Spread of Smoke and Fire Gases Via The Ventilation System.: Gordonova, Polina
Spread of Smoke and Fire Gases Via The Ventilation System.: Gordonova, Polina
Gordonova, Polina
1997
Link to publication
General rights
Copyright and moral rights for the publications made accessible in the public portal are retained by the authors
and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the
legal requirements associated with these rights.
• Users may download and print one copy of any publication from the public portal for the purpose of private study
or research.
• You may not further distribute the material or use it for any profit-making activity or commercial gain
• You may freely distribute the URL identifying the publication in the public portal
Take down policy
If you believe that this document breaches copyright please contact us providing details, and we will remove
access to the work immediately and investigate your claim.
LUNDUNI
VERSI
TY
PO Box117
22100L und
+4646-2220000
Lund University • Sweden
Lund Institute of Technology
Department of Building Science
Report TABK--97 I lOll
Polina Gordonova
Lund University
Lund University, with eight faculties and a number of research cen-
tres and specialized institutes, is the largest establishment for re-
search and higher education in Scandinavia. The main part of the
University is situated in the small city of Lund which has about
97 600 inhabitants. A number of departments for research and edu-
cation are, however, located in Malmo. Lund University was founded
in 1666 and has today a total staff of 5 850 employees and 38 200
students attending 50 degree programmes and 850 subject courses
offered by 170 departments.
Polina Gordonova
This report relates to Research Grant No 050-942 from the Swedish Fire Research Board to the
Department of Building Science, Lund University, Lund Institute of Technology, Lund, Sweden.
Spread of Smoke and Fire Gases via the Ventilation System
Keywords
Compartment fires, fire flow, fire pressure, fire simulation, smoke
spread, ventilation ducts.
Report TABK--97/1011
Spread of Smoke and Fire Gases via the Ventilation System
Lund University, Lund Institute of Technology, Department of Building Science
2
Abstract
Abstract
3
Spread of Smoke and Fire Gases via the Ventilation System
4
Table of Contents
Table of Contents
Abstract 3
Contents 5
Summary 11
1 Introduction 27
1.1 Background 28
1.2 Objective and limitations 29
1.3 Comprised fields of knowledge 29
5
Spread of Smoke and Fire Gases via the Ventilation System
2.3.3 SMAFS 45
2.4 Airtighteness 46
3. Fire simulations 49
3.1 Input data used in simulations 49
3.1.1 Geometrical data 49
3.1.2 Fire scenario and fire position 51
3.1.3 Assumed airtighteness 51
3.2 Analysis of parameters evaluated by CFAST 52
3.2.1 Predicted variables 52
3.2.2 Peak pressures and peak temperatures
in temperatures in fire rooms 57
3.2.3 Mass and volume flow 59
3.3 Comparisons of predicted parameters with
experimental data 60
3.4 Analysis of parameters evaluated by DSLAYV
andSMAFS 61
3.5 Window breakage modelling 63
3.5.1 Study of the literature 64
3.5.2 Simple window breakage model 65
3.5.3 Window glass temperature model 66
6
Table of Contents
Section 2 Operation of ventilation systems
during fires 93
6. Theoretical methods 97
6.1 Background 97
6.2 Flow model 98
6.3 Theoretical model for the analysis of ventilation
systems 99
6.3.1 Exhaust ventilation system 100
6.3.2 Exhaust and supply ventilation system without
air leakage 103
6.3.3 Exhaust and supply ventilation system with
air leakage 107
7
Spread of Smoke and Fire Gases via the Ventilation System
References 207
Appendix 211
8
Preface and Acknowledgements
This work was funded by the Swedish Fire Research Board, which
is gratefully acknowledged.
9
Spread of Smoke and Fire Gases via the Ventilation System
10
Summary
Summary
11
Spread of Smoke and Fire Gases via the Ventilation System
According to statistical estimation of the principal dangers and
damage caused by fire, presented in different sources, the most
probable items in which fires initiate in the chosen rooms are: sofa
[6] and bed [7] in dwelling houses, bed [9] in hospitals, equipment
and furnishing [10] in offices and bed [6] in hotels. "Real" fire
growth curves, based on measured heat release rate vs. time
during full-scale burning tests of these items, are chosen to
simulate fires in spaces. The fires analysed are single-room fires,
limited to the item in which the fire started.
The objective of airtighteness evaluation is to summarise
knowledge about the real magnitude of leakage in relation to the
whole building envelope including interior building constructions,
for the studied types of enclosures, built at different times. For
the purpose of this study, air leakage in accordance with the
Swedish Building Regulations, BBR 94, applied to the whole
buildings envelope, can be accepted as a suitable and probable
value.
Different computer programs are used to simulate fire progress
in chosen rooms and the parameters obtained with these are com-
pared. CFAST (Consolidated Model of Fire Growth and Smoke
Transport), which is part of the computer program HAZARD I, is a
basic tool of fire simulations in the presented study. Two other
programs: DSLAYV and SMAFS (Smoke Movement and Flame
Spread) are also used for fire simulations in order to compare
predicted parameters. Both programs, CFAST and DSLAYV, use
a two-layer model of fire, while SMAFS is a field model program.
Comparison of parameters predicted by CFAST with those obtai-
ned with DSLAYV and SMAFS shows that the order of magnitude
of values is reasonable.
One of the most important issues is to estimate the characte-
ristic parameters/features that are produced by certain fires, and
to assess their influence on the pressure/flow ratio in the ventila-
tion system. Peak mass flows, peak temperatures and peak pres-
sures, predicted by computer simulations, are analysed and com-
pared to each other. Results are presented in the form of a table
and show peak values for temperature, exceeding 340°C in certain
cases, and peak values for pressure which vary widely between 30
and 2100 Pa.
In this connection, evaluation of both the time at which the
window breaks and the temperature in the fire room at which this
12
Summary
13
Spread of Smoke and Fire Gases via the Ventilation System
The boundary case for smoke spread via ventilation ducts can be
described by zero airflux in the adjacent room(s) and also zero
pressure in the connecting junction between the fire room and the
main duct. All flows and pressure exceeding the "boundary" va-
lues cause smoke spread.
A description of basic principles and theoretical model of ex-
haust, supply-exhaust (open and closed) mechanical ventilation
systems serving two rooms, which determine boundary conditions
of smoke spread through ventilation ducts, are presented in the
report.
The most typical ventilation systems used in the studied types
of buildings and fire compartments in these are discussed in the
report. The analysis focuses on
-exhaust ventilation system with one exhaust fan and a distri-
bution system consisting of one or two main ducts with branches
to each compartment,
-supply-exhaust ventilation system with supply and relief fans
and distribution ductwork to each compartment,
-supply-exhaust ventilation system with a "zero" -duct. This me-
ans that supply air is distributed via terminals directly to the
compartments, while relief (exhaust) air collects in corridors
("zero" -ducts) and is removed via relief dampers by the exhaust
ventilation system.
In all types of ventilation systems the plenum can be both verti-
cal and horizontal. These ventilation systems can include different
variations of system layouts, and the degrees of complexity of the-
se systems can be widely different.
The report presents an evaluation of boundary conditions for
smoke spread in the types of ventilation systems discussed above
with four branches, general measures for the prevention of smoke
spread via ventilation ducts, and a brief description of PFS-
elements and layout.
PFS provides the opportunity to describe resistance properties
of wyes and junctions in two different ways: as a quadratic
function and with the help of empirical equations. Both types are
tested. As this study is interested in "abnormal" flow behaviour,
i.e. changes in flow directions and the consequent decrease in flow
in certain parts of junctions to zero value, it is not obvious how
wyes would respond. Higher flows cause higher velocities in ducts,
and, as a result, higher Reynolds numbers. Along with increasing
14
Summary
flow, turbulence increases pressure field described as quadratic
function. For these reasons, the resistance properties of wyes and
junctions described as a quadratic function is used in further
analysis.
Different solutions are analysed for the prevention of the smoke
spread to the adjacent room(s) via ventilation systems with four
branches. There are
shutting down the fan(s),
doubling the speed of rotation of the fan(s),
converting the supply fan into exhaust fan,
bypassing support plenum to the exhaust plenum
and a combination of these measures with ordinary fan function
and with each other.
Fire flow exceeding boundary fire flow, obtained in previous cal-
culations, is used as default flow. The studied cases do not cover
all possible measures for the prevention of smoke spread through
ventilation ducts, but they show method of evaluating the danger
due to this.
The "real case" study examines the risk of smoke spread
through the chosen ventilation systems in buildings of higher de-
gree of complexity. Ordinary design air flows are assessed in the
examined buildings. Different cases are studied in order to esti-
mate boundary fire flows and corresponding pressures in different
rooms. This problem is very numerically complex for such venti-
lation systems with numerous branches, because the flow in the
boundary room must be equal to zero, while other flows and pres-
sures are much higher then normal. Because of this, fire flows ob-
tained from fire simulations are used in smoke spread evaluation
in the studied ventilation systems. "Fires" are placed in different
rooms and the resulting smoke spread to the adjacent room(s), as
well as different measures of preventing this phenomenon, are
studied.
The problem of evaluation the toxicity of spread diluted smoke
is discussed in the report. This evaluation regarding the concent-
ration of CO is made step by step for an exhaust ventilation sys-
tem with a shut-down fan. An assessment of
the total volume of smoke spread,
relative smoke spread to a single room, including evaluation of
the proportion of
smoke reaching one of n rooms
15
Spread of Smoke and Fire Gases via the Ventilation System
the concentration of CO in a single room is presented in the
study. All rooms are assumed to be identical.
The concentration of CO, together with the duration of exposure
and the type of activity during which exposure takes place, de-
termines the CO-doze and toxic effects. Different recommenda-
tions about acceptable and dangerous GO-concentrations and also
CO-dozes are discussed. An evaluation of GO-concentrations in
ppm, corresponding to the IDLH (immediately dangerous to life
and health) CO level, limited to 1500 ppm during 30 min, which
reaches one of the n rooms is also presented.
Analogously with the evaluation of the toxicity of the diluted
spread smoke, evaluation of the visibility of this is discussed in
the report. The expressions presented give mean values of asses-
sed visibility in the space.
The whole study assumes that the examined flows, including fi-
re flows, have ambient parameters, "cold" flows. It is well known
and also as shown by compartment fire simulations that fire flow
temperatures can exceed 300°C - 340°C. This means that the as-
sessed smoke spread via ventilation ducts can differ from that in
reality. Evaluation of friction pressure drop in straight ducts
shows that it decreases to approximately one half as the tempera-
ture in K doubles. The pressure drop in wyes and junctions is mo-
re difficult to evaluate. At the same time, along with smoke dilu-
tion and heat loss downstream from the main duct, flow tempera-
tures decrease and "cold" flows become default ones.
One more method for the evaluation of possible smoke spread
via exhaust ducts is presented in the study. The "Alexander" met-
hod is a method for manual calculations, based on the" cut-off'
principle. The "cut-off' principle means, that a branch(es) at the
boundary conditions with zero pressure is cut off and the rest of
ventilation system is calculated once more regarding the new
pressure/flow conditions.
The problem examined in the present study appears complex,
and the assumptions, made with a certain lack of knowledge and
a paucity of empirical data, cannot diminish the uncertainty of the
results obtained. The results should not therefore be interpreted
as some sort of total solution to the elimination of smoke spread,
but should be considered as a guidance in such types of analysis.
16
Sammanfattning
Sammanfattning
17
Spread of Smoke and Fire Gases via the Ventilation System
redning i kontor och sang i hotell. ''Verkliga" brandkurvor
(varmeeffekt-tid samband) vilka erhallits vid fullstandig for-
branning av ovan presenterade foremal ligger till grund for rums-
brandssimuleringar. Brander antas vara begransade till ett rum
samt till det foremal, branden borjade i.
For att uppskatta yttre och inre tathet av analyserade lokaler
har en sammanstallning av kunskap betraffande hus byggda vid
olika tider genomforts. BBR 94:s krav pa hur stor en byggnads
otathet hogst far vara, tillampad pa hela omslutande skalet
inklusive inre konstruktioner, antas dimensionerande for det har
projektet.
For att uppskatta brandforlopp i en lokal har olika simulering-
sprogram anvants och resultatparametrar har jamforts. CFAST
(Consolidated Model of Fire Growth and Smoke Transport) som
ingar i dataprogrammet HAZARDl ar ett huvudsimuleringspro-
gram i det har projektet. Tva andra simuleringsprogram:
DSLAYV och SMAFS (Smoke Movement and Flame Spread) an-
vands ocksa for att kunna jamfora resultaten. Bade CFAST och
DSLAYV ar program baserade pa tvazonsbrandmodeller. SMAFS
ar ett faltmodelsprogram. Jamforelse mellan resultatparametrar
erhallna med CFAST med motsvarande parametrar erhallna med
DSLAYV och SMAFS visar varden inom samma storleksordning.
Maximalt brandmassflode, maximal temperaturer och maxi-
malt brandtryck erhallna med hjalp av simuleringarna har ana-
lyserats och jamforts med varandra. De maximala temperatur-
erna overskrider i vis sa fall 340°C och maximalt brandtryck veri-
erar avsevart mellan 30 och 2100 Pa.
I detta sammanhang verkar det viktigt att kunna uppskatta
tidpunkt och temperaturer i ett brandrum da fonster gar sander.
Sammanstallning av kunskap om brandpaverkan pa fonster ar
gjord. Dessutom presenteras en enkel modell for uppskattning av
tidpunkt och temperaturskillnad i sjalva fonsterglaset da det gar
sander. Analysen visar att glaset spricker p.g.a. termisk spanning
vid temperaturskillnader i glaset av 58°C - 100°C. Motsvarande
temperaturer i brandrum varierar mellan 200°C och 400°C .
Brandvolymflode erhallna med hjalp av simuleringar for olika
brander i de undersokta typer av byggnaderna med varierande lo-
kalgeometri analyseras i projektet for varje typ av lokaler var for
sig. Regressionsanalys av de maximala flodena ar gjord med hjalp
av statistiskt program Minitab och EXCEL. Dessutom presen-
18
Sammanfattning
teras nagra teoretiska modeller skapade for denna analys. Mod-
eller syftar pa att uppskatta brandflode som funktion av brandef-
fekt, utvecklad i de studerade rummen. Generalisering av de pa
ovannamnda satt uppskattade brandflodena efter jamforelse av
des sa med brandflodena fran CFAST simuleringarna resulterar i
beskrivning av brandflode som funktion av rumsvolym. Ekva-
tioner erhallna med hjalp av dataprogrammet EXCEL visar bra
overensstammelse och kan anvandas for brandflodesuppskattning
i de studerade byggnadstyperna. Motsvarande brandflode -
rumsvolym kurvor for rumsvolym mellan 30 m 3 och 240 m 3 pre-
senteras i rapporten. Dessa rumsvolymer antas vara de vanligaste
i de studerade byggnaderna. Ett kombinerade brandflode -
rumsvolym diagram till innehallande kurvor ritade enligt bade
beskriven metod och for traditionella al brander presenteras i
rapporten.
Olika databaser i vetenskap och teknologi genomsoktes, veten-
skapliga artiklar har genomlasts samt olika sokprogram i Inter-
net har anvants for att skaffa information om kunskaper
berorande behandling av ventilationssystem vid handelse av en
brand. Dessutom har vetenskapliga och tekniska tidskrifter inom
aktuellt amnesomrade foljts. Ett forsok har ocksa gjorts for att
diskutera problemet med forskare via Network motsvarande
vetenskapliga nyhetsgrupper.
Risk for rokspridning via ventilationskanaler ar uppskattat
med hjalp av datorprogram for godtyckliga flodessystem PFS.
Gransbrandflode, uppskattat med PFS jamforas med maximalt
brandflode enligt brandsimuleringar. Gransfallet for rokspridning
via F -system innebar att franluftsflodet ar noll vid alla rum
raknat uppstroms fran dar brandrummet ansluter. Gransfallet for
rokspridning via TF-system innebar att tilluftsflodet till bran-
drum ar noll. Rokspridningen sker nar dessa tilluftsflode vander
och till alla rum raknat nerstroms fran dar brandrummet ans.:.
luter.
Grundlaggande principer och teoretiska modeller for upp-
skattning av gransbrandflode for tvarums F- och TF-
ventilationssystem (oppet och stangt) presenteras i rapporten.
De mest typiska ventilationssystemen i de undersokta
byggnaderna samt brandcellsindelning i dessa diskuteras.
Foljande typer av ventilationssystem analyseras:
19
Spread of Smoke and Fire Gases via the Ventilation System
-F-system med en fHikt och kanalsystem bestaende av en eller
tva huvudkanaler,
-TF -system med tva fHiktar och kanalsystem med grenar till
varje brandcell,
-TF-system med "noll" -kanal. Detta innebar att tilluft fors
genom tilluftsdon till varje brandcell, medan franluft samlas i
korridor ("noll"-kanal) och sedan fors bort darifran via franlufts-
don med hjalp av franluftsflakt.
Den har undersokningen ar begransad till principiell analys av
risk for rokspridning via ventilationssystem av ovan presenterade
typer med fyra grenar, och till motsvarande analys for roksprid-
ning via "verkliga" forgrenade ventilationssystem med samma
grenar.
Uppskattning av gransfall for rokspridning via ventilationssys-
tem i de studerade typerna av ventilationssystem med fyra
grenar, atgarder mot rokspridning och en kort beskrivning av da-
taprogrammet PFS presenteras i rapporten.
Det finns tva olika satt att beskriva tryckfallsfunktioner forT-
och X-stycken i PFS. Bada satten har provas. Projektet under-
soker en "onormal" flodesriktning iT- och X-stycken, d.v.s. en om-
vand flodesriktning i en av delarna och flodesminskning till noll-
flode i vissa delar av formstycke som foljd. Hur blir
tryckfallsforhallandet i formstycke i det har fallet ar inte kant.
Hogre flode resulterar i hogre hastighet i ventilationskanaler och
hogre Reynoldstal. Okande flodesturbulens resulterar i sin tur i
sakrare satt att beskriva tryck som kvadratisk funktion.
Beskrivning av T- och X-stycken i PFS som kvadratiska funk-
tioner antas dimensionerande i detta sammanhang.
Olika atgarder mot rokspridning via ventilationssystem ana-
lyseras i projektet:
avstangda flakt(ar ),
flakt(ar), som varvas upp till dubbla varvtalet,
tilluftsflakt konverterad till franluftsflakt,
bypass fran tilluft- till franluftkanal,
kombination av ovan presenterade atgarder tillsammans med
normal flakt och med varandra.
Brandflode som overskrider gransfallets £lode fran tidigare be-
rakningar anvands i denna analys. De undersokta fallen omfattar
ej alla mojliga atgarder mot rokspridning via ventilationssystem,
20
Sammanfattning
men den presenterade metoden kan anvandas for uppskattning av
risk for sadan.
''Verkliga" fall analyserar risk for rokspridning via mer kom-
plicerade ventilationssystem typiska for de studerade byggnad-
styperna. Gransbrandflode och gransbrandtryck uppskattas for
olika ventilationssystem. Uppskattningen av gransfallet for rok-
spridning ar berakningstekniskt svart for forgrenade ventila-
tionssystem eftersom ett flode skall vara noll i en av grenar sam-
tidigt som andra flode och tryck ligger langt utover de normala
vardena. Brandflodena for respektive byggnadstyper uppskattade
och presenterade i form av diagram i detta projekt anvands for
undersokning av rokspridningsrisk via ventilationssystem.
"Brander" placeras i olika rum och rokspridning till de narlig-
gande rummen samt olika atgarder mot det fenomenet undersoks.
Uppskattning av giftighet av utspadd rok diskuteras i rappor-
ten. CO-nivan och CO-dosen kan uppskattas uppat med nagra
enkla berakningssteg for ett F -system med avstangd flakt. U pp-
skattningen av
total rokvolym som sprids,
andel av rok som sprids till ett enskilt rum, inklusive andel av
rok till ett utav n rum,
CO-niva i ett enskilt rum presenteras i rapporten. Alla rum an-
tas vara lika stora. CO-niva tillsammans med exponeringstid och
typ av aktivitet bestammer CO-dosen och forgiftningseffekter.
Olika rekommendationer angaende acceptabla och farliga CO-
nivaer och CO-doser diskuteras har. Uppskattning av CO-nivan i
ppm motsvarande IDLH (immediately dangerous to life and
health) begransat till 1500 ppm under 30 min vistelse, som nar ett
av n rum ocksa presenteras.
Uppskattning av medelsiktbarhet av rok ar analog med upp-
skattningen av CO-forgiftningsrisken. Presenterade ekvationer
ger medelvarde for siktbarhet.
Undersokningen ar gjord under forutsattningen att alla de ex-
aminerade flodena, inklusive brandflodena har normala tempera-
turer, d.v.s. "kalla" flodena. Samtidigt ar det valkant att tempera-
turer ar hogre an de normala temperaturerna och simuleringsre-
sultat i denna rapport visar att brandflodestemperaturer kan
overskrida 300°C - 340°C. Detta innebar att forvantad rok-
spridning via ventilationssystem enligt den presenterade ana-
lysen kan skilja sig fran den i verkligheten. Uppskattningen av
21
Spread of Smoke and Fire Gases via the Ventilation System
friktionstryckfall i raka ventilationskanaler visar att detta min-
skar c:a tva ganger samtidigt som lufttemperaturen i K okar tva
ganger. Tryckfall i motstycke ar svarare att uppskatta. Ett over-
slag visar att klarar man det kalla fallet, klarar man aven det
heta fallet. Sa smaningom tack vare rokutspadning och varmefor-
luster i ventilationskanaler, sjunker flodestemperaturerna och de
"kalla" flodena blir dimensionerande.
Ytterligare en metod for uppskattningen av eventuell rok-
spridning via F -system presenteras i rapporten. Den s.k.
"Alexandermetoden" ar en forenklad metod for handberakningar
baserad pa "borthuggningsprincip". "Borthuggningsprincipen" in-
nebar att den del av kanalsystem som kan utsattas for rok-
spridning huggas bort och resten av ventilationssystemet raknas
om med hansyn till de nya tryck/flode forhallandena.
Problemet som undersoks i denna rapport verkar komplicerad
och antaganden, gjorda med viss kunskapsbrist och brist av em-
piriska data, kan inte minska osakerheten av resultat. Resultaten
kan, alltsa, inte tolkas som en slags generelllosning for uteslut-
ning av rokspridning via ventilationssystem, utan skall betraktas
som en hjalp vid analyser inom detta omrade.
22
List of Symbols and Definitions
Symbols
A area, [m2 ]
b width, [m]
c specific heat of incompressible substance, [J/kg K]
c flow coefficient, [-]
d diameter, [m]
D optical density per meter, [m-1]
Ey elastic (Young's) modulus, [N/m2 ]
E energy, [J]
f coefficient of volumetric expansion, [(m3/s)/MWJ
h heat transfer coefficient, [W/m2 K]
l length, [m]
mb mass flow rate, [kg/s]
p pressure, [Pa]
q volume flow rate, [m3/s]
Q heat rate, [kW]
R resistance, [-]
s visibility range, [m]
t time, [s]
T temperature, [°C (K)]
V velocity, [m/s]
V volume, [m 3]
z height, [m]
Re Reynolds number, [-]
M{ mass loss of sample, [g]
23
Spread of Smoke and Fire Gases via the Ventilation System
Greek letters
Definitions
For the purpose of this dissertation, [5] and [6] were used as the
main material to describe research in this domain. Nevertheless,
some other terms has been used in order to express more recent
concepts. The definitions of this dissertation are as follows:
Air leakage:
The uncontrolled flow of air through a component of the building,
or the building envelope itself, when a pressure difference is ap-
plied across the compartment.
Airtighteness:
A general descriptive term for the air permeability resistance of a
building.
Building envelope:
The inside of the exterior surfaces of the building.
Buoyant flow:
A gas flow which is caused directly or indirectly by gravity.
24
List of Symbols and Definitions
Compartment fire:
Fire in enclosed spaces, which are commonly thought as rooms in
a building.
Constrained fire:
The availability of both fuel and oxygen are considered.
Fire flow:
Fire gas flow caused by temperature expansion of the heated gas
in the fire room in the case of fire.
Fire plume:
The generally turbulent buoyant flow, which includes any flames.
Natural ventilation:
Ventilation using only natural driving forces such as differences
in air temperature and density, wind pressure.
Overflash:
The transition from a growing fire to a developed fire in which all
combustible items in the compartment are involved in fire.
Ventilation:
The process of supplying and removing air intentionally by natu-
ral or forced (mechanical) means to and from any space.
Unconstrained fire:
Fuel is burned without regard for oxygen availability.
25
Spread of Smoke and Fire Gases via the Ventilation System
26
Introduction
1 Introduction
1.1 Background
According to the building regulations and codes in Sweden and in
other countries, until recently the only recommended way to pre-
vent the spread of smoke was to install different kinds of dampers
and smoke barriers and to shut down the ventilation system in
the event of fire, or to rely only on shutting down the ventilation
system designed accordingly to given pressure drop relations. The
disadvantage of this second method is that some fire gases will
always spread to adjacent rooms through the ventilation system.
27
Spread of Smoke and Fire Gases via the Ventilation System
The first attempt to analyse the problem was made in 1988 by
Lars Jensen. He presented the results of the analysis in [1]. The
main principles of this analysis will be discussed later in Section
2. Further studies in the field, made by Tobias Hielscher and
Bjorn Warelius, under the supervision of Lars Jensen, resulted in
dissertation [2] in 1992. The next work which expanded the prin-
cipal ideas of the above reports was published in 1993 [3]. In 1994
the Swedish Board of Housing, Building and Planning, Boverket,
published a report on this issue [19]. A handbook which summa-
rised up-to-date experiences on the subject was published in 1996,
[16]. The results and theoretical bases of all these works will be
discussed in Section 2.
- dwelling houses
-hospitals
-offices
-hotels.
The main objective is to assess the relationship between typical
fires in the above types of buildings, the airtightness of the con-
struction and the layout of the ventilation system, and to give rec-
ommendations on good practice to diminish or even eliminate the
risk of smoke spread through ventilation ducts to the adjacent
rooms. In this connection, one of the most important issues to es-
timate are the characteristic parameters/features that are pro-
duced by certain fires, and to assess their influence on the pres-
sure/flow ratio in the ventilation system.
The aim of this study is to clarify the following:
28
Introduction
Studied field
Building services
29
Spread of Smoke and Fire Gases via the Ventilation System
The whole study is divided into two sections, one of which exam-
ines fire behaviour and estimates characteristic parameters in the
chosen types of enclosures, and the other one examines the ability
of the ventilation system to spread smoke and fire gases via ducts.
30
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Behaviour in Single Spaces
31
Spread of Smoke and Fire Gases via the Ventilation System
carding to English statistical sources for death and property dam-
age for each hour of remaining in the burning space in different
types of buildings.
Table 2.1 Risk of death and property damage in case of fire in differ-
ent types of premises [4].
It is seen from Table 2.1 that the most dangerous fires, regarding
both injuries and the risk of death while remaining in the burning
space for a certain time, are those in hotels, but the danger in
other types of buildings cannot be ignored. At the same time it is
much more difficult to evaluate the number of injures than deaths
and to define the type of injury. SRV 1993 reports about 530 in-
jures in 1992.
To evaluate the most probable fire behaviour in the examined
cases, it is important to assess the objects which can cause igni-
tion.
Table 2.2 provides information about the objects which cause fa-
tal fires in dwelling houses.
32
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Behaviour in Single Spaces
Table 2.2 Objects which cause fatal fires in dwelling houses [4].
O~ecl %
Bedclothes 36
Sofa, armchair 14
Clothes (old people, handicapped) 11
Flammable liquid (suicide) 6
Food 3
Building construction 6
(electrical fault, defective fireplace etc.)
Other 4
Cannot be identified 20
As seen from Table 2.2, the most probable objects which cause fa-
tal fires in dwelling houses are bedclothes and sofas. Table 2.3
presents data regarding the probability of fire hazard annually in
different types of buildings.
It is seen from Table 2.3 that the most probable fires are those in
hospitals and the least probable are fires in offices. In order to
predict the fire behaviour in the building, it is significant to assess
the flashover phenomenon. Table 2.4 gives some data on limita-
33
Spread of Smoke and Fire Gases via the Ventilation System
tions of fire hazard to the object in which the fire started and to
the room in which it started.
Table 2.4 Fire behaviour related to the spread of fire from the object
in the room of fire origin and spread of the compartment
fire to another room [4].
As can be seen from Table 2.4, the majority of all fires remain in
the room of fire origin. At the same time, there is the risk of fire
spread to the other objects in the same room.
All the data on the statistical evaluation of fire behaviour in
chosen rooms is taken from [4].
To sum up the statistical data in this part regarding the danger
of fire in the analysed buildings, the most probable fire behaviour
is limited to the room of fire origin, and the most probable objects
where the fire starts are bedclothes and sofas in dwelling houses.
These data are very important in predicting fire behaviour in
buildings, which will be discussed in this section.
34
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Behaviour in Single Spaces
I
I
I
w POST-F LASHOVER
tf)
FLASHOVER
re I
w I
re I
::>
1-
<! I
re
w
I
FULL V-DEVELOPED FIRE I
0.
~
I
'W I
1- I
I
I DECAY
I
I
TIME--+
35
Spread of Smoke and Fire Gases via the Ventilation System
Fully developed fire
Decay.
36
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Behaviour in Single Spaces
In small compartments of the analysed types, real fires can be dif-
ferent from the above case.
Table 2.5 Fire growth parameter and time to reach 1 MW heat re-
lease for different types of idealised fires.
Note that each a value is four times as high as the previous one
and time to reach 1 MW heat release is two times as high as the
previous one.
37
Spread of Smoke and Fire Gases via the Ventilation System
38
Section 1. Analysis of Fire Behaviour in Sing le Spaces
Fire Behaviour in Single Spaces
- in hotels bed [6].
Figures 2.3- 2.7 present fire growth curves for these items.
RHR(kW)
4000
1500
1000
/''--.....'-
500
J ....________________________ .
1800 2400
time (s)
RHR(kvV)
400
200
time (s)
Figure 2.4 Heat release rate I time for burning bed [7].
39
Spread of Smoke and Fire Gases via the Ventilation System
400
300
200
100
time (SI
Figure 2.5 Heat release rate/time for burning hospital bed [9].
RHR
-without sprinklers
---------------------- 'vvith sprinklers
1000
500
tune (s)
Figure 2. 6 Heat release rate I time for burning equipment and furniture
in office [10].
40
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Behaviour in Sing le Spaces
RHR(kW)
2000
1500
1000
500
time (s)
41
Spread of Smoke and Fire Gases via the Ventilation System
decreases the temperature of the plume and, at the same time, in-
creases the volume flow rate. After reaching the ceiling, the plume
spreads out and forms a hot gas layer which descends as gases
continue to flow into it. Hot gases collect at the ceiling and fill the
room from the top. As the hot gas layer descends and reaches
openings in the compartment, hot gas flows out and the ambient
"cool" air flows in through the openings. This description of com-
partment fire is referred to as a two-layer or zone model. This
two-layer model has evolved from observation of such layering in
real-scale fire experiments. While these experiments show some
variation in conditions within the layer, these are small compared
with the differences between the layers. These two-layer models
can thus provide a fairly realistic simulation under most condi-
tions. This model assumes that the predicted parameters such as
temperature, pressure, smoke and gas concentration, and layer
height above the floor, are uniform at any time within this volume
which is referred to as the control volume.
There are different mathematical models based on different as-
sumptions, which describe the two-layer fire model with the help
of differential equations. The detailed analysis of such mathe-
matical models is beyond this study, but it can be interesting to
emphasise that two of them, constructed by Zukoski and McCa-
frey respectively, are used in different computer programs, dis-
cussed further.
Other types of models include field models. These models divide
the room into thousands or even hundreds of thousands of grid
points. Such models can predict the variation in conditions within
layers. They are used when highly detailed calculations are es-
sential.
The main compartment fire phenomenon is illustrated sche-
matically in Figure 2.7.
42
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Behaviour in Single Spaces
r layer
Ceil jet
Plume
Lower layer
43
Spread of Smoke and Fire Gases via the Ventilation System
nology, USA. The program uses the two-layer model described in
Subsection 2.2.4 in order to calculate the distribution of evolving
smoke, fire gases and temperature throughout a building during a
fire. In CFAST, each room is divided into two layers, all parame-
ters in which are assumed to be exactly the same at every point.
Since these layers represent the upper and lower parts of the
room, conditions within the room vary only vertically, from floor
to ceiling, and not horizontally. CFAST is based on solving a set of
equations that predict state variables (pressure, temperature,
heat release, species, etc.) based on the enthalpy and mass flux
over small periods of time. These equations are derived from the
conservation equations for energy, mass and momentum, and the
ideal gas law. The fire model involves an interdisciplinary consid-
eration of physics, chemistry, fluid mechanics and heat transfer.
The model is particularly well suited for predicting parameters
and for studies of changes, both subtle and large, within a single
room. The necessary approximations required by operational
practicality result in the introduction of uncertainties in the re-
sults. The fire plume model description follows McCafrey's plume
model.
Limitations:
- an important limitation of CFAST is the absence of a fire
growth model. The program utilises a user specified fire,
-the two zone model involves a mixture of established theory,
approximations and empirical correlation,
-burning is constrained by the available oxygen. An oxygen co
bustion chemistry scheme is employed only in constrained
(ventilation-controlled) fires. Predictions of concentrations of
chemical products are based on user-specified hydrocarbon r
tios,
-some coefficients, used in the equations, are empirically de
termined values.
The only mechanisms provided in zone models to move enthalpy
and mass into the upper layer of a room are two types of plumes:
those formed by the burning item in the room of fire origin, and
those formed by the jet of upper layer gases escaping through an
opening.
44
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Behaviour in Sing le Spaces
2.3.2 DSLAYV
DSLAYV is a computer program which predicts the conditions
within a single space, resulting from a user-specified fire. The
program uses the two-layer model described in Subsection 2.2.4 in
order to calculate the smoke filling process, temperature through-
out a space during a fire, pressure rise and other parameters. A
steep thermal gradient separates the two layers. For a given fire
size, specified in terms of heat release rate, the conservation
equations of mass and heat are solved for the layers, yielding the
smoke layer height, temperature and the radiant heat conditions
in the room of fire origin as a function of time. The fire plume
model description follows Zukoski's plume model. Only incombus-
tible linings are allowed for in the model. The surfaces enclosing
the lower layer are heated, but the air layer is considered to be at
ambient temperature. DSLAYV is an interactive program. A dia-
logue between the user and the program is governed by com-
mands adapted to the concepts of the user. The program is devel-
oped and written by Bengt Hagglund at the National Swedish De-
fence Research Institute, and is presented in [18].
2.3.3 SMAFS
SMAFS (Smoke Movement and Flame Spread) is a field model
program which is designed to simulate the fluid flow and com-
bustion processes in a general sense, especially those involved in
fire. The program is used at the Department of Fire Safety Engi-
neering, LTH, and simulations are made by guest researcher Yan
Zhenghua, which is gratefully acknowledged.
45
Spread of Smoke and Fire Gases via the Ventilation System
The purpose of developing this package is to have a theoretical
tool to predict turbulent flow and turbulent combustion which are
of great interest to industry and safety design. It includes the fol-
lowing models: turbulence model, combustion model, radiation
model, solid material pyrolysis model, heat transfer wall function,
etc. The limitation is determined by the accuracy and validity of
the incorporated models.
With the support of its pre-processor and post-processor, the
package is quite easy to use. The computer power requirement is
mainly dependent on the complexity of the problem under study.
In this study CFAST was chosen as the basic tool of fire simu-
lation owing to the fact that it is a modern program under con-
stant improving. DSLAYV was used for test fire simulations in
order to control and compare results. Both CFAST and DSLAYV
are zone-model based programs. As the zone-model based pro-
grams predict the average gas parameters in the various regions,
but do not provide information on local conditions which may be
obtained from field model studies, another program, SMAFS, was
used to estimate the danger of flashover effects, and for evaluat-
ing the temperature field near the ventilation terminal. These
simulations and their results will be discussed further.
2.4 Airtighteness
The expansion of gas caused by heat released during the fire in-
creases the pressure in the compartment and drives some gas out
of the room through leakage paths. All openings through which
gas flows out are called vents. If a window is open in the room of
fire origin little flow occurs through the remainder of the building.
When doors and windows are closed and there are no ventilation
openings, flow will move towards cracks and leaks wherever they
may be in the room. All these flows are initially nonbuoyant. As
the fire grows, hot gas flows buoyantly out of the place of origin,
while cold gas flows in below (Figure 2.8). To evaluate gas flux
(mass flow) out of the burning room with the help of the simula-
tion programs, it is essential to know the sizes of such vents.
46
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Behaviour in Single Spaces
Air leakage occurs as a consequence of building design, work-
manship and materials used. The amount of air leakage depends
on the magnitude of the driving forces in combination with the
size and shape of the leakage paths. In the normal case, these
driving forces are pressure differences across the structure, tem-
perature differences between the inside and outside of the struc-
ture and, if there is one, the ventilation system.
For new houses, the standard requirements specified in Swed-
ish Building Regulations, BBR 94, must be followed. According to
BBR 94, air infiltration should not exceed 0.8 lls,m 2 (3 m/h) for
dwellings and 1.6 l/s,m 2 (6 m/h) for other types of buildings at 50
Pa pressure difference. This requirement relates to the area of the
building envelope. The building envelope area is defined as the
area exposed to outside air.
The objective of this evaluation is to summarise knowledge
about the real magnitude of leakage, in relation to the whole
building envelope including interior building constructions, for the
types of enclosures, built at different times, which are described
in Subsection 1.2.
Air leakage, normally divided into external and internal leak-
age, is of interest for this study in terms of average values for the
whole building envelope of rooms or apartments. Tracer gas
measurements and pressurisation measurement, performed in
dwelling houses built in 1988 (Per Levin, [9]) have shown the fol-
lowing results.
Measured internal air leakage between apartments has been
found to account for 12- 33%, and in some cases up to 50%, of the
total air leakage at 50 Pa. Thus, small internal leaks have been
found to exist.
Measured air leakage for the whole apartment has shown good
agreement with the Swedish Building Regulations requirements
for the external building envelope even for a corner apartment.
This study includes several experimentally built energy effi-
cient apartment buildings of extremely good airtightness. The
techniques used for building construction and building services
systems are representative of those used for new Swedish multi-
family buildings.
In different investigations, made both in Sweden and abroad,
the problem of air leakage in single family houses was analysed
47
Spread of Smoke and Fire Gases via the Ventilation System
and air infiltration under different conditions was measured
(Technical Note AIVC [27], Ake Blomsterberg [10]). All these
studies relate to comparatively newly built dwellings of good air-
tightness, and show very good agreement with Code require-
ments.
The analysis described above are not sufficient for this study
which comprises different types of buildings. In particular, there
are no data for older buildings. At the same time, the information
from international scientific documents published abroad cannot
be used as straightforward data, due to Swedish construction
traditions and airtightness requirements which are different from
those in other countries.
As a reasonable assumption in this respect, the air leakage ac-
cording to the Swedish Building Regulations, BBR 94, applied to
the whole buildings envelope, can be accepted as a suitable and
probable value.
48
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Simulations
3 Fire simulations
49
Spread of Smoke and Fire Gases via the Ventilation System
The main purpose of this data was to choose the most typical sizes
of the assumed types of buildings.
50
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Simulations
q=CA~p
/UP (3.1)
51
Spread of Smoke and Fire Gases via the Ventilation System
It is assumed that there is no ventilation system and, therefore,
no influence on the fire progress.
52
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Simulations
Table 3.1 CFAST results in the form of diagrams and table for fire
behaviour in a 4x4x2.4 m hotel room (beginning).
53
Spread of Smoke and Fire Gases via the Ventilation System
Table 3.1 CFAST results in the form of diagrams and table for fire
behaviour in a 4x4x2.4 m hotel room (end).
54
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Simulations
300.0 200.0
0
~
[
--1 u
0.0 '--------'---__L.----'-----'-----' -800.0
0.0 500.0 0.0 500.0
_,1
n= 1 Time (s) n= 1 Time (s)
3000
I r
·a j
0.0
~
0.0 500.0
n= 1 Time (s)
22.0
0.2
f-
-- 1 u 0 --1 u '1- 2
0
..._____
rn
..._____
~ 6
..._____
c
(j)
(.)
(j)
.E
0..
6.0
0.0
0.0 500.0
n= 1 Time (s) 0.0
n= 1 Time (s)
500.0
0.3
-- 1 L 1- 2
1.0
2 L 2- 1
i i
~
~
.E .E
0.0 0.0
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 2 Time (s)
55
Spread of Smoke and Fire Gases via the Ventilation System
As can be seen from Table 3.1, the fire in this specific room can be
analysed in the above chosen terms. Peak temperature of 276°C is
reached 170 s after ignition. Peak heat release rate, 292 kW, is
reached at the same time. The lower limit of oxygen, which is as-
sumed at 12% in CFAST, determines the point below which
burning will not take place. As can be seen, the rate of burning
decreases as the oxygen level drops. Pressure reaches its peak of
136 Pa after 120 s, and causes fire gas and smoke to move
through the leakage paths with a mass flow which reaches its
peak value at the same time, 120 s. As smoke travels away from
the fire, its temperature drops due to heat transfer and dilution.
The upper layer reaches the floor after 150 s, and once the buoy-
ant outward flow exceeds gas expansion due to the fire, the pres-
sure at the floor falls below atmospheric. Outside air thus flows in
at the bottom 180 s after ignition.
As can be seen, in a ventilation controlled compartment fire
which is extinguished due to lack of oxygen, there is a limit to the
heat developed, the temperature rise and the volume of smoke
produced.
56
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Simulations
Table 3.2 Peak pressure, peak heat release rate and peak tempera-
ture, simulated with CFAST for the examined cases.
57
Spread of Smoke and Fire Gases via the Ventilation System
In the table, the peak values for temperature, heat release rate
and pressure are the maximum values obtained in these simula-
tions. These parameters may reach their peaks at different times.
As can be seen in Table 3.2, the temperature in the upper layer
of the majority of examined rooms varies between 150 and 300°C,
which is acceptable. In several cases, in dwellings, offices, and ho-
tels, it exceeds 300°C. Pressure in the majority of the rooms is
relatively low and in dwellings (bed), hospitals and offices it does
not exceed 135 Pa. In dwellings where the sofa is burning, the
pressure is considerably higher- up to 2057 Pa.
As this value seems high enough to be discussed, some assess-
ments have been made in order to predict some more "real" pres-
sures in these rooms. Simulations were made of the same fires as
before in the above rooms, on the assumption that ventilation
terminals were not blocked in addition to leakage paths. The re-
sults have shown considerably lower pressures in dwellings with
sofa-burning fires. The highest value does not exceed 647 Pa, as
against 2057 Pain the model assumed above.
The peak heat release rate shows considerable variation be-
tween 160 and 1569 kW.
(3.2)
58
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Simulations
CFAST defines the limits of integration with neutral planes, i.e.
the height at which flow reversal occurs, and physical boundaries
such as sills. As hot gases from the source compartment leave that
compartment and flow into an adjacent space, a door jet can exist
which is analogous to a normal plume.
Ventilation systems operate with volume flows. The term "flow"
or "fire flow" will be used to mean volume flow. Combination of
two parameters - mass flow and its temperature at a certain time
-determines the magnitude of volume flow. Peak values of flows,
predicted by source simulations, are used later in assessing the
probability of smoke spread in ventilation systems.
59
Spread of Smoke and Fire Gases via the Ventilation System
proximately 500 s after the start of the fire. Before this time,
measured and predicted temperatures are always close. For all
the tests, the time to peak values predicted by the model is on av-
erage within 25 s of experimentally measured values.
Predicted values of the single-room test concentrations of 0 2 are
lower than those measured experimentally (on average 5% low).
For the pressure predicted in the single room with certain leak-
age, agreement can be considered reasonable only for small leak-
age areas. Otherwise, both temperatures and pressures change by
more than a factor of two. For the type of cases examined in the
present study, with relatively small leakage areas, agreement can
be considered reasonable.
For the mass flow through vents in a single-room test, the
simulated values were somewhat underpredicted by the model.
However, owing to the scarcity of experimental data and the
complexity of comparing the numerous variables in a complex fire
model, true validation of the model cannot be made (true valida-
tion of a model would involve proper statistical analysis of a vari-
ety of compared variables). Nevertheless, in view of the lack of ex-
perimental data and the results of the comparison discussed
above, it may be assumed that fire parameters predicted by
CFAST agree quite well with measurements.
60
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Simulations
tain size with the help of DSLAYV, and his results are presented
in [16]. One of the cases from this study was chosen as a reference
case and the similar fire scenario in a similar room under similar
conditions was simulated with the help of SMAFS and CFAST. A
fire scenario for medium fast fire in a 6 x 5 x 2.5 m room was
tested.
The purpose of this comparison was to see how well the magni-
tude of the mass flow predicted by CFAST agrees with those pre-
dicted by the two other programs.
Some parameters predicted by these three programs are shown
in Table 3.3.
61
Spread of Smoke and Fire Gases via the Ventilation System
SMAFS is a field model program which divides the room into
thousands or even hundreds of thousands of grid points, as de-
scribed in Chapter 3. Such models can predict the variation in
conditions within layers. In this case it was used to determine pa-
rameters under the ceiling near the possible ventilation termi-
nals. Results from SMAFS simulations cannot be used directly in
smoke spread assessment, but they can show the trend in such
evaluations, such as:
- the pressure rise in the burning room can be approximately at
least double that predicted by CFAST
- temperatures near ventilation terminals can attain higher
values than those predicted by the two-zone model; it is however
difficult to draw any conclusions regarding flashover effects in
ducts due to lack of data on the subject
- mass and volume flows can exceed values predicted by two-
zone models.
One of the important conclusions in this connection is that it is
reasonable for safety evaluation to prefer higher parameters of
the kind, if possible, to lower ones.
62
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Simulations
during a fire and it assumes that the building envelope is of solid
construction.
The results of simulations should therefore be analysed further
concerning glazing behaviour. There are a lot of parameters which
can play an important role in the assessment of window breakage:
63
Spread of Smoke and Fire Gases via the Ventilation System
-No unequivocal conclusions, with a satisfactory level of uncer-
tainty, can be drawn regarding window breakage for different
window constructions.
- There are no data on window behaviour during a fire as a
function of two parameters, temperature rise and pressure.
- The simulation program "BREAK-1" examines single-pane
window behaviour, which is an unusual construction for real win-
dows in northern climates.
But
- All studies have shown that glass cracks due to thermal stress
if the temperature difference in the glass itself varies between
58°C and 100°C.
- Window glazing breaks at 200-400°C in the burning room.
64
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Simulations
A model is needed to predict the window glass breakage tern-
perature. Such a model has been developed and it is presented in
Subsection 3.5.3.
Physical model
Ts
Tft)
pAc
- total heat transfer for both radiation and convection between fire
and window glass is given by a constant hi (W/m2 K)
- total heat transfer for both radiation and convection between
outside air and window glass is given by a constant ho (W/m2 K)
- infinite heat conduction in window glass between inside and
outside surfaces
- heat conduction from window glass to the frame is described
through area rcrd and assumed distance r I 2
-the window glass temperature is connected to a single heat ca-
pacity
65
Spread of Smoke and Fire Gases via the Ventilation System
C=1C r 2 d pc J/K
Derived model parameters are
Qi =1C r2 hi W/K
W/K
we have
(3.5)
66
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Simulations
In the case of a linearly increasing fire temperature the product
gkT tells how much the glass temperature can be delayed after
the reduced fire temperature.
For the window glass of d=0.004 m, p=2800 kg/m3, c=BOO J!kg,K,
2 2
A=O.Sl W/m,K and assuming that hi=16 W/m K and h =6 W/m K, 0
k, k=T,d constant
Tft)= kt, k=T,d/td linear oc (3.6)
{
kt2, k=T,d!t/ quadratic
Tft),
(°C)
Tfd Constant
Linear
t (min)
Solving (3.4) along with fire temperature functions (3.5) for natu-
ral start condition gives the following expressions
67
Spread of Smoke and Fire Gases via the Ventilation System
Solving the above presented equations for the window glass with
p=2800 kg/m 3, c=800 J/kg K, A=0.81 W/m K and assuming that
temperature rise Tr=300°C in the fire room is achieved at different
times after ignition, t, the values presented in Table 3.4 are ob-
tained for different values of the thickness, d.
Tlr(t), K
td, Constant Linear Quadratic
mini d,mm
3 4 5 6 3 4 5 6 3 4 5 6
2 71 56 46 39 38 29 24 20 25 20 16 14
3 97 78 65 56 53 42 34 29 37 29 24 20
4 118 97 82 71 67 53 44 38 48 37 31 26
5 136 114 97 85 79 64 53 46 57 45 37 32
Table 3.4 shows that as the thickness of glass increases, the tem-
perature differences in the glass itself decrease. Standard window
glass thickness are 3, 4 and 5 mm.
The above presented temperatures can be interpreted as tem-
perature differences, as the start temperature for this case is as-
sumed to be equal to zero. The highest values of temperatures for
the same thickness of glass at the same time interval are observed
for constant fires, and the lowest for quadratic fires.
The most realistic fires are quadratic fires, i.e. Q:::: t 2 •
The temperature rise is less then 60 K for all cases with quadratic
temperature progress. This simple analysis shows that the win-
dows will not crack during first phase of the fire growth.
The radiation absorption length for glass is about 1 mm. This
means that most of the radiation is absorbed close to the entering
68
Section 1. Analysis of Fire Behaviour in Single Spaces
Fire Simulations
surface. The radiation intensity reduces with a factor of e -z for
each mm. This increases the normal temperature difference be-
tween the inside and outside surfaces in case of fire (heavy radia-
tion).
Owing to the lack of knowledge and experimental data, it ap-
pears difficult to make a proper analysis of window breakage
conditions, but it may be assumed for the purpose of this study
that a temperature interval of 200-300°C in the burning room can
be considered a "dangerous" temperature interval. As the goal of
this research is to provide the most reliable parameters (volume
flows) which determine the progress of fire in a space, one more
assumption can be made regarding the peak temperature that oc-
curs in the fire. Although the "dangerous temperatures" for win-
dow breakage should not exceed 300°C, even higher temperatures
can be accepted in the upper layer in the room of fire origin in or-
der to predict the peak volume flow out of the room.
69
Spread of Smoke and Fire Gases via the Ventilation System
70
Section 1. Analysis of Fire Behaviour in Single Spaces
Single Peak Fire Flow Models
Each MW heat release produces f(m 3/s) fire flow to the room
The share of room air volume used by the fire is given by the
factor r. This parameter can also be interpreted as the oxygen
reduction factor.
The fire flow depends directly on the rate of heat release. The
heat released is accumulated as released energy. The released
energy corresponds to the given amount of consumed room air.
The volume of room air limits the fire at a certain time. Thus the
peak fire flow is determined indirectly by the heat release at this
time.
The problem can be solved if the rate of heat release is a simple
function that can be integrated. One example is a tn-function. It is
also found that a heat release function described by linear
segments can be treated. A minor drawback is that the calculation
has to be made segment by segment until a solution is found.
71
Spread of Smoke and Fire Gases via the Ventilation System
t (s)
t (s)
72
Section 1. Analysis of Fire Behaviour in Single Spaces
Single Peak Fire Flow Models
The above schematic process description corresponds to a linear
fire progress. A more detailed and general analysis is presented in
this chapter.
aE(t)=V(t) (4.4)
73
Spread of Smoke and Fire Gases via the Ventilation System
Solving equation (4.6) fort, we have
t=((n + 1) rV I a)) 11 n+l s (4.7)
q(t)=fQ(t) (4.8)
Therefore, if
n=1 q~
Vl/2 a112 m 31s (4.12)
n=2 q~
V 213 al/3 m 31s (4.13)
n=3 q~
v314 al/4 m 31s (4.14)
One remark on the above numbers is that the peak fire flow
increases less than in proportion to the room volume. This means
that a fire in a small room creates a relatively large peak fire flow.
74
Section 1. Analysis of Fire Behaviour in Single Spaces
Single Peak Fire Flow Models
The coefficient of determination, R2 , is equal to 99.3%, and R2
adjusted for degrees of freedom, R 2(adj), is equal to 99.2%.
Equation (4.15) can be rewritten with certain approximation, as
q~ 0.3${i (4.16)
75
Spread of Smoke and Fire Gases via the Ventilation System
76
Section 1. Analysis of Fire Behaviour in Single Spaces
Single Peak Fire Flow Models
Table 4.2 shows that in certain cases peak flows are obtained
when the temperature of the upper hot gas layer is higher then
300°C. Although such temperatures can be dangerous with regard
to window breakage, they are considered acceptable (see
Subsection 3.5).
Note that the values of oxygen in the room at the time
corresponding to maximum flows vary quite a lot even in the same
room, depending on fire placement.
It is seen from Table 4.2 that peak fire flow occurs shortly after
ignition. This period of time varies between 1 and 5 min. One
exception is a fire in a dwelling with a bed as the source of
ignition, where this period can be as long as 7 min 30 sec.
All fire flows presented in Table 4.2 are obtained for closed
spaces with assumed leakage paths at the sill of the closed
doorways. Some other leakage paths were also tested- at the top
of the door and vertically along the sides of the door. Mass flows
through leakage at the sill were larger then those at the other
locations (5-20%) which depends on higher density of air at the sill
of the door. At the same time temperature, pressure, heat release
rate and interface position were insignificantly affected. The
location of fire in the room affects fire progress as burning can be
constrained by the available oxygen. Wall and corner effects
describes with an "image method" in CFAST model, which uses
different coefficients- 1/2 open fire for a wall fire and%, open fire
fore a corner fire.
77
Spread of Smoke and Fire Gases via the Ventilation System
Owing to the complications in the program in determining fire
location according to given fire position co-ordinates, different
cases for the same rooms were tested. For the purpose of
generalisation, fire locations which give cases highest fire flow
values were chosen.
A regression analysis of the flows presented in Table 4.2 for the
studied cases was made with the statistical program Minitab [17].
Owing to the paucity of data and generalisation of the whole
range of predicted flows, the results are poor since there are
different fire models which determine different fire flows.
The results of the analysis for each fire model are set out below.
Table 4.3 shows good agreement (R2 and R2(adj)) between flows
predicted by CFAST and the regression line in the case of fires in
dwellings and fires in hotels. The paucity of data could influence
the results of this analysis.
78
Section 1. Analysis of Fire Behaviour in Single Spaces
Single Peak Fire Flow Models
approximated as tn-fires using two points on the fire curve. The
exponent of interest n is calculated as
4.2.3 Model 2
The heat release rate given as a linear segment function can for
the n-th segment be stated as
Q(t) = Qn-l + kn-1 f w (4.17)
where t is the relative time in the interval (0, tn-tn_1 ) and the slope
kn_ 1 is given by
W/s (4.18)
79
Spread of Smoke and Fire Gases via the Ventilation System
It is possible to calculate when the room air is consumed to the
extent of the factor r. This gives the relation similar to (4. 7) and a
second order equation in t.
(4.19)
-·-·····"·'····'·················i----
4.2.4 Model 3
The two previous models assume that no volume is driven out of
the room during timet.
This subsection presents a model which predicts flows according
to the principle outlined in Subsection 4.2.1. It describes the
studied hazards in terms of atn -fires on the assumption that a
certain volume is driven from the burning room during timet.
80
Section 1. Analysis of Fire Behaviour in Single Spaces
Single Peak Fire Flow Models
We have
rV I (1 + E(t) I CT0 ) =a E( t), and
r V =a E ( t) + a E 2 ( t) I CTa ,
By solving the last equation for E(t) and substituting it in the
equation for Q and q (algorithm 1, Subsection 4.2.2), the
corresponding flow can be calculated.
Flows predicted with the help of this method depend on the
value of C. The major problem in this method is to evaluate C.
Due to the complexity of the problem, method 3 was not chosen
as a working method.
81
Spread of Smoke and Fire Gases via the Ventilation System
82
Section 1. Analysis of Fire Behaviour in Single Spaces
Single Peak Fire Flow Models
No Type of V, q qp q 2' f, q2
building ma CFAST, m /s 3 3 3
m /s (m /s)/ (edited),
m 3/s MW m 3/s
18 31.5 * 0.20 0.23 0.23 1.10 0.23
19 31.5 * 0.22 0.23 0.23 1.80 0.23
20 31.5 * 0.20 0.23 0.23 1.30 0.23
21 45.0 * 0.23 0.27 0.26 1.00 0.26
22 Office 45.0 * 0.28 0.27 0.26 1.80 0.34
23 75.0 * 0.25 0.34 0.30 1.00 0.30
24 75.0 * 0.32 0.34 0.30 1.73 0.41
25 120.0 0.33 0.42 0.42 1.43 0.42
26 38.4 0.31 0.46 0.41 1.50 0.41
27 Hotel 57.6 0.52 0.65 0.56 1.30 0.56
28 84.0 0.74 0.90 0.73 1.70 0.84
29 224.0 1.45 2.06 1.29 1.61 1.58
*-Hazards with different placement of burning items.
83
Spread of Smoke and Fire Gases via the Ventilation System
Q(W)
Real fire
Error field
t (s)
84
Section 1. Analysis of Fire Behaviour in Single Spaces
Single Peak Fire Flow Models
85
Spread of Smoke and Fire Gases via the Ventilation System
2.5
y = 1.4922Ln(x) - 5.380
2
R =1
2
1.5
0.5
0
0 50 100 150 200
2.5
2 - y =0.1902Ln(x)- 0.5021-
R2=0.9946 I
1.5
y =0.0022x + 0.0915
2
R =0.9821
L__----~---------
0.5
o+--------+--------,_--------r--------+------~
V(m)
Figure 4.9 Predicted flows (rhombus) and trend lines for dwelling
houses.
86
Section 1. Analysis of Fire Behaviour in Single Spaces
Single Peak Fire Flow Models
Hospitals
3
o (m /s)
0.6
0.5
0.4
0.3
0.2
0.1
0
0 50 100 150 200
Figure 4.10 Predicted flows (rhombus) and trend line for hospitals.
Offices
3
q (m /s)
0.6
0.5
0.4
0.3
0.2
0.1
0
0 50 100 150 200 250
V(ml
Figure 4.11 Predicted flows (rhombus) and trend lines for offices.
87
Spread of Smoke and Fire Gases via the Ventilation System
Hotels
1.8 , - - - - - - - - - - - - - - - - - - - - - - - - - - ,
1.6
0 7677
y = 0.0256x '
2
1.4 R = 0.9898
1.2
0.8
0.2
0+----~----+----r-----+---~
Figure 4.12 Predicted flows (rhombus) and trend lines for hotels.
88
Section 1. Analysis of Fire Behaviour in Single Spaces
Single Peak Fire Flow Models
is the most dangerous case that is of interest for flow assessment,
only the case with a sofa as the burning item will be presented
below for fires in dwellings.
Flow obtained for a 100m3 hospital room according to Table 4. 6
agrees with that presented in [34].
As the equations presented in Table 4.6 show sufficient
agreement with predicted flows, they can be applied to
corresponding types of buildings of different sizes, i.e. they can be
used for generalisation of the results obtained. Characteristic flow
curves for the chosen buildings are presented in Figure 4.13.
Space volume varies from 30 m 3 to 240 m 3 . These volumes are
assumed to be those most usual for the described types of
buildings. Flows in spaces smaller then 30 m 3 can be assumed to
be equal to those for rooms of 30 m 3 .
Flows
-+-Dwelling houses
~Hospitals
.......,._Offices
V(m)
89
Spread of Smoke and Fire Gases via the Ventilation System
Curves of (4.18) for different al - fires, simulated with the
computer program DSLAYV, are plotted in the figure below.
2
Flows (<X{: -fires)
3
q (m/s)
2.5
2
-::K- q 1,medium
1.5 ........_ q2, fast
--+- q3 ultrafas
0.5
0
0 50 100 150 200 250
3
V(m)
2
Figure 4.14 Flows for different at - fires according to the equation
(4.18).
Curves in the above figures are all plotted in the figure below for
purposes of comparison.
90
Section 1. Analysis of Fire Behaviour in Single Spaces
Single Peak Fire Flow Models
~Offices
hotel
-*-- q 1,medium
---q2, fast
V(ml
Figure 4.15 Flows according to the equations in Table 4.3 and equation
(4.18).
Figure 4.15 shows that flows obtained for offices agree very well
with those predicted for the medium fast al - fires. Flows
obtained for hospitals correspond to values between those
predicted for medium and fast al -fires over the whole range of
3
volumes. Flows obtained for hotels up to approximately 100 m
are insignificant lower than those predicted for fast al - fires,
3
while flows in hotels larger than 100 m correspond to values
2
between those predicted for fast and ultrafast at - fires.
3
Flows obtained for dwellings up to approximately 100 m are
2
lower than those predicted for ultrafast at - fires. In contrast,
3
flows in dwellings larger than 100 m have higher values than
2
those predicted for ultrafast at - fires.
91
Spread of Smoke and Fire Gases via the Ventilation System
windows in the building envelope will be broken, as the
temperatures which develop in the hot gas layer during the
examined fires of one - four minutes' length can exceed the
temperature level which is dangerous for glass breakage. This
means that fire flow generation process which is of interest for
this particular study can be limited so far to the above presented
cases.
92
Section 2. Operation of Ventilation Systems during Fires
Study of Literature
Section 2. Operation of
ventilation systems
during fires
93
Spread of Smoke and Fire Gases via the Ventilation System
5.1 Databases
All in all seven major databases were searched through twice with
a one year interval. These databases are as follows:
-IBSEDEX, which covers all aspects of building serv-
ices world-wide, published since 1960. It includes information on
technical books, reports, conference papers, journal articles and
standards,
-ICONDA, which covers the world-wide literature on
all fields of building construction and design, energy conservation,
civil and structural engineering, architecture and town planning,
published since 1976. Sources of information are technical books,
conference papers and journal articles,
-COMPENDEX, which is a comprehensive interdis-
ciplinary engineering database, covering different areas of engi-
neering, civil, energy, mechanical, environmental, etc. Sources of
information are technical reports, conference papers and proceed-
ings, published since 1970,
-BRIX-FLAIR, which covers technical information
published since 1960,
-TRADE and INDUSTRY Database, which covers
technical information for industrial needs published since 1976,
-CORDIS, which includes nine different databases,
provides information on all aspects of EU R&D activities includ-
ing current calls for proposals and tenders, events, publications
and activities in preparation. Publications contain abstracts and
bibliographic information on publications, reports and scientific
papers arising from EU research activities as well as other scien-
94
Section 2. Operation of Ventilation Systems during Fires
Study of Literature
tific and technical documents in the fields of the environment, en-
ergy and information sciences,
- AIRBASE, which is the Bibliographic Database of
the International Energy Agency's Air Infiltration and Ventilation
Centre. It contains abstracts of articles and publications relating
to energy efficient ventilation and includes topics on ventilation
strategies, design and retrofit methods, calculation techniques,
standards and regulations, measurement methods, indoor air
quality and energy implications. Entries are based on articles and
reports published in journals, internal publications and research
reports.
The information search showed that there are few articles on
this issue. Some of these are comparatively old, from the 60s and
early 70s, which makes them nearly unobtainable. The author
was unsuccessful in getting information on corresponding re-
search with regard to the operation of ventilation systems during
a fire or, at least, in discussing its possibilities.
95
Spread of Smoke and Fire Gases via the Ventilation System
96
Section 2. Operation of Ventilation Systems during Fires
Theoretical Methods
6 Theoretical methods
6.1 Background
The main principles of running ordinary ventilation systems dur-
ing compartment fires were formulated in [1], [2], and [3]. The
principal points in these reports are as follows ..
Whether or not smoke spread will occur is determined by the
energy released by the fire, the airtighteness of buildings and the
layout of the ventilation system. There are three main types of
ventilation systems: exhaust, supply and exhaust, and natural
ventilation. If a natural ventilation system serves each separate
room with a separate duct, smoke spread will never occur unless
the duct itself leaks. In both exhaust and supply-exhaust me-
chanical ventilation systems, on the contrary, spread of smoke via
ducts is always possible as a certain number of rooms are con-
nected by those ducts.
Assuming that air in the burning room is heated from Tr toTe,
at every point in the room during a fuel controlled fire, the air
volume V will increase by
(~!If -l)V (6.1)
97
Spread of Smoke and Fire Gases via the Ventilation System
98
Section 2. Operation of Ventilation Systems during Fires
Theoretical Methods
qi flow in a component i
Ri resistance (turbulent) of a component i
(6.3)
For a flow junction, the sum of all inlet and outlet flows is equal to
zero, which gives
0= L junction qi (6.6)
For an arbitrary loop duct, the sum of all pressure looses in the
loop is always equal to zero, which gives
O=Lzoop Pi (6.7)
99
Spread of Smoke and Fire Gases via the Ventilation System
The layout of an exhaust ventilation system for two rooms and its
model are presented in Figure 6.1.
p=O
q 1- q
ROOM A ROOM B
p=-b
p= -a
p='-1
p=O
Figure 6.1 Layout of exhaust ventilation system for two rooms and its
model [3].
In the following analysis further assumptions were made:
(6.8)
100
Section 2. Operation of Ventilation Systems during Fires
Theoretical Methods
R 2 = (a-b) I (1- q) 2 (6.9)
(6.10)
(6.11)
(6.12)
Pb=R1q~ (6.14)
Pb =R3q; (6.15)
This gives
q~ =1 I (1- a) (6.16)
101
Spread of Smoke and Fire Gases via the Ventilation System
q1 I q k =(a I b- 1) o.s
If the pressure drop in the main duct is high, the danger of smoke
spread is significant. A relatively little fire flow can be enough to
cause spread of smoke and fire gases to the other room.
102
Section 2. Operation of Ventilation Systems during Fires
Theoretical Methods
p=O
p=a
p=b
ROOM A ROOM B
p=O
P= -c
P= -d
p=O
Figure 6.2 Layout of an exhaust and supply ventilation system for two
rooms without air leakage and its model [3].
103
Spread of Smoke and Fire Gases via the Ventilation System
R2 = (1- q) 2 I b (6.21)
2
R5 =q I c (6.22)
R6 = (1 - q) 2 I c (6.23)
R8 =1 I (d- c) (6.25)
In case of fire with fire flow q b in room A, smoke spread will occur
if the inlet flow q 1 is equal to 0 (zero). The boundary condition for
smoke spread from the burning room A, assuming that the pres-
sure drop in terminals does not change, gives
(6.26)
Using the subscripts i for supply air, o for exhaust air and n for
ordinary operation, the last equation can be rewritten as
qb = (Ri I Ro + 1)o.s qn (6.27)
IfR. =R
l 0
(6.28)
104
Section 2. Operation of Ventilation Systems during Fires
Theoretical Methods
In this case two fans can be interpreted as only one fan, because
both the duct network and the building are closed systems.
Switched off the exhaust fan affects the evaluated fire flow and
pressure for boundary case as d=O in Figure 6.2.
Switched off the supply fan will cause spread of smoke which
does not depend on the pressure in the fire room, because an out-
door air terminal is closed. The exhaust fan will have no effect in
this case if the inlet terminal is tight.
The proportion of smoke, k, which spreads to the other room is
k=f I (1+ f) (6.30)
where
(6.31)
If both fans are switched off, this would also result in smoke
spread, which is similar to the previous case.
The smoke goes the normal way through R 5 and the non desired
"wrong" way through R 1, R 2, the other way, and R6'
If equal flows goes both ways, q 1=q 2 =q I 2, then
R 1=R 5=R2 =R 6 , and
f= 11-../3,
k = 1 1( -../3 + 1) = 0.366
If only one out of ten ordinary flows goes non desired way (from
a small room to a big one), then
R 1=R5 and R 2=R 6 ,
R1 q; =R q; 9
2
2
and R 5 q; =R q; 9
6
2
R2 =R 6 = R1 I 81 = R5 I 81
According to (6.30), (6.31)
f=(RIR (1+1181+1181)) 0 ·5 ~1 andkz0.5
Conclusion: 50% smoke goes the non desired way to the rest of the
building or rooms.
105
Spread of Smoke and Fire Gases via the Ventilation System
If nine out of ten ordinary flows go the non desired way (from a
large room to a small one), then
R 1=R5 andR2 =R 6 ,
R 1 qn2 92
=R 2 qn2 an d R5 qn2 92
=R 6 qn2
R2 =R 6 = R1 I 81 = R5 I 81
According to (6.30), (6.31)
f =(RI 81R (1 I 81 + 1 + 1)
05
' ;::: 0.79 and k ;:::0.07
Conclusion: 7% smoke goes the non desired way to the rest of the
building or rooms.
106
Section 2. Operation of Ventilation Systems during Fires
Theoretical Methods
Figure 6.3 Layout of exhaust and supply ventilation system for two
rooms with air leakage, and its model.
(6.33)
107
Spread of Smoke and Fire Gases via the Ventilation System
(6.34)
(6.35)
108
Section 2. Operation of Ventilation Systems during Fires
Design of Ventilation Systems
7 Design of ventilation
systems
Table 7.1 Evaluating of the risk of smoke spread in buildings via the
ventilation systems duct network.
109
Spread of Smoke and Fire Gases via the Ventilation System
As this project is focused on certain types of buildings, the most
typical ventilation systems used in them will be discussed later
on.
One of the most typical ventilation systems in residential
buildings is an exhaust ventilation system with one exhaust fan
and a distribution system consisting of one or two main ducts with
branches to each flat. Another type of ventilation system, supply-
exhaust ventilation system, with supply and exhaust fans and dis-
tribution ductwork to each flat is also used in dwellings.
In both types of ventilation systems plenums can be both vertical
and horizontal.
Hospitals are usually ventilated by supply-exhaust ventilation
systems with branches connected to the dampers in each hospital
section.
Offices can be ventilated in different ways with the help of or-
dinary supply-exhaust ventilation systems with dampers in each
of the departments or rooms. "Zero"-ducts can be also used in such
buildings. This means that supply air is distributed via terminals
direct to office rooms, while exhaust air collects in corridors
("zero"-ducts) and is removed via exhaust terminals by the ex-
haust ventilation system.
Hotels are usually ventilated by supply-exhaust ventilation sys-
tems with branches connected to the dampers in each hotel room
or each hotel suite.
110
Section 2. Operation of Ventilation Systems during Fires
Design of Ventilation Systems
compartmentation, for the purpose of the present study - on fire
compartmentation.
According to Swedish Building Codes [8] and Quality assurance
requirements [20] a fire compartment is defined as a room or a
group of rooms, in which activity has no direct connection with the
activities in the rest of the building.
-In dwellings it embraces each self-contained flat.
-In hospitals it comprises each ward.
-In offices it comprises all rooms in each office.
-In hotels it comprises each hotel room or hotel suite.
Since the layout of the ventilation system generally conforms to
the layout of compartments, the risk of the spread of smoke to
adjacent fire compartments via ducts connecting different fire
compartments will be discussed with reference to fire compart-
mentation.
The problem of smoke spread within a fire compartment can
also be analysed in certain cases. In such cases the problem will
be confined to the evaluation of the risk of smoke spread to adja-
cent rooms, instead of to adjacent fire compartments.
In this study the risk of smoke spread via ducts to adjacent fire
compartments will be evaluated.
111
Spread of Smoke and Fire Gases via the Ventilation System
112
Section 2. Operation of Ventilation Systems during Fires
Models and Tools
113
Spread of Smoke and Fire Gases via the Ventilation System
114
Section 2. Operation of Ventilation Systems during Fires
Models and Tools
115
Spread of Smoke and Fire Gases via the Ventilation System
Some of the usually occurring PFS elements and symbols are as
follows:
"+" define flow direction downwards and to the right as
positive
"" define flow direction upwards and to the left as
negative
h?O printout pressure
h?200 describes a fire with a flow of 200 lis, downwards or
to the right, and prints out pressure
h?-200 describes flow of 200 lis, upwards or to the left, and
prints out pressure
h,100:q describes pressure of 100 Pa and prints out flow
h?:q describes boundary case conditions and prints out
pressure and flow in a room
q,O describes boundary case's zero flow
s,value describes some initial flow for calculation, which
facilitates convergence
FF:hq< describes a fan with flow direction upwards and to
the left, and prints out pressure and flow produced by
this fan
FF:hq> describes a fan with a flow direction downwards and
to the right, and prints out pressure and flow
produced by this fan
t,10,50:q describes an unit with quadratic pressure loss of 10
Pa at flow of 50 1/s and prints out flow
d,200,6 describes 6 m long ventilation duct of 200 mm
diameter
UD notation for outdoor air intake
TD notation for transfer air device.
Calculations were made for the fan with the following character-
istics.
There are four rooms with 50 lis air flow in each. Air leakage of 50
1/s at 50 Pa pressure difference is assumed in this case.
PFS provides the opportunity to describe resistance properties of
wyes and junctions in two different ways: as a quadratic function
116
Section 2. Operation of Ventilation Systems during Fires
Models and Tools
and with the help of empirical equations. This is ruled by the con-
trol operator con=1 and con=2 respectively. Both types were
tested.
Table 8.1 Flows and pressure for boundary cases in rooms of fire ori-
gin for the examined exhaust ventilation system.
As Table 8.1 shows, flows and pressures for boundary cases differ
significantly from one fire room to another. This generally de-
pends on the resistance properties of wyes and the resulting pres.,.
sure drop in these. As calculated in Subsection 6.1.3, the expected
flows and pressures for boundary cases are considerably higher
than in the normal (ordinary) case. Boundary flows and pressure
drops predicted with con=1 are higher then those for con=2, ex-
cept for fire case in room 1. According to Table 8.2 flow values
show sufficient agreement with theoretically predicted qb. The
deviation is due to the resistance properties of wyes and the re-
sulting pressure drop in these.
117
Spread of Smoke and Fire Gases via the Ventilation System
begin
flow 1/s
pressure Pa
control bend=1 con=1 duct=1 i tmax=99 table=12 dxs=25
set UD=t,10,50:q 160=d,160 200=d,200
fan FF 100:0 100:200 0:800
160, 6 160, 6 200,6 200,6 FF:hq
s,200
160,3 160, 3 160,3 160,3
h?-50 h?-50 h?-50 h?-50
h?O
h?:q
h?O
h?O
h?O
end
118
Section 2. Operation of Ventilation Systems during Fires
Models and Tools
begin
flow 1/s
pressure Pa
control bend=1 con=1 duct=1 itmax=99 table=12 dxs=25
set UD=t,10,50:q 160=d,160 200=d,200
fan FF 100:0 100:200 0:800
160, 6 160,6 200,6 200,6 FF:hq
s,200 h:100.00
160, 3 160, 3 160,3 160,3 q:200.00
h?-50
h=85.062
h?O
h=-10.00
h=1551. 0
q:948.64
h?O
h= 0.000
h?O
h= 0.000
h?O
h= 0.000
119
Spread of Smoke and Fire Gases via the Ventilation System
Table 8.2 Flows and pressures for boundary cases in rooms of fire
origin for the examined closed supply-exhaust ventilation
system.
As Table 8.2 shows, boundary values for both flows and pressures
are considerably lower than those in the case with exhaust venti-
lation, and the difference between con=l and con=2 cases is in-
significant. As calculated in Subsection 6.1.4, the expected flow for
the boundary case is qb =~2 qn, which in the present case is 71
lis. According to Table 8.2, the difference between flows and pres-
sures for the boundary cases is insignificant from one fire room to
another, and flow values show sufficient agreement with the theo-
retically predicted qb. The deviation is due to the resistance prop-
erties ofwyes and the resulting pressure drop in these.
120
Section 2. Operation of Ventilation Systems during Fires
Models and Tools
begin
flow l/s
pressure Pa
control bend=1 con=1 duct=1 itmax=20
set 160=d,160 200=d,200
fan FF 100:0 100:200 0:800
160, 6 160, 6 200,6 200,6 FF:hq<
F:hq>
h?O
F:hq>
o, 3
h?O
s, 50
t,38.1,50:q t,SS.O,SO:q t,69.5,50:q t,95.1,50:q
160,3 160,3 160,3 160,3
F:hq>
end
Figure 8.4 PFS-layout of closed supply-exhaust ventilation system for
four rooms.
121
Spread of Smoke and Fire Gases via the Ventilation System
F:hq>
h:99.201
q:217.62
end block 1 problems 5 elements 257
Figure 8.5 PFS-result of closed supply-exhaust ventilation system for
four rooms.
122
Section 2. Operation of Ventilation Systems during Fires
Models and Tools
Table 8.3 Flows and pressures for boundary cases in rooms of fire
origin for the examined open supply-exhaust ventilation
system.
As Table 8.3 shows, the boundary values for both flows and pres-
sures are considerably lower than those in the case with exhaust
ventilation, but higher than those in the case with a closed sup-
ply-exhaust ventilation system, and the difference between con=1
and con=2 cases is insignificant. As calculated in Subsection 6.1.4,
the expected flow for the boundary case follows (6.37) and the fire
flow varies between --.12 and (--.12+--.110) of ordinary air flow. Fire flow
in the present case should vary between 71l/s and 229l/s. Accord-
ing to Table 8.2, the difference between flows and pressures for
boundary cases is insignificant from one fire room to another and
flow values show sufficient agreement with theoretically predicted
123
Spread of Smoke and Fire Gases via the Ventilation System
qb. The deviation is due to the resistance properties of wyes and
the resulting pressure drop in these.
Boundary fire flows, leakage flows and duct flows for resistance
of wyes as a quadratic function, con= 1, are shown in more detail
in Table 8.4.
Table 8.4 Fire flows, leakage flows and duct flows for boundary cases
in rooms of fire origin for the examined open supply-
exhaust ventilation system.
Table 8.4 shows, that flows in the duct in this case agree with
those presented in Table 8.2 for the closed supply-exhaust venti-
lation system. Leakage flow can be evaluated with the help of
(6.35).
124
Section 2. Operation of Ventilation Systems during Fires
Models and Tools
begin
flow 1/s
pressure Pa
control bend=l con=1 duct=1 itmax=20
set leak=t,50,50:q 160=d,160 200=d,200
fan FF 100:0 100:200 0:800
160,6 160, 6 200,6 200,6 FF:hq<
s,200
160,3 160,3 160,3 160, 3
q,O t,50.2,50:q t,63.3,50:q t, 63. 8, 50:q
h?:q
leak
F:hq>
leak
F:hq>
leak
leak
F:hq>
end
Figure 8.6 PFS-layout of open supply-exhaust ventilation system for
four rooms.
125
Spread of Smoke and Fire Gases via the Ventilation System
begin
flow 1/s
pressure Pa
control bend=1 con=1 duct=1 itmax=20
set 1eak=t,50,50:q 160=d,160 200=d,200
fan FF 100:0 100:200 0:800
126
Section 2. Operation of Ventilation Systems during Fires
Models and Tools
Table 8.5 Flows and pressures for boundary cases in rooms of fire
origin for the examined open supply-exhaust ventilation
system with a "zero" duct.
127
Spread of Smoke and Fire Gases via the Ventilation System
and in this case qbk:=::115 1/s. For leakage paths in the case of fire
yields
=50( 80)0.5
q bf 50
and in this case qbr:=::65 1/s. Total expected boundary fire flow is 180
1/s. This agrees very good with the presented results (Table 8.5).
Note, that in the open supply - exhaust ventilation with a
"zero" -duct smoke spreads via exhaust ducts and collects in the
corridor.
128
Section 2. Operation of Ventilation Systems during Fires
Models and Tools
begin
flow 1/s
pressure Pa
control bend=1 con=1 duct=1 itmax=99 dxs=20
set 160=d,160 200=d,200 TD=t,15,50:q leak=t,50,50:q
fan FF 100:0 100:200 0:800
h?:q
t,70.4,200 FF:hq>
00, 6 s,200
h?O
t,70.4,200 FF:hq>
00,6 s,200
h?O
t,70.4,200 FF:hq>
00,6 s, 200
h?O
FF:hq>
00,6 s,200
end
129
130
Section 2. Operation of Ventilation Systems during Fires
Models and Tools
131
Spread of Smoke and Fire Gases via the Ventilation System
132
Section 2. Operation of Ventilation Systems during Fires
Models and Tools
133
Spread of Smoke and Fire Gases via the Ventilation System
Case 2.
In case of fire, usual fans can be used in an unusual way. This
case examines fans with the rotational speed doubled (FF,2). The
fans produce increased flows and pressures, and there is no smoke
spread at all via ducts.
Case 3.
This case studies the behaviour of the systems with both fans
shut down (natural ventilation). It shows total spread of smoke to
all rooms through all branches.
Case 4.
This case examines the behaviour of the whole system, with the
supply fan shut down and the exhaust fan in operation. The calcu-
lation shows that smoke spreads to all three rooms via supply
ducts.
Case 5.
This case studies the behaviour of the systems with the supply
fan shut down and the supply plenum connected to the exhaust
plenum and to the exhaust fan. The result is no smoke spread at
all and insignificant underpressure, 40-52 Pa, in three "clear"
rooms.
Case 6.
This case studies the behaviour of the systems with the supply fan
shut down and the supply plenum connected to the exhaust ple-
num, combined with doubling the rotational speed of the exhaust
fan. The result is no smoke spread at all and significant under-
pressure, up to 228 Pa, in three "clear" rooms. The last observa-
tion can be decisive in choosing this measure since the underpres-
sure, converted into door opening force, should never exceed 130
N.
Case 7.
This case examines the theoretical possibility of converting the
supply fan into an exhaust fan. The calculation shows that there
is no spread of smoke via the ventilation system, but underpres-
sure of up to 72.5 Pa can occur in rooms. This case can be com-
bined with increasing n times the rotational speed of one or both
fans, which will result in lower pressure in the rooms.
A very rough estimate of smoke spread can be made with the
help of flow direction and PFS layout, which are shown in Figures
8.9 and 8.12.
134
Section 2. Operation of Ventilation Systems during Fires
Models and Tools
135
Spread of Smoke and Fire Gases via the Ventilation System
begin
flow 1/s
pressure Pa
control bend=1 con=1 duct=1 itmax=20
set leak=t,SO,SO:q 160=d,160 200=d,200
fan FF 1 0 0 : 0 1 0 0 : 2 0 0 0 : 8 0 0
leak
leak
F, 2 :hq>
leak
leak
136
Section 2. Operation ofVentilation Systems during Fires
Models and Tools
137
Spread of Smoke and Fire Gases via the Ventilation System
begin
flow 1/s
pressure Pa
control bend=l con=l duct=l itmax=20
set
fan ~~aki8 6 ~g.s~b3: 2 ~go=g;~gg 200=d,200
Figure 8.9 PFS-layout and flow direction for open supply-exhaust ven-
tilation system for four rooms with 200 lIs flow in the fire
room and four cases 1-4. "+" shows flow direction down-
wards and to the right, while"-" shows flow direction up-
wards and to the left. "0" corresponds to no flow.
138
Section 2. Operation of Ventilation Systems during Fires
Models and Tools
begin
flow 1/s
pressure Pa
control bend=1 con=1 duct=1 itmax=20
set leak=t,SO,SO:q 160=d,160 200=d,200
fan FF 1 0 0 : 0 10 0 : 2 0 0 0 : 8 0 0
leak
leak
leak
F:hq>
end
139
Spread of Smoke and Fire Gases via the Ventilation System
begin
flow 1/s
pressure Pa
control bend=1 con=1 duct=1 itmax=20
set leak=t,50,50:q 160=d,160 200=d,200
fan FF 100:0 100:200 0:800
140
Section 2. Operation of Ventilation Systems during Fires
Models and Tools
begin
flow 1/s
pressure Pa
control bend=1 con=1 duct=1 itmax=20
set leak=t,50,50:q 160=d,160 200=d,200
fan FF 100:0 100:200 0:800
L+ L+ L+ L+ +
+ + + + +
+t,38.1,50:q +t,55.0,50:q +t,69.5,50:q +t,95.1,50:q +
+ + + + +
+160,3 +160,3 +160,3 +160,3 +
+ + + + s,200 +200,1
lb+++++++++++++£+++++++++++++£+++++++++++++£+++++++++++++£+++
160,6 160,6 200,6 200,6 FF:hq>
end
Figure 8.12 PFS-layout and flow direction for open supply-exhaust ven-
tilation system for four rooms with 200 lIs flow in the fire
room and four cases 5, 6 and 7. "+" shows flow direction
downwards and to the right, while"-" shows flow direction
upwards and to the left. "0" corresponds to no flow.
141
Spread of Smoke and Fire Gases via the Ventilation System
142
Section 2. Operation of Ventilation Systems during Fires
"Real Case" Study
143
Spread of Smoke and Fire Gases via the Ventilation System
Exhaust branches from each space can also pass vertically
through the building and connect to the plenum just before the
fan.
These types of exhaust ventilation systems can be combined with
supply ventilation system with a similar duct layout.
The design of ventilation systems in hospitals is much more
complicated than in other types of buildings because of the variety
of services they provide. Mechanical ventilation systems in hospi-
tals are usually of the supply-exhaust type. Each ward is sup-
plied with air through one or several terminals, and air is ex-
hausted via terminals in lavatories and wash rooms. In some
wards, operating theatres, delivery rooms, labour rooms and
nurseries, both supply and exhaust systems can deliver and ex-
haust air directly from the room served.
Accommodation in hotels and motels is usually in the form of
single rooms with toilet and bathroom adjacent to a corridor,
flanked on both sides by other guest rooms. Mechanical ventila-
tion systems in hotels are usually of the supply-exhaust type.
Each hotel room or each suite is supplied with air through one or
more terminals, and air is exhausted via terminals in lavatories
and bathrooms.
The variety of functions and range of design criteria applicable
to office buildings have allowed the use of almost every available
ventilation system. While multi-storey structures are discussed
here, the principles are similar for all sizes of office buildings. Me-
chanical ventilation systems in offices are usually of the supply-
exhaust type described before. Another type of ventilation system
which can also be used in offices is the "zero duct" ventilation sys-
tem in which the corridor, the "zero duct", collects vitiated air
through transfer air devices from all rooms in the office and trans-
fers it to the exhaust plenum in the ceiling through terminals.
Some of the above systems will be analysed further in Chapter
10 in connection with the danger of CO poisoning when smoke
spreads to adjacent spaces.
144
Section 2. Operation of Ventilation Systems during Fires
"Real Case" Study
10 l/s air flow from a kitchen, high sped extraction rate min
75% of extraction capacity
15 l/s air flow from a pantry
10 l/s air flow from a bathroom with openable window (if
area exceeds 5m2 , required air flow increases by
1 l/s, m 2 )
15 l/s air flow from a bathroom without window (if area
exceeds 5m2 , required air flow increases by
1 l/s,m2 )
10 l/s air flow from a toilet
145
Spread of Smoke and Fire Gases via the Ventilation System
146
Section 2. Operation of Ventilation Systems during Fires
"Real Case" Study
plenum 1
"" plenum2
Figure 9.1 Layout of exhaust ventilation system for four floors and ten
rooms on each floor.
The layout of the exhaust ventilation system with the total air
flow of 1200 1/s at 107 Pa pressure, which exhausts via two verti-
cal plenums from four floors, and further via branches from ten
rooms on each floor, is presented in Figure 9.2. The exhaust fan
has the following characteristics:
147
Spread of Smoke and Fire Gases via the Ventilation System
begin
flow 1/s
pressure Pa
control bend=1 con=1 duct=1 itmax=99 table=3
set UD=t,10,30
fan FF 100:200 125:750 75:1500
s,150
s,150
s,150
s,150
148
Section 2. Operation of Ventilation Systems during Fires
"Real Case" Study
d,160,4 '160, 4 d,200,4 d, 200,4 d, 250,4
s,150
d,160,3 d,160,3 d,160,3 d,160,3 d,160,3
t,50.7,30 t,56.5,30 t,60.5,30 t,68.9,30 t,71.3,30
d,400,4:hq d,400,4:hq
FF:hq<
s,-1200 ,630,8 d,400,8
end
149
Spread of Smoke and Fire Gases via the Ventilation System
begin
flow 1/s
pressure Pa
control bend=l con=l duct=l itmax=99 table=3
set UD=t,10,30
fan FF 100:200 125:750 75:1500
UD:hq
h:10.003
q:-30.00 q:-30.00
d,200,4 d,200,4 d,250,4
s,150
UD:hq
h: 9.997
q:-30.00 q:-30.00
d,200,4 d,200,4 d,250,4
s,150
UD:hq
h: 9. 998
q:-30.00 q:-30.00
d,200,4 d,200,4 d,250,4
s,150
s,150
150
Section 2. Operation of Ventilation Systems during Fires
"Real Case" Study
d,160,4 d,160,4 ,200,4 d,200,4 d, 250,4
s,150
d,160,3 d,160,3 d,160,3 d,160,3 d,160,3
t,50.7,30 t,56.5,30 t,60.5,30 t,68.9,30 t, 71. 3, 30
FF:hq<
h:- 06.600 d,630,8 ,400,8
q; -1200
151
Spread of Smoke and Fire Gases via the Ventilation System
Different cases were studied in order to figure out boundary fire
air flows and corresponding pressures in different rooms. This
problem is very numerically complex for such ventilation systems
with several branches, because the flow in the boundary room
must be equal to zero, while other flows and pressures are much
higher then normal. There is an impossible case in exhaust venti-
lation systems, where zero air flow can never be achieved owing to
the entraiment effect in the side branch of a converging wye. This
problem was studied in [27].
The above presented statements agree sufficiently well with the
results from test simulations. In some simulations the program
did not manage to get any result at all and informed about differ-
ent types of faults. Because of this it seems more reasonable to
test the behaviour of the ventilation system regarding smoke
spread to the adjacent rooms by using flows predicted in Section 1
and Table 9.1.
According to Building Code requirements for minimum outdoor
air which are 0.35 l/s,m2 , and taking into account the assumed 30
1/s air flow in and out of each room along with usual height of
dwellings in Sweden, 2.4 m, the volume of a ventilated room is
approximately 200 m 3 • According to Table 9.1, the flow produced
by fire in e.g. hotel rooms of this volume is 1500 1/s.
"Fires" were placed in different rooms and the behaviour of
ventilation systems was studied with the PFS-program. According
to the results obtained, a flow of 1500 1/s from the majority of
burning rooms will definitely cause spread of smoke to all adja-
cent rooms on the same floor which are served by the same branch
as the burning room. One of the PFS-results with fire flow of 1500
1/s in the first room in branch 5 is set out in Figures 9.4.
152
Section 2. Operation of Ventilation Systems during Fires
"Real Case" Study
153
Spread of Smoke and Fire Gases via the Ventilation System
begin
flow 1/s
pressure Pa
control bend=1 con=1 duct=1 i tmax=99 table=3 dxs=25
set UD=t,10,30
fan FF 100:200 125:750 75:1500
d,250,4
s,150
d,250,4
s,150
d,250,4
s,350
UD:hq
h:-12889
q:19.143 q:1077.0
d,160,4 d,160,4 d,200,4 d,200,4 d,250,4
s,150
UD:hq
h: 8.233
q:-27.22 q:-27.22 q:-27.23 q:-27.23 q:-27.24
Figure 9.4 PFS-result of exhaust ventilation system according to figure
9.1 with a fiow of 1500 lIs in the first room in branch 5
(beginning).
154
Section 2. Operation of Ventilation Systems during Fires
"Real Case" Study
d,l60,4 d,l60,4 d,200,4
d,400,4:hq d,400,4:hq
h:-2.297 h:-3.845
q:569.11 q: 753.34
, 630, 8 d,400,8
155
Spread of Smoke and Fire Gases via the Ventilation System
begin
flow 1/s
pressure Pa
control bend=1 con=1 duct=1 itmax=99 table=3 dxs=25
set UD=t,10,30
fan FF 100:200 125:750 75:1500
c:J +
CJ+
CJ+
c:J +~:!~~~E:J
+ +
+UD:hq +UD:hq +UD:hq +UD:hq +UD:hq
+ + + + +
156
Section 2. Operation of Ventilation Systerns during Fires
"Real Case" Study
d,160,4 d,160,4 d,200,4 d,200,4 d,250,4
~r+++++++++++if+++++++++++if+++++++++++if+++++++++++if++++++++++++++++++++
- - - - - s,150 7
-d,160,3 -d,160,3 -d,160,3 -d,160,3 -d,160,3
-t,50.7,30 -t,56.5,30 -t,60.5,30 -t,68.9,30 -t,71.3,30
d,250,1 d,250,1
r-----1- r-----:s-
+d,250,4:hq +d,250,4:hq
+ +
+ d,250,1 + d,250,1
!------2- !------6-
+d,315,4:hq +d,315,4:hq
+ +
+ d,250,1 + d,250,1
!------3- !------7-
+d,400,4:hq +d,400,4:hq
+ +
+ +
+ d,250,1 + d,250,1
!------:;- ~------8-
+d,400,4:hq +d,400,4:hq
+ +
+ +
+ +
+ +
_::~~~~---------1--------------------~
s,-1300 d,630,8 d,400,8
end
157
Spread of Smoke and Fire Gases via the Ventilation System
Figures 9.4 and 9.5 show that in the studied case all flows in all
adjacent rooms are positive (supply). It means that a flow of 1500
lis exceeds the boundary flow and causes spread of smoke to all
adjacent rooms on the same floor.
The layout of the ventilation system plays an important role in
this kind of assessment, since the resistance properties of wyes
and bends affect the resulting pressure drop and thus the flow
distribution in these (e.g. Table 8.1 -Table 8.3). Normal ventila-
tion flow of 30 lis can ventilate even smaller spaces. The assumed
fire flow of 1500 lis seems high regarding smoke spread through
the ventilation system. In this case it can be interesting to assess
flow in the burning room that can be as close as possible to
boundary flow. According to Table 8.1 the lowest expected bound-
ary flow in a four-room duct system is the flow from the last but
one room (room 2). Calculations show that a flow of 550 lis from
each last but one room in the present system layout, connected to
each floor branch (rooms No 2, Figure 9.1), will cause smoke to
spread to the adjacent room 1 on the same floor which is served by
the same branch. At the same time there are some differences in
"boundary" flows between different branches, with the lowest flow
of 450 lis in branch 5 situated furthest away from the fan. This
calculation is presented in Figure 9.6. Some other fire cases were
studied for the present ventilation system. Flows of 1100 lis in the
nearest room of each branch cause smoke to spread to all other
four rooms on the same floor or a significant reduction, down to
zero, in flows in other rooms, which is characteristic of flows close
to boundary values. One of the calculations is presented in Figure
9.7.
158
Section 2. Operation of Ventilation Systems during Fires
"Real Case" Study
159
Spread of Smoke and Fire Gases via the Ventilation System
begin
flow 1/s
pressure Pa
control bend=1 con=l duct=1 itmax=99 table=3 dxs=25
set UD=t,10,30
fan FF 100:200 125:750 75:1500
d,160,4 d,160,4 d,200,4 d,200,4 d,250,4
s, 150
d,160,3 d,160,3 d,160,3 d,160,3 d,160,3
t,42.1,30 t,47.8,30 t,51.9,30 t,60.2,30 t,62.6,30
UD:hq
h: 9. 662
q:-29.49 q:-29.49
d,200,4 d,200,4 d,250,4
s,l50
d,250,4
s, 350
d,250,4
s,150
160
Section 2. Operation of Ventilation Systems during Fires
"Real Case" Study
d,160,4 d,160,4 d, 200, 4 d,200,4 d,250,4
s, 150
d,160,3 d,160,3 d,160,3 d, 160,3 d, 160,3
t,50.7,30 t,56.5,30 t,60.5,30 t,68.9,30 t,71.3,30
d,400,4:hq d,400,4:hq
h:-2.451 h:-2.976
q:589.64 q: 655.25
,400,8
161
Spread of Smoke and Fire Gases via the Ventilation System
begin
flow 1/s
pressure Pa
control bend=1 con=1 duct=1 itmax=99 table=3 dxs=25
set UD=t,10,30
fan FF 100:200 125:750 75:1500
UD:hq
h: 9. 348
q:-29.00 q:-29.01
d,160,4 d,160,4 d,200,4 d,200,4 d,250,4
s, 150
s,150
d,250,4
s,350
g~:~~924
q:789.39
d,160,4 d,160,4 d,200,4 d,200,4 d,250,4
s,150
UD:hq
h: 8. 786
q:-28.12 q:-28.12 q:-28.13 q:-28.12 q:-28.13
Figure 9. 7 PFS-result of exhaust ventilation system according to figure
9.1 with a flow of 1100 lIs in the nearest room in branch 5
(beginning).
162
Section 2. Operation of Ventilation Systems during Fires
"Real Case" Study
d,160,4 d,160,4 d,200,4 d,200,4 d,250,4
s,150
d,160,3 d,160,3 d,160,3 d,160,3 d,160,3
t,50.7,30 t,56.5,30 t,60.5,30 t,68.9,30 t,71.3,30
d,400,4:hq d,400,4:hq
h:-2.378 h:-3.389
q:579.92 q:703.30
,630,8 d,400,8
Figure 9.6 shows, that flow in one adjacent room has a positive
value, i.e. air flows out of the room. The pressure drop in the other
parts of the ventilation system and flows in the other branches
and terminals are also affected by the fire flow in the tested room.
Figure 9.7 shows that flows in all four rooms adjacent to the
burning room have small positive values, i.e. air flows out of the
room. In this case fire flow is very close to the boundary flow. The
pressure drops in the other parts of the ventilation system and
flows in the other branches and terminals are also affected by the
fire flow in the tested room.
Calculations show that there are some differences in fire flow,
causing smoke to spread to the adjacent room(s), in different
163
Spread of Smoke and Fire Gases via the Ventilation System
branches (serving different floors) in similar rooms. Flows causing
smoke spread via the same branch can differ significant from case
to case. Note, that fire flows from different rooms can cause smoke
to spread to different numbers of rooms served by the same
branch.
Some measures to prevent smoke spread were discussed in
Chapter 8. Two of these were tested for all the above fire flows,
with the rotational speed of the exhaust fan doubled and with the
fan switched off. The results are presented in Table 9.1.
The case when the rotational speed of the fan is doubled is a very
hard measure and can be applied e.g. in ventilation systems with
reduced normal capacity. The case when the fan is switched off
corresponds to natural ventilation.
164
Section 2. Operation of Ventilation Systems during Fires
"Real Case" Study
to plenum 1
"" ""
"" ""
"" ""
"" ~~--~--~--~~
to plenum2
Figure 9.8 Layout of exhaust ventilation system with two plenums for
four floors and five rooms on each floor.
Two different cases were studied. In the first case air is ex-
hausted at the rate of 15 lis from each of two terminals in the
room. In the second case air is exhausted at different rates, 10 lis
and 20 lis, from the terminals. The total exhaust air flow from the
room is 30 lis for both cases. A fan with the same characteristics
is installed in all studied cases.
The exhaust fan has the following similar characteristics as the
fan in Subsection 9.3.1.
The exhaust ventilation system drives out the total air flow of
600 lis at 123 Pa pressure, which exhausts via two vertical ple-
165
Spread of Smoke and Fire Gases via the Ventilation System
nums from four floors, and further via branches from five rooms
on each floor.
Different "fire" cases were studied in order to test the behaviour
of ventilation system regarding the risk of smoke spread to the
adjacent rooms. "Fires" were placed in different rooms and the
behaviour of the ventilation systems was studied for two major
cases with fires in the last but one room and the nearest room
with the help of PFS-program. Flows predicted in Section 1 and
Table 9.1 were used for the purpose of this study.
For the first ventilation system with equal air flows
(symmetrical case), air flows of 1100 1/s from the last but one room
and 2350 1/s from the nearest room cause smoke to spread to adja-
cent room (s).
For the second ventilation system with unequal air flows
(asymmetrical case), air flows of 700 1/s from the last but one room
and 1450 1/s from the nearest room cause smoke to spread to adja-
cent room (s).
This example shows that even small changes in the layout of
the ventilation system can affect the behaviour of the whole sys-
tem regarding the risk of smoke spread.
Table 9.2 Data for the examined measures to prevent smoke spread
via double-plenum exhaust ventilation system
166
Section 2. Operation of Ventilation Systems during Fires
"Real Case" Study
The case with a fan whose rotational speed is doubled is a very
hard measure and can be applied. in e.g. ventilation systems with
reduced normal capacity. The case with the fan shut down corre-
sponds to natural ventilation.
to supply plenum
to exhaust plenum
167
Spread of Smoke and Fire Gases via the Ventilation System
were placed in different rooms and the behaviour of the ventila-
tion system was studied with the PFS-program. Though such
problems are usually very numerically complex for the majority of
ventilation systems with several branches, calculations succeeded
in this case. Boundary fire flow for the majority of "fire" cases was
140 lis. Smoke spreads to the adjacent rooms via supply ducts,
while higher values of gas flows spread directly to the corridor
("zero-duct") through transfer air devices.
Table 9.3 Data regarding the examined measures for the prevention
of smoke spread via supply-exhaust ventilation system with
"zero-duct"
The case when the rotational speed of the fan is doubled is a very
hard measure and can be applied e.g. in ventilation systems with
reduced normal capacity. The case when the fan is switched off
corresponds to natural ventilation.
168
Section 2. Operation of Ventilation Systems during Fires
"Real Case" Study
The studied cases do not cover all possible measures to prevent
smoke spread via ventilation ducts, nor do they examine system
behaviour with fire dampers.
to supply plenum
to exhaust plenum
169
Spread of Smoke and Fire Gases via the Ventilation System
Both supply and exhaust fans have similar characteristics as
the fan in Subsection 9.3.1.
Different cases were studied in order to calculate boundary fire
air flows and corresponding pressures in different rooms. "Fires"
were placed in different rooms and the behaviour of the ventila-
tion system was studied with the PFS program. Though such
problems are usually very numerically complex for the majority of
ventilation systems with several branches, calculations succeeded
in this case. Boundary fire flow for the majority of "fire" cases was
130 lis. All fire flows which exceed the boundary flow will cause
smoke to spread to the adjacent room(s) via supply ducts. Accord-
ing to Table 9.1, fires in all types of buildings with a volume
larger then 30 m3 will cause spread of smoke through supply
ducts.
Table 9.4 Data regarding the examined measures for the prevention
of smoke spread via supply-exhaust ventilation system
170
Section 2. Operation of Ventilation Systems during Fires
"Real Case" Study
The case when the rotational speed of the fan is doubled is a
very hard measure and can be applied e.g. in ventilation systems
with reduced normal capacity. Note, that doble speed results in
eight times higher moter effect. The case when the fan is switched
off corresponds to natural ventilation.
The studied cases do not cover all possible measures to prevent
smoke spread via ventilation ducts, nor do they examine system
behaviour with fire dampers.
171
Spread of Smoke and Fire Gases via the Ventilation System
172
Section 2. Operation of Ventilation Systems during Fires
Evaluation of the Toxicity of Diluted Smoke
10.1 Background
In certain cases, where predictions show that comparatively low
volumes of smoke will spread to adjacent rooms, another situation
can be discussed. It can be reasonable to look at the degree of di-
lution of smoke instead of totally forbidding the spread of smoke
to adjacent rooms. In this connection, the toxicity of the diluted
smoke may have to be evaluated. It is well known that roughly
two-thirds of all deaths from enclosure fires can be attributed to
the presence of carbon monoxide (CO) which is known to be the
dominant toxicant in fire deaths. In the literature, some astonish-
ing facts concerning fatal fires can be found. One of the most ex-
treme cases is the fatal town house fire in Sharon, USA, 1987. Al-
though the fire was essentially localised in the first floor kitchen,
deaths occurred on the second floor. One of the victims had an ex-
traordinarily high level of carboxyhaemoglobin, suggesting expo-
sure to very high concentrations of CO. This fact and the later as-
sessment of the highest CO concentration produced by enclosure
fires are discussed in [28] and [29]. In these papers very special
cases of fire in an enclosure with ceiling and upper walls lined
with plywood were studied. The most dramatic effect was the
rapid growth and peak level of CO observed. Dry CO concentra-
tions reached 7% at the front sampling position and 14% at the
rear 200 s after ignition. The enclosure was fuelled by a natural
gas flow corresponding to 400 kW. The above reported levels are
extremely high and represent an unusual CO/C02 ratio. The tem-
perature observed was higher than 500°C. The fire was under-
ventilated (ventilation-controlled fire).
173
Spread of Smoke and Fire Gases via the Ventilation System
(10.1)
174
Section 2. Operation of Ventilation Systems during Fires
Evaluation of the Toxicity of Diluted Smoke
(10.3)
The next step is to calculate facade flow with the help of fire pres-
sure and the following expression
(10.7)
175
Spread of Smoke and Fire Gases via the Ventilation System
Table 10.1 shows that the proportion of smoke volume, r, reaching
one of the rooms decreases with increasing number of rooms, n,
and decreasing airtighteness of the facade, b.
r
a b n=2 n=5 n=lO n=20
5 1.0 0.212 0.047 0.027 0.014
5 0.5 0.163 0.037 0.021 0.011
5 0.2 0.111 0.026 0.014 0.008
5 0.1 0.082 0.020 0.011 0.006
176
Section 2. Operation of Ventilation Systems during Fires
Evaluation of the Toxicity of Diluted Smoke
r
a b/4 n=2 n=5 n=lO n=20
5 1.0 0.344 0.200 0.118 0.064
5 0.5 0.273 0.153 0.088 0.047
5 0.2 0.195 0.106 0.060 0.032
5 0.1 0.149 0.080 0.045 0.024
c,
Te
=(- Te
- 1) I (1 + (T - 1)) r cb -Vb = (1 - TJ Vb
- ) r cb - (10.10)
T1 1 V, Te V,
177
Spread of Smoke and Fire Gases via the Ventilation System
178
Section 2. Operation of Ventilation Systems during Fires
Evaluation of the Toxicity of Diluted Smoke
179
Spread of Smoke and Fire Gases via the Ventilation System
gerous CO dose, but at the expense of the risk of several rooms
being subjected to equal smoke spread.
10.7 Application
CO concentrations of smoke reaching a single room can be calcu-
lated according to (10.10) and Table 10.1 for rooms of different de-
grees of airtighteness and different CO concentrations in the
smoke itself. Assuming expansion (T)Trl) equal to 1, which cor-
responds to temperature change from 20°C to 313°C, we have
er= 0.5rcb
CO,ppm
b n=2 n=5 n=lO n=20
1.0 1060 235 135 70
0.5 815 185 105 55
0.2 555 130 70 40
0.1 410 100 55 30
180
Section 2. Operation of Ventilation Systems during Fires
Evaluation of the Toxicity of Diluted Smoke
CO,ppm
b n=2 n=5 n=lO n=20
1.0 14840 3290 1890 980
0.5 11410 2590 1470 770
0.2 7770 1820 980 560
0.1 5740 1400 770 420
181
Spread of Smoke and Fire Gases via the Ventilation System
182
Section 2. Operation of Ventilation Systems during Fires
Evaluation of Visibility of Diluted Smoke
11 Evaluation of visibility of
diluted smoke
11.1 Background
As discussed in Subsection 10, it may be reasonable in certain
cases where the predicted spread of smoke to adjacent rooms has
comparatively low values to look at the degree of dilution of the
smoke instead of totally forbidding the spread of smoke to adja-
cent rooms. In this connection, evaluation of risk due not only to
the toxicity of diluted smoke but also to visibility may be neces-
sary. Visibility through smoke can be of great importance for the
survival of an individual in a fire. Visibility depends on many dif-
ferent factors, such as wavelength of the light, whether the sign is
emits or reflects light, illumination of the room(s), the visual acu-
ity of the individual, the absorption coefficient of the smoke, etc.
However, there are methods for smoke visibility estimation. One
of them, for safe level, is presented in Swedish Buildings Codes
[8]; the height of the smoke layer above the floor must not be less
than 1.6 m+ 10% of room height. This smoke visibility can be re-
garded as safe if it is combined with other limiting parameters,
such as level of heat radiation and air temperature. Another
method is presented in [5]; visibility scan be described as
!~
!5__ for light- emitting sign
(11.1)
s= for light- reflecting sign
183
Spread of Smoke and Fire Gases via the Ventilation System
where k is the smoke extinction coefficient and is a product of an
extinction coefficient per unit mass, km, and mass concentration of
the smoke, m.
k=k m m (11.2)
D=-D_m_Mf_ (11.3)
VC
where Dm is the empirical mass optical density, m 2/g, .1M is the
mass loss of the sample, g, and Vc is the volume of the fire room,
m 3 • This method is regarded to be more reliable and more direct.
According to [32], [33] lowest visibility value in familiar spaces
is 3-5 m, but never less then 2 m, and in unfamiliar spaces it is
15-20 m.
184
Section 2. Operation of Ventilation Systems during Fires
Evaluation of Visibility of Diluted Smoke
(11.5)
185
Spread of Smoke and Fire Gases via the Ventilation System
186
Section 2. Operation of Ventilation Systems during Fires
"Cold" Case Assessment
The whole study assumes that all flows have ambient parameters,
"cold flows". In fact, according to results obtained in Section 1,
flow temperatures can exceed 300 °C. Although all evaluations of
smoke spread via ventilation ducts take the temperature factor
into consideration in dealing with volume flows, the problem of
calculating pressure drop in ventilation systems can be discussed
further. According to [31], Fanning friction factor f for fully devel-
oped tube flow is inversely proportional to the Reynolds number
based on mean velocity and tube diameter. At the same time, the
Darcy - W eisbach friction factor fD is four times as large as f.
fv=4f (12.1)
or
(12.5)
187
Spread of Smoke and Fire Gases via the Ventilation System
or, as a function of flow
M _ o.25 p o.75 ql.75
17
-~-= 0.158 d4.75 (12.6)
4
2.5 ·103 < q/dv < 2.5 ·10
and
M V0.25p 1.75
4 6
2.5 ·10 < q/dv < 1.3 ·10
An empirical relation that holds at high Reynolds numbers is
2
fv =:4 X 0.046Re-;}· (12.8)
or
M vo.2p Ul.8
-=
l
0.092
d"
12 (12.10)
4 6
2.5 ·10 < q/dv < 1.3 ·10
and
M
-=
l
0.092
v0.2p
4;
d .
1.8
(12.12)
4 6
2.5 ·10 < q/dv < 1.3 ·10
Expressions (12.11) and (12.12) describe fully developed turbu-
lent flow with high Reynolds numbers, which is characteristic for
high temperature flows.
For fully developed turbulent flows through ducts with cross
sections other than round, provided ReD should be replaced by the
Reynolds number based on hydraulic diameter, ReDh'
188
Section 2. Operation of Ventilation Systems during Fires
"Cold" Case Assessment
The relationship between temperature, density p and v0 ·2 p-term
from (12.12) and (12.10) is illustrated in Figure 12.1
p 1.4,...------------------------rQ.14 V0.2.p
1.2 0.12
0.1
0.8 0.08
0.6 - - - - - - - - 0.06
0.4 - - - - - - - 0.04
0.2 - - - - - - - - - - - - - - - - - - 0.02
o~---+---+----~-----~--~~---4o
Temperature (C)
02
Figure 12.1 Density p and the v p-term vs. temperature for fully devel-
·
Figure 12.1 shows that density p and the v0·2 p-term decrease by
approximately a factor of two as temperature in K doubles. This
means that the pressure drop per meter length of duct (friction
pressure drop in straight ducts) also decreases by a factor two.
This seems to indicate that all ventilation system calculations
for the "cold" case are overestimated. At the same time, as smoke
is diluted downstreams in the main duct, flow temperatures de-
crease and "cold" flows are the default values.
The pressure drop in wyes and junctions is more difficult to
evaluate, as data is not available.
189
Spread of Smoke and Fire Gases via the Ventilation System
190
Section 2. Operation of Ventilation Systems during Fires
"Alexander" Method
b d f
where
qn is a normal ventilation flow
191
Spread of Smoke and Fire Gases via the Ventilation System
a-f roonas
G,H junctions.
In the ordinary case the present ventilation systena is regulated
and the pressure loss in branch a -G is equal to pressure loss in
branch b-G. In the case of fire, pressure in the burning roona, e.g.
in roona a, rises and affects pressure in branch a-G. The boundary
or linait condition, when snaoke frona roona a starts to spread to the
adjacent roona b, is reached when pressure in junction G beconaes
equal to zero. The described naethod uses this phenonaena and
replaces the layout presented above with an abridged ventilation
systena layout, shown in Figure 13.2
.G H
I
c d e f
qn qn qn qn
Part of the naain duct a-G and branch G-b is cut offinG and is
replaced by sonae fictitious "roona" with atnaospheric pressure and
flow of 2qn. If the pressure loss in branch G-H is pP the "new" flow
frona roona c is
q=qn (pl /pc-H)O.S
where PcHn is pressure loss in G-H deternained for the nornaal case.
This principle is used to calculate "new" flows in each branch
for the abridged ventilation systena. The resulting total flow qa
and the resulting total pressure loss Pa are plotted in Figure 13.3.
192
Section 2. Operation of Ventilation Systems during Fires
"Alexander" Method
qs qa Flow, 1/s
Pressure Ps and flow qs are new fan values for this abridged venti-
lation system. The corresponding boundary fire flow in branch G-
H (instead of assumed flow of 2q n) can be calculated
q b = 2q n q s I q a
where
q b is boundary fire flow.
The corresponding boundary fire pressure can be calculated
2
Pb = Pa-G (qb I qn )
where
Pa-G is pressure loss In branch a-G at the normal ventilation
flow, qn.
193
Spread of Smoke and Fire Gases via the Ventilation System
194
Discussions and Conclusions
14 Discussions and
conclus ions
Introduction
The theoretical studies along with computer simulations have
provided knowledge regarding smoke production of different typi-
cal fires in certain types of buildings, as well as knowledge regard-
ing spread of smoke to adjacent room(s) via ventilation ducts.
Application of this basic knowledge largely depends on the charac-
teristic parameters estimated for different types of buildings. The
main building types chosen for this work are dwelling houses,
hospitals, offices and hotels. The study is interdisciplinary and
comprises different fields of knowledge: fire protection engineer-
ing, building science and building services.
Whether or not smoke spread will occur is determined by factors
such as the typical fire scenario in the above types of buildings,
the airtightness of the construction, window breakage as a result
of heat stress and the layout of the ventilation system.
195
Spread of Smoke and Fire Gases via the Ventilation System
full-scale tests in which different items were burnt in the labora-
tory and heat release rate as a function of time was measured.
The following items were assumed to initiate fires: sofa and bed
in dwelling houses, bed in hospitals, equipment and furnishing in
offices and bed in hotels. Data provided by these fire growth
curves is used as basic fire data in evaluating fire progress in the
examined rooms with the help of computer programs.
The geometry of the studied types of rooms is chosen in diapa-
son of 30 -224m3 for the standard room areas and room heights
for each type of buildings. Doors and windows are closed and un-
damaged, and the only vents are leakage paths.
196
Discussions and Conclusions
Airtightness
Validation of the magnitude of internal and external leakage
paths in the studied buildings is an important issue for evaluation
of both fire progress in the room and predicted parameters.
The study of relevant literature has shown that the air leakage
according to the Swedish Building Regulations BBR 94 (1.25
cm2/m2 for dwellings and 2.5 cm2/m2 for other types of studied
buildings), applied to the whole building envelope, can be accepted
as a suitable and probable value.
The analysed data are not sufficient for less robust validation
as they cover mostly dwellings, while this study comprises differ-
ent types of buildings. In particular, there are no data for older
buildings. At the same time, due to Swedish construction tradi-
tions and airtightness requirements which are different from
those in other countries, the information from international sci-
entific documents published abroad cannot be used as straight-
forward data.
Window breakage
As the CFAST fire model assumes that the envelope of the fire
room is perfectly airtight during the entire fire progress, except
for the leakage paths, the evaluation of the time and ambient
conditions at which window breakage occurs seems important.
A study of the literature, together with the simple window
breakage model presented in this work, shows that the tempera-
ture difference of 58-100°C in the glass itself can be assumed to be
dangerous for glass cracking. The most probable temperatures in
the fire room which cause this phenomenon vary between 200 and
400°C.
For this study, the temperature of 350°C in the fire room is ac-
cepted as the limiting temperature value. The uncertainty of such
assumptions is aggravated by lack of data on window breakage as
a result of the simultaneous effect of both high pressure and high
temperature in the enclosure.
Further research on the issue appears necessary.
197
Spread of Smoke and Fire Gases via the Ventilation System
198
Discussions and Conclusions
those predicted for fast l - fires, while flows in hotels larger than
3
100m have values between those predicted for fast and ultrafast
2 3
t - fires. Flows obtained for dwellings up to approximately 100m
are lower than those predicted for ultrafast l - fires. In contrast,
3
flows in dwellings larger than 100 m have higher values than
2
those predicted for ultrafast t - fires.
199
Spread of Smoke and Fire Gases via the Ventilation System
In mechanical ventilation systems designed according to given
pressure drop relations, in which prevention of smoke spread re-
lies only on shutting down the ventilation system, some smoke
spread to the adjacent room(s) will always occur.
The proportion of smoke which reaches adjacent room(s) in me-
chanical systems in which the supply fan or both fans are
switched off depends on the number of rooms and their sizes. The
maximum amount of smoke spreads to the adjacent room(s) from
the burning room in cases where there are two equal rooms (with
fire in one of them), a lot of smoke spreads from a small burning
room to the rest of the building, and little smoke spreads from a
large burning room (or several burning rooms) to the small room.
The magnitude of fire flow is not discussed here. The term
"adjacent room(s)" in this study can refer to any fire compartment
on the same floor or on another floor nearest to the burning room,
served by the same ventilation system.
Boundary conditions
Exhaust and supply-exhaust (open and closed) systems and sup-
ply-exhaust systems with "zero"-duct ventilation are studied with
the help of the semi-graphical computer program PFS which
treats arbitrary flow systems of any structure and layout, any
media, and any problem, design and investigation.
Boundary conditions, e.g. boundary fire flows when smoke from
the burning room starts spreading via ducts to the adjacent room
(zero air flow in the adjacent room(s)), are in good agreement with
values expected according to the general models.
As this study is interested in "abnormal" flow behaviour, i.e.
changes in flow directions and consequent decrease in flow in cer-
tain parts of junctions to zero value, it is not obvious how wyes
would respond.
PFS provides the opportunity to describe the resistance proper-
ties of wyes and junctions in two different ways: with a quadratic
function and with the help of empirical equations. Both types are
tested, and the resulting boundary fire flows are different. Pres-
sure loss as a quadratic function, which takes account of high
Reynolds numbers in duct flows in case of fire, is chosen as the de-
200
Discussions and Conclusions
fault. More detailed research into the behaviour of wyes under
such conditions seems important.
"Real-case"
The types of buildings examined in this study are equipped, as
usual, with ventilation systems, the degree of complexity of which
can be different. Evaluation of boundary fire flows in these venti-
lation systems is very numerically complex. Assessment of the
risk of smoke spread via ducts seems more manageable when fire
flows typical for the studied buildings presented in this work are
used.
201
Spread of Smoke and Fire Gases via the Ventilation System
It can be reasonable to look at the degree of dilution of the
smoke instead of totally forbidding the spread of smoke to adja-
cent rooms. In this connection, the risk of toxicity and visibility of
diluted smoke may have to be evaluated. Evaluation of the con-
centration of CO in the smoke spread is then important. In cer-
tain underventilated fires, with the ceiling and upper walls lined
with plywood, dry CO concentrations are reported to reach 14%.
These reported levels are extremely high and represent an un-
usual CO/C0 2 ratio. Generally, CO concentrations increase dra-
matically in underventilated fires.
Evaluation of the concentration of CO which spreads to the ad-
jacent room(s), made step by step for exhaust and supply-exhaust
ventilation systems, comprises evaluation of the total volume of
smoke spread, evaluation of the proportion of this smoke volume
which reaches another room, evaluation of the concentration of
CO in a single room, and evaluation of the CO - dose.
The CO-dose is a product of GO-concentration, the duration of
exposure, and the type of activity during which exposure takes
place.
There are different criteria which determine the fatal dose of
CO. Information about the toxic effects of CO in respiration air
varies a lot both in terms of both concentration and dose. Thus it
seems difficult to draw unequivocal conclusions about the risk
rate due to GO-concentrations. IDLH (immediately dangerous to
life and health), limited to 1500 ppm during 30 min, is used as the
default value in this study.
Visibility through smoke can be of great importance to an indi-
vidual attempting to survive a fire. The evaluation of the visibility
of smoke in another room, as a result of smoke spread via venti-
lation ducts, is analogous to evaluation of the concentration of CO
in the spread smoke. In actual fact, visibility will be higher than
assessed, because the concentration of smoke will be higher near
the ceiling and will gradually decrease downwards.
202
Discussions and Conclusions
tions of smoke spread via ventilation ducts take into consideration
the temperature factor in dealing with volume flows, the pressure
drop per meter length of duct (friction pressure drop in straight
ducts) at such temperatures seems to decrease to one half of ordi-
nary values. This statement seems to indicate that all ventilation
system calculations made for the "cold" ventilation systems are
over estimated. The pressure drop in wyes and junctions is more
difficult to evaluate due to the paucity of data.
Further research in this field is needed. At the same time, along
with smoke dilution downstream from the main duct, flow tem-
peratures decreases and "cold" flows become the default ones.
Manual methods
One more method for evaluating of possibility og smoke spread via
ducts is presented in the study. The "Alexander" method is a
method for manual calculations, based on the" cut-off' principle.
The "cut-off' principle means that a branch(es) at the boundary
conditions with zero pressure is cut off and the rest of the venti-
lation system is calculated once more with respect to the new
pressure/flow conditions. This calculation results in new total
pressure loss and flow values. On the bases of these new parame-
ters and the fan curve, the new total pressure and flow are as-
sessed for the abridgedventilation system. The fire flow for such a
system can be calculated. The method is named after Alexander
the Great and myth of the Gordian knot.
Application
To evaluate smoke spread via ventilation systems in case of fire,
the following procedures can be applied.
For ventilation systems of all types, the risk of smoke spread
via ducts can be evaluated step by step with the help of computer
programs as follows:
"Boundary" fire flow:
step 1 the ventilation system studied is described with the
help of a computerprogram,
step 2 the "boundary" fire flow in the room studied or in
one of the rooms connected with the branch located
203
Spread of Smoke and Fire Gases via the Ventilation System
furthest away from the fan are evaluated. It means
that the supply flow to the room studied in the case
of supply and exhaust ventilation system is replaced
by the zero flow. In the case of exhaust ventilation
system, the flow(s) in the exhaust branch calculated
upwards from the "fire" room is replaced by the zero
flow,
step 3 the "boundary" flow(s) is compared with a fire flow(s)
(Figure 4.13) for the room of corresponding volume in
the corresponding type of building. If the "boundary"
flow is higher than the fire flow from the Figure 4.13,
smoke does not spread via the ventilation system. If
the "boundary" flow is lower than the fire flow from
the Figure 4.13, smoke spread occurs via the ventila-
tion system.
"Alexander" method
204
Discussions and Conclusions
In certain cases, when toxicity of assessed smoke spread via ex-
haust ventilation system and supply and exhaust ventilation sys-
tem are of interest, it can be rapidly evaluated using Table 10.4
and Table 10.5 respectively.
Future research
This work along with other reports [1], [2], [3] and [27] is a pio-
neering research attempts in regard to the evaluation of smoke
spread via ventilation ducts in ventilation systems in operation.
Owing to the great uncertainty of the assumptions made, the
paicity of experimental data and lack of knowledge regarding cer-
tain fire processes, it is necessary to investigate the problem fur-
ther.
The fire scenario in the buildings studied, with more than one
burning item involved, is of interest as such fires can produce fire
flows different from those predicted in this work.
The issue of the reliability of the parameters predicted by
CFAST, along with true validation of the model, should be ana-
lysed in a proper way.
The problem of flashover in smoke in ventilation ducts or ter-
minals, i.e. ignition of unburned fuel in fire gases, must be studied
properly, probably with the help of field model computer pro-
grams.
Window breakage phenomena as a result of both high tempera-
tures and the influence high pressures must be studied.
The "cold" case as against the real high temperature smoke flow
in ventilation systems must be examined in greater detail, since
no examination has been made as yet of pressure drop in junc-
tions and wyes in cases with "abnormal" flow behaviour, i.e.
changes in flow directions and consequent decrease in flow in cer-
tain parts of junctions to zero value.
The problem of smoke spread via ventilation ducts in other
types of buildings, e.g. in industrial buildings and stores, seems
important. The possibility of using ordinary ventilation systems
along with other safety measures (smoke venting, sprinklers, etc.)
in the event of fire in such buildings can improve safety, and the
economic consequences of it are far from negligible.
205
Spread of Smoke and Fire Gases via the Ventilation System
The problem of eliminating or reducing smoke spread via ducts
to the adjacent room(s) is connected with evaluation of the toxic-
ity and visibility of the diluted smoke. This matter needs further
research.
206
References
References
207
Spread of Smoke and Fire Gases via the Ventilation System
9. P. Levin, "Building Technology and Air Flow Control in
Housing", Stockholm (1991).
15. "An Update Guide for HAZARD 1 Version 1.2", Building and
Fire Research Laboratory Gaithersburg, U.S.Department
of Commerce, (1994).
208
References
20. "Kvalitetsansvarig tekniska foreskrifter, Niva K", Bygginfo,
(1995) (in swedish).
209
Spread of Smoke and Fire Gases via the Ventilation System
31. A. Bejan, "Heat transfer", John Wiley & Sons, Inc. (1993).
32. T. Jin, ''Visibility through fire smoke, Part 5", Fire Research
Institute of Japan, Tokyo (1976).
210
Appendix
Appendix
211
Spread of Smoke and Fire Gases via the Ventilation System
300.0 600.0
--1 u
-50.0 -100.0
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 1 Time (s)
3.0 .300.0
--1 u --1 u
1~ I
t>, ·a
5!
0.0
500.0 0.0 500.0
n= 1 Time (s) n= 1 Time (s)
25.0
0.2
-- 1 u 02 --1 1-2
'--._ (;)
'--._
E
Q_
Q_
6
'--._
c
(!) >
2 .E
(!)
Q_
0.0 0.0
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 1 Time (s)
0 ..3
0.0
--1 L 1- 2 2 'L 2- 1 1
I
V; (;)
'--._
'--._
0'
Cl'
6 6
•E
.
0.0 0.0
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 2 Time (s)
212
Appendix
300.0 ,------,.---,.---,.---_-_,_-----,;-;-;-u--,1ooo.o
1
0
o_
l::'
Q_
-50.0
0.0 500.0 0.0 500.0
n= 1 Time (s) Time (s)
3.0 .-----------,.-----------,----;-----,--, ---,-c-:ol
--1U
300.0
--1 u
f
·I
0.0
0.0
0.0 500.0
n= 1 Time (s) 0.0 500.0
n= 1 T'1me (s)
22.0 0.2
1-
-.-1U02 1 ti 1- 2 I
1-
0
""'- m
""'-
Ql
E 6
0.
I
0.
""'-
c
Q)
2
Q)
0.
6.0 0.0
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 1 Time (s)
0.3 1.0
--1 L ,_ 2 2 L 2- 1
(j) m
""'-
ry ""'-
Ql
6 6
.E
0.0
0.0
n= 1 Time (s)
500.0
0.0
0.0
n= 2
~ Time (s)
500.0
213
Spread of Smoke and Fire Gases via the Ventilation System
300.0 600.0
--1 u
-50.0 -100.0
0.0 500.0 0.0 500.0
n= 1 T1me (s) n= 1 Time (s)
3.0 ~-~--~----.--~--- 300.0
--1 u -'- 1 u
~
i
Q1
~
([)
>,
·a
_Q
0.0
500.0
n= 1 Time (s) 0.0 500.0
Time (s)
25.0 0.2
-- 1 u 02 -- 1 1-2
1-
u
"'- en
~
E CJ'
0.
0.
CS
"'-
c
~
~
0.0
0.0
0.0 500.0
Time (s) 0.0 500.0
n= 1 Time (s)
0 ..3 0.0
--1 L 1- 2 2 l 2- 1
"'
~
({) en
~
Q1 CJ'
6 CS
.E
500.0
0.0 L'===:=:r::====:r::::==:::::::r====:::r:===-
n= 1 Time (s) 0.0 500.0
n= 2 Time (s)
214
Appendix
400.0 2500.0 , - - - , - - - - - - , - - - - - - , - - - - . . , . . - - - - ,
--1 u --1 u
0.0 -500.0
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 1 Time (s)
1200.0
3.0
--1 u --1 u
~
i
_c
.'2'
1'
(\)
·a
>-
_Q
0.0 0.0
0.0 500.0 0.0 500.0
n= 1 Time (s) Time (s)
25.0 1.0
--
~ 21
I
--1 I)
I
"l
1-
u
-....._ m
-....._
E
Q_
-1 ~
Q)
Q_ I N
"-.. i -'-
c
1
I
(\)
2
(\)
Q_
-1.0 I
500.0
n= 1 Time (s) 0.0 500.0
n= 1 Time (s)
2.0 0.0
--1 L 1- 2 2 L 2- 1'
m
"-..
00
"-..
Q)
6 ~
.E .E
0.0 0.0
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 2 Time (s)
215
Spread of Smoke and Fire Gases via the Ventilation System
i a.
0.0 -500.0
0.0 500.0 0.0 500.0
n= 1 Time (s) Time (s)
3.0 1200.0
--1 -- 1 u
~.2"'
1! I
iG ·o
>,
.Q
0.0 0.0
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 1 Time (s)
25.0 1.0
-- 1 u 02 --1 u 1-2
1-
u
........ if)
........
0>
E
Q. 6
a.
........
~
c
2 .E
~
0.0 -1.0
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 1 T"1me (s)
2.0
0.0
--1 L 1- 2 2 L 2- 1
if) if)
........ ........
0>
0>
6 6
.E
0.0 0.0
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 2 Time (s)
216
Appendix
400.0 2000.0
--1 --1
l a.
0.0 -500.0
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 1 Time (s)
3.0 1400.0
--1
~.'2'
<1.)
s:.
I
<1.) ·a
:>-
.!2
0.0 0.0
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 1 T'1me (s)
25.0
f-
I
u 0, 1.0
1 u 1- 2
"-. lf)
-......_
E
Q_
a.
6
"-.
c
<1.)
0
Q;
a.
0.0
-1.0
0.0 500.0
n= 1 Time (s) 0.0 500.0
n= 1 T'1me (s)
2.0 0.1
1L 1- 2 2 L 2- 1
--:;; --:;;
-......_ "-.
0'
6 .:s
~
.E
0.0
500.0 0.0 500.0
Time (s) n= 2 Time (s)
217
Spread of Smoke and Fire Gases via the Ventilation System
0.0 -500.0
0.0 500.0 0.0 500.0
n= 1 Time (s) Time (s)
3.0 2000.0
-'-1 u -- 1 u
~ .Q' I
1:
'a
a:>
>,
_Q
0.0
0.0
0.0 500.0
0.0 500.0 n= 1 Time (s)
n= 1 Time (s)
25.0 1.0
--1U02 -1u 1- 2
r-
0
'--... -;;;-
'--...
ry
E
Q_
Q_
6
'--...
c
Ql
2
Ql
Q_
-1.0
500.0
n= 1 Time (s) 0.0 500.0
n= 1 Time (s)
2.0 0.1
--1 L 1- 2 2 L 2- 1
(;)
'6; z ry
6 6
.E
0.0 0.0
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 2 Time (s)
218
Appendix
250.0 500.0
--1 u
0.0 c_l- - - - ' - - - - - ' - - - - - ' - - - - - ' - - - - - - - '
0.0 500.0
n= 1 T1me (s) 0.0 500.0
n= 1 Time (s)
·a
0.0
0.0
0.0 500.0
n= 1 Time (s) 0.0 500.0
n= 1 Time (s)
22.0 0.1
-' 1 U021 I 1()l 'F2 I
1-
u
""- Ul
""-
ry
E
Q. 6
Q_
""-
c >
~ .E
~
6.0 00
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 1 Time (s)
0.1 03
--1L 1- 2 2 L 2- 1
Ul
"--,
0'
<ry
6 6
.E .E
0.0
0.0
,\
0.0 500.0
o.o n= 1 Time (s)
500.0 n= 2 Time (s)
219
Spread of Smoke and Fire Gases via the Ventilation System
250.0 200.0
-1
1
Q
0
~
!
0.0 L _ __ ___L_ _ _ L _ _ _. . J __ _. . L __ ___;
--1 u ~
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 1 Time (s)
500.0
--1
1
·a
0.0
500.0 0.0 500.0
n= 1 Time (s) n= 1 Time (s)
22.0 1.0
--1 u 'I- 2
f-
u
~ Ul
~
C)1
E
Q_ ~
Q_
c
Q)
~
.E
2
Q)
Q_
-- 1 u 02
8.0 -1.0
Ul Ul
~ ~
C)1 C)1
~ ~
>
.E .E
- 2
0.0 0.0
0.0 500.0 0.0 500.0
n= Time (s) n= 2 Time (s)
220
Appendix
250.0 200.0
--1'U
0
s
I
2::-
-
~
Q_
--1 u
OD
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 1 Time (s)
3.0 500.0
--1
~ .<:2'
2 1
(jj ·o
>,
_Q
0.0
0.0 500.0 500.0
n= 1 Time (s) n= 1 Time (s)
22.0 1.0
1 'u
~:
f-
0
""-. (/)
""-.
V'
E
Q_ 6
Q_
......_
c
<lJ !
(.)
.E
v
Q_
--1U02
8.0 -1.0
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 1 Time (s)
0.3 1.0
--2 L 2- 1
(/)
~ry
""-.
V'
6 6
>
.E .E
0.0 0.0
o.o n= 1 Time (s)
500.0 0.0
n= 2 Time (s)
500.0
221
Spread of Smoke and Fire Gases via the Ventilation System
250.0 200.0
--1
--1 u
0.0 '--------'-----'----'-------'------'
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 1
'? J
~
1'
;I
1...
·o
<lJ
A
.2
0.0
0.0 '---------'-----'----'-----....J_-------1 o.o 500.0
n= 1 Time (s)
0.0 500.0
n= 1 Time (s)
22.0 lO
-- 1 u 1-2
f-
u
(;)
~
Ql
6
c >
<lJ
(.) .E
Q;
0.
(;)
~
Ql
6
.E .E
222
Appendix
200.0 100-D
--1 u
0.0 -500.0 t _ __ ____j__ _ _--l-_ __ j_ _ __ J
r--
0.0 800.0 0.0 800.0
n= 1 Time (s) n= 1 Time (s)
3D
500.0 1 u,
~
.2'
~
~ 'o
>,
_Q
0.0 0.0
0.0 800.0 0.0 800.0
n= 1 Time (s) n= 1 T'1me (s)
22.0 1.0
-- 1 u 1- 2
Ul
"--..
E
0.
0.
J£ N
c
([)
~ .E
([)
0.
Ul
"--..
CJl
6
.E
.E
--1L 1-2
0.0
0.0
~ _ ____[__ _ __L__-\;;;;;=~=;;;;--__J
800.0
0.0 1---------.J' "---
c___ ____j__ _ _--L-_ _ _c _ __ ____j
n= 1 Time (s)
0.0 800.0
n= 2 : 1me (s)
223
Spread of Smoke and Fire Gases via the Ventilation System
300.0
__ , u 200.0
0
D..
I ~
0.
--1 u
0.0 L _ _ . . . . J __ ___t._ _ j __ _L...._ __j__ _
-300.0 '-------'-----'----'-------'-----'--~
0.0 600.0
n= 1 Time (s) 0.0 600.0
n= 1 Time (s)
0.0 L _ _ . . . . J __ __j__ _ j __ _ j __ _ _ j __ _
0.0 600.0
n= 1 Time (s) 0.0 600.0
n= 1 Time (s)
22.0
- ' - 1 1.! 1- 21
1-
u 021
"-
E
z
o>
0. 6
0.
c
(l)
2 .E
(l)
0.
.E .E
Hospital13
224
Appendix
250.0 200.0
--1 u
0.0 ' - - - - - ' - - - - ' - - - - - - - ' - - - - ' - - - - - - ' - - _ _ _ _ j -600.0 L...__ _ j __ _. L __ _ j __ __L__ ___L_ _
'o
E
Cl
Cl
c
(l)
I
()
Q:;
Q.
zry
~
~
~
.E .E
Hospital14
225
Spread of Smoke and Fire Gases via the Ventilation System
200.0 140.0
--1U --1 u
0.0 -20.0
0.0 400.0 0.0 400.0
n= 1 Time (s) n= 1 Time (s)
4.0 .300.0
I .s::
-"'
1!
([)
>--
.Q
22.0 0.2
--1 u '1- 2
1-
u
""'E
Q
Q
c
I])
2
~ --1U02
12.0 0.0
0.0 400.0 0.0 400.0
n= 1 Time (s) n= 1 Time (s)
1.0 0.2
--1L 1-2 -- 2 L 2- 1
';;)
6""'
I
"'
~
.E
Hospital15
226
Appendix
150.0
250.0 I--1U I --1 u
0.0 -100.0
0.0 400.0 0.0 400.0
Time (s) n= 1 Time (s)
300.0
0.0 0.0
0.0 400.0 0.0 400.0
n= 1 Time (s) n= Time (s)
22.0 0.3
1-- 1 U I 1- 2
I
1-
u
(i)
I
"'-._
"'-._ I
01
E
0.
0.
"'-._
-:::s
r
I
c
<!)
~
u .E
a;
0.
8.0
r- 1 u 02
0.0
0.0 400.0 0.0 400.0
n= 1 Time (s) n= 1 Time (s)
0.2 0.3
2 L I 2- 1
(i) if)
"'-._ "'-._
01 01
-:::s -:::s
~
.E .E
1 L 1- 2
0.0 0.0
0.0 400.0 0.0 400.0
n= 1 Time (s) n= 2 Time (s)
Hospital 16
227
Spread of Smoke and Fire Gases via the Ventilation System
.300.0 100.0
--1 u
1 u
0.0 ' - - - - . . . . . . l . . - - - - ' - - - - - - - - ' - - - . . . . J -400.0 t _ __ _.......L._ _ _..J___ __ _ t_ _ _ _ ....J
0.0 :.--=---.......L.----'--------'-='----....J
0.0 400.0
n= 1 Time (s)
22.0 0.2 r - - - - - - , - - - - - - , - - - - - , - - - - - - ,
- - 1 U 1-2
f-
u
c
([)
u .E
Q;
Q.
.E
Hospital17
228
Appendix
400.0
-- 1 u
60.0
-- 1 u
s ~
0
-
~
()_
0.0 -10.0
0.0 600.0 0.0 600.0
r.= 1 Time (s) n= 1 Time (s)
3.0 200.0
-- 1 u
~-~
.c
(!) I
(!)
·o
>,
_Q
0.0 0.0
0.0 600.0 0.0 600.0
n= 1 Time (s) n= 1 Time (s)
25.0 1.0 I
~ 21
-- 1 u 02 1 u
1-
()
'--... In
'--...
(J1
E
0. 6 I
a. I
'-....
c (!)
2 .E
(!)
Q.
0.0 -1.0
0.0 600.0 0.0 600.0
n= 1 Time (s) n= 1 Time (s)
0.2 0.0
- '- 1 L 1- 2 1- 2 L 2.!. 1
~
({)
-------
'--...
!£ !£
.E
0.0
o.o n= 1 Time (s)
600.0
.E
J 0.0
n= 2 Time
~
(s)
I
600.0
Office 18
229
Spread of Smoke and Fire Gases via the Ventilation System
300.0 250.0
--1U 1 u
0
s
~
~
Q)
Q
0.0 -50.0
0.0 800.0 0.0 800.0
n= 1 T1me (s) n= 1 Time (s)
3.0 200.0
-- 1 u
~
.'2' 'i'
-""
~
<!.)
·o
>-
S2
0.0
800.0 0.0 800.0
Time (s) Time (s)
0.1
25.0
-- 1 u 02 1 u 1-2
1-
0
~
'--...._ '--...._
CJ'
E 6
Cl
o_
'--...._
(
c
Q)
2
Q)
Q
0.0 0.0
"'--...._
(j) ~
'--...._
0' CJ'
6 6
.E .E
~
I
0.0 o.o I
0.0 800.0 0.0 800.0
n= 1 Time (s) n= 2 Time (s)
Office 19
230
Appendix
400.0 140.0
-- 1 u
2
0 'l
-
1
0.0 0.0
0.0 800.0 0.0 800.0
n= 1 Twne (s) n= 1 T"1me (s)
3.0 200.0
-- 1 u
~.'2'
1! l
i>,
D ·o
.2
0.0 0.0
0.0 800.0 0.0 800.0
n= 1 Time (s) n= 1 Time (s)
25.0
1-
0
-- 1 u 02
0.1
.- 1 U I 1- 2
if)
""-
""-
CJl
E
0. 6
Q_
I
""-
I I
!l
c
J
Q)
.E
2
Q)
Q_
0.0
0.0 800.0 0.0 800.0
n= 1 Time (s) Time (s)
0.2 0.0
1 L 1- 2 --2 L 2- 1
(;; [f)
""-
ry ""-
CJl
CS 6
N
.E .E
0.0 0.0
0.0 800.0 0.0 800.0
n= 1 Time (s) n= 2 Time (s)
Office 20
231
Spread of Smoke and Fire Gases via the Ventilation System
40.0
.350.0
-- 1 u
s ~
- i::.'Q.
0.0 0.0
0.0 600.0 0.0 800.0
n= 1 Time (s) Time (s)
.3.0 250.0
-- 1 u
I ~ I
t>-. ·a
.2
0.0 0.0
0.0 600.0 0.0 600.0
n= 1 Time (s) n= 1 T"1me (s)
25.0
1.0
- - 1 u 02 1 u 1- 2
1-
0
'-...._
if)
'-...._
E Ql
D.
D. 6
""'-
c
([)
2
([)
D.
0.0 -10
0.0 800.0 0.0 800.0
n= 1 Time (s) n= 1 Time (s)
0.2 0.0
--1L 1- 2 2 L 2- 1
{j)
'-...._
0'
z Ql
6 6
N
.E .E
0.0
800.0 0.0 800.0
n= 1 Time (s) n= 2 Time (s)
Office 21
232
Appendix
300.0 __ , u 5=.o
!\ I
0
~
2
-
~
Q.
-- 1 u
0.0
0.0 800.0 0.0 800.0
n= 1 Time (s) n= 1 T"1me (s)
250.0
3.0
-- 1
I "'
.c
I
'o
"'>,
2
0.0
800.0 0.0 800.0
n= 1 Time (s) n= 1 Time (s)
25.0 0.0
-- 1 u 02 --1U 1-2
f-
0
E
0.
0.
I
c
"'u .E
G>
0.
0.0 L___ _ _L __ _ _L __ _ _ j _ __ __ _ j
0.0 .!...~~~.b.~~~.b.~~~.b.~~.J.-...J
0.0 800.0 0.0 800.0
n= 1 Time (s) n= 1 Time (s)
.E .E
Office 22
233
Spread of Smoke and Fire Gases via the Ventilation System
300.0 30.0
--1 u
1 u
0.0 -5.0
o.o 800.0 0.0
(s)
800.0
n= 1 T1me (s) n= 1 Time
3.0 300.0
--1 u
t.'2'
(]) I
.c
:u ·a
>-.
..Q
0.0 0.0
o.o 800.0 0.0
(s)
800.0
n= 1 Time (s) n= 1 T'1me
25.0
1.0
f-
-- 1 u 02 --1 u 1- 2
u
'--.._
Ul
'--.._
E en
D.
D. 6
"""c
(])
2
(])
D.
0.0 -1.0
0.0 800.0 0.0 800.0
n= 1 Time (s) n= 1 1'1me (s)
0.0
0.2
-- 1 L 1- 2 2 L 2- 1
Ul Ul
'--.._ '--.._
ry en
6 6
>
.E
0.0
800.0 0.0 800.0
n= 1 Time (s) n= 2 Time (s)
Office 23
234
Appendix
r
250.0 100.0
0
I
11.
l Q_
-- 1 u
0.0 -400.0
~
~
ry
~
Q) 0
>--
.2
0.0
0.0 800.0 800.0
n= 1 Time (s) n= 1 Time (s)
25.0 1.0
--1U02 -- 1 u 1- 2
f--
0
-........ --;;;-
-........
ry
E 6
0.
0.
-........
~
~ .E
Q)
0.
0.0 -1.0
0.0 800.0 0.0 800.0
n= 1 Time (s) n= 1 Time (s)
0.3 1.0
1 L 1- 2 2 L 2- 1
--;;;- --;;;-
-........ -........
ry ry
6 6
.E
0.0 0.0
0.0 800.0 0.0 800.0
n= 1 Time (s) n= 2 Time (s)
Office 24
235
Spread of Smoke and Fire Gases via the Ventilation System
250.0 50.0
~
--1U
V
0
I
2 0..
- 1 ~
0..
-- 1 u
0.0 -300.0
0.0 800.0 0.0 800.0
n= 1 Time (s) n= 1 T"1me (s)
3.0 400.0
--1 u
~.'2'
.L
([) i
0:; ·o
>,
.Q
0.0 0.0
0.0 800.0 0.0 800.0
n= 1 Time (s) n= 1 Time (s)
25.0
_'_ 1 u 021 1.0
--1 u 1-2
f-
u
"-... en
"-...
E
0.
0..
"-...
j 6
0"'
c
([)
0
v
0..
0.0 -1.0
0.0 800.0 0.0 800.0
n= 1 Time (s) n= 1 Time (s)
1.0 1.0
--1 L 1- 2 --'2 L 2- 1
V; V;
"-... "-...
0"' 0"'
6 6
I
"'
.E
0.0
800.0 0.0 800.0
n= 1 Time (s) n= 2 Time (s)
Office 25
236
Appendix
300.0
--1 u
200.0
s
0
,
-
__ )
0.0
0.0
n= Time (s)
600.0
-OO~J'------'-~1.
0.0
n= 1 Time (s)
600.0
400.0 3.0
--1
·a
0.0 t=====""'-___.,=======~
0.0
n= 1 Time (s)
600.0
I
0.2 1.0
--1L 1-2 2 L 2- 1
~~
.E .E
0.0 ' - - - - - - ' - - - - - l . . - " " " " ' ' - _ L _ - - - - - - ' 0.0 '------'
0.0 600.0 0.0 600.0
n= 1 Time (s) n= 2 Time (s)
Hotel26
237
Spread of Smoke and Fire Gases via the Ventilation System
300.0 200.0
0
Q s
-
~
Q
--1 u
0.0
0.0 500.0 0.0 500.0
n= 1 Time (s) n= 1 Time (s)
4.0 1000.0
--1U
~
.Q'
1! I
(l) 'o
>,
_Q
0.0
500.0 0.0 500.0
n= 1 Time (s) n= 1 Time (s)
25.0 1.0
-- 1 u 02 1 u 1-2
1-
u
......... (/)
.........
ry
E
Q 6
Q
.........
c
(l)
f
2 .E
(l)
Q
5.0 0.0
0.0 600.0 0.0 600.0
n= 1 Time (s) n= 1 rime (s)
0.3
1.0
--1 L 1- 2 --'- 2 L 2- 1
(;) (/)
......... .........
CJ1 ry
6 6
.'-
>
.E
0.0
0.0
n= 1 Time (s)
600.0
0.0
0.0
n= 2 Time
\ (s)
600.0
Hotel27
238
Appendix
350.0 1000.0
--1 u
--tu
l
600.0 0.0 600.0
n= 1 Time (s) n= 1 Time (s)
4D ,--------,-------,---_-_-..:::--:,---,u:-:1
800.0
0.0 OD
0.0 600.0 0.0 600.0
n= 1 Time (s) n= 1 Time (s)
25.0 1.0
I
--1 --1 u 1-2
f-
0
"'--.
"l "'
(/)
"'--.
Cl'
E
I
Q_ 6
Q_
"'--.
c
~
~
Q_
I
.E n
0.0 0.0 I
0.0 600.0 0.0 600.0
n= 1 Time (s) n= 1 Time (s)
1.0 2.0
1 L 1- 2 -- 2 L 2- 1
if;' if)
"'--. "'--.
6
01
£
>
.E .E
I
0.0 o.o I
0.0 600.0 0.0 600.0
n= 1 Time (s) n= 2 Time (s)
Hotel28
239
Spread of Smoke and Fire Gases via the Ventilation System
300.0 I 1000.0
¥ I
"
~
[J)
[J)
Q)
0..
0.0
~~,)
.. -
1 u
0.0 600.0
n= 1 Time (s) 0.0 600.0
n= 1 Time (s)
1200.0 4.0 , - - - - - - - - , - - - - - - , - - _------:-1-:-:lU
·a
0.0 0.0
0.0 600.0 0.0 600.0
n= 1 Time (s) n= 1 Time (s)
22.0 1.0
f-
0
(;)
""'E ""'
CJl
0. ~
0.
""'
c
Q)
2
Q)
0.
--1 u 1-2
6.0 0.0
0.0 600.0 0.0 600.0
n= 1 Time (s) n= 1 T"1me (s)
2.0 3.0
--1 L 1- 2 2 L 2- 1
(;)
~
6
CJl ""'
~
CJl
.E
0.0
600.0 0.0 600.0
n= 1 Time (s) n= 2 Time (s)
Hotel29
240