Outgoing VCB: Test Module

The document summarizes the results of an outgoing voltage circuit breaker test. It performed 8 different tests at various fault levels and phases including 150% and 200% for steps 1 and 2. All tests passed with trip times ranging from 0.059 to 2.885 seconds. The overall test passed with a 100% success rate.

Uploaded by

Aschenberg
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
31 views

Outgoing VCB: Test Module

The document summarizes the results of an outgoing voltage circuit breaker test. It performed 8 different tests at various fault levels and phases including 150% and 200% for steps 1 and 2. All tests passed with trip times ranging from 0.059 to 2.885 seconds. The overall test passed with a 100% success rate.

Uploaded by

Aschenberg
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Outgoing VCB

Test Module
Name: OMICRON QuickCMC Version: 3.00
Test Start: 12-Oct-2019 21:56:09 Test End: 12-Oct-2019 22:03:47
User Name: Manager:
Company:

Test Results

Title: 50/51 Step-1 150%

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 7,500 A 0,00 ° 50,000 Hz
I L2 7,500 A -120,00 ° 50,000 Hz
I L3 7,500 A 120,00 ° 50,000 Hz

Generator Settings
I L1 7,500A 0,00° +90°
I L2 7,500A -120,00° I L3
I L3 7,500A 120,00°

I L1
180° 0°

I L2
8,0 A -90°

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
2,914s n/a n/a

Title: 50/51 Step-1 200%

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 10,00 A 0,00 ° 50,000 Hz
I L2 10,00 A -120,00 ° 50,000 Hz
I L3 10,00 A 120,00 ° 50,000 Hz

Generator Settings
I L1 10,000A 0,00° +90°
I L2 10,000A -120,00° I L3
I L3 10,000A 120,00°

I L1
180° 0°

I L2
10,0 A -90°

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
1,697s n/a n/a
Title: 50/51 Step-2 150%

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 30,00 A 0,00 ° 50,000 Hz
I L2 30,00 A -120,00 ° 50,000 Hz
I L3 30,00 A 120,00 ° 50,000 Hz

Generator Settings
I L1 30,000A 0,00° +90°
I L2 30,000A -120,00°
I L3 30,000A 120,00° I L3

I L1
180° 0°

I L2

40,0 A -90°

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,059s n/a n/a

Title: 50/51 Step-2 200%

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 40,00 A 0,00 ° 50,000 Hz
I L2 40,00 A -120,00 ° 50,000 Hz
I L3 40,00 A 120,00 ° 50,000 Hz

Generator Settings
I L1 40,000A 0,00° +90°
I L2 40,000A -120,00° I L3
I L3 40,000A 120,00°

I L1
180° 0°

I L2
40,0 A -90°

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,049s n/a n/a

Title: 50N/51N Step-1 150%

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 1,500 A 0,00 ° 50,000 Hz
I L2 0,000 A -120,00 ° 50,000 Hz
I L3 0,000 A 120,00 ° 50,000 Hz
Generator Settings
I L1 1,500A 0,00° +90°
I L2 0,000A -120,00°
I L3 0,000A 120,00°

I L1
180° 0°

2,0 A -90°

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
2,885s n/a n/a

Title: 50N/51N Step-1 200%

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 2,000 A 0,00 ° 50,000 Hz
I L2 0,000 A -120,00 ° 50,000 Hz
I L3 0,000 A 120,00 ° 50,000 Hz

Generator Settings
I L1 2,000A 0,00° +90°
I L2 0,000A -120,00°
I L3 0,000A 120,00°

I L1
180° 0°

2,0 A -90°

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
1,701s n/a n/a

Title: 50N/51N Step-2 150%

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 6,000 A 0,00 ° 50,000 Hz
I L2 0,000 A -120,00 ° 50,000 Hz
I L3 0,000 A 120,00 ° 50,000 Hz

Generator Settings
I L1 6,000A 0,00° +90°
I L2 0,000A -120,00°
I L3 0,000A 120,00°

I L1
180° 0°

8,0 A -90°
Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,066s n/a n/a

Title: 50N/51N Step-2 200%

Fault Calculator:
Table Inputmode Parameters (All values are secondary)
Direct I L1 8,000 A 0,00 ° 50,000 Hz
I L2 0,000 A -120,00 ° 50,000 Hz
I L3 0,000 A 120,00 ° 50,000 Hz

Generator Settings
I L1 8,000A 0,00° +90°
I L2 0,000A -120,00°
I L3 0,000A 120,00°

I L1
180° 0°

8,0 A -90°

Binary Inputs
Trip Start Overload
0->1 1->0 1->0
0,059s n/a n/a

Summary
8 tests passed, 0 tests failed, 0 tests not assessed 100,00% passed
Test passed