This document summarizes the air system sizing for a package unit serving a 46.5 square meter zone in Dubai, United Arab Emirates. The central cooling coil is sized to handle a peak cooling load of 1.1 kW occurring in June with supply air delivered at 14.4°C. The central heating coil is sized for a maximum load of 0.4 kW occurring during design heating conditions. Both the supply and return fans are sized for a maximum airflow of 85 liters per second. Outdoor ventilation air is designed at 15 liters per second.

Uploaded by

MJ
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views

Hap Sample Calculations

This document summarizes the air system sizing for a package unit serving a 46.5 square meter zone in Dubai, United Arab Emirates. The central cooling coil is sized to handle a peak cooling load of 1.1 kW occurring in June with supply air delivered at 14.4°C. The central heating coil is sized for a maximum load of 0.4 kW occurring during design heating conditions. Both the supply and return fans are sized for a maximum airflow of 85 liters per second. Outdoor ventilation air is designed at 15 liters per second.

Uploaded by

MJ
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 1

Air System Sizing Summary for PACKAGE UNIT

Project Name: SAMPLE PROJECT.1111 11-28-2018


Prepared by:ENGINEERS 02:28PM

Air System Information


Air System Name ............................... PACKAGE UNIT Number of zones ............................................................. 1
Equipment Class ........................................ PKG ROOF Floor Area ................................................................... 46.5 m²
Air System Type ................................................ SZCAV Location ............................ Dubai, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s .......................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space L/s ...................... Individual peak space loads Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ............................................................ 1.1 kW Load occurs at ................................................... Jun 1700
Sensible coil load ..................................................... 1.1 kW OA DB / WB ...................................................... 40.1 / 23.6 °C
Coil L/s at Jun 1700 ................................................... 85 L/s Entering DB / WB ............................................. 27.7 / 20.0 °C
Max block L/s ............................................................ 85 L/s Leaving DB / WB .............................................. 17.2 / 16.5 °C
Sum of peak zone L/s ............................................... 85 L/s Coil ADP ..................................................................... 16.1 °C
Sensible heat ratio ............................................... 0.996 Bypass Factor .......................................................... 0.100
m²/kW ..................................................................... 43.3 Resulting RH ................................................................. 58 %
W/m² ....................................................................... 23.1 Design supply temp. ................................................... 14.4 °C
Water flow @ 5.6 °K rise ......................................... N/A Zone T-stat Check .................................................... 1 of 1 OK
Max zone temperature deviation .................................. 0.0 °K

Central Heating Coil Sizing Data

Max coil load ............................................................ 0.4 kW Load occurs at ..................................................... Des Htg
Coil L/s at Des Htg .................................................... 85 L/s W/m² ............................................................................. 7.7
Max coil L/s ............................................................... 85 L/s Ent. DB / Lvg DB .............................................. 19.5 / 23.0 °C
Water flow @ 11.1 °K drop ...................................... N/A

Supply Fan Sizing Data

Actual max L/s ........................................................... 85 L/s Fan motor BHP ........................................................... 0.00 BHP
Standard L/s .............................................................. 85 L/s Fan motor kW ............................................................. 0.00 kW
Actual max L/(s-m²) ................................................ 1.82 L/(s-m²) Fan static ......................................................................... 0 Pa

Return Fan Sizing Data

Actual max L/s ........................................................... 85 L/s Fan motor BHP ........................................................... 0.00 BHP
Standard L/s .............................................................. 85 L/s Fan motor kW ............................................................. 0.00 kW
Actual max L/(s-m²) ................................................ 1.82 L/(s-m²) Fan static ......................................................................... 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s ...................................................... 15 L/s L/s/person ................................................................... 0.00 L/s/person
L/(s-m²) ................................................................... 0.32 L/(s-m²)

Hourly Analysis Program v.4.3 Page 1 of 1