Differential Pressure Transmitter in Cleanroom-Conform Panel Design
Differential Pressure Transmitter in Cleanroom-Conform Panel Design
The differential pressure transmitter testo 6383 was The testo 6383 is particularly outstanding thanks to the
developed specially for monitoring low differential pressures automatic zero-point adjustment which ensures high
in the measuring range from 10 Pa to 10 hPa. In cleanroom accuracy and long-term stability.
technology, the maintenance of positive pressure prevents
The integrated self-monitoring and early warning function
the entry of contaminated air in critical zones. Thanks to
also guarantees the operator high system availability.
an optional internal or external probe from the probe series
6610, the additional recording of humidity and temperature
with one instrument is also possible.
www.testo.com
testo 6383 – Differential pressure transmitter in cleanroom-conform panel design
Technical data
Parameters Inputs/outputs
Differential pressure Analog outputs
Measuring range 0 to 10 Pa -10 to +10 Pa Quantity Standard: 1;
0 to 50 Pa -50 to +50 Pa with optional humidity probe: 3
0 to 100 Pa -100 to +100 Pa
0 to 500 Pa -500 to +500 Pa Output type 0/4 to 20 mA (4-wire) (24 VAC/DC)
0 to 10 hPa -10 to +10 hPa 0 to 1/5 to 10 V (4-wire) (24 VAC/DC)
Measurement ±0.3% of measurement range final value Scaling Differential pressure: scalable ±50% of
uncertainty* ±0.3 Pa measuring range final value;
Temperature gain drift: 0.02% of measuring freely scalable within measuring range
range per Kelvin deviaton from nominal
Meas. cycle 1/sec
temperature 22 °C
Zero point drift: 0% (thanks to cyclic zero- Resolution 12 bit
point adjustment) Max. load max. 500 Ω
Other outputs
Selectable units Differential pressure in Pa, hPa, kPa,
mbar, bar, mmH2O, kg/cm2, PSI, inch Ethernet Optional
HG, inch H2O Relay Optional: 4 relays (free allocation to
measurement channels or as collective alarm
Sensor Piezoresistive sensor in operating menu/P2A), up to 250 VAC/3A
Autom. zero-point via magnetic valve (NO or NC)
adjustment Frequency adjustable: 15 sec, 30 sec, 1 min, Digital Mini-DIN for P2A software
5 min, 10 min Supply
Voltage supply 20 to 30 VAC/DC, 300 mA current
Overload Measuring range Overload
consumption, galvanically separate signal
0 to 10 Pa 20000 Pa and supply line
0 to 50 Pa 20000 Pa
0 to 100 Pa 20000 Pa
0 to 500 Pa 20000 Pa General technical data
0 to 10 hPa 200 hPa Model
-10 to 10 Pa 20000 Pa
-50 to 50 Pa 20000 Pa Material Front plate stainless steel, housing
-100 to 100 Pa 20000 Pa plastic
-500 to 500 Pa 20000 Pa Dimensions without humidity/temperature:
-10 to 10 hPa 200 hPa 246 x 161 x 47 mm
with humidity/temperature:
Parameters 396 x 161 x 78 mm
Humidity/temperature optional Weight Version without humidity: 0.9 kg;
Version with integrated humidity
Probe Integrated testo 6613 testo 6614 testo 6615 testo 6617 probe:1.35 kg; version with preparation
Type probe Channel Duct heated Cable trace Cable with for external humidity probe: 1.26 kg
humidity cover elec- Display
trode moni-
Display 3-line LCD
toring
with multi-language operating menu
Parameters %RH / °C/°F / °Ctd / °Ftd / g/kg / gr/lb / g/m3 / gr/ft³ / ppmV Resolution
/ °Cwb / °Fwb / kJ/kg / mbar / inch H2O / °Ctm (H2O2)/°Ftm Differential pressure Measuring range Resolution
(H2O2) / % Vol 0 to 10 Pa 0.1 Pa
0 to 50 Pa 0.1 Pa
Meas. range 0 to 100 Pa 0.1 Pa
0 to 500 Pa 0.1 Pa
Humidity / 0 to 100 %RH -60 to +30 °C td 0 to 100 %RH
0 to 10 hPa 0.01 hPa
trace humidity -10 to 10 Pa 0.1 Pa
-50 to 50 Pa 0.1 Pa
Temperature -20 to +70 °C -40 to +180 °C -40 to +120 °C -40 to +180 °C -100 to 100 Pa 0.1 Pa
-4 to +158 °F -40 to +356 °F -40 to +248 °F -40 to +356 °F -500 to 500 Pa 0.1 Pa
-10 to 10 hPa 0.01 hPa
Measurement
uncertainty* Humidity 0.1 %RH
±1 K at 0 °Ctd
Operating conditions
Dewpoint
±2 K at -40°Ctd Operation temperature -5 to +50 °C / +23 to +122 °F
±4 K at -50 °Ctd
Storage temperature -20 to +60 °C / -4 to +140 °F
Temp. at ±0.15 °C / 32.2 °F ±0.15 °C/ ±0.15 °C/ Process temperature -20 to +65 °C / -4 to +149 °F
+25°C / Pt1000 Class AA 32.2 °F 32.2 °F
Pt100 Class Pt1000 Class
+77°F
AA AA
testo 6383 – Differential pressure transmitter in cleanroom-conform panel design
Technical drawings
396 mm
396 mm
47 mm
47 mm
78 mm
Connection plan
20-30 V
AC/DC
+
0V - 1
DXX Integrated humidity probe IXX Units channel 3 (pre-set, only if opt.
AXX Measuring range D00 no humidity/temperature probe humidity probe connection available)***
BXX Analog display/supply D04 humidity probe integrated in panel I01 % RH/Min/Max
0981 8294/msp/I/06.2017
D05 preparation for external humidity/ I02 °C/Min/Max
CXX Display / menu language temperature probe testo 6610 I03 °F/Min/Max
DXX Integrated humidity probe I04 °Ctd / min / max
EXX Ethernet I05 °Ftd / min / max
EXX Ethernet I06 g/kg / min / max
E00 without Ethernet module I07 gr/lb /Min/Max
FXX Differential pressure unit (pre-set) E01 with Ethernet module I08 g/m³ / min / max
GXX opt. Analog output for humidity I09 gr/ft³ / min / max
probe connection (probe series FXX Differential pressure unit (pre-set)* I10 ppmV / min / max
testo 6610) units (pre-set) F01 Pa / min / max I11 °Cwb / min / max
F02 hPa / min / max I12 °Fwb / min / max
HXX Relay I13 kJ/kg / min / max (enthalpy)
F03 kPa / min / max
IXX Units channel 3 (pre-set, only if F04 mbar / min / max I14 mbar / min / max (water vapour partial
opt. humidity probe connection F05 bar / min / max pressure)
F06 mmH2O / min / max I15 inch H2O / min/ max (water vapour
available) partial pressure)
F07 inch H2O / min / max
F08 inch HG / min / max I16 °Ctm (mixture dewpoint for H2O2)
F09 kg/cm² / min / max I17 °Ftm (mixture dewpoint for H2O2)
F10 PSI / min / max I18 % Vol
*Scaling: 50% of measuring range ***only possible when D04 or D05 selected
final value; freely selectable within measuring
range
AXX Measuring range GXX opt. Analog output for humidity probe
A01 0 to 10 Pa connection (probe series testo 6610)
A02 0 to 50 Pa units (pre-set)**
A03 0 to 100 Pa G01 %RH / min / max Ordering example
A04 0 to 500 Pa G02 °C/Min/Max
A05 0 to 10 hPa G03 °F/Min/Max
www.testo.com