Automatic Power Factor Correction - Electrical Notes & Articles
Automatic Power Factor Correction - Electrical Notes & Articles
Power Factor Definition: Power factor is the ratio between the KW and the KVA drawn by an electrical load where
the KW is the actual load power and the KVA is the apparent load power. It is a measure of how effectively the
current is being converted into useful work output and more particularly is a good indicator of the effect of the
load current on the efficiency of the supply system.
All current flow causes losses both in the supply and distribution system. A load with a power factor of 1.0 results
in the most efficient loading of the supply. A load with a power factor of, say, 0.8, results in much higher losses in
the supply system and a higher bill for the consumer. A comparatively small improvement in power factor can
bring about a significant reduction in losses since losses are proportional to the square of the current.
When the power factor is less than one the ‘missing’ power is known as reactive power which unfortunately is
necessary to provide a magnetizing field required by motors and other inductive loads to perform their desired
functions. Reactive power can also be interpreted as wattles, magnetizing or wasted power and it represents an
extra burden on the electricity supply system and on the consumer’s bill.
A poor power factor is usually the result of a significant phase difference between the voltage and current at the
load terminals, or it can be due to a high harmonic content or a distorted current waveform.
A poor power factor is generally the result of an inductive load such as an induction motor, a power transformer,
and ballast in a luminary, a welding set or an induction furnace. A distorted current waveform can be the result of
a rectifier, an inverter, a variable speed drive, a switched mode power supply, discharge lighting or other electronic
loads.
A poor power factor due to inductive loads can be improved by the addition of power factor correction
equipment, but a poor power factor due to a distorted current waveform requires a change in equipment Design
or the addition of harmonic filters.
Some inverters are quoted as having a power factor of better than 0.95 when, in reality, the true power factor is
between 0.5 and 0.75. The figure of 0.95 is based on the cosine of the angle between the voltage and current but
does not take into account that the current waveform is discontinuous and therefore contributes to increased
losses.
An inductive load requires a magnetic field to operate and in creating such a magnetic field causes the current to
be out of phase with the voltage (the current lags the voltage). Power factor correction is the process of
compensating for the lagging current by creating a leading current by connecting capacitors to the supply.
Privacy & Cookies: This site uses cookies. By continuing to use this website, you agree to their use.
P.F (Cos Ǿ)= K.W / KVA Or
To find out more, including how to control cookies, see here: Cookie Policy
P.F (Cos Ǿ)= True Power / Apparent Power.
KW is Working Power (also called Actual Power or Active Power or Real Power). Close and accept
It is the power that actually powers the equipment and performs useful work.
KVAR is Reactive Power.
It is the power that magnetic equipment (transformer, motor and relay)needs to produce the magnetizing flux.
KVA is Apparent Power.
It is the “vectorial summation” of KVAR and KW.
An induction motor draws current from the supply that is made up of resistive components and inductive components.
The resistive components are:
1) Load current.
2) Loss current.
And the inductive components are:
3) Leakage reactance.
4) Magnetizing current.
The current due to the leakage reactance is dependent on the total current drawn by the motor, but the
magnetizing current is independent of the load on the motor. The magnetizing current will typically be between
20% and 60% of the rated full load current of the motor. The magnetizing current is the current that establishes
the flux in the iron and is very necessary if the motor is going to operate.
The magnetizing current does not actually contribute to the actual work output of the motor. It is the catalyst that
allows the motor to work properly. The magnetizing current and the leakage reactance can be considered
passenger components of current that will not affect the power drawn by the motor, but will contribute to the
power dissipated in the supply and distribution system.
Take for example a motor with a current draw of 100 Amps and a power factor of 0.75 The resistive component of
the current is 75 Amps and this is what the KWh meter measures. The higher current will result in an increase in
the distribution losses of (100 x 100) /(75 x 75) = 1.777 or a 78% increase in the supply losses.
In the interest of reducing the losses in the distribution system, power factor correction is added to neutralize a
portion of the magnetizing current of the motor. Typically, the corrected power factor will be 0.92 – 0.95
Power factor correction is achieved by the addition of capacitors in parallel with the connected motor circuits and
can be applied at the starter, or applied at the switchboard or distribution panel. The resulting capacitive current is
leading current and is used to cancel the lagging inductive current flowing from the supply.
Privacy & Cookies: This site uses cookies. By continuing to use this website, you agree to their use.
To find out more, including how to control cookies, see here: Cookie Policy
Displacement Static Correction (Static Compensation).
Close and accept
As a large proportion of the inductive or lagging current on the supply is due to the magnetizing current of
induction motors, it is easy to correct each individual motor by connecting the correction capacitors to the motor
starters.
With static correction, it is important that the capacitive current is less than the inductive magnetizing current of
the induction motor. In many installations employing static power factor correction, the correction capacitors are
connected directly in parallel with the motor windings.
When the motor is Off Line, the capacitors are also Off Line. When the motor is connected to the supply, the
capacitors are also connected providing correction at all times that the motor is connected to the supply. This
removes the requirement for any expensive power factor monitoring and control equipment.
In this situation, the capacitors remain connected to the motor terminals as the motor slows down. An induction
motor, while connected to the supply, is driven by a rotating magnetic field in the stator which induces current into
the rotor. When the motor is disconnected from the supply, there is for a period of time, a magnetic field
associated with the rotor. As the motor decelerates, it generates voltage out its terminals at a frequency which is
related to its speed.
The capacitors connected across the motor terminals, form a resonant circuit with the motor inductance. If the
motor is critically corrected, (corrected to a power factor of 1.0) the inductive reactance equals the capacitive
reactance at the line frequency and therefore the resonant frequency is equal to the line frequency. If the motor is
over corrected, the resonant frequency will be below the line frequency. If the frequency of the voltage generated
by the decelerating motor passes through the resonant frequency of the corrected motor, there will be high
currents and voltages around the motor/capacitor circuit. This can result in severe damage to the capacitors and
motor. It is imperative that motors are never over corrected or critically corrected when static correction is
employed.
Static power factor correction should provide capacitive current equal to 80% of the magnetizing current, which is
essentially the open shaft current of the motor.
The magnetizing current for induction motors can vary considerably. Typically, magnetizing currents for large two
pole machines can be as low as 20% of the rated current of the motor while smaller low speed motors can have a
magnetizing current as high as 60% of the rated full load current of the motor
Where the open shaft current cannot be measured, and the magnetizing current is not quoted, an approximate
level for the maximum correction that can be applied can be calculated from the half load characteristics of the
motor. It is dangerous to base correction on the full load characteristics of the motor as in some cases, motors
can exhibit a high leakage reactance and correction to 0.95 at full load will result in over correction under no load,
or disconnected conditions.
Static correction is commonly applied by using on e contactor to control both the motor and the capacitors. It is
better practice to use two contactors, one for the motor and one for the capacitors. Where one contactor is
employed, it should be up sized for the capacitive load. The use of a second contactor eliminates the problems of
resonance between the motor and the capacitors.
Induction motors, transformers and many other electrical loads require magnetizing current (kvar) as well as
actual power (kW). By representing these components of apparent power (kVA) as the sides of a right triangle, we
can determine the apparent power from the right triangle rule: kVA2 = kW2 + kVAR2.
To reduce the kva required for any given load, you must shorten the line that represents the kvar. This is precisely
what capacitors do. By supplying kvar right at the load, the capacitors relieve the utility of the burden of carrying
the extra kvar. This makes the utility transmission/distribution system more efficient, reducing cost for the utility
Privacy
and& Cookies: This site uses
their customers. cookies.
The ratio By continuing
of actual power toto apparent
use this website,
power you agree to
is usually their use. in percentage and is called
expressed
To find out more, including how to control cookies, see here: Cookie Policy
power factor.
Since power factor is defined as the ratio of KW to KVA, we see that low power factor results when KW is small in
relation to KVA. Inductive loads. Inductive loads (which are sources of Reactive Power) include:
1. Transformers
2. Induction motor
3. Induction generators (wind mill generators)
4. High intensity discharge (HID) lighting
These inductive loads constitute a major portion of the power consumed in industrial complexes.
Reactive power (KVAR) required by inductive loads increases the amount of apparent power (KVA) in your
distribution system .This increase in reactive and apparent power results in a larger angle (measured between
KW and KVA). Recall that, as increases, cosine (or power factor) decreases.
You want to improve your power factor for several different reasons. Some of the benefits of improving your
power factor include:
Inductive loads, which require reactive power, caused your low power factor. This increase in required reactive
power (KVAR) causes an increase in required apparent power (KVA), which is what the utility is supplying. So, a
facility’s low power factor causes the utility to have to increase its generation and transmission capacity in order
to handle this extra demand.
By lowering your power factor, you use less KVAR. This results in less KW, which equates to a dollar savings from
the utility.
Utilities usually charge customers an additional fee when their power factor is less than 0.95. (In fact, some
utilities are not obligated to deliver electricity to their customer at any time the customer’s power factor falls
below 0.85.) Thus, you can avoid this additional fee by increasing your power factor.
2) Increased system capacity and reduced system losses in your electrical system
By adding capacitors (KVAR generators) to the system, the power factor is improved and the KW capacity of the
system is increased.
For example, a 1,000 KVA transformer with an 80% power factor provides 800 KW (600 KVAR) of power to the
main bus.
By increasing the power factor to 90%, more KW can be supplied for the same amount of KVA.
1000
Privacy KVA =
& Cookies: This site(900 KW)2
uses + ( ?
cookies. ByKVAR)2
continuing to use this website, you agree to their use.
KVAR = 436
To find out more, including how to control cookies, see here: Cookie Policy
The KW capacity of the system increases to 900 KW and the utility supplies only 436 KVAR.
Uncorrected power factor causes power system losses in your distribution system. By improving Close and
your accept
power
factor, these losses can be reduced. With the current rise in the cost of energy, increased facility efficiency is very
desirable. And with lower system losses, you are also able to add additional load to your system.
3) Increased voltage level in your electrical system and cooler, more efficient motors
As mentioned above, uncorrected power factor causes power system losses in your distribution system. As
power losses increase, you may experience voltage drops. Excessive voltage drops can cause overheating and
premature failure of motors and other inductive equipment. So, by raising your power factor, you will minimize
these voltage drops along feeder cables and avoid related problems. Your motors will run cooler and be more
efficient, with a slight increase in capacity and starting torque.
The compensation for motor should be calculated taking the details from the rating plate of motor Or
the capacitor should be rated for 1/3 of HP
Fix compensation should be provided to take care of power transformer. Power and distribution transformers,
which work on the principle of electro-magnetic induction, consume reactive power for their own needs even
when its secondary is not connected to any load. The power factor will be very low under such situation. To
improve the power factor it is required to connect a fixed capacitor or capacitor bank at the LT side of the
Transformer. For approximate kVAr of capacitors required
If the installation is having various small loads with the mixture of large loads then the APFC should be
recommended. Note that APFC should have minimum step rating of 10% as smaller step.
If loads
Privacy are small
& Cookies: then
This site thecookies.
uses capacitor
By should be connected
continuing parallel you
to use this website, to load.
agreeThe connection
to their use. should be such that
whenever the loads are switched on the capacitor also switches
To find out more, including how to control cookies, see here: Cookie Policy on along with the load.
Note that APFC panel can maintain the power factor on L.T side of transformer and it is necessary to provide fix
compensation for Power transformer. Close and accept
In case there is no transformer in the installation, then the C.T for sensing power factor should be provided at the
incoming of main switch of the plant.
Suppose Actual P.F is 0.8, Required P.F is 0.98 and Total Load is 516KVA.
Power factor = kwh / kvah
kW = kVA x Power Factor
= 516 x 0.8 = 412.8
Required capacitor = kW x Multiplying Factor
= (0.8 x 516) x Multiplying Factor
= 412.8 x 0.547 (See Table to find Value according to P.F 0.8 to P.F of 0.98)
= 225.80 kVar
Target PF
0.6 0.9 0.91 0.92 0.93 0.94 0.95 0.96 0.97 0.98 0.99 1
0.6 0.849 0.878 0.907 0.938 0.970 1.005 1.042 1.083 1.130 1.191 1.333
0.61 0.815 0.843 0.873 0.904 0.936 0.970 1.007 1.048 1.096 1.157 1.299
0.62 0.781 0.810 0.839 0.870 0.903 0.937 0.974 1.015 1.062 1.123 1.265
0.63 0.748 0.777 0.807 0.837 0.870 0.904 0.941 0.982 1.030 1.090 1.233
0.64 0.716 0.745 0.775 0.805 0.838 0.872 0.909 0.950 0.998 1.058 1.201
0.65 0.685 0.714 0.743 0.774 0.806 0.840 0.877 0.919 0.966 1.027 1.169
0.66 0.654 0.683 0.712 0.743 0.775 0.810 0.847 0.888 0.935 0.996 1.138
0.67 0.624 0.652 0.682 0.713 0.745 0.779 0.816 0.857 0.905 0.966 1.108
0.68 0.594 0.623 0.652 0.683 0.715 0.750 0.787 0.828 0.875 0.936 1.078
0.69 0.565 0.593 0.623 0.654 0.686 0.720 0.757 0.798 0.846 0.907 1.049
0.7 0.536 0.565 0.594 0.625 0.657 0.692 0.729 0.770 0.817 0.878 1.020
0.71 0.508 0.536 0.566 0.597 0.629 0.663 0.700 0.741 0.789 0.849 0.992
0.72 0.480 0.508 0.538 0.569 0.601 0.635 0.672 0.713 0.761 0.821 0.964
0.73 0.452 0.481 0.510 0.541 0.573 0.608 0.645 0.686 0.733 0.794 0.936
0.78 0.318 0.347 0.376 0.407 0.439 0.474 0.511 0.552 0.599 0.660 0.802
0.79 0.292 0.320 0.350 0.381 0.413 0.447 0.484 0.525 0.573 0.634 0.776
0.8 0.266 0.294 0.324 0.355 0.387 0.421 0.458 0.499 0.547 0.608 0.750
0.81 0.240 0.268 0.298 0.329 0.361 0.395 0.432 0.473 0.521 0.581 0.724
0.82 0.214 0.242 0.272 0.303 0.335 0.369 0.406 0.447 0.495 0.556 0.698
0.83 0.188 0.216 0.246 0.277 0.309 0.343 0.380 0.421 0.469 0.530 0.672
0.84 0.162 0.190 0.220 0.251 0.283 0.317 0.354 0.395 0.443 0.503 0.646
0.85 0.135 0.164 0.194 0.225 0.257 0.291 0.328 0.369 0.417 0.477 0.620
0.86 0.109 0.138 0.167 0.198 0.230 0.265 0.302 0.343 0.390 0.451 0.593
0.87 0.082 0.111 0.141 0.172 0.204 0.238 0.275 0.316 0.364 0.424 0.567
0.88 0.055 0.084 0.114 0.145 0.177 0.211 0.248 0.289 0.337 0.397 0.540
0.89 0.028 0.057 0.086 0.117 0.149 0.184 0.221 0.262 0.309 0.370 0.512
0.9 0.029 0.058 0.089 0.121 0.156 0.193 0.234 0.281 0.342 0.484
0.91 0.030 0.060 0.093 0.127 0.164 0.205 0.253 0.313 0.456
Measurement of Voltage:
Privacy & Cookies: This site uses cookies. By continuing to use this website, you agree to their use.
Example
To find : including how to control cookies, see here: Cookie Policy
out more,
1. Name plate details – 15kVAr, 3 phases, 440v, and 50Hz capacitor.
Measured voltage – 425v , Measured frequency – 48.5Hz Close and accept
Kvar = (fM / fR) x (VM / VR)2 x kvar
Kvar = (48.5/50) x (425 / 440)2 x 15
= 13.57kVAr.
kVAr 440V Line current 440V kVAr at 415V Line Current at Measured capacitance across
415V two terminals with third terminal
open.(Micro farad) 440V
kVAr 415V Line current 415V kVAr at 440V Line Current at Measured capacitance across
415V two terminals with third terminal
open.(Micro farad) 415V
l = kvar x 103 / ( 3 X V ) L L
Example:
15kVAr, 3 phase, 440v, 50Hz capacitor.
l = kVAr x 103 / ( 3 X V ) L L
l = (15 x 1000) / (1.732 x 440) L
l = 19.68AMPs L
15kVAr, 3 phases, 415v, 50Hz capacitor
l = kVAr x 103/ ( 3 X V ) L L
l = (15 x 1000) / (1.732 x 415) L
l = 20.87 Amps
Discharge of Capacitor:
L.T power capacitors are provided with discharge resistor to discharge the capacitor which is limited to one min.
The resistor are provided as per clause No-7.1 of IS 13340-1993.
Switch off the supply to the capacitor and wait for 1 minute and then short the terminals of capacitor to ensure
that the capacitor is completely discharged.
This shorting of terminals ensures the safety while handling the capacitor
Discharge of capacitor also becomes necessary for the safety of meter used for capacitance measurement.
Use suitable size lugs for connecting the cable to the terminals of capacitor.
Ensure that there is no loose connection: As loose connection may lead to failure of capacitor / insulation break
down of cable.
Use proper tools for connection / tightening.
Ensure that the capacitor is mounted vertically.
The earthing of capacitor should be done before charging.
The applied voltage should not exceed more than 10%. Refer technical specification of capacitor.
The capacitor should be provided with the short circuit protection device as indicated in following Table
5 12 Amps 12 Amps
10 32 Amps 32 Amps
Privacy & Cookies: This site uses cookies. By continuing to use this website, you agree to their use.
To find out more, including how to control cookies, see here: Cookie Policy
12.5 32 Amps 32 Amps
25 63 Amps 63 Amps
The capacitor should be provided with suitable designed inrush current limiting inductor coils or special capacitor
duty contactors. Annexure d point no d-7.1 of IS 13340-1993
Once the capacitor is switched off it should not be switched on again within 60 seconds so that the capacitor is
completely discharged. The switching time in the relay provided in the APFC panel should be set for 60 seconds
for individual steps to discharge. Clause No-7.1 of IS 13340-1993
If the capacitor is switched manually or if you are switching capacitors connected in parallel with each other then
“ON” delay timer (60sec) should be provided and in case of parallel operation once again point No 1 should be
taken care. Clause No-7.1 of IS 13340-1993
The capacitor mounted in the panel should have min gap of 25-30 mm between the capacitor and 50 mm around
the capacitor to the panel enclosure.
In case of banking a min gap of 25mm between the phase to phase and 19mm between the phases to earth
should be maintained. Ensure that the banking bus bar is rated for 1.8 times rated current of bank.
The panel should have provision for cross ventilation, the louver / fan can be provided in the care Annexure d point
No d-3.1 IS 13340-1993
For use of reactor and filter in the panel fan should be provided for cooling.
Short circuit protection device (HRC fuse / MCCB) should not exceed 1.8 x rated current of capacitor.
In case of detuned filter banks MCCB is recommended for short circuit protection.
Supply voltage to capacitor should be checked for any over voltage. This can be verified of voltage stabilizers are
connected in the installation, light fitting are regularly replaced, this indicates the over voltage.
It is generally found that i.c. base APFC relays are big in size as compared to microprocessor relays. These ic
based relays are found to be malfunctioning. The capacitors are switched “OFF” & “ON” very fast without
discharge of capacitor, leading to high current drawn by capacitors. Such operation leads to failure of capacitor.
Check the time set in APFC relays connected for the operation, as various make of relays are preset for 15-20 sec.
This setting of time should be verified in presence of customer at panel with operation of relay. The switching of
capacitor from one step to another should have min time gap of 60 second. This should be physically watched.
No replacement shall be considered in such cases where in the time is set below 60sec.
The chattering of contactor can also lead to failure of capacitor. This chattering may happen due to low voltage or
loose connection to contactor coils etc. If the capacitors are operated in manual mode using push button, check
whether the on delay timer is provided in the individual steps. Verify whether the time set of 60sec or not. No
Privacy & Cookies: This
replacement site be
should uses cookies. By
considered incontinuing
such casesto where
use thisinwebsite, youisagree
the timer to their60sec.
set below use. or it is not provided.
To find out more, including how to control cookies, see here: Cookie Policy
Check whether capacitor duty contactor is provided or if the inrush limiting inductor coils are used. This becomes
important in case the capacitors are switched ‘ON’ with the other capacitor connected in the same bus. Parallel
Close and accept
switching of capacitor is generally found in capacitor panels having APFC and push buttons for switching “on” &
“off”.
Check whether the harmonic is present. For this take a fresh capacitor, charge the capacitor and then calculate
whether the current drawn by capacitor is within the limit. If the current is more, then it may be due to over
voltage. If not then it is clear that the capacitor is drawing high current due to presence of harmonics.
The harmonics in the plant can be easily found If the plant has loads using power electronic components such as
ups, drives and furnace. Loads such as are welding, cfl tubes and electronic controlled machines also generate
harmonics. Note that neighboring plant connected to the grid may also affect the capacitors by importing the
harmonic. (Harmonic voltage easily travels through the grid from one installation to another, the effect of such
voltage leads to failure of capacitor).
Check other points given in installation guide line of capacitor.
In case the installation is having MD-XL capacitors with connected loads generating harmonics then the capacitor
may be drawing additional 30% current. In such conditions the fuses may blow out cable will heat up and
Temperature of capacitor will be also increased. Ensure that the fuse rating should not be increased. The
switchgear and cable size should be suitably increased. The capacitor will continue to work but the life of
capacitor may not be longer. This clearly indicates that the capacitor is over loaded and if required the reactor
Should be provided for controlling the over current.
Check the short circuit protection device. Please note that you may come across the customer using fuses
almost double the current rating of capacitors. This is generally found in the plants having harmonic problems
and the installations having hired local electricians for maintenance.
Check the date of installation of capacitor and type of additional load being connected after installation of
capacitors. As it is observed in certain cases that the type of capacitor was selected without considering future
expansion of machineries in the plant. Some time these machines are found to be generating harmonic affecting
the life of capacitor.
No replacement should be considered if capacitor is failed due to harmonics and customer has used normal
capacitors without consulting Engineers.
Capacitor voltage rating is equal to the max voltage recorded in the installation.
Capacitor is mounted vertically.
Earthing at two different points is done.
Proper lugs are used for termination.
Proper size of cable is used.
Ph- ph gap is 25mm and ph-earth is 19mm.
The bus bar used for banking is 1.8 x rated current of the bank.
Cross ventilation provision is provided in the installation area / in the panel.
The plant has the facility to trip the capacitor under over voltage conditions.(10%)
Capacitor is provided with suitable size of HRC fuse / MCCB rating for protection.
Suitable inrush current device is connected in series with contactor to limit the inrush current or capacitor duty
contactor is used.
Capacitor is provided with suitable on delay timer to ensure that the capacitor is not switched on within 60sec.
After it is switched off.
Capacitor is provided with insulating cover to ensure the safety.
Capacitor is installed in the area free from entry of dust, chemical fume and rain water.
APFC relay provided in the panel is set for 60 second. ‘On delay’ provided are also set for 60 second.
The filter banks are provided with MCCB for protection apart from above points.
Privacy & Cookies: This site uses cookies. By continuing to use this website, you agree to their use.
The MCCB should be set for 1.3 x rated current of filter bank
To find out more, including how to control cookies, see here: Cookie Policy
Rate this:
42 Votes
Share this:
Like
Related
Total Losses in Power Demand Factor-Diversity Factor- Size and Location of Capacitor
Distribution & Transmission Utilization Factor-Load Factor in Electrical System-(Part 2)
Lines-Part 1 With 87 comments With 13 comments
With 33 comments
« Previous Next »
Privacy & Cookies: This site uses cookies. By continuing to use this website, you agree to their use.
Leave a Reply
To find out more, including how to control cookies, see here: Cookie Policy
Your email address will not be published. Required fields are marked *
Close and accept