-type load cells
Hydraulic and pneumatic systems
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Proving Ring
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Measurement of Pressure
Absolute pressure
Gage pressure
Vacuum
14
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Pressure-Measuring Transducers
Gravitational types
Liquid columns
Pistons or loose diaphragm, and weights
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Elastic Diaphragms
Use elastic diaphragm as primary
pressure transducer
Flat type –
Used in conjunction with electrical secondary
transducers whose sensitivity permits quite
small diaphragm deflections
Corrugated type is particularly useful
when larger deflections are required
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Secondary Transducers
Used with Diaphragms
Resistance strain gages with flat diaphragms
Inductive types
Piezoelectric-type pressure cells
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Location of strain
gages on flat
diaphragm
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Inductive Types
Differential pressure
cell with inductance-
type secondary
transducer
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Measurement of Motion
Displacement
Velocity
Acceleration
Jerk
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Human Touch
In spite of the tremendous advances made in
vibration-measuring instrumentation, one of the
most sensitive vibration detectors is the human
touch
Fingertips – sinusoidal vibrations
having amplitudes as low as 12 µ in
Vibrating member tightly gripped – average
minimum detectable amplitude was only
slightly greater than 1 µ in
Greatest sensitivity occurred at a frequency
of about 300 Hz
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
www.jntuworld.com || www.jwjobs.net
www.jntuworld.com || www.android.jntuworld.com || www.jwjobs.net || www.android.jwjobs.net
Advantages of Piezoelectric-
Type Accelerometers
High sensitivity
Extreme compactness
Ruggedness
Introduction to Humidity or dampness:
The amount of water vapour contained in air or gas is called humidity. It plays a vital role in many
industrial processes such as chemical, textile, paper, food, leather, pharmaceutical Industries as Well as
precision equipment manufacturing.
13. Humidity should be measured and controlled to prevent the food products to become dry,
spoilage of dried milk, eggs and for successful storage of fruits, meat etc.
14. Humidity should be controlled in order to reduce the affects of surface leakage in
electrical installations.
15. It should be controlled to maintain proper environment conditions for human comforts.
16. Textile and paper industries require high humidity conditions. Any variations in humidity may
cause the nature, behavior, characteristics of paper pulp and synthetic fibers to change.
17. It should be maintained and controlled in the required levels for proper drying process.
If the humidity increases beyond the desired level (upper limit) the dry process may get
retarded.
If it decreases below the lower limit the surface of the material becomes over dry.
Hence, the humidity is a very important process variable that should be controlled within the
desired limits.
“Before going into the details of measuring of humidity it is important to known some terms related to
humidity measurement”.
Terminology:
14. Humidity: The amount of Water vapour contained in air or gas is called humidity.
15. Dry Air: When there is no Water vapour contained in the atmosphere, it is called dry air.
16. Moist Air: When their is water vapour contained in the atmosphere, then the air is called moist
air.
17. Saturated Air: Saturated air is the moist air where the partial pressure of water - vapour
equals the saturation pressure of steam corresponding to the temperature of air.
18. Humidity Ratio or Specific Humidity or Absolute Humidity or Moisture Content: It is defined
as the ratio of the mass of water vapour to the mass of dry air in a given volume of the mixture and is
denoted by w
Humidity ratio = mass of water vapour
xiii. Relative Humidity: It is defined as the ratio of the mass of water vapour in a certain volume of
moist
air at a given temperature to the mass of water vapour in the same volume of saturated air at the same temperature and is denoted by RH or ∅.
Relative humidity = (Water vapour required for saturation) (At a given temperature)
Here a comparison is made between the humidity of air and the humidity of saturated air at the same
temperature and pressure. It is to be noted that if relative humidity is 100 % it is saturated air, i.e., the
air contains all the moisture it can hold.
It should also be noted that the degree of saturation (percentage of relative humidity ) of air keeps on
changing with temperature.
j) Dew Point Temperature: By continuous cooling at constant pressure if the temperature of air is
reduced, the water - vapour in the air will start to condense at; particular temperature. The temperature
at which the water vapour starts condensing is called as dew point temperature.
k) Dry Bulb Temperature: When a thermometer bulb is directly exposed to an air -water vapour
mixture, the temperature indicated by the thermometer is the dry –bull temperature.
This dry- bulb temperate is not affected by the moisture present in the air i.e. the temperature of air is
measured in a normal way by the thermometer.
12. Wet Bulb Temperature: When a thermometer bulb is covered by a wet wick, and if the bulb
covered by the wet wick is exposed to air, water vapour mixture, the temperature indicated by the
thermometer is the wet bulb temperature. When air passed on the wet wick present on the bulb of the
thermometer, the moisture present in the wick starts evaporating and this creates a cooling effect at
the bulb. The bulb now measures the thermodynamic equilibrium temperature reached between then
cooling affected by the evaporation of water and heating by convection.
13. Wet - Bulb Depression: Wet - bulb depression = (Dry - bulb temperature) - (Wet bulb temperature )
Always dry - bulb temperature is higher than the wet bulb temperature.
14. Percentage Humidity: It is defined as ratio of weight of water vapour in a unit weight of air to weight of
water vapour in the same weight of air if the air were completely saturated at the same temperature.
Percentage humidity = (Weight of water vapour in a unit weight of air)
Weight of water vapour in the same weight of air if the air were completely saturated at the same temperature.
1. Sling psychrometer:-
Principle: This instrument is used to measure both the dry bulb and wet bulb temperatures at a time
with these temperatures we can measure the humidity content in air.
A frame holding two thermometers to measure dry & wet bulb temperatures as shown fig. Two mercury
in glass thermometers, one to measure dry - bulb temperatures and the other to measure Wet-bulb
temperature.
The frame carrying the thermometers is covered by a glass casing. A swivel handle is attached to the
frame - glass casing - thermometer arrangement to ensure that the air at the wet bulb is always in
immediate contact with the wet wick.
Operation: Accurate measurement of wet bulb temperature is obtained only if air moves with a velocity
around the wet wick.
In order to measure wet bulb temperature, the psychrometer frame 4 glass covering thermometer
arrangement is rotated at 5 m/ s to 10 m/ s to get the necessary air motion. The thermometer whose
bulb is bare (Without wick) contacts the air and indicates the dry bulb temperature. At the same time,
the thermometer whose bulb is covered with the wet wick comes in contact with the air and when this
air passes on the wet Wick, the moisture present in the wick starts evaporating and a cooling effect is
produced at the bulb. This temperature is the wet bulb temperature, which will be naturally less than
the dry bulb temperature.
Applications:
It is used for checking humidity level in air conditioned rooms and installations.
It is used in the measurement range of 0 to lO0 % RH and can measure Wet bulb temperatures
between 0° C to 180° C.
- It is used for measuring wet bulb temperatures between 0° C to 180° C.
Limitations:
24) Continuous recording of humidity is not possible. The evaporation process at the wet bulb
will add moisture to the air, which will distrub the measured medium. Antomation is not possible
with this instruments.
25) If the wick is covered with dirt, the wick will become stiff and its water absorbing capacity will
reduce.
2. Absorption hygrometer:
Principle: Humidity changes the physical, chemical and electrical properties of several materials. This
property is used in transducers that are designed and calibrated to read relative humidity directly.
Hygroscopic materials such as human hair, animal membranes, Wood, paper etc, under go changes in
linear dimensions when they absorb moisture form their surrounding air. This change in linear
dimension is used for the measurement of humidity present in air. A hair hygrometer has been shown
in fig.
Description:
s) Human hair as the humidity sensor. The hair is arranged in parallel beam and they are
separated from one another to expose them to the surrounding air. Number of hairs are placed in
parallel to increase mechanical strength as shown in fig.
xvii. The hair arrangement is subjected to light tension by the use of a tension spring to ensure
proper functioning.
xviii. The hair arrangement is connected to an arm and a link arrangement and link in turn is
attached to a pointer, pivoted at one end. The pointer sweeps on a humidity calibrated scale.
Operation: When the humidity of air is to be measured, the hair arrangement is exposed to the air
medium and this absorbs the humidity from the surrounding air and expands or contracts in the linear
direction.
This expansion or contraction of the arrangement moves the arm & link and thus the pointer on the
calibrated scale, indicating the humidity present in the atmosphere. These hygrometers are called
membrance hygrometers when the sensing element is a membrance.
Applications:
Limitations:
Humidity changes the resistance of some material. This change in resistance is taker as a measure of
humidity
Description:
(x) The two metal electrodes, which are coated and separated by a humidity sensing hygroscopic salt
(lithium chloride) as shown in fig.
(xi) The leads of the electrodes are connected to a null balance Wheatstone bridge
Operation:
The electrodes coated with lithium chloride are exposed to atmosphere, whose humidity is to be
measured.
Humidity variation causes the resistance of lithium chloride to change. i.e., the chemical absorbs or loses
moisture and causes a change in resistance.
Higher the humidity ( RH) in the atmosphere, more will be the humidity absorbed by lithium chloride
and lower will be the resistance and higher will be the resistance in case of lesser humidity.
The change in resistance is measured using a Wheatstone bridge which becomes a measure of humidity
(RH) present in the atmosphere.
Applications:
Limitations:
This instrument should not be exposed to 100 % humidity as this makes chemical absorb all the humidity
and damage the instrument.
Temperature corrections must be made if they are not used at constant temperature conditions.
Principle: At constant pressure if the temperature of air is reduced, the water vapour in the will start to
condense at a particular temperature. This temperature is called dew point temperature.
Description:
I) A photo cell to detect the amount of light reflected from the mirror.
Operation:
-The mirror is constantly cooled by a cooling medium, which is maintained at a constant temperature.
-A thermocouple is attached to this mirror, whose leads are connected, to a milli voltmeter.
-Constantly a light is made to fall at an angle on the mirror and the amount of reflected light is sensed by
a photo cell as shown in fig.
-Now an air jet is made to fall on the mirror and the water- vapour (moisture) contained in the air starts
condensing on the mirror and they appear as small drops (dews) or the mirror.
-This moisture formed on the mirror reduces the amount of light reflected, which is detected by the
photocell. When for the first time, there is a change in the amount of transmitted light, it becomes an
indication of dew formation. At this instance i.e., the temperature indicated by the thermocouple
attached to the mirror becomes the dew-point temperature.
-This instrument is used to know the time at which the dew appears for the first time and to know
the dew point temperature.
Applications:
-Cargoes can be protected from condensation damage by this instrument by maintaining the dew point
of air in holds lower than the cargo temperature.
Limitations:
A hygrometer based on the quartz crystal oscillator is used to measure the moisture content of
gases such as ethylene, hydrogen, refrigerants and natural gas.
When a quartz crystal coated with a layer of hygroscopic materials (the materials which exhibit a change
in their dimensions when they absorb moisture) is subjected to gas sample, the weight of the crystal
increases as the hygroscopic materials absorbs the moisture. As the ‘weight of the crystal increases, its
frequency changes. An oscillator employing quart crystal coated with hygroscopic material and used for
the measurement of humidity (or moisture) is shown in figure given below,
In the above arrangement, two crystals are used. The two crystals are alternately subjected to two
different gases for a period of about 30 seconds, so that their contaminations become same and a
stable frequency output is obtained.
The frequency shifts of the crystal due to the change of its weight fin the presence of moisture of sample gas
are measured electronically and the difference in frequency is determined. This frequency difference is
converted into signal, which is then converted into digital form and displayed. Thus, quartz crystal
hygrometer can measure humidity or moisture content of gases ranging from 1Vppm to 30Vppm.
UNIT-V
MEASUREMENT OF FORCE, TORQUE AND POWER
An engineer is concerned not only with the generation of power by a prime-mover but is also required
to measure the useful output. That helps the engineer to know how well prime-mover is doing its job in
relation to the energy supplied to it. The terms related to engine output are:
xiii) Force: Force represents the mechanical quantity which changes or tends to change the
relative motion or shape of the body on which it acts. Force is vector quantity specified
completely by its magnitude, point of application, line of action and direction.
The relationship between motion and force is provided by the laws of dynamics. Newton’s second low of
motion states that force is proportional to the rate of change of momentum. That is
11)Work: Work represents the product of force and the displacement measured in the direction of
force.
Work done = force × displacement; W= F s
The unit of work is joule (J) which is defined as the work done by a constant force of one newton acting
on a body and moving it through a distance of one metre in its direction.
1J=1Nm
11. Torque: It represents the amount of twisting effort, and numerically it equals the product of force
and the moment arm or the perpendicular distance from the point of rotation (fulcrum) to the point
of application of force. Consider a wheel rotated by the force F applied at radius r. Torque or twisting
moment is then given by
T=F×r
g) Power: Power is the rate of doing work and is obtained by dividing the work done by time. The unit
of power is watt (W), kilowatt (kW) or megawatt (MW). Watt represents a work equivalent of one joule
done per second.
In one rotation =2 . If the wheel thus N revolutions per minute, then the angular displacement per second is 2 /60.
Force Measurement:
A measure of the unknown force may be accomplished by the methods incorporating following
principles:-
u) Balancing the force against a known gravitational force on a standard mass (scales balances)
v) Translating the force to a fluid pressure and then measuring the resulting pressure and pneumatic
load cells)
w) Applying the force to some elastic member and then measuring the resulting (proving ring)
x) Applying the force to a known mass and then measuring the resulting acceleration
y) Balancing the force against a magnetic force developed by interaction of a magnet current
carrying coil.
Force or weight is indicated by making a comparison the force due to gravity acting on a standard mass
and the force due to gravity on the unknown mass.
An equal-arm beam balance of a beam pivoted on a knife-edge fulcrum the centre. Attached to the centre of the beam a pointer which points vertically downwards the beam
is in equilibrium. The equilibrium exist when the clockwise rotating equals the anti-clockwise rotating moment i.e., 1 1= 2 2. Since the two arms of the beam equal; the beam
would be in equilibrium again 1= 2. Further for a given location, the attraction acts equally on both the masses therefore at the equilibrium conditions 1= 2 , i. e., the
unknown force or weights equal known force or weights.
Instead of deflection, strain in an elastic member may be measured by a strain gauge, and then
correlated to the applied force.
Mechanical load cells: The term load cell is used to describe a variety of force transducers which may
utilize the deflection or strain of elastic member, or the increase in pressure of enclosed fluids. The
resulting fluid pressure is transmitted to some form of pressure sensing device such as a manometer or
a bourdon tube pressure gauge. The gauge reading is identified and calibrated in units of force.
In a hydraulic load cell the force variable is impressed upon a diaphragm which deflects and there by
transmits the force to a liquid. The liquid medium, contained in a confined space, has a preload pressure
of the order of 2 bar. Application of force increases the liquid pressure; it equals the force magnitude
divided by the effective area of the diaphragm. The pressure is transmitted to and read on an accurate
pressure gauge calibrated directly in force units. The system has a good dynamic response; the
diaphragm deflection being less than 0.05 mm under full load. This is because the diaphragm has a low
modulus and substantially all the force is transmitted to the liquid. These cells have been to measure
loads up to about 2.5 MN with an accuracy of the order of 0. I percent of full scale; resolution is about
0.02 percent.
A pneumatic load cell operates on the force-balance principle and employs a nozzle-flapper transducer
similar to the conventional relay system. A variable downward force is balanced by an upward force of
air pressure against the effective area of a diaphragm. Application of force causes the flapper to come
closer to the nozzle, and the diaphragm to deflect downwards. The nozzle opening is nearly shut-off and
this results into an increased back pressure in the system. The increased pressure acts on the
diaphragm, produces an effective upward force which tends to return the diaphragm to its preload
position.
For any constant applied force, the system attains equilibrium at a specific nozzle opening and a corresponding pressure is
indicated by the height of mercury column in a manometer. Since the maximum pressure in the system is limited to the air-
supply pressure, the range of 'M unit can be extended only by using a larger diameter diaphragm. The commercially available
load cells operating on this principle can measure loads up to 250 KN with an accuracy of 0.5 percent of full scale. The air
consumption is of the order of 0.17 3/hr of free air.
Strain gauge load cell:
The strain gauge load cell converts weight or force into electrical outputs which are provided by the
strain gauges; these outputs can be connected to various measuring instruments for indicating,
recording and controlling the weight or force.
A simple load cell consists of a steel cylinder which has four identical strain gauges mounted upon it; the gauges 1 and 4 are along the direction of applied load and the gauges 2
and 3 are attached circumferentially at right angles to gauges 1 and 4. These four gauges are connected electrically to the four limbs of a Wheatstone bridge circuit. When there
is no load on the cell, all the four gauges have the same resistance. Evidently then the terminals B and D are at the same potential; the bridge is balanced and the output voltage
is zero
applications such as draw-bar and tool-force dynamometers, crane load monitoring, and road vehicle
weighing device etc.
Problem:
Torques measurement:
The main purpose of torque measurement is to determine the mechanical power required or developed
by a machine. Torque measurement also helps in obtaining load information necessary for stress or
strain analysis. In some cases other variables are determined by measuring torque. For example, in the
case of rotating cylinder viscometer, measurement of torque developed at the fixed end of the
stationary cylinder help in determining the viscosity of the fluid between the movable and stationary
cylinder.
Figure shows the schematics of an elastic torsion bar meter wherein angular deflection of a parallel
length of shaft is used to measure torque. The angular twist over fixed length of the bar is observed on
a calibrated disk (attached to the rotating shaft) by using the stroboscope effect of intermittent viewing
and the persistence of vision. The system gives a varying angle of twist between the driving engine and
the driven load as the torque changes.
Optical torsion meter: The meter uses an optical method to detect the angular twist of a rotating shaft.
The unit comprises two castings A and B which are fitted to the shaft at a known distance apart. These
castings are attached to each other by a tension strip C which transmits torsion but has little resistance
to bending. When the shaft is transmitting a torque, there occurs a relative movement between the
castings which results in partial inclination between the two mirrors attached to the castings. The
mirrors are made to reflect a light beam onto a graduated scale; angular deflection of the light ray is
then proportional to the twist of, and hence the torque in, the shaft. For constant torque measurements
from a steam turbine, the two mirrors are arranged back to back and there occurs a reflection from each
mirror during every half revolution. A second system of mirrors giving four reflections per revolution is
desirable when used with a reciprocating engine whose torque varies during a revolution.
Electrical torsion meter: A system using two magnetic or photoelectric transducers, as shown in
Fig, involves two sets of measurements.
(i) a count of the impulse from either slotted wheel. This count gives the frequency or shaft speed.
(xi)a measure of the time between pulses from the two wheels. This signal is proportional to the twist 6
of, and hence torque T in the shaft.
These two signals, T and , can be combined to estimate the power being transmitted by the shaft.
Strain- gauge torsion meter: A general configuration of a strain gauge bridge circuit widely employed for
torque measurement from a rotating shaft is shown in Fig.
Four bonded-wire strain gauges are mounted on a 45' helix with the axis of the rotation and are placed
in pairs diametrically opposite, If the gauges are accurately placed and have matched characteristics, the
system is temperature compensated and insensitive to bending and thrust or pull effects. Any .change in
the gauge circuit then results only from torsional deflection. When the shaft is under torsion, gauges I
and 4 will elongate as a result of the tensile component of a pure shear stress on one diagonal axis,
while gauges 2 and 3 will contract owing to compressive component on the other diagonal axis. These
tensile and compressive principal strains can be measured, and the shaft torque can be calculated
A main problem of the system is carrying connections from the strain gauges (mounted on the rotating
shaft) to a bridge circuit which is stationary. For slow shaft rotations, the connecting wires are simply
wrapped around the shaft. For continuous and fast shaft rotations, leads from the four junctions of the
gauges are led along the shaft to the slip rings. Contact with the slip rings is made with the brushes
through which connections can be made to the measuring instrument.
Commercial-strain-gauge torque sensors are available with built-in slip rings and speed sensors. A family
of such devices covers the range 6 Nm to 1000 kNm with full-scale output of about 40 mV.
The dynamometer is a device used to measure the torque being exerted along a rotating shaft so as to
determine the shaft power input or output of power-generating, transmitting, and absorbing machinery.
Dynamometers are generally classified into:
(j) Absorption dynamometers in which the energy is converted into heat by friction whilst being
measured. The heat is dissipated to the surroundings where it generally serves no useful purpose.
Absorption dynamometers are used when the test-machine is a power generator such as an engine,
turbine and an electric motor. The types commonly used include Prony brakes, hydraulic or fluid friction
brakes, fan brakes and eddy current dynamometers.
(k) Transmission dynamometers in which the energy being transmitted either to or from dynamometer
is not absorbed or dissipated. After measurement, the energy is conveyed to the surroundings in a
useful mechanical or electrical form. A small amount of power ma). However, be lost by friction at the
joints of the dynamometer. The type includes torsion and belt dynamometers, and strain gauge
dynamometers.
g) Driving dynamometer which may be coupled to either power-absorbing or power generating
devices since it may operate either a motor or a generator. These instruments measure power and also
supply energy to operate the tested devices. They are essentially useful in determining performance
characteristics of such machines as pumps and compressors. Electric cradled dynamometer is a typical
example of the driving dynamometer.
Mechanical brakes: The Prony and the rope brakes are the two types of mechanical brakes chiefly
employed for power measurement. The prony brake has two common arrangements in the block type
and the band type. Whereas the block type is employed to high speed shafts with a small pulley, the
band type measures the power of low speed shafts having a relatively large pulley.
The block type prony brake consists of two blocks of wood each of which embraces rather less than one
half of the pulley rim. One block carries a lever arm to the end of which a pull can be applied by means
of a dead weight or spring balance. A second arm projects from the block in the opposite direction and
carries a counter-weight to balance the brake when unloaded. When operating, friction between the
blocks and the pulley tends to rotate the blocks in the direction of the rotation of the shaft. This
tendency is prevented by adding weights at the extremity of the lever arm so that it remains horizontal
in a position of equilibrium.
Let W be the weight in newton, I be the effective length of the lever arm in meter, and N be the
revolutions of the crankshalt per minute. Then:
Rope brake dynamometers:
A rope brake dynamometers consists of one or more ropes wrapped around the fly wheel of an engine
whose power is to be measured. The ropes are spaced evenly across the width of the rim by means of U-
shaped wooden blocks' located at different points of the rim of the flywheel. The upward ends of the
rope are connected together and attached to a spring balance, and the downward ends are kept in place
by a dead weight. The rotation of flywheel produces frictional force and the rope tightens. Consequently
a force is induced in the spring balance. Generation of heat is enormous and that necessitates a cooling
arrangement for the brake. The rim is made trough shaped internally. Water is run into the trough and
kept in place by the centrifugal force.
Hydraulic dynamometer:-
A hydraulic dynamometer uses fluid-friction rather than dry friction for dissipating -the input energy.
The unit consists essentially of two elements namely a rotating disk and stationary casing. The rotating
disk is keyed to the driving shaft of the prime-mover and it resolves inside the stationary casing. The
casing is mounted on antifriction (trunnion) bearings and has a brake arm and a balance system
attached to it. Such bearings allow the casing to rotate freely except for the restraint imposed by the
brake arm. Further, the casing is in two-halves; one of which is placed on either side of the rotating disk.
Semi-elliptical recesses in the casing match with the corresponding grooves inside the rotating disk to
form chambers through which a stream of water flow is maintained. When brake is operating, the water
follows a helical path in the chamber. Vortices and eddy-currents are set-up in the water and these tend
to turn the dynamometer casing .in the direction of rotation of the engine shaft. This tendency is
resisted by the brake arm balance system that measure the torque.
ELEMENTS OF CONTROL SYSTEMS:
Introduction:
A system is an assemblage of devices and components connected or related by some form of regular
interation or interdependence to form an organised whole and perform specified tasks. The system
produces an output corresponding to a given input.
Ex: The thermometer and the mass-spring damper system can be indentified as systems. He
thermometer has the input x = (temperature) and the output y = l (length of the mercury column in
the capillary).
The term control implies to regulate, direct or command. A control system may thus be defined as;
”an assemblage of devices and components connected or related so as to command direct or regulate it
self or another system".
EX:1
19. An electrical switch which serves to control the flow of electricity in a circuit. The input signal
(command) is the flippling of the switch on or off; and the corresponding output (controlled) signal is the
flow or non-flow of electric current.
20. A thermal system where it is desired to maintain the temperature of hot water at a prescribed
value. Before the operator can carry out his task satisfactorily, the following requirements must be met:
xiv. The operator must be told what temperature is required for the water. This temperature,
called the set point or desired value, constitutes the input to the system.
xv. The operator must be provided with some means of observing the temperature (sensing element).
For that a thermometer is installed in the hot water pipe and it measures measured temperature
compares with the desired value. This difference between the desired value and the
actual measurement value is error or actuating signal.
e=r-c
where r refers to the set-point or reference input and c denotes the controlled variable.
l) The operator must be provided with some means of influencing the temperature (control elemeny and
must be instructed what to do to move the temperature in a desired direction (control function).
15. A driving system of an automobile (accelerator, carburettor and an engine vehicle) where
command signal is the force on the acceleration pedal and the automobile speed is the controlled
variable. The desired change in engine speed can be obtained by controlling pressure on the
accelerator pedal.
15) An automobile steering system where the driver is required to keep the automobile in the
appropriate lane of the roadways. The eyes measure the output (heading of the automobile), the brain
and hands react to any error existing between the input (appropriate lane) and the output signals, and
act to reduce the error to zero.
14) A biological control system where a person moves his finger to point towards an
object. The command signal is the position of the object and the output is the actual pointed
direction.
Other well-known examples of control systems are: electric frying pans, water pressure regulators,
toilet-tank water level, electric irons, refrigerators and household furnaces with thermostatic control.
Classification of control systems:
These are two basic types of control systems, 1. open loop and 2. closed loop systems.
1 Open-loop systems (unmonitored control system). The main features of an open loop system are:
26) there is no comparison between the actual (controlled) and the desired values of a variable.
27) for each reference input, there corresponds a fixed operating condition (output) and this output
has no effect on the control action, i. e., the control action is independent of output.
28) for the given set-input, there may be a big variation of the controlled variable depending
upon the ambient conditions. Since there is no comparision between actual output and the desired
value, rapid changes can occur inthe output if there occurs any change in the external load.
Trying to guide a car by setting the steering wheel, together with a pattern of subsequent changes of
direction, at the beginning of a journey and making no alternation enroute as and when the car deviates
form the desired path.
Hitting the golf ball where the player knows his goal to get the ball into a particular hole. To achieve
it, the player hits the ball correctly at the beginning of its flight. Once the moment of impact ispassed,
he loses his control on any further flight ofthe ball.
The automobile traffic control signals at roadway intersections are the open loop systems. The red
and green light travels (input to the control action) are predetermined by a calibrated timing mechanism
and are in no way influanced by the volume of traffic (output).
An open loop system has the following advantages and limitations:
u) no stability problems
v) convenient when the controlled variable is either difficult to measure or it is economically not
feasible
w) system affected by internal and external disturbances ; the output may differ from the desired
value
2. Closed-loop systems (monitored control systems). The main features of a closed loop system are:
xix. There is comparison between the actual (controlled) and the desired values of the
variable. To accomplish it, the output signal is fed back and the loop is completed.
xx. The error signal (deviation between the reference input the feedback signals) then actuates the
control element to minimize the error and bring the system output to the desired value.
xxi. The system operation is continually correcting any error that may exist. As long as the output
does not coincide with the desired goal, there is likely to be some kind of actuating signal.
The performance of such a system is evaluated with reference to the following desireable
characteristics:
24) The control of the thermal system is a closed loop, when the operator detects that the output
temperature is different from the desired or reference temperature, he initiates an action to reduce the
discrepency by operating a value that controls the steam supply to water.
25) The automobile driving system would become a closed-loop system when the driver makes a
visual observation of the speed indicated by a speedometer and compares this mentally with the
desired speed.
Example of automatic control systems:
13) In the automatic feed-back control of a thermal system (Fig. 15.9), the human operator has
been replaced by an automatic controller. The actual temperature of the hot water is measured by a
thermometer and is fed to the controller for comparison with the reference temperature whose value
has been specified by appropriate, setting of the thermostat/regulator. Based on the error signal, the
controller generates an output (correcting signal) which is taken to the control valve in order to change
the valve opening for steam supply.
(xii) The level control system depicted in Fig. 15.10 is an automatic control system. Where inflow of
water to the tank is dependent on the water; level in the tank. The automatic controller maintains the
liquid level by comparing the actual level with a desired level and correcting any error by adjusting the
opening of the control valve.
J) A pressure control system where the pressure inside the furance is automatically controlled by
affecting a change in the position of the damper (Fig 15.12).