Instructions for Danfoss
Refrigeration & Air conditioning Controls
REFRIGERATION &
AIR CONDITIONING DIVISION Catalogue
Contents
Electronically operated valves
AKV 15/AKVA 15 ................................................................................................... 39
AKV 20 ...................................................................................................................... 41
AKVA 10-n (n=1-8) ................................................................................................ 43
AKVA 20 ................................................................................................................... 45
AKV 10-n (n=1-7) .................................................................................................. 47
ETS 12½. 25 & KVS 15 .......................................................................................... 49
ETS 25, 50 & 100 .................................................................................................... 53
ETS 250 & 400 ........................................................................................................ 57
PHTQ ......................................................................................................................... 59
TEAQ ......................................................................................................................... 61
TQ ............................................................................................................................... 63
068R9548
Electrically operated expansion valve
AKV/ AKVA 15
AKV 15
AKVA 15
Media:
AKV 15: HCFC, HFC,R744
AKVA15: R717,R744, HCFC, HFC
Max working pressure Ps / MWP:
AKV 15-1, 2, 3: 42 barg / 610 psig
AKV 15-4: 28 barg / 406 psig
AKVA 15: 42 barg / 610 psig
Max test pressure PT:
AKV 15-1, 2, 3: 47 barg / 680 psig
AKV 15-4: 31 barg / 450 psig Clip-on coil
AKVA 15: 47 barg / 680 psig
Max differential pressure:
MOPDmax = P1-P2 = 20 bar / 290 psi
Do not insulate.
39
Instructions
Pakningen skal skiftes, hvis ventilen adskilles.
The gasket must be exchanged, if the valve is dismantled.
Bei Zerlegung des Ventils muß die Dichtung ausgewechselt werden.
Changer le joint chaque fois que la vanne est démontée.
Es preciso cambiar la junta si se desmonta la válvula
kv R22 kv R717
AKV 15-n AKVA 15-n
m3/h kW TR m3/h kW TR
AKV 15-1 0,25 25 7 AKVA 15-1 0,25 125 35
AKV 15-2 0,4 40 11 AKVA 15-2 0,4 200 60
AKV 15-3 0,63 63 18 AKVA 15-3 0,63 300 90
AKV 15-4 1,0 100 28 AKVA 15-4 1,0 500 140
40
Instructions
068R9523
068R9523
Electrically operated expansion valve
AKV 20
Media:
HCFC, HFC,R744
Max working pressure :
Ps 28 barg / MWP 400 psig
Max test pressure :
PT 31 barg / 260 psig
Max differential pressure:
MOPDmax = P1-P2 = 20 bar / 290 psi
41
Instructions
42
Instructions
068R9546
068R9546
Electrically operated expansion valve
AKVA 10 - 1, 2, 3, 4, 5, 6 7,8
43
Instructions
Clip-on coil
Pakningen skal
skiftes, hvis ventilen
adskilles
Changer le joint
chaque fois que la
vanne est démontée
Es preciso cambiar la
junta si se desmonta
la válvula
44
Instructions
068R9558
068R9558
Electrically operated expansion valve
AKVA 20
Kølemidler/ Refrigerants/ Kältemittel/ Réfrigérants/ Köldmedier: R717,
HCFC, HFC
MWP = PS 42 bar g (609 psi g)
MOPD max. = (P1-P2)max. = 18 bar g (261 psi g)
Dæksel
Les tubes de raccordement sont en acier type P 285 QH EN 10222-4. L’instal-lation doit
Cover être réalisée suivant la procédure en vigueur, par du personnel quali-fié. Après soudage
Deckel les raccords doivent être protégés contre la corrosion.
Raccordement
Lock/Anslutning, material P285QH EN 10222-4. Ventilen skall inmonteras i
Lock/Anslutning
spänningslöst tillstånd i rörsystemet och montaget får endast ske av behörig personal
enligt anvisningarna. Efter inmonteringen bör ventilen ytbehandlas för att skydda mot
korrosion.
45
Instructions
Pakning skal skiftes, hvis ventilen adskilles.
Hver linjemarkering indikerer ventilstørrelsen. Her er AKVA 20-3 vist. Antal linjer Type
No of line marking
Each line marking indicates size of valve. Here shown AKVA 20-3. Anzahl Linien
Nombre de ligne
Jede Linienmarkierung zeigt die Ventilgrösse an. Hier ist AKVA 20-3 abgebildet. Antal linjer
1 AKVA 20-1
Le nombre de ligne sur le piston indique la taille de la vanne. Exemple 3 lignes
2 AKVA 20-2
veut dire AKVA 20-3.
3 AKVA 20-3
Varje linjemarkering indikerar ventilstorleken. Här visas AKVA 20-3. 4 AKVA 20-4
5 AKVA 20-5
30 ± 3 Nm
46
Instructions
068R9514
068R9514
Electrically operated expansion valve
AKV 10 - 1, 2, 3, 4, 5, 6 7
c 75 73
d 67 75
R404A
Dyse, Düse, Orifice, Orificio R 22 R 134a R407C
R507
Best.nr.
Code no.
Bestell-Nr.
N° de code
n Núm. de código kW kW kW kW
1 068F0506 1.0 0.9 0.8 1.1
2 068F0507 1.6 1.4 1.3 1.7
3 068F0508 2.6 2.1 2.0 2.5
4 068F0509 4.1 3.4 3.1 4.0
5 068F0510 6.4 5.3 4.9 6.4
6 068F0511 10.2 8.5 7.8 10.1
7 068F0512 16.3 13.5 12.5 17.0
47
Instructions
Do not insulate
Ambient temperatur range:
-50°C < tamb < 50°C
-58°F < t amb < 120°F
Media:
HCFC, HFC,R744
Max working pressure :
AKV 10-1 to 6 Ps 52 barg / MWP 753 psig
AKV 10-7 Ps 42 barg / MWP 610 psig
Max test pressure :
PT 60 barg / 869 psig
Max differential pressure:
MOPDmax = P1-P2 = 18 bar / 260 psi
Clip-on coil
Pakningen skal
skiftes, hvis ventilen
adskilles
Ny
Bei Zerlegung des New
Ventils muß die Dich- Neu
tung ausgewechselt Neuf
werden. Nueva
Brugt
Used
Changer le joint Gebraucht
Usagé
chaque fois que la
Usado
vanne est démontée
Es preciso cambiar la
junta si se desmonta
la válvula
48
034R9527
Instruction
034R9527
ETS 12½, ETS 25 & KVS 15
Tilladt omgivelsestemperatur
Allowable ambient temperature
Zulässige Umgebungstemperatur
Température ambiante admissible
Temperatura ambiente permisible
Anvendelse
Application
Anwendung
Application
Apicación
ETS 12½, 25
KVS 15
Montage
Mounting
Einbau
Montage
Installación
49
Lodning Samling
Brazing Assembling
Löten Zusammenbau
Soudure Assemblage
Soldadura Montaje
Adskillelse
Disassembling
Auseinanderbauen
Désassemblage
Desmontaje
50
Stepper motor switch sequence:
Coil I Coil II
STEP
Red Green White Black
1 + - + -
↑ CLOSING ↑ 2 + - - + ↓ OPENING ↓
3 - + - +
4 - + + -
1 + - + -
Electrical specifications
51
Advarsel!
Warning!
Achtung!
Attention !
Advertencia
52
Instructions
ETS 25, 50 & 100
034R9510
034R9510
Tilladt omgivelsestemperatur
Allowable ambient temperature
Zulässige Umgebungstemperatur
Température ambiante admissible
Temperatura ambiente permisible
Anvendelse
Application
Anwendung
Application
Aplicación
Montage
Mounting
Einbau
Montage
Installación
53
Lodning Max. tryk
Brazing Max. pressure
Löten Max. Druck
Soudure Pression maximale
Soldadura Presión máx.
Adskillelse
Disassembling
Zerlegung
Désassemblage
Desmontaje
Closed
Open
⇒
Samling
Assembling
Zusammenbau
Assemblage
Montaje
Closed
Open ⇒
54
Tilslutning
Connection
Anschluss
Raccordement
Conexión
Electrical specifications
Parameter ETS 50B / ETS 100B
Stepper motor type Bi-polar - permanent magnet
Step mode 2 phase full step
Phase resistance 52Ω ±10%
Phase inductance 85 mH
Holding current Depends on application.
Full current allowed (100% duty cycle)
Step angle 7.5° (motor),
0.9° (lead screw),
Gearing ration 8.5:1. (38/13)2:1
Nominal voltage (Constant voltage drive) 12 V dc -4% +15%, 150 steps/sec.
Phase current (Using chopper drive) 100 mA RMS -4% +15%,
Max. total power Voltage / current drive: 5.5 / 1.3 W (UL: NEC class 2)
Step rate 150 steps/sec. (constant voltage drive)
0-300 steps/sec. 300 recommended (chopper current drive)
Total steps ETS 25: 2625 [+160 / -0] steps
ETS 50: 2625 [+160 / -0] steps
ETS 100: 3530 [+160 / -0] steps
Full travel time ETS 50: 17 / 8.5 sec. (voltage / current)
ETS 50: 17 / 8.5 sec. (voltage / current)
ETS 100: 23 / 11.5 sec. (voltage / current)
Reference position Overdriving against the full close position
Electrical connection 4 wire 0.5 mm2 (0.02 in2), 2 m (6.5 ft) long cable
55
Advarsel!
Warning!
Achtung!
Attention !
Advertencia
56
Instructions
ETS 250 & 400
034R9525
034R9525
Temperature range
Max. +60°C (140°F)
Min. -40°C (-40°F)
Max. pressure
Application
EKC
controller
ETS
Mounting
57
Brazing
Sil-Fos 15
Electrical connection
58
Instructions
PHTQ
o n
c ti
d u
r o
f p
t o
ou
RC-ET
pe t amb. max
Bar °C
-0,6 25
0 35
1 50
TR kW Dyse, Düse,
(tons) Orifice
No,
1 3.5 068G2050
2 7.0 068G2051
3 10.5 068G2052
TEA 20 5 17.5 068G2053
8 28 068G2054
12 42 068G2055
20 70 068G2056
33 115 068G2057
TEA 85 55 190 068G2058
85 295 068G2059
AG-RDT
068R9648
068R9648
o n
c ti
d u
r o
f p
t o
ou
63
Y±0.5 mm
Code no. Type Orifice
TQ PHTQ
068F2041 TQ 5 No.1 26.5 27.5
068F2042 TQ 5 No.2 26.5
068F2043 TQ 5 No.3 27.0
64