User Manual: Free Cooling System
User Manual: Free Cooling System
FREE
COOLING
SYSTEM
USER
MANUAL
-‐
Provided
by
Sunstone
Power
Industry
Co.,Ltd
Contents
1
Composition
......................................................................................................................................................................................
3
1.0 Composition
1.
LCD
Screen
2.
Louver
1
3.
Louver
2
Figure
1
:
Host
Appearance
Figure
2
:
IP55
Inlet
Louver
Table
1
:
Accessories
3 IP55 Louver 1
4 Exhaust Window 1
5 Rain Cover 1
1.
Door
Sensor
1
2.
Wind
Pressure
Sensor
1
==>>
Barometer
3.
LCD
Screen
4.
Main
Control
Board
5.
Fan
1
6.
Wind
Pressure
Sensor
2
==>>
Barometer
7.
Louver
1
8.
Fan
2
9.
Door
Sensor
2
10.
Louver
2
Figure
3
:
Internal
Construction
Figure
4
:
Wiring
Diagram
User
can
view
and
set
the
parameters
of
the
device
through
the
panel.
Under
normal
mode,
the
device
works
in
auto
mode.
B u tto n s a r e :
【ESC】 :Cancel the current operation, returning to the previous level
【SET】
:Enter
the
main
setting
interface
Display:External
Room
Temperature;
Current
Power
Percentage
Between
Upper
and
Lower
Fan;Internal
Room
Temperature
&
Humidity
The
display
time
of
the
standby
page
is
10
minutes,
after
that
the
system
is
still
working
normally
but
LCD
screen
will
be
closed.
You
can
press
any
button
to
wake
up
to
standby
display
state.
Figure
5
:
Function
Module
Diagram
4.1.4.1
Press【 SET】on
the
standby
page,
enter
the
default
password
“1234”
through【 UP】,【 DOWN】and
【 OK】 buttons
to
enter
into
the
setting
page.
4.1.4.2
Use【 UP】or【 DOWN】
button
to
select
the
parameters
needed
to
set.
And
then
press【 OK】to
enter
the
page.
4.1.4.3
Through【 UP】and【 DOWN】button
to
change
the
digital
value
at
the
cursor.
Then
enter【 OK】
to
confirm
or【ESC】to
return.
4.1.4.4
Press【ESC】to
exit
the
current
parameter
setting
page
to
selection
menu
page.
3 1 Fan Max Speed 70% 0%~100% Max Speed for Single Fan
4 2 Fan ON 32°C 19°C~40°C The Min Temperature that 2 Fans Operates
5 2 Fan Full Speed 38°C 30°C~80°C Fans Full Speed Starting Condition
8 Fan OFF H Ri 95%RH 80%RH ~99%RH Internal Humidity Alarm Value
11
OTLAV
5°C
0°C~10°C
Low
Outdoor
Temperature
Alarm
Value
4.1.5.1 On the main page, press【 ESC】 to enter the system information view page.
4.1.5.2
Through【 UP】 and【 DOWN】 to
move
the
cursor
to
device
information
item
and
display
the
information
item.
Press【 ESC】 to
back
to
the
main
menu
page.
4.1.6.1 On Standby page, use【 UP】 and【 DOWN】 to view the fan operation information.
This
system
is
FCU
monitoring
system,
mainly
monitoring
the
parameters
of
the
intelligent
new
fan,
including
fan
speed
/
status,
fan
safety
door
status,
air
pressure,
and
indoor/outdoor
temperature.
Meanwhile,
it
can
also
provide
the
functions
as
parameters
setting,
fan
test
and
system
upgrade
etc.
2-‐5
minutes
after
the
fan
is
connected
to
the
computer
through
the
cable,
the
FCU
monitoring
system
will
automatically
starts.
Use
any
browser
(recommend
using
Chrome,
Firefox,
or
higher
version
of
IE
browser),
at
address
bar
enter
the
system
IP
address
to
access
the
system,
for
example:
http:
//192.168.3.92
.
4.2.2.1 Exit
Close the web page or browser to exit the system safely.
Entering
IP
address
in
the
browser
address
bar
to
visit
the
monitoring
interface
of
the
system
running
status
.
On
this
page,
you
can
view
all
the
system
parameters
which
will
be
updated
according
to
the
system
running
state
with
once
per
second
frequency.
At
the
same
time,
this
interface
also
provides
system
alarm
function,
if
any
parameter
is
abnormal,
there
will
appear
a
red
word
alarm
on
the
bottom
of
the
page,
and
display
the
alarm
content.
Alarm
information
will
be
updated
according
to
the
system
running
state.
As
shown
below:
Figure
6
:
System
Parameter
Monitoring
Page
The
system
provides
the
function
of
viewing
device
information.
Click
the
[Device
Info]
button
through
the
menu
bar
at
the
bottom
of
the
system
page
to
enter
the
system
device
information
interface.
In
this
case,
the
user
can
view
the
machine
model,
device
serial
number,
motherboard
hardware
version
number,
motherboard
software
version
number,
SNMP
hardware
version
number,
SNMP
software
version
number
and
so
on.
As
shown
below:
Figure
7
:
Device
Info
(1)Administrator
login
When
system
setting,
administrator
authentication
is
needed.
Click
the
[General
Setting]
button
on
the
home
page
to
jump
to
the
general
settings
page.
Then
the
system
will
check
the
administrators’
login
status.
If
not
logged
in
or
login
status
is
invalid,
then
it
will
redirect
to
administrator
login
interface;
To
log
in,
you
need
to
enter
the
user
name
and
password,
and
root
is
the
user
name
with
the
initial
password
123456.
If
succeed,
you
will
see
the
project
settings
page;
or
it
will
return
to
the
login
page
to
try
again.
(2)General
Setting
The
general
settings
page
provides
the
viewing
and
modifying
functions
of
the
system
related
parameters.
Including
IP
address,
subnet
mask,
gateway,
server
IP,
system
date,
system
time
and
so
on.
When
modifying
such
parameters,
you
need
to
modify
them
in
the
appropriate
format.
Or
the
modification
will
be
unsuccessful
or
cause
a
system
error.
When
modifying
the
system
date,
if
the
time
selector
does
not
appear
or
is
abnormal,
please
use
the
higher
version
browser
and
try
again.
Edit
the
content
needed
to
be
modified,
then
click
the
"Save
Configuration"
button
to
save
the
corresponding
contents.
As
shown
below:
Figure
8
:
General
Setting
(3)Modify Password
This
system
provides
the
function
of
modifying
the
administrator
password.
Click
the
"Modify
password"
button
on
the
system
settings
page
to
redirect
to
the
Modify
Password
page,
where
you
can
modify
the
administrator
password
but
can
not
modify
the
user
name.
When
modifying
the
password,
we
need
to
verify
whether
the
original
password
is
matched,
and
whether
the
new
password
entered
twice
is
consistent.
If
the
verification
doesn’t
pass,
the
password
modification
will
be
failed.
As
shown
below:
Figure
9
:
Modify
Test
Password
When
engineering
setting,
we
need
to
enter
/
QhSeerMAdmin.html
/
into
the
address
bar
to
check
the
administrators’
login
status;
if
not
logged
in
or
login
status
is
invalid,
then
it
will
redirect
to
administrator
login
interface;
To
log
in,
you
need
to
enter
the
user
name
and
password,
and
root
is
the
user
name
with
the
initial
password
123456.
If
succeed,
you
will
see
the
project
settings
page;
or
it
will
return
to
the
login
page
to
try
again.
You
can
also
set
the
fan
serial
number,
asset
number
and
production
date,
etc.
Similarly,
the
modified
parameters
should
comply
with
the
relevant
provisions,
otherwise
the
change
will
be
unsuccessful.
Edit
the
content
you
need
to
modify,
then
click
the
"Save
configuration"
button
to
save
them.
As
shown
below:
(2)Engineering Setting
Each
parameter
can
be
set
on
the
page
of
engineering
setting,
including
the
alarm
threshold
(gate
temperature
alarm
value,
filter
pressure
alarm
value,
etc.),
fan
opening
or
closing
temperature
and
so
on.
Meanwhile,
you
can
also
set
the
fan
temperature
control
strategy.
This
system
provides
three
modes:
auto
mode
(ladder
temperature
control),
manual
mode,
and
constant
temperature
control
mode.
Select
auto
mode,
you
need
to
set
the
ladder
temperature
control
value,
that
is,
the
temperature
per
1
degree
Celsius,
the
percentage
of
speed
the
fan
increases;
select
manual
mode,
you
need
to
set
the
fixed
air
volume
percentage;
select
the
constant
temperature
mode,
you
need
to
set
the
constant
temperature
value.
Similarly,
when
modifying
parameters,
you
must
comply
with
the
relevant
provisions,
or
it
will
be
failed.
Edit
the
content
needed
to
be
modified,
click
[Save
configuration]
button
to
save
the
corresponding
contents.
As
shown
below:
Figure
10
:
Engineering
Setting
(3)Modify Password
The
system
allows
the
administrator
to
change
the
password,
clicking
"Modify
password"
button
on
the
engineering
setting
page,
then
it
will
redirect
to
the
“modify
password”
page,
where
you
can
modify
the
password
but
not
user
name
also.
(4)System Upgrade
Upgrade
function
is
provided.
Enter
the
page
of
“engineering
setting”
and
click
"System
Update"
button
to
visit
the
relevant
interface.
This
interface
requires
administrator’s
authentication,
if
the
login
status
is
not
logged
in
or
invalid,
then
it
will
redirect
to
the
administrator
login
interface
to
log
in.
System
upgrade
is
divided
into
server
system
upgrade,
main
board
upgrade,
SNMP
upgrade.
The
entry
of
these
three
types
are
same
to
the
upgrade
operation.
Each
upgrade
package
will
be
provided
by
the
Manufacturer.
When
upgrading
Server,
the
upgrade
package
should
be
named
systemUpdatePackageV1.0.0.tar.
system
Update
Package
V
can
not
be
changed,
and
1.0.0
which
is
the
version
number
can
be
revised;
When
upgrading
motherboard,
the
upgrade
package
should
be
named
boardUpdatePackageV1.0.0.tar,
board
Update
Package
V
is
fixed
,
and
1.0.0
which
is
the
version
number
can
be
revised;
For
SNMP
upgrade,
the
upgrade
package
is
named
netSnmpV1.0.0.tar,
net
SNMP
V
can
not
be
modified,
the
version
number
1.0.0.
can
be
adjusted.
Manual
modification
is
prohibited
to
change
the
upgrade
package
name
(including
suffix),
or
it
will
cause
upgrade
failure
and
system
crash.
On
the
upgrade
page,
select
the
upgrade
package,
then
click
“Upgrade
Now”
button
to
enter
the
system
upgrade.
This
process
may
last
2-‐5
minutes.
In
the
process
of
system
upgrade,
please
ensure
that
the
original
systems
are
running
normally,
and
the
network
is
stable
and
continuous
power
supply.
After
completing
the
upgrade,
the
system
will
restart
automatically
and
reboot
to
re-‐enter
the
system.
As
shown
below:
Figure
11
:
System
Upgrade
Engineering
setting
module
provides
the
reset
function
for
system
parameters.
Clicking
the
"System
Reset"
button
to
enter
the
page
to
reset
all
the
variable
parameters,
including
system
settings
and
engineering
settings.
When
succeed,
the
system
will
automatically
restart.
This
process
will
last
2-‐5
minutes.
After
restarting,
just
input
the
IP
again
to
enter
the
system.
Wifi
visiting
is
also
provided.
Turn
on
the
system
wifi,
then
you
can
visit
the
system
through
mobile
phone
and
other
mobile
devices.
It
should
be
noted
that
access
to
the
system
through
the
wifi
system,
you
need
the
wireless
card
ip
(for
example:
http:
//
192.168.1.99)
,
but
not
using
the
cable
network
card
ip
(for
example:
http://192.168.3.92).
On
engineering
setting
page,
click
“
Modify
wifi”
to
enter
the
modify
wifi
configuration
interface.
You
can
modify
the
wifi
name
and
password.
When
modifying
wifi
name,
1-‐8
digits
or
letters
is
supported,
but
not
support
Chinese,
Japanese
and
Korean
etc.
When
modifying
the
wifi
password,
8-‐16
digits
or
letters
is
supported.
If
not
meet
the
input
conditions,
the
modification
will
be
failed.
As
shown
below:
Figure
12
:
Modify
WIFI
Configuration
The
system
provides
system
testing
function.
Enter
ip
/
commonTestEntryPage.html
(for
example:
http:
//192.168.3.92/commonTestEntryPage.html)
in
the
address
bar
to
visit
the
public
portal
page
of
test
mode.
The
system
test
is
divided
into
single
device
test
and
system
environment
simulation.
You
can
choose
one
to
enter.
After
entering
the
test
mode,
system
tester
identification
should
be
verified.
If
not
logged
in
or
login
status
is
invalid,
then
it
will
redirect
to
system
tester
login
interface.
Under
single
device
test
mode,
you
can
control
the
fan
running
state,
including
fan
speed
control,
relay
status
and
so
on.
At
the
same
time,
you
can
see
the
parameters
changes
according
to
the
fan
speed
changes.
When
the
test
is
completed,
click
the
[Exit
Test
Mode]
button
to
exit
the
single
device
test
mode.
Do
not
close
the
test
mode
page
directly.
After
exiting
the
test
mode,
the
system
will
continue
running
before
entering
the
test
mode.
If
the
operation
mode
does
not
return
to
the
previous
state,
click
the
[Exit
Single
Device
Test]
button
on
the
home
page
to
exit
the
single
device
test
mode.
As
shown
below:
Figure
13
:
Single
Device
Test
System
Environment
Simulation
means
this
system
providesthe
function
of
simulation
of
the
fan
operating
environment.
When
entering
the
function
module,
it
can
real-‐time
simulate
the
fan
operating
environment
inside
and
outside
door
temperature,
the
pressure
value,
security
door
status,
and
auxiliary
input,
etc.
After
inputting
all
the
simulation
parameters,
click
[Test
Now]
to
enter
the
simulation,
and
you
can
view
the
parameters
of
the
fan
running
under
the
simulation
environment.
Click
the
“Exit
Test
Mode”
button
to
exit
the
system
environment
simulation.
Do
not
close
the
test
mode
page
directly.
As
shown
below:
Figure
14
:
System
Environment
Simulation
Control
logic
refers
to
the
control
logic
under
[1.AUTO
MODE],
[2.MANU
MODE]
the
fan
run
at
the
manually
set
the
fan
power
.
l When
the
indoor
and
outdoor
temperature
difference>
(1.TD0),
the
fan
is
turned
ON
l When
the
indoor
and
outdoor
temperature
difference
<(2.TD1),
the
fan
is
OFF
l When
the
fan
is
OFF
(within
the
above
temp
range)
Indoor
temp
>
(3.T0)
value,
fan
run
minimum
35%
l Temperature
difference
of
1
degree
Celsius,
fan
power
35%
+
(5.TDFon)
*
temp
difference.
Up
to
95%
l When
the
door
1
or
door
2
open
is
detected,
the
corresponding
fan
is
turned
OFF
l When
the
indoor
temperature
grater
than
(4.THA),
the
fan
run
100%,
output
alarm
l When
the
filter
inside
and
outside
the
pressure
difference
grater
than
(6.F1HA),
output
alarm
l Current
pressure
inside
and
outside
the
filter
grater
than
(7.F2HA),
output
alarm
5.2Alarm Output
There
are
three
ways
to
output
system
alarm,
through
the
relay
output
alarm,
LCD
panel
indicator
alarm
output,
SNMP
card
alarm
output.
Table
5
:
Relay
Alarm
Output
Table
E2
System
Status
Alarm:
High
Relative
Humidity
Alarm