UMG 508 - Multifunctional Power Analyser: Smart Energy & Power Quality Solutions
UMG 508 - Multifunctional Power Analyser: Smart Energy & Power Quality Solutions
The Power Analyser UMG 508 is an all-rounder for the gle-phase loads. The UMG 508 has per each current input
front door panel mounting. The device is equipped with a separate energy counter. The very large data memory
a colourful graphic display with intuitive user interface. of 256 MB permits the logging of all readings for months
The extensive measuring functions, such as monitoring even without intermediate reading.
of short term interruptions, inrush currents, transients,
harmonics up to the 40th order …) are unique in this price Areas of application
range.
t.POJUPSJOHPGBXJEFSBOHFPGFMFDUSJDBMBOEFOFSHZQBSBNFUFST
1
Main features and customer‘s benefit UMG 508
Modbus Gateway:
Easy integration of devices without Ethernet interface
With the Modbus Gateway function of UMG 508 you can connect less
sophisticated Modbus RTU meters to Ethernet.The UMG 508 can be used
simultaneously as a gateway for sub-meters or prior instruments exis-
ting within the installation. Each instrument with a Modbus RTU interface
can be connected, if its data format and function codes correspond. Data
can be scaled and labelled.
Highspeed Modbus
The UMG 508 series can transfer data via RS485 interface with a speed
of up to 921.6 kB/s among each other device of this series.
Alarm management:
E-mail and homepage inform you, wherever you are...
Who would not agree? Just leaving the building the first call arrives
about certain problems in production, computer failure, energy
breakdown...
2
Main features and customer‘s benefit UMG 508
Grids
t5/
55HSJET
tBOEXJSFHSJET
Router SPS Software tVQUPTJOHMFQIBTFHSJET
8 Digital inputs
t1VMTFJOQVU
Interfaces t"MBSNJOQVUMPHJD
t&UIFSOFU t$POEJUJPONPOJUPSJOH
t1SPmCVT34 %46#
t)JHIMPXUBSJGGDIBOHFPWFS
t&NBYSFTFU
5 Digital outputs
t1VMTFPVUQVUL8ILWBSI
t4XJUDIJOHPVUQVU
t-JNJUPVUQVU
t&NBYPVUQVU
t-PHJDBMPVUQVU
Communication
t1SPUPDPMT1SPmCVT %17
t5$1*1
t#"$OFU
t)551GSFFMZQSPHSBNNBCMFIPNFQBHF Memory
t'51 mMFUSBOTGFS
t.#ZUF'MBTI
t4/.1 t.CZUF3".
t5'51 BVUPNBUJDDPOmHVSBUJPO
t/51 UJNFTZODISPOJTBUJPO
t4.51 FNBJMGVODUJPO
t&OFSHZDMBTT "
t6OCBMBODF
t$VSSFOU t'VMMQFSJPE3.4SFDPSEJOH NJO
t7PMUBHF
3
Power analyser UMG 508
Three / four phase universal measurement instrument; 50/ 60Hz; current transformer ../1/5A;
including GridVis programming and analysis software
application programmes
PGOPNJOBMSBOHF
PGOPNJOBMSBOHF
PGOPNJOBMSBOHF
GSFFMZQSPHSBNNBCMF
Additional memory
Ethernet 100baseT
5 digital outputs
4 current inputs
8 digital inputs
Profibus DP V0
4 voltage and
256 MB Flash
95...240V AC,
7%$
48...180V DC
7"$
7%$
20...50V AC
RS 485*
Type Item number
optionally available
Application programme Emax function Emax 52.21.080
Features
Memory 256 MB
Clock +/- 1 min per month
Integrated logic Programming language Jasic®
Operating hours counter yes
Weekly switching clock Jasic®
Periphery
Communication
Interfaces
RS 485*
LCQT yes
Profibus DP* Sub D9-pole up to 12 Mbps yes
Ethernet 10/100 Base- TX RJ-45 connector yes
Protocols
Modbus RTU yes
Profibus DP V0 yes
Modbus TCP yes
Modbus over TCP yes
Modbus-Gateway yes
HTTP homepage (configurable) yes
SMTP E-Mail yes
SNTP time synchronization yes
TFTP automatic configuration yes
FTP file transfer yes
SNMP yes
DHCP yes
TCP/IP yes
BACnet yes
*1 x DSUB-9 connector
4
Power analyser UMG 508
Technical data
one wire, more wires, fine stranded wires 0.08 - 2.5 mm²
Connectable wires (U/I)
cable end sleeve 1.5 mm²
Measuring range
Measured values
Power quality
5
UMG 508
Typical connection
6
Smart Energy &
Power Quality Solutions
The UMG 511 power quality analyser is particularly suitable Areas of application
for monitoring power quality according to standards such • Continuous monitoring of the power quality e.g. EN 50160
as the EN 50160. All power quality parameters are collected • Ethernet gateway for subordinate measurement points
and analysed e.g. flicker, short term interruptions with • Analysis of electrical faults for network problems
fault recorder function, transients, harmonics up to the • Monitoring of the internal distribution network according to
63rd and inrush currents etc. Extensive communication EN 61000-4-7, 4-15, 4-30
possibilities e.g. RS 485 Modbus, Profibus, Ethernet (TCP/ • Report generator for EN 50160 analysis
IP), BACnet, HTTP, FTP, SMTP, SNTP, DNS ... allow cost • Remote control
effective and rapid integration in existing communication
networks. Worldwide access to the embedded web
server can be gained through a web browser. The GridVis
software included in the content of delivery allows
extensive analysis just by the click of a button.
1
Power quality analyser UMG 511
UMG 511
Main features
• Measurement of power quality according to • Continuous sampling of voltage and current inputs with 20kHz
DIN EN 61000-4-30, Class A • Recording of more than 2000 different measurement parameter
• Fourier analysis 1st to 63rd harmonic for U-LN, U-LL, I, P per measuring cycle (200ms)
(consumption/supply) and Q (ind./cap.) • Detection of transients >50µs and storage with up
• Measurement of harmonics and interharmonics (U-LN, U-LL, I) to 16.000 samples
according to DIN EN 61000-4-7 • Data logger / event memory (256MB Flashdisk)
• Analysis and evaluation according to DIN EN 50160 with the • 8 digital inputs and 5 digital outputs
contained programming and analysis software GridVis • Proibus DP/V0 alternatively RS 485 (Modbus RTU, Modbus-
• Flicker measurement according to DIN EN 61000-4-15 Master, optional BACnet)
• Measurement in TN and TT grids (600V CAT III) • Ethernet (Web-Server, E-Mail, optional BACnet)
• 4 voltage measuring inputs, 4 current measuring inputs • Programming of customer speciic applications in Jasic®
Applications
The power quality analyser which is equipped with serves the UMG 511 as a reference voltage for harmonic
4 current and voltage inputs collects and digitalises measurement, transient and event recording and for
the effective values (True RMS) from currents and the flicker meter. A nominal current can be set using
voltages in 40-70Hz (15-440Hz) networks. The integrated this for the measurement of electrical current events.
microprocessor calculates the electrical parameters The 4th current and voltage input represents a separate
from the sampling values. The relevant voltage can be measurement system. However, it is generally used for
defined as a phase-neutral or a phase-phase voltage measuring the current in the neutral or PE conductor or
for measurement in a three-phase system. The voltage used for measuring a voltage difference between N and PE.
2
Power quality analyser UMG 511
Display examples
The backlighted active matrix display (5,7“) of the UMG
511 enables the presentation of measurement values
in numerical form, as a bar chart or as a line graph.
Selected displays can automatically be displayed in
alternation (automatic display rotation). The instrument is
programmed using userfriendly clear text menus or the
GridVis software.
Auxiliary measurement
The auxiliary measurement can be used for measurement
in a single-phase or symmetrical three-phase system.
Alternatively, the current input can be allocated to
the three-phase system of the main measurement for
measuring the neutral-conductor current. For example, the
voltage input could then be used for recording the voltage
between the neutral conductor and PE. The auxiliary
measurement provides all measurement parameters
like in the main measurement (current, voltage, power,
harmonics, transients, events and flicker).
Measurement in a four-phase network with main
measurement and auxiliary measurement
3
Scope of operation UMG 511
Networks
• IT, TN, TT networks
• 3 phase and 4 phase networks
Router PLC Software
8 digital inputs
• Pulse input
Interfaces • Logic input
• Ethernet • Status monitoring
• Proibus 485 • HT/LT switch over
• Emax (max. demand) resetting
5 digital outputs
• Pulse output kWh/kvarh
• Switch output
• Limit value output
• Emax output
• Logic output
Communication
• Proibus (DP/V0)
• Modbus (RTU, UDP, TCP, gateway)
• TCP/IP
• BACnet
• HTTP (freely conigurable homepage) Memory
• FTP (ile transfer) • 256 MByte Flash
• TFTP (automatic coniguration) • 16 Mbyte RAM
• NTP (time synchronisation)
• SMTP (e-mail function)
• DHCP
• SNMP Power quality
• Harmonics up to 63rd
• Short-term interruptions
• Transient recorder (>50μs)
• Starting current (>10ms)
Measurement accuracy • Unbalance
• Class: 0.5S (…/5A) class • Half wave-effective value
• Current: 0.2% recordings (up to 4.5 min)
• Voltage: 0.2% • Flicker
4
Scope of operation UMG 511
Typical connection
5
Product variants and technical data UMG 511
Three/four phase power quality analysers; current transformer .../1/5a; including GridVis programming and analysis software
Ethernet 100baseT
4 current inputs
Profibus DP V0
digital outputs
4 voltage and
256 MB Flash
digital inputs
95...240V AC,
80...340V DC
48...180V DC
44...130V AC
20...70V DC
20...50V AC
Memory
RS 485*
Type Item number
6
Product variants and technical data UMG 511
Measurement range
L-N voltage, AC (without voltage transformer) Free voltage transformer settings 10…600 V AC rms
L-L voltage, AC (without voltage transformer) Free voltage transformer settings 18…1000 V AC rms
Current (transformer: x/1 and x/5A) 0.005..6 A
Frequency of mains (only for static frequence) 15...440 Hz
Networks TN, TT, IT
Measurement in single/multi-phase networks 1 ph, 2 ph, 3 ph, 4 ph
Periphery
Digital inputs Status, logic or pulse input 8
Digital outputs Switch logic output or pulse output 5
Password protection Multilevel yes
Peak load management Optional 64 channels yes
Software GridVis yes
Features
Memory 256 MB
Clock +/- 1 min per month
Integrated logic Programming language Jasic®
Operating hour meter yes
Weekly time switch Jasic®
Measurement values
Voltage L1, L2, L3, L4, L1-L2, L2-L3, L1-L3 Accuracy ±0.1 %
7
Product variants and technical data UMG 511
Power quality
Communication
RS 485 9.6, 19.2, 38.4, 57.6, 76.8, 115.2, 921.6 kbps yes
faces
Inter-
8
Smart Energy &
Power Quality Solutions
2
Power analyser UMG 604
Applications
Major increases of energy costs make electrical energy a with 20 KHz per channel enables the collection of all
driving force in costing. With the UMG 604, you can make relevant electrical parameters (more than 800 values),
the irst step towards better cost eficiency. The precise minimum and maximum values, the basic power quality
collection of all energy data and electrical parameters values such as harmonics (up to the 40th, each phase
ensures the necessary amount of transparency in your with direction recognition) and short-term interruptions.
energy supplies. Concepts can be developed on the Even fast transients (> 50µs) can be safely identiied.
basis of the data e.g. electricity cost reductions and the Using modern communication processes, the collected
introduction of measures. These targeted improvements data is conducted to a central location, stored centrally
can also be monitored and recorded with the UMG 604. in a high-performance database and provided for further
processing in an open system. Simple integration in an
The UMG 604, equipped with a 500 MHz DSP (digital existing building management system control or PLC
signal processor), is a fast and high performing power environment expands the areas of application of the UMG
analyser. The continuous scanning of eight channels 604.
3
Power analyser UMG 604
4
Power analyser UMG 604
Functionality
All lines on the output to be monitored are fed through
the current transformer, with the exception of the PE line.
If the system is operating correctly, the sum of all currents
is equal to zero so that no voltage is induced in the current
transformer. In the event that a fault current lows via
ground or other channel, the current difference induces
a current in the current transformer which is captured by
the residual current measurement device.
UMG 604D
The UMG 604D monitors the residual currents of pure
alternating currents in TN and IT networks in electrical
systems, displays the current value and issues a warning
if the limit values are exceeded.
Differently coloured terminals
for residual current measure-
In addition to the operating currents L1-L3, the fourth
ment (current input 14)
measurement input for residual current measurement is
coloured differently (light grey) and suitable for currents up
to 30 mA. The current transformer with a transformation
ratio of 600/1A and suficiently-dimensioned internal
dimensions (20x30, 50x80 or 80x120mm) can be found in
section 6, page 166.
Extended main features of UMG 604D
5
Power analyser UMG 604
Main features
6
Power analyser UMG 604
Graphic programming
The graphic programming option for user programs is
completely new in the ield of digital power analysers.
Programs speciic to the application can be created with
this method such as the free programming of inputs and
outputs, monitoring of processes or the issue of reports
when deined limit values are achieved. In addition to the
operator-friendly graphic programming, the user is also
free to program the Jasic® code directly.
programming language
7
Power analyser UMG 604
Networks
• IT, TN, TT - networks
• 3 phase and 4 phase networks
Router SPS Software • Up to 4 single phase networks
2 digital inputs
• Pulse input
Interfaces • Logic input
• Ethernet • Status monitoring
• RS 232 • HT/LT conversion
• RS 485 • Emax (max. demand) resetting
2 digital outputs
• Pulse output kWh/kvarh
• Switch output
• Limit value output
• Emax output
• Logic output
Profibus connection
8
Product variants and technical data UMG 604
Three/four phase power analysers; 50/60Hz; current transformer .../1/5a; including GridVis programming and analysis software
7 freely programmable
±10% of nominal range
application programs
1 temperature input
Ethernet 100baseT
2 digital outputs
4 current inputs
2 digital inputs
Proibus DP V0
135...340 V DC
4 voltage and
128 MB Flash
95...240 V AC,
50...155V DC
50...110V AC
20...77V DC
20...55V AC
Memory
RS 232
RS 485
Type Item number
Differential current transformer, transmission ratio of 600/1A, interior dimensions: 20mm x 30mm KBU 23D 15.03.400
Differential current transformer, transmission ratio of 600/1A, interior dimensions: 50mm x 80mm KBU 58D 15.03.401
Differential current transformer, transmission ratio of 600/1A, interior dimensions: 80mm x 120mm KBU 812D 15.03.402
- = Not possible • = Contained Not suitable for use in residential areas.
Measurement range
L-N voltage, AC
Free voltage transformer settings Networks to 480 V AC
(without voltage transformer)
Current (transformer: x/1 and x/5A) 0.001..7.5 A
Frequency of mains 45 ..65 Hz
Networks IT, TN, TT
Measurement in single/multi-phase networks 1 ph, 2 ph, 3 ph, 4 ph and up to 4 x 1 ph
Periphery
Digital inputs Status, logic or pulse input 2
Digital outputs Switch logic output or pulse output 2
Temperature measurement input PT100, PT1000, KTY83, KTY84 1
Password protection Multilevel yes
Peak demand management Optional 64 channels yes
Software GridVis yes
9
Product variants and technical data UMG 604
Measurement values
Voltage L1, L2, L3, L4, L1-L2, L2-L3, L1-L3 Accuracy ±0.2%
Current L1, L2, L3, L4, Sum L1-L3, Sum L1-L4 Accuracy ±0.2%
K-factor L1, L2, L3, L4 yes
Three-phase current components Positive/negative/zero phase sequence yes
Effective, reactive and apparent power L1, L2, L3, L4, Sum L1-L3, Sum L1-L4 Accuracy ±0.4%
Cos-phi, power factor L1, L2, L3, L4, Sum L1-L3, Sum L1-L4 yes
Phase angle L1, L2, L3, L4 yes
L1, L2, L3, L4, Sum L1-L3, Sum L1-L4:
Class 0.5S (…/5 A),
Effective energy (kWh) - Purchased effective energy (tariff 1, tariff 2)
Class 1 (…/1 A)
- Supplied effective energy (tariff 1, tariff 2)
Features
Memory 128 MB
Clock +/- 1 min per month
Integrated logic Programming language Jasic®
Operating hour meter yes
Weekly time switch Jasic®
Power quality
Current, voltage reactive/effective power (±)
Harmonics, 1-40 harmonic Accuracy ±0,5%
L1, L2, L3, L4
Distortion factor THD- U in % L1, L2, L3, L4 yes
Distortion factor THD- I in % L1, L2, L3, L4 yes
Unbalance yes
Positive/negative/zero system yes
Transients 50 μs yes
Start-up processes 10 ms yes
Fault recorder function yes
Short-term interruptions yes
Communication
RS 232 9.6, 19.2, 38.4, 115.2 kbps yes
RS 485 9.6, 19.2, 38.4, 57.6, 76.8, 115.2, 921.6 kbps yes
Interfaces
DHCP yes
BACnet / IP yes, option
10
UMG 604
Connection illustration
Dimensional drawing
90 mm
90 mm
107.5 mm 50 mm
76 mm
82 mm
11
Smart Energy &
Power Quality Solutions
1
Power quality analyser UMG 605
Main Features
• Measurement of power quality according to DIN EN 61000-4-30 • Recording of more than 2000 different measurement parameters
• Measurement method class A per measuring cycle (200ms)
• Fourier analysis 1st to 63rd harmonics for U-LN, U-LL, I, P • Detection of transients >50µs and storage with up to 16.000
(consumption/supply) and Q (ind./cap.) samples
• Measurement of harmonics and interharmonics (U-LN, U-LL, I) • Data logger/event memory (128MB Flashdisk)
• Analysis and evaluation according to DIN EN 50160 with the • 2 digital inputs and 2 digital outputs
contained programming and analysis software GridVis • Proibus DP/V0 alternatively RS 485 (Modbus RTU, Modbus-
• Flicker measurement according to DIN EN 61000-4-15 Master, optional BACnet)
• Measurement in IT and TT grids (300V CAT III) • Ethernet (Web-Server, E-Mail, optional BACnet)
• 4 voltage measuring inputs, 4 current measuring inputs • Programming of customer speciic applications in Jasic®
• Continuous sampling of the voltage and current measuring
inputs with 20kHz
Applications
The power quality analyser which is equipped with serves the UMG 605 as a reference voltage for harmonic
4 current and voltage inputs collects and digitalises measurement, transient and event recording and for
the effective values (True RMS) from currents and the flicker meter. A nominal current can be set using
voltages in 40-70Hz (15-440Hz) networks. The integrated this for the measurement of electrical current events.
microprocessor calculates the electrical parameters The 4th current and voltage input represents a separate
from the sampling values. The relevant voltage can be measurement system. However, it is generally used for
defined as a phase-neutral or a phase-phase voltage measuring the current in the neutral or PE conductor or
for measurement in a three-phase system. The voltage used for measuring a voltage difference between N and PE.
2
Power quality analyser UMG 605
Networks
• IT, TN, TT networks
• 3 phase and 4 phase networks
Router SPS Software • Up to 4 single phase networks
2 digital inputs
• Pulse input
Interfaces • Logic input
• Ethernet • Status monitoring
• RS232 • HT/LT switch over
• RS485 • Emax (max. demand) resetting
2 digital outputs
• Pulse output kWh/kvarh
• Switch output
• Limit value output
• Emax output
• Logic output
Profibus connection
3
Scope of operation and types of variants UMG 605
Overview
Three/four phase power quality analysers; current transformer .../1/5a; including GridVis programming and analysis software
1 temperature input
Ethernet 100baseT
4 current inputs
Profibus DP V0
digital outputs
135...340 V DC
4 voltage and
95...240 V AC,
128 MB Flash
digital inputs
50...155V DC
50...110V AC
20...77V DC
20...55V AC
Memory
RS 232
RS 485
Type Item number
Measurement range
L-N voltage, AC (without voltage transformer) Free voltage transformer settings Networks to 480 V AC
Current (transformer: x/1 and x/5A) 0.005...6 A
Frequency of mains (only for static frequence) 15...440 Hz
Networks IT, TN, TT
Measurement in single/multi-phase networks 1 ph, 2 ph, 3 ph, 4 ph and up to 4 x 1 ph
Periphery
Digital inputs Status, logic or pulse input 2
Digital outputs Switch logic output or pulse output 2
Temperature measurement input PT100, PT1000, KTY83, KTY84 1
Password protection Multilevel yes
Demand management Optional 64 channels yes
Software GridVis yes
Features
Memory 128 MB
Clock +/- 1 min per month
Integrated logic Programming language Jasic®
Operating hour meter yes
Weekly time switch Programming language Jasic®
4
Scope of operation and types of variants UMG 605
Measurement values
Voltage L1, L2, L3, L4, L1-L2, L2-L3, L1-L3 Accuracy ±0.2%
Current L1, L2, L3, L4 / Calculated sum current ±0.2% / ±0.6%
K-factor L1, L2, L3, L4 yes
Three-phase current components Positive/ Negative/ Zero Phase Sequence yes
Cos-phi, power factor L1, L2, L3, L4, Sum L1-L3, Sum L1-L4 yes
Phase angle L1, L2, L3, L4 yes
L1, L2, L3, L4, Sum L1-L3, Sum L1-L4:
Class 0.5S (…/5 A),
Effective energy (kWh) - Purchased effective energy (tariff 1, tariff 2)
Class 1 (…/1 A)
- Supplied effective energy (tariff 1, tariff 2)
L1, L2, L3, L4, Sum L1-L3, Sum L1-L4:
Reactive energy (kvarh) - Inductive reactive power (tariff 1, tariff 2) Class 2
- Capacitive reactive power
Apparent energy (kVAh) L1, L2, L3, L4, Sum L1-L3, Sum L1-L4 yes
Current/voltage wave form L1, L2, L3, L4 yes
Frequency of mains Accuracy ±0.1%
Temperature measurement Accuracy±1.5%
Average value yes
Minimum and maximum values yes
Power quality
Harmonics order, 1.- 63.
Voltage L1, L2, L3, L4 Accuracy ± 0.5%
Harmonics, even/odd
Communication
Interfaces
RS 232 9.6, 19.2, 38.4, 115.2 kbps yes
RS 485 9.6, 19.2, 38.4, 57.6, 76.8, 115.2, 921.6 kbps yes
Profibus DP Plug, sub D 9-pole up to 12Mbps yes
Ethernet 10/100 Base- TX RJ-45 sockets yes
Protocols
Modbus RTU yes
Profibus DP V0 yes
Modbus TCP yes
Modbus over TCP yes
Modbus-Gateway yes
HTTP Homepage (configurable) yes
SMTP E-Mail yes
SNMP yes
SNTP Time synchronisation yes
TFTP Automatic configuration yes
FTP File Transfer yes
DHCP yes
BACnet / IP yes, Option
5
UMG 605
Connection illustration
Dimensional drawing
90 mm
90 mm
107.5 mm 50 mm
76 mm
82 mm