Compensación Electrónica
de Sistemas Eléctricos
Claudio Canizares
Dept. Electrical and Computer Engineering
www.power.uwaterloo.ca
www.wise.uwaterloo.ca
Review
• Power system basics:
– Structure
– Supply technologies
– AC power
– Per unit
• Basic element models:
– Generators
– Transmission system:
• Transformers
• Transmission lines
– Loads:
• Inductions motors
• Aggregate loads
– Solar Photo-Voltaic Generation (SPVG)
– Wind Generation (WG)
– Battery Energy Storage System (BESS)
2
Power System
• Operated by independent system operators (e.g.
IESO):
Connecting Buses
or Nodes
Transmission Lines
Generator
500kV
(station) Transformer
Milton
Load
3
Power System
• Ontario’s grid:
4
Power System Components
• Generator station:
– Synchronous machine, exciter, primary
voltage regulator and stabilizer.
– Turbine (e.g. thermal, gas, hydro) and primary
frequency controls (governor).
– Fuelling system and controls (e.g. boiler,
reservoir, valves)
– Owned and run by generation companies or
GENCOS (e.g. OPG).
5
Power System Components
• Transmission system:
– High voltage transmission lines: overhead
wires and towers, underground cables.
– Transformers: step-up or step-down voltage
levels to reduce transmission losses.
– Switching stations (buses/nodes):
connections, breakers, protections, etc.
– Owned and maintained by transmission
companies or TRANSCOS (e.g. Hydro One).
6
Power System Components
• Loads:
– Large industrial customers and distribution
networks.
– Represent aggregate models of the
distribution grid, including motors, lighting,
heating, feeders, etc.
– Owned by large customers and/or local
distribution companies or LDCs (e.g. Toronto
Hydro)
7
Power System Components
• Renewable Energy (RE) generation:
– Mostly wind and SPV generation:
• Wind mostly at the transmission system level as wind farms.
• Solar mostly at the distribution system level as rooftop and ground-mounted.
– Wind generation more significant than SPVG at most jurisdictions, with
a few exceptions where solar resources are high (e.g. Hawaii, Arizona,
Australia).
– Mostly interfaced to the system through power electronic converters.
– Generation technologies are relatively mature but new installations,
connection standards, and controls are still under development, with
system impacts not yet fully understood and thus being still studied.
– Mostly privately owned by GENCOS (wind farms) and consumers
(SPVG rooftop/ground-mounted).
8
Supply Technologies
• Europe’s electrical energy supply and demand
[UCTE/ENTSO-E]:
9
Supply Technologies
• US electricity supply and demand [US gov.]:
5,000
4,500
4,000
3,500
Others
3,000 G/S/W/B
TWh
2,500 Nuclear
Therm al
2,000
Hydro
1,500
1,000
500
year
1000
900
800
700
600
Dem and
GW
500
Res erves
400
300
200
100
0
1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 10
year
Supply Technologies
• Canada’s electricity supply and demand [NRC]:
700 80
600 70
60
500
50 G/S/W/B
400 Nuclear
TWh
GW
40 Thermal
300 Hydro
30 GW Consumption
200
20
100 10
0 0
1993 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003
year
11
Supply Technologies
• Supply and demand in Ontario-Canada [IESO, ON gov.]:
2009
12
Supply Technologies
• Nuclear power
generation [European
Nuclear Society]:
– Clean from green
house gases
emissions point of
view.
– To supply base load
since does not control
f.
13
Supply Technologies
• Coal plant (thermal) [TVA]:
– “Dirty” from GHG point of view.
– Mainly to supply base load given slow response.
14
Supply Technologies
• Combined-cycle plant
(thermal) [power-
technology.com]:
– Gas + steam turbine.
– Cleaner that coal
plants.
– To supply base
(steam) and peak load
(gas).
15
Supply Technologies
• Hydro plant [US DOE]:
– Large and small (run of the
river).
– Supplies base and peak load
(fast response)
16
Supply Technologies
• Wind power [EON]: Clean, but not yet dispatchable.
gears
wind turbine
generator
substation
17
Supply Technologies
– Types of wind power
units [PSAT]:
18
Supply Technologies
• Solar power:
– PV [an-energy-efficient-
home.com] and thermal
[acciona-energia.com]
– Dispatchable with energy
storage systems.
19
Supply Technologies
• Load supply in Ontario by generator type [MEI]:
20
AC Circuits
• Voltage, current and instantaneous power in power
system elements:
21
AC Circuits
• This circuits are analyzed using phasors
(complex numbers):
22
AC Circuits
• AC power:
– In the phasor domain, complex power is defined as:
23
AC Circuits
– For inductive elements (L), Q is positive (+).
– For capacitive elements (C), Q is negative (-).
– Inductors “consume” Q, capacitors “produce” Q.
– The larger the Q, the larger the currents and hence
the larger the voltage drops.
– Thus, the Q flowing through the system should be as
close to zero as possible, i.e. the power factors in the
system should be close to 1.
24
3-Phase Circuits
25
3-Phase Circuits
26
3-Phase Circuits
• This leads to:
27
Per Unit
• Definitions of per-unit (pu) quantities:
28
Per Unit
29
Example
30
Example
• Generator:
31
Example
• Transformer 1-2:
32
Example
• Line 2-3:
33
Example
• Transformer 3-4:
34
Example
• Load:
35
Generator
• Generator components:
– Generator:
– Synchronous machine: AC stator and DC rotor.
– Excitation system: DC generator or static converter plus voltage
regulator and stabilizer.
36
Generator
• Generator with DC exciter and associated controls:
37
Generator
• Generator with static exciter and associated controls:
38
Synchronous Machine
39
Synchronous Machine
• Park’s transformation equations:
40
Synchronous Machine
• 3-phase short circuit at generator terminals:
41
Simplified Models
• Assuming balanced operation (null zero
sequence), the detailed machine model can be
reduced to phasor models useful for stability and
steady state analysis.
• Phasor models are based on the following
assumptions:
– The rotor speed does not deviate “much” from the
synchronous speed, i.e. ωr ≈ ωs = (2/P) 2 π fo, i.e.
θr = ωs t + π/2 + δ
– The rate of change in rotor speed is “small”, i.e.
|dωr/d t | ≈ 0.
42
Simplified Models
• Subtransient models capture the full machine
electrical dynamics, including the “few” initial
cycles (ms) associated with the damper windings.
• Transient models capture the machine electrical
dynamics starting with the field and induced rotor
core current transient response. Damper windings
transients are neglected.
• Steady sate models capture the machine electrical
response when all transients have disappeared
after “a few” seconds.
43
Subtransient Model
44
Subtransient Model
45
Subtransient Model
• The subtransient reactances (Xq", Xd") and open circuit time
constants (Tqo", Tdo"), as well as the transient reactances (Xq',
Xd') and open circuit time constants (Tqo', Tdo') are directly
associated with the machine internal resistances and
inductances.
• In practice, most of these constants are determined from short
circuit tests.
• All the E voltages are “internal” machine voltages directly
associated with the “internal” phase angle δ.
• The internal field voltage Ef is directly proportional to the
actual field dc voltage, and is typically controlled by the
voltage regulator.
• The mechanical power Pm is controlled through the governor.
46
Subtransient Model
• Typical machine parameters:
H = π fo M = J ωo/SB
Xo = 0.1 to 0.7 of Xd"
rs = Ra
47
Subtransient Model
48
Transient Model
• Obtained by eliminating the damper
winding dynamic equations as follows:
49
Transient Model
50
Transient Model
• The damping D in the mechanical
equations, which is typically a small value,
is assumed to be large to indirectly model
the significant damping effect of these
windings on ωr.
• It’s the typical model used in stability
studies.
51
Transient Model
• Neglecting the induced currents in the rotor (winding
Q2):
52
Transient Model
• The phasor diagram in this case is:
53
Transient Model
• For faults near the generator terminals, the q axis has
little effect on the system response, i.e. Iqs ¼ 0.
• This results in the classical voltage source and transient
reactance generator model used in most theoretical
stability studies:
54
Transient Model
where:
55
Transient Model
• A further approximation in some cases is used by
neglecting the field dynamics, i.e. Tdo' = 0.
• In this case, Ea' is a “fixed “ variable controlled
directly through the voltage regulator via Ef, i.e.
Ea' = Ef.
• The limits in the voltage regulator are used to
represent limits in the field and armature currents.
• These limits can be “soft”, i.e. allowed to
temporarily exceed the hard steady state limits, to
represent under- and over-excitation.
56
Controls
• A simple voltage regulator model (IEEE
type 1):
57
Controls
• A static voltage regulator model:
58
Controls
• A simple governor model (hydraulic valve
plus turbine):
59
Controls
• A governor-steam turbine model:
60
Steady State Model
• When all transients are neglected, the generator model
becomes:
61
Steady State Model
• Based on this simple
model, the field and
armature current
limits can be used to
define the generator
capability curves (for
a given terminal
voltage Vas = Vt):
62
Steady State Model
• Considering the voltage regulator effect, the generator can be
modeled as a constant terminal voltage within the generator
reactive power capability, delivering constant power (Pm).
• This yields the PV generator model for power flow studies:
63
Single-phase Transformers
64
Single-phase Transformers
• The phasor equivalent circuit is, assuming
Zm >> Zl1:
65
Single-phase Transformers
• Or Π form:
66
Single-phase Transformers
• Neglecting Zm (Ym is small given the core
magnetic properties):
67
Single-phase Transformers
• Some programs/data formats (e.g. PSAT and IEEE
common format) model the transformer as follows:
68
Single-phase Transformers
• Certain transformer have built-in Under-Load Tap Changers (ULTC).
• This are either operated manually (locally or remote controlled) or
automatically with a voltage regulator; the voltage control range is
limited (approximately ± 10%) and on discrete steps (about ± 1%).
• The time response is in the order of minutes, with 1-2 min. delays,
due to ULTCs being implemented using electromechanical systems.
• These are typically used to control the load voltage side, and hence
are used at subtransmission substations.
• Nowadays, power electronic switches are used, leading to Thyristor
Controller Voltage Regulators (TCVR), which are faster voltage
controllers and are considered Flexible AC Transmission Systems
(FACTS).
• These types of transformers are modeled using the same
transformer models, but a may be assumed to be a discrete
controlled variable through a voltage regulator with a dead-band.
69
Single-phase Transformers
• Transformers with special connections and under-load tap changers can also be used for
phase shift control and are known as Phase Shifters.
• These control the phase shift difference between the two terminal voltages within
approximately ± 30o, thus increasing the power capacity of a transmission line (e.g.
interconnection between Ontario and Michigan).
• Phase shifters are modeled using a similar model but the tap is a phasor as opposed to a
scalar: a=a∠α
70
Three-phase Transformers
71
Three-phase Transformers
• The 3 single-phase transformers form a
3-phase bank that induces a phase shift,
depending on the connection:
72
Three-phase Transformers
73
Three-phase Transformers
• In balanced, “normal” systems, the net phase shift between
the generation and load sides is zero, and hence is neglected
during system analyses:
74
Saturation
• The magnetization inductance Lm changes with
the magnetization current due to saturation of the
magnetic core.
• Saturation occurs due to a reduction on the
number of “free” magnetic dipoles in the enriched
core.
• This results in the core behaving more like air than
a magnet, i.e. magnetic “conductivity” decreases.
• It’s typically represented using a piece-wise linear
model.
75
Transmission Lines
(and Cables)
76
Transmission Lines
• In transmission systems, most lines are overhead lines,
like for example the 500 kV near the 401 in Milton:
77
Transmission Lines
• If a line is transposed to balance the phases, the length
of the barrel B must be much less than the wavelength
(s/f ≈ 5,000 km @ 60 Hz ) B ≈ 50 km), thus leading to:
78
Transmission Lines
• Sequence transformation: Vopn = Ts-1 Vabc
Iopn = Ts-1 Iabc
79
Transmission Lines
• Positive sequence (per-phase) phasor model:
80
Transmission Lines
81
Transmission Lines
• This can be converted into the Π
equivalent circuit:
82
Loads
• Load classification by demand level:
– Residential: lighting and heating (RL + controls); AC (motor + controls);
appliances (small motors + controls)
– Commercial: similar types of devices as residential.
– Industrial: motor drives (induction and dc motor-based mostly); arc
furnaces; lighting; heating; others (e.g. special motor drives).
• By type:
– RLC + controls
– Drives: ac/dc motors + electronic controls
– Special (e.g. arc furnaces).
• Most controls are implemented using a variety of power electronic
converters.
• Aggregate load models are necessary at the transmission system
modeling level; only large loads are represented with their actual
models.
83
Induction Motor
84
Induction Motor
• Assuming a balanced, fundamental frequency (ω =ωo) system, the
model can be reduced to a p.u. “transient” model (3rd order model):
85
Induction Motor
86
Induction Motor
• If the electromagnetic transients are neglected,
the system can be reduced to the following
quasi-steady state equivalent circuit model:
87
Induction Motor
• Or equivalently:
88
Induction Motor
• This simplification can be justified from the point
of view of the Torque-speed characteristic:
89
Induction Motor
• If the mechanical dynamics are ignored, the slip S becomes a
fixed value, and hence the equivalent circuit can be reduced
to a simple equivalent reactive impedance, i.e. a Z load.
• For loads with multiple IMs, an equivalent motor model can be
used to represent these motors.
• Neglecting the motor dynamic equations in large or equivalent
aggregate motors can lead to significant modeling errors, as
the transient model and mechanical time constants can be on
the same range as the generator time constants.
• Double-cage IMs can be modeled by introducing an additional
inductance on the rotor side, which leads to a “subtransient”
model.
90
Impedance Load Models
• Ignoring “fast” and “slow” transients, certain loads can
be represented using an equivalent impedance.
• A Z load model is typically used for a variety of
dynamic analysis of power systems.
• Using these load models, an equivalent impedance
can be readily obtained for all loads connected at a
particular bus at the transmission system level.
• ULTCs are used to connect distribution systems
(subtransmission and LV systems and the loads
connected to these) to the transmission system to
control the steady state voltage on the load side.
91
Power Load Models
• Hence, for “slow” dynamic analysis of balanced, fundamental
frequency system models:
92
Power Load Models
• Load recovery of certain loads (e.g thermostatic) with
respect to voltage changes can be modeled as:
93
Power Load Models
• This results in the following time response:
94
Power Load Models
• Certain loads have been shown to behave in steady
state as follows:
95
Power Load Models
• ZIP model:
96
Power Load Models
• Mixed dynamic model:
97
SPVG
~100 MWpeak solar farm
connected to Bluewater Power
distribution system near Sarnia,
ON, (largest in the world in 2010;
as of 2016 the largest is a ~1.55
GW farm in Tengger Desert, China)
98
SPVG Controls
• Original PQ controls:
– P output kept at maximum using an MPPT control of the dc-dc
converter VI output:
99
SPVG Controls
• RE generators were required
to disconnect under faults,
which created low voltage and
frequency problems with loss
of power.
• Now they are required to
provide reactive power during
fault conditions via Low-
Voltage Ride-Through (LVRT)/
or Fault Ride-Through (FTR)
control, i.e. converter Q
injection.
LVRT/FTR converter
• More jurisdictions are now output characteristics
requiring full V output control
like standard generators.
100
SPVG Controls
• Some jurisdictions are also
requiring nowadays some
frequency control:
– MPPT control is deactivated
to allow some limited P
control, thus de-rating the
generator.
– Some manufactures are
providing controls so that
generator provide also
virtual inertia, such as the
Synchronous Power
Controller (SPC) [11], which
renders the generator a
Virtual Synchronous
Generator (VSG):
101
WG
• Ripley-Kincardine, ON, WG plant: 76 MW with 38x2 MW
Enercon Type 4/D SGPM generators connected at
230kV (largest farm as of 2010 is the on-shore 6.8 GW
plant in Gansu, China):
102
WG
• Type 1/A: Fixed speed with pitch control.
vw
Gear
Generator
Box
ωm
Pm
Tm
P controls
Pitch
β
103
WG
• Type 2/B: Doubly Fed Induction Generator (DFIG) with variable
speed through variable rotor resistance, plus pitch control.
vw
Gear
Generator
Box
ωm
Pm
Tm
P controls
Pitch
β
104
WG
• Type 3/C: DFIG with rotor converters plus pitch controls.
vw
Gear
Generator
Box
ωm
Pm DC Link
Tm
VR VSC VSC Vt
IR Vdc It
Idc Pt
P and V/Q DC link Qt
controls controls
β Pitch
105
WG
• Type 4/D: Permanent Magnet Synchronous Generator (PMSG) or IG
with ac-dc-ac full converter interface, similar to SPCG.
vw
DC Link
Generator
ωm
VG VSC VSC
Pm
IG
Tm Vdc Vt
Idc It
Q/V Pt
P controls
controls Qt
Pitch
106
WG Controls
• Depend on technology:
– Type 1/A: Only slow pitch controls to keep torque
and/or turbine speed at rated values and/or within
limits to avoid turbine problems.
– Type 2/B: Slow pitch control plus some fast P
control through variable resistors.
– Type 3/C: Slow pitch control plus fast P and Q/V
control through rotor ac-dc-ac converter.
– Type 4/D: Slow pitch control plus fast P and Q/V
control through full ac-dc-ac converter interface.
107
WG Controls
• Type 3/C and 4/D P control:
– MPPT based on:
108
WG Controls
• Virtual Inertia Control (VIC) for Types 3/C and 4/D WGs:
– Different from de-rating
(de-loading) plus droop
control.
– MPPT is maintained.
– Takes advantage of wind
turbines’ inertia.
109
BESS
110
BESS
• Average model:
111
BESS Controls
Buck/boost control
Current control
112
BESS Controls
• Power, damping, and frequency regulation:
113
SPVG, WG and BESS
Simplified Models
• Simplified model,
based on WECC wind
generator phasor
(average) model:
• V and f droop controls
for this model:
114