User Manual: Free Cooling System

The document provides a user manual for a free cooling system. It describes the system components, including the LCD screen, louvers, fans, sensors and control board. It outlines the performance parameters of temperature and humidity detection. It also provides instructions for operating the control panel and Ethernet interface, and describes the control logic and alarm outputs.

Uploaded by

Ma Zhenfa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
128 views22 pages

User Manual: Free Cooling System

The document provides a user manual for a free cooling system. It describes the system components, including the LCD screen, louvers, fans, sensors and control board. It outlines the performance parameters of temperature and humidity detection. It also provides instructions for operating the control panel and Ethernet interface, and describes the control logic and alarm outputs.

Uploaded by

Ma Zhenfa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 22

 

 
FREE  COOLING  SYSTEM  
   
                 
 
USER  MANUAL  
 
 
 
 
 
 
  -­‐  Provided  by  Sunstone  Power  Industry  Co.,Ltd  
   

 
 
Contents  
1  Composition  ......................................................................................................................................................................................  3  

1.1  Product  View  .......................................................................................................................................................................  3  

1.2  Accessories  Table  ..............................................................................................................................................................  4  

1.3  Machine  Disassembly  ......................................................................................................................................................  5  

2  Performance  Parameter  ..............................................................................................................................................................  6  

3  Electrical  Wiring  Diagram  of  Board  .......................................................................................................................................  6  

4  Operation  Guide  ..............................................................................................................................................................................  7  

4.1  Panel  Operation  .................................................................................................................................................................  7  

4.1.1  Panel  Introduction  ...............................................................................................................................................  7  

4.1.2  Standby  Page  ..........................................................................................................................................................  8  

4.1.3  Function  Tree  .........................................................................................................................................................  9  

4.1.4  Parameter  Setting  ..............................................................................................................................................  10  

4.1.5  Equipment  Information  ...................................................................................................................................  11  

4.1.6  Operating  Status  .................................................................................................................................................  12  

4.2  Ethernet  Interface  Operation  .....................................................................................................................................  13  

4.2.1  System  Overview  ................................................................................................................................................  13  

4.2.2  System  Start  up  and  Exit  .................................................................................................................................  13  

4.2.3  System  Common  Function  .............................................................................................................................  13  

4.2.4  System  Testing  ....................................................................................................................................................  19  

5  Control  Logic,  Input  &  Output  .................................................................................................................................................  21  

5.1Control  Logic  ......................................................................................................................................................................  21  

5.2  Alarm  Output  ....................................................................................................................................................................  21  

 
   

 
 

1.0   Composition  

1.1     Product  View  

 
 
1.   LCD  Screen   2.   Louver  1   3.   Louver  2  
 
Figure  1  :  Host  Appearance  

 
 

 
Figure  2  :     IP55  Inlet  Louver  

1.2  Accessories  Table  

Table  1  :  Accessories  
 

No.   Description   Quantity  


1   Host   1  

2   Temperature  &  Humidity  Sensor  Module   1  

3   IP55  Louver   1  

4   Exhaust  Window   1  

5   Rain  Cover   1  

 
 

1.3  Machine  Disassembly  

 
1.   Door  Sensor  1                 2.     Wind  Pressure  Sensor  1  ==>>  Barometer               3.     LCD  Screen  
4.   Main  Control  Board       5.     Fan  1                         6.     Wind  Pressure  Sensor  2  ==>>  Barometer  
7.     Louver  1                         8.     Fan  2               9.     Door  Sensor  2                           10.     Louver  2  
 
Figure  3  :  Internal  Construction  

 
 

2.0   Performance  Parameters  

l Outdoor  Temperature  Detection:-­‐50℃~150℃(accuracy±1%)  


l Indoor  Temperature  Detection:-­‐40℃~125℃(accuracy±0.1%)  
l Indoor  Humidity  Detection:0%-­‐99%(accuracy±3%)  
l Air  Pressure  Difference  Detection  (Inside  and  Outside  Filter):50-­‐500pa(precision  10pa)  
l Cabinet  Open  Switch  Detection:2  way  
l Alarm  Input  Point:3  way  
l Alarm  Output  Point:3  way  
l Communication:TCP  
l Power:48VDC±10%,power  consumption  is  less  than  360W  
l Working  Environment  Temperature:10℃~45℃  
l Working  Environment  Humidity:30%~95%  

3.0   Electrical  Wiring  Diagram  of  Board  

 
 

 
Figure  4  :  Wiring  Diagram  

4.0   Equipment  Operation  Guide  

4.1   Panel  Operation  

4.1.1  Panel  Introduction  

User   can   view   and   set   the   parameters   of   the   device   through   the   panel.   Under   normal   mode,   the   device  
works  in  auto  mode.  
 

B u tto n s  a r e :  

【ESC】     :Cancel  the  current  operation,  returning  to  the  previous  level  

【OK】   :Confirm  the  current  operation  

 
 
【SET】   :Enter  the  main  setting  interface  

【UP】   :Forward  the  current  number,  forward  the  current  page  

【DOWN】  :Backward  the  current  number,  backward  the  current  page  


 
2  combination  keys  are:  
【ESC+OK】   :ON,   Turn  ON  
【SET+UP】   :OFF,     Turn  OFF  
 
2  LED  lights  are:  
Green  for  power  indicator  
Red  for  system  alarm  indicator  

4.1.2  Standby  Page  

Display:External  Room  Temperature;  Current  Power  Percentage  Between  Upper  and  Lower  Fan;Internal  
Room  Temperature  &  Humidity    
 
The  display  time  of  the  standby  page  is  10  minutes,  after  that  the  system  is  still  working  normally  but  LCD  
screen  will  be  closed.  You  can  press  any  button  to  wake  up  to  standby  display  state.  

 
 

4.1.3  Function  Tree  

 
Figure  5  :  Function  Module  Diagram  

 
 

4.1.4  Parameter  Setting  

4.1.4.1    Press【 SET】on  the  standby  page,  enter  the  default  password  “1234”  through【 UP】,【 DOWN】and
【 OK】 buttons  to  enter  into  the  setting  page.  
 
4.1.4.2    Use【 UP】or【 DOWN】   button  to  select  the  parameters  needed  to  set.  And  then  press【 OK】to  enter  
the  page.  
 
4.1.4.3    Through【 UP】and【 DOWN】button  to  change  the  digital  value  at  the  cursor.  Then  enter【 OK】   to  
confirm  or【ESC】to  return.  
 
4.1.4.4    Press【ESC】to  exit  the  current  parameter  setting  page  to  selection  menu  page.    

Table  2  :  Parameters  Table  


No   Parameter   Default   Description  
Range  
Value  
Auto1:  Ladder  Auto  Temperature  Control  
1   Mode  Set   AUTO1     Manu:  Manual  Air  Temperature  Control  
Auto2:  Constant  Temperature  Control  Mode  

The  Minimum  Temperature  that  Single  Fan  


2   1  Fan  ON     25°C   19°C~40°C  
Operates  

3   1  Fan  Max  Speed   70%   0%~100%   Max  Speed  for  Single  Fan  

4   2  Fan  ON     32°C   19°C~40°C   The  Min  Temperature  that  2  Fans  Operates  

5   2  Fan  Full  Speed     38°C   30°C~80°C   Fans  Full  Speed  Starting  Condition  

Fan  Starting  Condition-­‐Internal  &  External  


6   Fan  ON  (ΔT)   2°C   2°C~6°C  
Temperature  Difference  

Fan  Closing  Condition-­‐Internal  &  External  


7   Fan  OFF  (ΔT)   1°C   0°C~2°C  
Temperature  Difference  

8   Fan  OFF  H  Ri   95%RH   80%RH  ~99%RH   Internal  Humidity  Alarm  Value  

9   TLAV   5°C   0°C~10°C   Low  Indoor  Temperature  Alarm  Value    

10   ITHAV   45°C   30°C~80°C   High  Indoor  Temperature  Alarm  Value  

 
 
11   OTLAV   5°C   0°C~10°C   Low  Outdoor  Temperature  Alarm  Value    

12   OTHAV   45°C   30°C~80°C   High  Outdoor  Temperature  Alarm  Value  

13   F1BAV   420pa   100-­‐500pa   Upper  Filter  Alarm  Value  

14   F2BAV   420pa   100-­‐500pa   Lower  Filter  Alarm  Value  

15   ARV   OPEN   OPEN/CLOSE   Relay  Effective  Status  Alarm  Value  

16   AAIV   CLOSE   OPEN/CLOSE   Auxiliary  Input  Valid  Status  Alarm  Value  

17   Password  set   Parameter  Setting  Login  Password  


1234   0000-­‐9999  
Modification  

4.1.4.5  Mode  Selection  


(1)On  the  main  page,  through【 UP】and【 DOWN】buttons  to  move  the  cursor  to【 1.Mode  set】and  
press【 OK】   to  mode  setting  page.  
 
(2)Through【 UP】and【 DOWN】buttons  to  move  the  cursor  to【 AUTO1】,【MANU】,【AUTO2】.  
Press【 OK】 to  select  the  setting  item,or  press【 ESC】 to  discard  the  current  mode  and  return  to  the  
parameter  selecting  page.  
 
(3)Select【MANU】   to  enter  manual  mode  setting.  Then  through【 UP】,【 DOWN】and【OK】to  input  
the  fixed  air  volume  percentage  MFonR.  
 
(4)Select【AUTO1】   to  enter  auto  mode1  setting.  Then  through  【 UP】,【 DOWN】and【 OK】to  input  
ladder  air  volume  percentage  and  press【 OK】 to  set.  
 
(5)Select【AUTO2】   to  enter  auto  mode2  setting.  Then  through  【 UP】,  【 DOWN】and【 OK】to  input  
constant  value  and  press【 OK】 to  set.  

4.1.5  Device  Information  

4.1.5.1  On  the  main  page,  press【 ESC】 to  enter  the  system  information  view  page.  

 
4.1.5.2   Through【 UP】 and【 DOWN】 to   move   the   cursor   to   device   information   item   and   display   the  
information  item.  Press【 ESC】 to  back  to  the  main  menu  page.  

 
 
 

Table  3  :  Device  Information  Table  


No   Item   Description  

1   DEV  Model   Equipment  Model  

2   HW  Ver   Hardware  Version  No.  

3   SW  Ver   Software  Version  No.  

4   Dev  ID   Equipment  Code  

4.1.6  Operating  Status  

4.1.6.1  On  Standby  page,  use【 UP】 and【 DOWN】 to  view  the  fan  operation  information.  

Table  4  :  Operating  State  Description  


NO   Parameters   Description  

1   Fan1  Rate  &  Speed   Fan  1  pwm/speed  

2   Fan2  Rate  &  Speed   Fan  2  pwm/speed  

3   Press1  Press2   Pressure  Value  1、2  

4   Door1  Door2   Fan  Safety  Door  1、2  State  

5   Indoor  Temp  &  Hum   Indoor  Temperature、Humidity  Value  

6   Outdoor  Temp   Outdoor  Temperature  Value  

7   Aux  in  1  2  3   Auxiliary  Input  1、2、3  

8   Relay  out  1  2  3   Relay  out  1、2、3    

9   Relay  out  4  5  6   Relay  out  4、5、6  


 

 
 

4.2  Ethernet  Interface  Operation  

4.2.1  System  Overview  

This   system   is   FCU   monitoring   system,   mainly   monitoring   the   parameters   of   the   intelligent   new   fan,  
including   fan   speed   /   status,   fan   safety   door   status,   air   pressure,   and   indoor/outdoor   temperature.  
Meanwhile,  it  can  also  provide  the  functions  as  parameters  setting,  fan  test  and  system  upgrade  etc.  

4.2.2  Start  up  and  Exit  

4.2.2.1  Start  Up  

2-­‐5  minutes  after  the  fan  is  connected  to  the  computer  through  the  cable,  the  FCU  monitoring  system  will  
automatically   starts.   Use   any   browser   (recommend   using   Chrome,   Firefox,   or   higher   version   of   IE  
browser),   at   address   bar   enter   the   system   IP   address   to   access   the   system,   for   example:   http:  
//192.168.3.92  .  

4.2.2.1  Exit  

Close  the  web  page  or  browser  to  exit  the  system  safely.  

4.2.3  Common  Function  

4.2.3.1  Operating  Status  

Entering   IP   address   in   the   browser   address   bar   to   visit   the   monitoring   interface   of   the   system   running  
status   .   On   this   page,   you   can   view   all   the   system   parameters   which   will   be   updated   according   to   the  
system   running   state   with   once   per   second   frequency.   At   the   same   time,   this   interface   also   provides  
system  alarm  function,  if  any  parameter  is  abnormal,  there  will  appear  a  red  word  alarm  on  the  bottom  of  
the   page,   and   display   the   alarm   content.   Alarm   information   will   be   updated   according   to   the   system  
running  state.  As  shown  below:  

 
 

 
Figure  6  :  System  Parameter  Monitoring  Page  

4.2.3.2  Device  information  view  

The   system   provides   the   function   of   viewing   device   information.   Click   the   [Device   Info]   button   through  
the  menu  bar  at  the  bottom  of  the  system  page  to  enter  the  system  device  information  interface.  In  this  
case,  the  user  can  view  the  machine  model,  device  serial  number,  motherboard  hardware  version  number,  
motherboard   software   version   number,   SNMP   hardware   version   number,   SNMP   software   version  
number  and  so  on.  As  shown  below:  

 
Figure  7  :  Device  Info  

 
 

4.2.3.3  General  Setting  

(1)Administrator  login  
 
When   system   setting,   administrator   authentication   is   needed.   Click   the   [General   Setting]   button   on   the  
home   page   to   jump   to   the   general   settings   page.   Then   the   system   will   check   the   administrators’   login  
status.  If  not  logged  in  or  login  status  is  invalid,  then  it  will  redirect  to  administrator  login  interface;  To  
log  in,  you  need  to  enter  the  user  name  and  password,  and  root  is  the  user  name  with  the  initial  password  
123456.  If  succeed,  you  will  see  the  project  settings  page;  or  it  will  return  to  the  login  page  to  try  again.  
 
(2)General  Setting  
 
The  general  settings  page  provides  the  viewing  and  modifying  functions  of  the  system  related  parameters.  
Including   IP   address,   subnet   mask,   gateway,   server   IP,   system   date,   system   time   and   so   on.   When  
modifying  such  parameters,  you  need  to  modify  them  in  the  appropriate  format.  Or  the  modification  will  
be  unsuccessful  or  cause  a  system  error.  When  modifying  the  system  date,  if  the  time  selector  does  not  
appear  or  is  abnormal,  please  use  the  higher  version  browser  and  try  again.  Edit  the  content  needed  to  be  
modified,  then  click  the  "Save  Configuration"  button  to  save  the  corresponding  contents.  As  shown  below:  
 

 
Figure  8  :  General  Setting  

(3)Modify  Password  

This   system   provides   the   function   of   modifying   the   administrator   password.   Click   the   "Modify   password"  
button   on   the   system   settings   page   to   redirect   to   the   Modify   Password   page,   where   you   can   modify   the    
administrator  password  but  can  not  modify  the  user  name.  When  modifying  the  password,  we  need  to  verify  
whether  the  original  password  is  matched,  and  whether  the  new  password  entered  twice  is  consistent.  If  the  
verification  doesn’t  pass,  the  password  modification  will  be  failed.  As  shown  below:  

 
 

 
Figure  9  :  Modify  Test  Password  

4.2.3.4  Engineering  Setting  

(1)Engineering  Administrator  Login  

When   engineering   setting,   we   need   to   enter   /   QhSeerMAdmin.html   /   into   the   address   bar   to   check   the  
administrators’  login  status;  if  not  logged  in  or  login  status  is  invalid,  then  it  will  redirect  to  administrator  login  
interface;  To  log  in,  you  need  to  enter  the  user  name  and  password,  and  root  is  the  user  name  with  the  initial  
password  123456.  If  succeed,  you  will  see  the  project  settings  page;  or  it  will  return  to  the  login  page  to  try  
again.  
 
You   can   also   set   the   fan   serial   number,   asset   number   and   production   date,   etc.   Similarly,   the   modified  
parameters   should   comply   with   the   relevant   provisions,   otherwise   the   change   will   be   unsuccessful.   Edit   the  
content  you  need  to  modify,  then  click  the  "Save  configuration"  button  to  save  them.  As  shown  below:  

(2)Engineering  Setting  

Each   parameter   can   be   set   on   the   page   of   engineering   setting,   including   the   alarm   threshold   (gate  
temperature   alarm   value,   filter   pressure   alarm   value,   etc.),   fan   opening   or   closing   temperature   and   so   on.  
Meanwhile,  you  can  also  set  the  fan  temperature  control  strategy.  This  system  provides  three  modes:  auto  
mode   (ladder   temperature   control),   manual   mode,   and   constant   temperature   control   mode.   Select   auto  
mode,  you  need  to  set  the  ladder  temperature  control  value,  that  is,  the  temperature  per  1  degree  Celsius,  
the   percentage   of   speed   the   fan   increases;   select   manual   mode,   you   need   to   set   the   fixed   air   volume  
percentage;   select   the   constant   temperature   mode,   you   need   to   set   the   constant   temperature   value.  
Similarly,  when  modifying  parameters,  you  must  comply  with  the  relevant  provisions,  or  it  will  be  failed.  
Edit   the   content   needed   to   be   modified,   click   [Save   configuration]   button   to   save   the   corresponding  
contents.  As  shown  below:  

 
 
 

 
 
Figure  10  :  Engineering  Setting  

(3)Modify  Password  

The  system  allows  the  administrator  to  change  the  password,  clicking  "Modify  password"  button  on  the  
engineering  setting  page,  then  it  will  redirect  to  the  “modify  password”  page,  where  you  can  modify  the  
password  but  not  user  name  also.  

(4)System  Upgrade  

Upgrade  function  is  provided.  Enter  the  page  of  “engineering  setting”  and  click  "System  Update"  button  to  
visit  the  relevant  interface.  This  interface  requires  administrator’s  authentication,  if  the  login  status  is  not  
logged  in  or  invalid,  then  it  will  redirect  to  the  administrator  login  interface  to  log  in.  System  upgrade  is  
divided  into  server  system  upgrade,  main  board  upgrade,  SNMP  upgrade.  The  entry  of  these  three  types  
are  same  to  the  upgrade  operation.  Each  upgrade  package  will  be  provided  by  the  Manufacturer.  When  
upgrading  Server,  the  upgrade  package  should  be  named  systemUpdatePackageV1.0.0.tar.  system  Update  
Package   V   can   not   be   changed,   and   1.0.0   which   is   the   version   number   can   be   revised;   When   upgrading  

 
 
motherboard,   the   upgrade   package   should   be   named   boardUpdatePackageV1.0.0.tar,   board   Update  
Package  V  is  fixed  ,  and  1.0.0  which  is  the  version  number  can  be  revised;  For  SNMP  upgrade,  the  upgrade  
package  is  named  netSnmpV1.0.0.tar,  net  SNMP  V  can  not  be  modified,  the  version  number  1.0.0.  can  be  
adjusted.   Manual  modification  is  prohibited  to  change  the  upgrade  package  name  (including  suffix),  or  it  
will  cause  upgrade  failure  and  system  crash.  On  the  upgrade  page,  select  the  upgrade  package,  then  click  
“Upgrade  Now”  button  to  enter  the  system  upgrade.  This  process  may  last  2-­‐5  minutes.  In  the  process  of  
system  upgrade,  please  ensure  that  the  original  systems  are  running  normally,  and  the  network  is  stable  
and   continuous   power   supply.   After   completing   the   upgrade,   the   system   will   restart   automatically   and  
reboot  to  re-­‐enter  the  system.  As  shown  below:  

 
Figure  11  :  System  Upgrade  

(5)System  Parameter  Reset  

Engineering   setting   module   provides   the   reset   function   for   system   parameters.   Clicking   the   "System  
Reset"   button   to   enter   the   page   to   reset   all   the   variable   parameters,   including   system   settings   and  
engineering   settings.   When   succeed,   the   system   will   automatically   restart.   This   process   will   last   2-­‐5  
minutes.  After  restarting,  just  input  the  IP  again  to  enter  the  system.  

(6)Modify  WIFI  Configuration(Optional)  

Wifi   visiting   is   also   provided.   Turn   on   the   system   wifi,   then   you   can   visit   the   system   through   mobile  
phone  and  other  mobile  devices.  It  should  be  noted  that  access  to  the  system  through  the  wifi  system,  you  
need  the  wireless  card  ip  (for  example:  http:  //  192.168.1.99)  ,  but  not  using  the  cable  network  card  ip  
(for  example:  http://192.168.3.92).  

 
 
 
On  engineering  setting  page,  click  “  Modify  wifi”  to  enter  the  modify  wifi  configuration  interface.  You  can  
modify  the  wifi  name  and  password.  When  modifying  wifi  name,  1-­‐8  digits  or  letters  is  supported,  but  not  
support   Chinese,   Japanese   and   Korean   etc.   When   modifying   the   wifi   password,   8-­‐16   digits   or   letters   is  
supported.  If  not  meet  the  input  conditions,  the  modification  will  be  failed.  As  shown  below:  

 
Figure  12  :  Modify  WIFI  Configuration  

4.2.4  System  Test  

4.2.4.1  Single  Device  Test  

The  system  provides  system  testing  function.  Enter  ip  /  commonTestEntryPage.html  (for  example:  http:  
//192.168.3.92/commonTestEntryPage.html)   in   the   address   bar   to   visit   the   public   portal   page   of   test  
mode.   The   system   test   is   divided   into   single   device   test   and   system   environment   simulation.   You   can  
choose   one   to   enter.   After   entering   the   test   mode,   system   tester   identification   should   be   verified.   If   not  
logged  in  or  login  status  is  invalid,  then  it  will  redirect  to  system  tester  login  interface.  
 
Under   single   device   test   mode,   you   can   control   the   fan   running   state,   including   fan   speed   control,   relay  
status   and   so   on.   At   the   same   time,   you   can   see   the   parameters   changes   according   to   the   fan   speed  
changes.   When   the   test   is   completed,   click   the   [Exit   Test   Mode]   button   to   exit   the   single   device   test   mode.  
Do   not   close   the   test   mode   page   directly.   After   exiting   the   test   mode,   the   system   will   continue   running  
before  entering  the  test  mode.  If  the  operation  mode  does  not  return  to  the  previous  state,  click  the  [Exit  
Single  Device  Test]  button  on  the  home  page  to  exit  the  single  device  test  mode.  As  shown  below:  
 

 
 

 
      Figure  13  :  Single  Device  Test  

4.2.4.2  System  Environment  Simulation  

System   Environment   Simulation   means   this   system   providesthe   function   of   simulation   of   the   fan  
operating   environment.   When   entering   the   function   module,   it   can   real-­‐time   simulate   the   fan   operating  
environment   inside   and   outside   door   temperature,   the   pressure   value,   security   door   status,   and   auxiliary  
input,   etc.   After   inputting   all   the   simulation   parameters,   click   [Test   Now]   to   enter   the   simulation,   and   you  
can  view  the  parameters  of  the  fan  running  under  the  simulation  environment.  Click  the  “Exit  Test  Mode”  
button   to   exit   the   system   environment   simulation.   Do   not   close   the   test   mode   page   directly.   As   shown  
below:  
   

 
Figure  14  :  System  Environment  Simulation  

 
 

5.0  Control  logic,  input  and  output  

Control   logic   refers   to   the   control   logic   under   [1.AUTO   MODE],   [2.MANU   MODE]   the   fan   run   at   the  
manually  set  the  fan  power  .  

5.1  Control  logic  

l When  the  indoor  and  outdoor  temperature  difference>  (1.TD0),  the  fan  is  turned  ON  
l When  the  indoor  and  outdoor  temperature  difference  <(2.TD1),  the  fan  is  OFF  
l When  the  fan  is  OFF  (within  the  above  temp  range)  Indoor  temp  >  (3.T0)  value,  fan  run  minimum  35%  
l Temperature  difference  of  1  degree  Celsius,  fan  power  35%  +  (5.TDFon)  *  temp  difference.  Up  to  95%  
l When  the  door  1  or  door  2  open  is  detected,  the  corresponding  fan  is  turned  OFF  
l When  the  indoor  temperature  grater  than  (4.THA),  the  fan  run  100%,  output  alarm  
l When  the  filter  inside  and  outside  the  pressure  difference  grater  than  (6.F1HA),  output  alarm  
l Current  pressure  inside  and  outside  the  filter  grater  than  (7.F2HA),  output  alarm  

5.2Alarm  Output  

There   are   three   ways   to     output   system   alarm,   through   the   relay   output   alarm,   LCD   panel   indicator  
alarm  output,  SNMP  card  alarm  output.  
 
Table  5  :  Relay  Alarm  Output  Table  
 

Relay   Alarm  Content  

Relay  Alarm  Output  1   System  Operating  Status  Alarm  

Relay  Alarm  Output  2   System  Hardware  Failure  Alarm  

Relay  Alarm  Output  3   Auxiliary  Alarm  Input  Alarm  


 
Table  6  :  Panel  Indicators  Alarm  and  SNMP  Card  Output  Alarm  
 

Alarm  code   Alarm  Content  

E0   System  Status  Alarm:  Indoor  Low  Temperature  Alarm  

E1   System  Status  Alarm:  Indoor  High  Temperature  Alarm  

 
 
E2   System  Status  Alarm:  High  Relative  Humidity  Alarm  

E3   Hardware  Fault  Alarm:  Fan  1  

E4   Hardware  Fault  Alarm:  Fan  2  

E5   Hardware  Fault  Alarm:  Indoor  Temperature  and  Humidity  Sensor  

E6   Hardware  Fault  Alarm:  Outdoor  Temperature  Sensor  

E7   Hardware  Fault  Alarm:  Filter  1  

E8   Hardware  Failure  Alarm:  Filter  2  

E9   System  Status  Alarm:  Outdoor  Low  Temperature  Alarm  

E10   System  Status  Alarm:  Outdoor  High  Temperature  Alarm  

E11   System  Status  Alarm:  Filter  1  Replacement  

E12   System  Status  Alarm:  Filter  2  Replacement  

E13   Auxiliary  Alarm  Input  Alarm:  Auxiliary  Input  1  

E14   Auxiliary  Alarm  Input  Alarm:  Auxiliary  Input  3  

E15   Auxiliary  Alarm  Input  Alarm:  Auxiliary  Input  2  


 
 
 