Movement: Multi-Room
Movement: Multi-Room
Reference Publi-
cations AlllOt, MQ75SQ
NBSIR 81-2404
U S. DEPARTMENT OF COMMERCE
National Bureau of Standards
National Engineering Laboratory
Center for Building Technology
Washington, DC 20234
November 1 981
Sponsored by
National Bureau of Standards
and
Passive and Hybrid Solar Energy Division
Office of Solar Heat Technologies
_QQ S. Department of Energy
3shington, DC 20585
j^QQ
.U56
z\-im
1931
I
VATIONAL BURKai
OF ITANDAItU«(
Lirnary
JAN 8 1982
NBSIR 81-2404
e A •
not
Ocioo
^
CALCULATION OF INTER-ROOM AIR . Ui^(o
MOVEMENT FOR MULTI-ROOM BUILDING mo
ENERGY ANALYSIS
George N. Walton
November 1 981
Sponsored by
National Bureau of Standards
and
Passive and Hybrid Solar Energy Division
Office of Solar Heat Technologies
U.S. Department of Energy
Washington, DC 20585
^1
List of Figures
it
ABSTRACT
A model is presented for computing the infiltration and air flow between rooms
of a multi-room building in terms of basic principles of fluid mechanics. This
model has been incorporated into a comprehensive loads-predicting computer pro-
gram. Air flows, room temperatures, and heating loads for a typical townhouse
under different conditions of environment and with various construction features
are computed. These calculations show the feasibility of detailed multi-room
air movement analysis. They also indicate that when the inter-room openings of
a low-rise structure are large compared to the envelope openings, the infiltra-
tion and total load can be accurately, and more quickly, computed by assumming
no resistance to air flow between rooms. This property will also allow simpli-
fied calculations for high-rise buildings with many rooms. Methods are proposed
for handling more complex air flow phenomena.
iii
TABLE OF CONTENTS
Page
ABSTRACT ill
1. INTRODUCTION I
1. 1 Background 1
1.2 Objective 1
1.3 Scope 2
2. METHODS 3
1.1 BACKGROUND
1.2 OBJECTIVES
[1] Hittle, D.C., The Building Loads Analysis and System Thermodynamics (BLAST)
Program, Version 2.0: Users Manual, U.S. Army Construction Engineering
Research Laboratory Report TR-E-153, June 1979.
[2] DOE-2 Users Guide, Version 2.1 , Lawrence Berkeley Laboratory Report
LBL-8698, May 1980.
1
1.3 SCOPE
2
2 . METHODS
The Multi-Room Loads Program uses detailed heat balance techniques to compute
room loads, as described below in section 2.2. The program uses a one-hour
time step. Transient features are modeled by a quasi-steady-state analysis
except for thermal conduction. The MRLP may be used to evaluate single "design"
days or use up to one year of measured weather data. A large number of occupant
usage features may be scheduled with hourly, daily, and seasonal variations.
The effects of temperature drifts in response to various control strategies can
be accurately evaluated. Other capabilities can be grouped by the three modes
of heat transfer.
The calculation of the room air temperature is based on a heat balance on the
room air. The convective gains from the room surfaces and internal sources
plus the sensible gains from incoming air plus the energy added by the air
handling system must equal zero.
\
where
3
HCj = convection coefficient of surface j
Tj = temperature of surface j
TZ = room air temperature
= mass flow of air through opening i
Cp = specific heat of air
TS^ = temperature of the air through opening i
L = energy from the air handling system
The summations apply to all surfaces/openings which are part of the room. The
values of the surface temperatures T j are obtained by evaluating a heat balance
,
at every suface of the room using an assumed room temperature. A better esti-
mate of the room temperature is then obtained by solving equation 1 for TZ.
Repeating this process leads to successively better approximations of the sur-
face and air temperatures. The process is rapidly convergent. Multiple rooms
can be handled within the iterative scheme given an appropriate data structure
and proper heat balances on the surfaces between rooms. Details of the surface
heat balances are beyond the scope of this report. They are essentially the
same as those Implemented in BLAST, version 3.0. The remainder of this report
will discuss the method for computing the air flows through envelope and
inter-room openings.
Most building surfaces contain openings, either large or small, which permit
the movement of air through them whenever there is a pressure difference across
the surface. Pressure differences arise from naturally occurring wind and
thermal forces. The following discussion of air movements emphasizes the rela-
tionships to basic principles of fluid mechanics.
The density of air is related to the barometric pressure (PB) and air temperature
(Ta) by
V = Vq * b * (Z/Zo)**a ( 4 )
4
where
Class Description a _b
Wind direction effects are dependent on the building’s configuration and its
relationship to surrounding structures. No single correlation can truly model
directional effects on all buildings or even the effects on a single building
in different environments. The following correlation is a compromise derived
by averaging several published correlations. It accounts for the trends
observed in wind pressure measurements [5, 6].
[5] Shaw, C.Y. and G.T. Tamura, "The Calculation of Air Infiltration Rates
Caused by Wind and Stack Action for Tall Buildings," ASHRAE Transactions ,
[6] Shaw, C.Y., "A Method for Predicting Infiltration Rates for a Tall Building
Surrounded by Lower Structures of Uniform Height," ASHRAE Transactions,
'Vol. 85, Part 1, 1979.
5
2.3.2 Thermal Forces
The same formulae apply to a vertical surface as in figure 2. They also apply
to an envelope surface where Pj is the pressure of the outside air (figure 3).
Ambient air variables are substituted for the room m variables
AP = Pj - Pi
= Pm - Pn + PSl (7)
where
6
E
INI hij INI
I
I I
I
I
' I
I
I
' >
I
I
I
1 I
1
I
I
! I I
I I I I
I I I I
I I I I
n
ROOM
7
Figure 2. Horizontally adjacent rooms
8
\\\\<\\\\\^
9
2.3.3 Flow Equations
The flow through small openings in a surface is based on the orifice equation
where A is the observed opening area and where the flow coefficient, C, is a
function of the Reynolds number and the ratio of the opening size to the entire
surface. When the opening is small, C equals 0.6 for a wide range of Reynolds
numbers [7]. The MRLP assumes this value of C. The user may modify c by using
an effective flow area (FA) which differs from the actual opening area. Experi-
mental results indicate that flow through real surfaces is a combination of
orifice flow (Fo:/AP) and capillary flow (F“:AP) with an exponent of about 0.65
[8] In order to retain the concept of opening area and provide a simple
grouping of all other terms in equation 8, C is multiplied by /T and D divided
by /D to give
where FA^ is the effective flow area of the openings in the surface and D is
the density of Incoming air. The pressure difference for envelope surfaces is
AP = PSi + Pm - Pn (10b)
or
Fs + S Fi = 0 (12)
where Fg is the net mass flow into the room from the air-handling system.
These mass balances form a system of non-linear algebraic equations which can
be solved for the room pressures.
[ 7 ]
ASHRAE Handbook 1977 Fundamentals , p 4.10.
10
2.3.4 Solution of the Flow Equations
There are several methods for solving such a set of equations. Most involve
computing the following partial derivatives:
3Fi
= -Xi * F^/AP (13a)
9Pn
3Fi
= Xj * Fj/AP (inter-room surface) (13b)
9 Pm
or
9 Pi
= 0 (envelope surface) (13c)
9 Pm
Two methods for solving the air flow equations were studied. First was the
standard Newton's method for systems of equations [9]. This method was found
to give fast solutions in several test cases but to be non-convergent in other
very similar cases. Convergence could be obtained in those cases by the choice
of a suitable relaxation coefficient. The tests showed no pattern of non-
convergence which would allow prediction of a usable relaxation coefficient.
The second method tested was a simple iterative scheme from Conte and De Boor
[10]. It called for successively approximating each zone pressure according to
Pn^^'*'^^ = ^ Fi/2
^
—
9Pn
(14)
where k is the iteration number. This method was often slower than Newton's
method, but it converged for all of the simple test cases. It was therefore
chosen for use in the MRLP.
[9] Stoecker, W. F., Design of Thermal Systems , McGraw-Hill, 1971, pp. 92-93.
[10] Conte, S.D. and De Boor, C., Elementary Numerical Analysis, an Algorithmic
Approach, McGraw-Hill, 1972, p. 88.
11
2.4 SAMPLE PROBLEM
A study of the combined multi-room heat balance with air flow simulation was
done by using a "typical design" townhouse [11]. The floor plan is shown in
figure 4. and figure 5 is a section of the townhouse. There is a total of
(1315 ft^) 122 m^ living area on the two levels and (10850 ft^) 307 m^ of
conditioned space.
The MRLP input deck describing this building is given in appendix C. The
building is divided into 5 thermal zones: the first floor and stairwell (room
1), each of the three bedrooms (rooms 2, 3, and 4), and the attic (room 5).
Conductive heat transfer was modeled with 98 surfaces, and air flows were
modeled in 37 openings. The model probably uses much more detail than is neces-
sary to obtain a reasonable estimate of the energy requirements, but the detail
is useful in testing the capabilities of the program.
The opening areas were assumed according to ASHRAE [12] which suggests openings
of about .02 percent to .05 percent of the total surface area for frame walls
and .01 percent to .04 percent for ceilings. The largest values were chosen
for the test building. Inter-room partitions and floors were also given .05
percent openings. Additional inter-room opening areas of 0.046 m^ (0.5 ft^) for
the (almost closed) doors were used in the base case. The attic had a soffit
area of 0.186 m^ (2.0 ft^) on the north side only and a porosity of .10 percent
for the roof.
[11] Hastings, S.R., "Three Proposed Typical House Designs for Energy
Conservation Research," National Bureau of Standards Interagency Report
(NBSIR) 77-1309, 1977.
12
Q£
O
ft^)
ft^
(10,840
(1315
307
-
122
volume
area
Total Total
.001
13
3. RESULTS AND DISCUSSION
Figure 6 shows the results of three test computer runs for a winter weather
condition with only the wind direction changed. When the wind blew perpendicu-
lar to the exposed sides of the house (cases 6a and 6c), an infiltration rate
of just over one air change per hour (ach) was produced. The location of the
soffit is the primary reason for the difference in results between the cases
of north and south winds. When the wind blew parallel to the townhouse (case
6b), infiltration was only .22 ach. This was due mostly to stack effect.
These values compare favorably to ASHRAE design air change rates for residences
[13]. ASHRAE recommends 1 ach for rooms with windows or exterior doors on one
side and 1.5 ach for rooms with windows or exterior doors on two side. For
rooms with weatherstripped windows or with storm sash, two thirds of these
values should be used. The estimated loads (case a = 7.41 kW, case b = 4.68 kW,
case c = 7.87 kW) show that infiltration and wind direction effects on infil-
tration are important components of total heating load of this typical structure
Computation times varied from about 7 to 15 seconds per simulation day.
Figure 7 shows four cases comparing the effects of the size of inter-room
openings on the air change rates, loads, and calculation times. The small
openings simulation (case 7a) assumes 0.009 m^ (0.1 ft^) openings between rooms
instead of the standard 0.046 m^ (0.5 ft^) (case 7b) openings. The third case
(7c) simulated infinite openings between rooms by modeling the four rooms of
the townhouse as a single room. There is no significant change in the calcu-
lated loads in these three cases (7.34 kW, 7.41 kW, and 7.42 kW) which go from
the smallest reasonable inter-room openings to no inter-room flow resistance.
Although the total load in the small openings case is only one percent smaller
than the base case, there are much greater differences in the loads of the
Individual rooms (room 1 = +1 percent, room 2 = +6 percent, room 3 = -8 percent,
room 4 = -8 percent). This is noticeable in real buildings where closed-off
rooms on the windward side become colder than the leeward rooms.
The fourth case (7d) used the air change rate computed for the single room
model to compute loads based on a known air change rate instead of on the pres-
sure and air flow balance model. This gave the same load, as it should, and
required only 3.9 seconds/day simulation time. The time of other cases in
excess of this amount is the computation cost of the detailed air flow algorithm
These calculation times are good only for relative comparsions because they are
greatly affected by the numbers of surfaces, rooms, and openings and the conver-
gence limits of the simulation. Comparing case 7c to 7d, the increase in com-
putation time of 18 percent appears justified because of the importance of
infiltration in the total heating load of the building. However, in case 6b
infiltration is making a much smaller contribution to the load and calculation
15
6.7
NORTH WIND m/s
(15 mph)
-14.4°C
(6°F)
I.02 ach
6.7
7.41 kWh
II. 1 sec/day
m/s
WEST WIND
0.22 ach
4.68 kWh
14.7 sec/day
6.7 m/s
SOUTH WIND
1.17 ach
7.87 kWh
7.0 sec/day
16
21 JAN SMALL INTER-ROOM OPENINGS
6.7 m/s
-14.4°C
1.00 ach
7.34 kWh
8.2 sec/day
STANDARD OPENINGS
I. 02 ach
7.41 kWh
II. 1 sec/day
SINGLE ZONE
1.03 ach
7.42 kWh
4.6 sec/day
CASE 7d
AIR CHANGE METHOD: using same ach
gives same load
3.9 sec/day
17
time is almost 15 seconds. In this situation the computational cost is not
justified.
Note in the multi-room cases that as the areas of the inter-room openings
increase, the calculation time goes up dramatically. In fact, it was not
possible to simulate a case with 0.186 m^ (2.0 ft^) openings between rooms.
This situation called for the development of a simple test case to study the
effects of inter-room opening area on the calculation technique. The results
are shown in figure 8. The first case represents a single room consisting of
two walls, each with opening areas of 0.01 m^ (0.11 ft^) one facing into a
6.7 m/s (15 mph) wind and one facing away from it. The flow through the room
is computed to be 2.98 m^/h (105. ft^/h) and requires only 2 Iterations. The
next case shows the original room divided into two rooms by a partition contain-
ing a 0.01 m2 opening. This reduces the air flow rate to 1.95 m^/h (68.9 ft^/h)
and raises calculation time to only 3 iterations. As the area in the partition
opening is doubled in succeeding cases, the air flow rate approaches the single
room flow rate while the calculation time increases rapidly. For example, the
partition with 0.08 m^ opening area has a flow within one percent of the single
room value but requires over twelve times as long to calculate. The next larger
case, 0.16 m^, could not be calculated within the iteration limit. However, it
is obvious that assuming the single room air flow value would be correct to
within one percent.
Other tests of the two-room model indicated that it is the relative size of the
inter-room and envelope openings, not the absolute size, which is affecting
computation time. Solutions were reached rapidly for all cases where the
envelope openings were larger than the partition openings. This property per-
mitted modeling the soffit of 0.186 m^ (2.0 ft^) with no problems. It suggested
that it should be possible to simulate the condition where the envelope openings
are about the same size as the inter-room openings. This is the case when win-
dows have been opened to get natural ventilation. Figure 9 shows how ventila-
tion can affect the building conditions. A warm, sunny fall afternoon was
chosen as the test weather condition. The top figure (case 9a) shows the air
flow rates and room temperatures for the standard configuration of envelope and
partition openings. Note that the south bedroom is at 35.8 C (96.4 F). In
18
WALL PTN WALL aOW ITERATIONS
2.98 mVhr
a
0.01 FLOW AREAS 0.01 m2
I 1.95
I
O01 0.01 aoi
I 1 2.56
I I I
001 ao2 aoi
I
2.85 8
I
O01 ao4 aoi
1
2.95 25
I
O01 0.08 aoi
I unsolved >80
I I
0.01 0.16 0.01
19
21 SEP
3 P.M. CLOSED WINDOWS — 3.3 m/s
26.7X
(80°F)
0.41 ach
16.0 sec/day
5.26 ach
7.5 sec/day
The MRLP air movement algorithm is theoretically capable of modeling high and
low openings in a single wall. This was not tested in the sample problem. It
has potential use in the case where one room is significantly hotter than the
other and a stack effect is developed between the high and low openings. This
condition occurs in a Trombe wall where the space between the cover and the
wall may be considered and extremely narrow room. The narrowness of the room
adds a further resistance to air flow (besides that of the wall openings) which
should be added to the air flow model.
The air flow model does not address two important classes of openings. One is
the doorway where bi-directional flows can occur. It may be possible to handle
this by using a high and a low opening. The other case is the opening between
floors as it is affected by thermal stratification. A very rapid air exchange
will take place between a warm room below a cold room, whereas almost no air
will move between a cold room below a warm one. This diode effect will add a
further complication to the already non-linear air flow equations. Two openings
may set up a large convection pattern with much greater air movement than a
single opening of equivalent area.
The possibility of separating the envelope from the inter-room air flow
calculation suggests a way of handling these additional features. ASHRAE [14]
shows that the flow through an orifice is no longer proportional to the square
root of AP at very low Reynolds number. In fact, it becomes proportional to
AP. The Reynolds number of air flow between rooms connected by an open door
appears to be typically in a transition region. If it can be modeled to suffi-
cient accuracy by the linear assumption, solution of the multi-room flow problem
would be greatly simplified. Only simultaneous linear equations would have to
be solved. It may also be possible to superimpose bi-directional effects.
The general problem of thermal stratification in the room air should also be
addressed. Two simple models are possible. The first would assume a linear
temperature profile from the room's coldest point at the floor to its warmest
point at the celling. The slope of this profile would be determined experimen-
tally. The second method would divide the room air into two parts: a warm
upper layer and a cooler bottom layer. Energy would be convected between these
layers and from walls and internal sources to each layer according to experi-
mentally determined coefficients. Heat balances could then be performed for
each layer.
The current air flow model and the possible extensions all require experimental
validation to show if they are sufficiently accurate. If it is also shown that
the computation cost is low enough, the method can be recommended for use in
21
energy analysis design tools. It would then be necessary to develop a data
base of openings areas and flow exponents for different building constructions
for design ;v^5e.
22
APPENDIX A: PROGRAM STRUCTURE
The MRLP is divided into two subprograms: the input processor (IP) and the
loads calculator (LG). This structure is illustrated in figure Al. The IP
checks the user input, prepares input files for the LC, and reports the array
sizes that the LC will require. The LC performs the building loads simulation
and reports the results. This separation of subprograms allows a reduction in
computer core requirements. The IP uses minimal array sizes because it processes
the input one element (surface, schedule, material, etc.) at a time. The LC
uses large arrays which consider these elements simultaneously. The LP and LC
may be run as separate jobs when it is necessary to recompile the LC for correct
array sizes, or they may be run as a single job if the LC is known to have
sufficiently large arrays.
The input processor is divided into four major sections. These correspond to
the input language sections which they process. This sectioning allows further
reductions in core requirements by the use of overlays (or segments). A small
input processor is important to allow the fast job turn-around necessary to
quickly debug the user input deck. Each section contains several subroutines
which process the input language "keys" plus others for special elements of
certain keys. The two largest of these special routines are the groups of sub-
routines which evaluate the conduction transfer functions and the window optics.
The loads calculator is divided into three sections. The first section reads
the file created by the IP and fills the LC arrays. It checks for sufficient
array space and performs some checks which require that all data for the problem
description be present in the arrays. The second section uses the geometric
and optical descriptions of the building surfaces to compute solar gain factors
for various periods of the year. The third section does the actual heat balances
necessary to compute the multi-room loads on a hour-by-hour basis.
A-1
LOADS CALCULATOR
It is intended that the MRLP input deck be an on-line file which is created and
modified by a text editing system. It can also be a deck of punched cards.
There is a simple, consistent input structure. The input is based on a keyword
system (keyword = value) to produce a free-fomat, self-descriptive input lan-
guage. In some ways it is similar to NAMELIST input which is a feature of some
versions of FORTRAN. The keyword system is organized in a logical heirarchy
which groups related concepts and data. Defaulting is used extensively. This
applies to individual values and to groups of values representing entire elements
of building operation or description. Some groups of often used data can be
named and then used many times by referring to the name.
The input deck for the test case (appendix C) demonstrates the features of the
input language. On the first page of the townhouse input deck nine lines below
"LIBRARY" is the line:
This line of input describes the conductivity (K=.42), density (D=100.), and
specific heat (CP=.2) of a gypsum wallboard, and gives this material the name
GYP. Other properties of this material which are not mentioned, such as its
roughness, solar absorptance, and thermal emittance, are given default values
by the input processor. Twelve lines further down is the input:
This describes the partition walls at the studs and gives this construct the
name PTN-S. It consists of two .0417 ft (.5 in) thick layers of the already
defined GYP (wallboard) with a 0.292 ft (3.5 in) thick layer of WD-S (softwood)
between them. This construct is then used in the input at the bottom of the
second page
This line is describing the stud area of the partition along the east side of
the first zone of the townhouse. IN means this is an interior rather than enve-
lope surface. This will determine the type of surface heat balance performed.
OP means it is opaque instead of transparent and determines which algorithm is
used to model the effects of solar energy and other short-wavelength thermal
radiations on the surface. BS means it is a base surface. That is, its loca-
tion and orientation are not based on another surface. This surface faces east
(AZM=90) and is 3.5 ft wide by 8.5 ft high (SIZE=3.5,8.5) . This width is the
combined width of all studs in the wall.
B-1
I
'JK"
APPENDIX C; TOWNHOUSE INPUT DECK
PROJECT C
RC<XREF/DEH/UIN=EN6LISH/U0UT=METRIC/
DESC=M ZONE HASTINGS TOWN HOUSE PLUS ATTIC')
RPT<RNOS = 8» 21)
LOC(DESC='COLUMBIAj M0» '/LATD=38*9/L0N6=?2,3/TZ=6)
GRND(GRT=56»55..56j!=i9j61f65f68j70f69f A6»62f59)
DDY(DESC=' COLUMBIA WINTER /HIGH=26/L0W=6/WB=20/DATE=21JAN/PRES=405/
'
WS=1320/DIR^0/CLR=1 ./SAT)
1
LIBRARY C
LIB(NMATL=32/NC0NS=32)
MATL(NAME=C-HW/DESC='CONCRETE - SAND i GRAVEL /K=l 104/D=140 /CP= .2 ' . .
MATL(NAME=R11/DESC='R11 INSULATION'/R=ll .
C-1
C0NS(NAME=FLR2-A/DESC='SEC0ND FLOOR FLOOR - AIR SPACE AREA'/
MATL^»0417fGYPf 0jE4f »0625»WD-B» O.CPT)
C0NS(NAME=FLR2-T/DESC='SEC0ND FLOOR FLOOR - TRUSS AREA'/
HATL^»0417y6YPf 792»UD-Sf »0625fUD-S» OjCPT)
C0NS(NAME=FLR2-I/DESC='SEC0ND FLOOR FLOOR - INSULATION AREA'/
HATL=»03125fWD-SF 0»R11> »0625 jWD-S.. OjCPT)
CONS(NAME=PTN-I/DESC='PARTITION - INSULATION AREA'/
MATL=.0417»GYP, OfRll» »0417fGYP)
CONS(NAME=ROOF-A/DESC='ROOF - BETWEEN TRUSSES'/
MATL^,01.04f ASH» 04l7fWD-S)
CONS<NAME=ROOF-T/DESC='ROOF - AT TRUSSES'/
MATL=^0104..ASH^ 04176?WD-S» f292»WD-S)
CONS (NAME=BLAB/DESC=' SLAB FLOOR'/
MATL:--,5fIiIRTf 0fR5» »333i.C-HW. OjCPT)
CONS (NAHE=HOOR/DESC=' FRONT ENTRY /MATL=» 146 jWD-H)
'
CPFL(NAME=CL/DESC='COOLING'/TMP=65 j65j78»78/CAP=1»0»O>-1)
CDS (NAME=WD/DESC=' WINTER - WEEKDAY '/CPFL = 6!|!SB.2)KHTj9*SB.6*HTj SB)
CWS(NAME=WINTER/DESC=' WINTER '/WD=WD)
D
BUILDING C
SIM<SLDS=2/HTB=1/FL0W=.0001 »0001>80 »9/CNVG=»Ol5 »001» *1 j12)
j j
ZONE L
C-2
$ INTERNAL PARTITIONS - 167 .4 »24 »9 80
» *
SRF(C0NS=PTN-A/IN/OP/BS/AZM=180/SIZE^19»44f7»67/Z0NE=liBIiRM)
SRF<C0NS=PTN-S/IN/0P/BS/AZM=180/SIZE=2»39,7»67/Z0NE=MBIiRM)
AFS(AREA=»5/ZS=12.5)
BRF<C0NS=PTN-A/IN/0P/BS/AZM=90/SIZE=2.9f7.67/Z0NE=BDRM2)
SRF(C0NS=PTN-S/TN/0P/BS/AZM-=90/SIZE=t35»7»67/Z0NE=BDRM2)
AFS(AREA=»5/ZB=12.5)
SRF(C0NS=PTN-A/IN/0P/BS/AZH=0/SIZE=9.36j7»67/Z0NE=BDRM3)
SRF(C0NS=PTN-S/IN/0P/BS/AZM=0/SIZE=1»15»7.67/Z0NE=BDR«3)
AFS(AREA=.5/ZS=12»5)
i INTERNAL MASS
MASS(C0NS=PTN-A/AREA=795)
MASS(C0NS=PTN-S/AREA=98)
% NORTH EXTERIOR WALL - 165.1
SRF(C0NS=WL-S/EX/0P/BS/AZM=0/SIZE^2.0?8.5/0RG^2.29j34j .67)
AFS(AREA=.050)
AFS(AREA=.047/ZS=.l)
SRF(C0NS=WL-I/EX/0P/BS/AZM=0/SIZE=17.42j8.5/0R6=19.71r34» .67)
$ GLASS DOOR
SRF(C0NS=WDU/EX/TR/SS/SIZE=5.73j6.72/0RG=2.24>.47j-.17)
$ WINDOW
SRF(C0NS=WDW/EX/TR/SS/SIZE=4.98j3.83/0RG=12.2j3.5»-.17)
$ SOUTH EXTERIOR WALL - 222.9
SRF(C0NS=PTN-I/EX/0P/BS/SIZE=5.3»8.5)
0SC(TZP=.3/TAP=.7)
SRF<C0NS=WL-I/EX/0P/BS/AZM=180/SIZE=6.67j8/0RG=3.75j3.67j 67)
SRF(C0NS=D00R/EX/0P/SS/SIZE^3.1f6.97/0RG^^0» .IfO)
SRF(CONS=WL-S/EX/OP/BS/AZM=180/SIZE=7»8/ORG=10.4 ?jO> 67)
SRF(C0NS=WDW/EX/TR/SS/SIZE=5.73j6.72/0RG=.63f .33J-.17)
SRF(C0NS=WL-I/EX/0P/BS/AZM=270/SIZE=2.77 j8/0RG=10.42j 2.77» .67)
SRF(C0NS=WL-S/EX/0P/BS/AZM=270/SIZE=.9f8/0RG=l0.42f3.67j .67)
SRF(CONS=WL-I/EX/OP/BS/AZM=90/SIZE=2 j8.5/ORG=17.4jOj 67)
SRF(C0NS=WL-I/EX/0P/BS/AZM=180/TILT=90/SIZE-2.6j8.5/0R6=17.4f2. .67)
AFS<AREA=.060)
AFS(AREA=.058/ZS=.l)
$ FLOOR
SRF(CONS=SLAB/EX/0P/BS/AZM=18O/TILT=180/SIZE=20f31.6/ORG=0.34j .67)
0SC(TGP=1)
$ CEILINGS - 129. 1j 216. 4j 129.? 104.3
SRF(C0NS^CLG2-I/1N/0P/BS/TILT=0/SIZE=11.97?10/Z0NE=ATTTC)
SRF(C0NS=CLG2-T/IN/0P/BS/TILT=0/SIZE=.94?10/Z0NE=ATTIC)
AFS(AREA=.049/ZS=16.5)
SRF(C0NS=CLG1-A/IN/0P/BS/TILT=0/SIZE=19.27?10/Z0NE=MBDRM)
SRF(C0NS=CLG1-T/IN/0P/BS/TILT=0/SIZE==2.37?10/Z0NE=MBDRM)
AFS(AREA=.167/ZS=8.5)
SRF<C0NS=CLG1-A/IN/0P/BS/TILT=0/SIZE=11.49?10/Z0NE=BDRM2)
SRF(C0NS^CLG1-T/IN/0P/BS/TILT=0/SIZE-=1.41?10/Z0NE=BDRM2)
AFS(AREA=.065/ZS=8.5)
SRF(C0NS=CLG1-A/IN/0P/BS/TILT=0/SIZE=9.29»10/Z0NE=PDRM3)
SRF(C0NS=CLG1-T/IN/0P/BS/TILT^0/SIZE-1.14?10/Z0NE=BDRM3)
AFS(AREA=.080/ZS=8.5)
SRF(C0NS=CLGl-I/EX/0P/BS/TILT=0/AZM=0/SIZE=7»2/nRG=10.4»2?8)
C-3
% SCHEDULES
LIT(WS=LKW/CAP=»7)
LIT(WS=LLW/CAP=1*2/RAD=»8/UIS=,1)
EQP(US=EKW/CAP=5»9)
EQP(WS=C0NST/CAP=1»5)
CTRL(CWS=WINTER/)
3
ZONE C
$ MASTER BEDROOM
GE0M(NAME=MBDRM/Z=9.17/CLHT=8)
$ PARTITIONS - 76»5j 137. 167. 41.4
SRF(C0NS=PTN-A/IN/0P/BS/AZM=180/SIZE=8.88?7.67)
SRF(C0NS=PTN-S/IN/0P/BS/AZM=270/SIZE=1.09»7.67)
SRF(C0NS=PTN-A/IN/0P/BS/AZM=90/SIZE=15.96f7.67)
SRF(C0NS=PTN-S/IN/0P/BS/AZM=90/SIZE=1.96»7.67)
SRF(C0NS=PTN-A/IN/0P/BS/AZM=^0/SI7E = 19.44»7.67/Z0NE=FLR1)
SRF<C0NS=PTN-S/IN/0P/BS/AZM=0/SIZE=2.39»7.67/Z0NE=FLR1)
AFS(AREA=.5/ZS=4.
SRF(C0NS=PTN-A/IN/0P/BS/AZM=0/SIZE=4.8j7.67/Z0NE=BDRM2)
SRF(C0NS=PTN-S/IN/0P/BS/AZM=0/SIZE=.6f7.67/Z0ME=BDRM2)
AFS(AREA=.019/ZS=4.
SRF CONS=PTN-A/ IN/OP/BS/SI ZE=9 8
( .
SRF(C0NS=WL-S/EX/0P/BS/AZM=180/SIZE=.97»8/0R6=18.67j2j0)
AFS(ARFA=.055)
AFS(AREA=.054/ZS=8.
$ FLOOR
SRF(CONS=FLR2-I/EX/OP/BS/AZM=180/TILT=180/SIZE=3.27>10.42/ORG=0»3.67f0)
SRF(C0NS--FLR2-T/EX/0P/6S/AZM=1.B0/TILT = 180/SIZE=.40f 10.42/0RG=0f .40.-0)
SRF(C0NS=FLR2-A/IN/0P/BS/TILT=180/SIZE=19.27»10/Z0NE=FLR1)
SRF(C0NS=FLR2-T/IN/0P/BS/TILT=180/SIZE--2.37f 10/Z0NE=FLR1)
AFS(AREA=.167)
$ CEILING - 256.7
SRF(C0NS=CLG2-I/IN/0P/BS/TILT=0/SIZE=23.8j 10/Z0NE=ATTIC)
SRF(CONS=CLG2-T/IN/OP/BS/TILT=O/SIZE=1.87»10/ZONE=ATTIC)
AFS(AREA=.096/ZS=8.)
% SCHEDULES
LIT(WS=LBW/CAP-=.6/RAD=.8/VIS=.l)
CTRL(CWS=WINTER)
3
ZONE C
$ BEDROOM *2
GE0M(NAME=BDRM2/Z=9.17/CLHT=8>
C-4
$ PARTITIONS - -> 82.8
SRF(C0NS=PTN-A/IN/0P/BS/AZM=90/SIZE=14.16»7.67)
SRF<C0NS=PTN-S/IN/0P/BS/AZM=90/SIZE=1 .74»7.67)
SRF(C0NS=PTN-A/IN/0P/BS/AZ«=180/SIZE--^4,8»7.67/Z0NE=MBDRM)
SRF(C0NS=PTN-S/IN/0P/BS/AZM=180/SIZE=.6»7.67/Z0NE=fiBDRM)
AFS(AREA=.019/ZS=4.
SRF(C0NS=PTN-A/IN/0P/BS/AZM=270/SIZE=2.9»7.67/Z0NE=FLR1)
SRF(C0NS=PTN-S/IN/0P/BS/AZM=270/SIZE=.35j7.67/Z0NE=FLR1)
AFS(AREA=.5/Z8=4.)
SRF(C0NS=PTN-A/IN/0P/BS/AZM=270/SIZE=9.6»7.67/Z0NE=BDRM3)
SRF(C0NS=PTN-S/IN/0P/BS/AZh=270/SIZE^1.2f7.A7/Z0NE=BDRM3)
AFS(AREA=.038/ZS=4.
$ NORTH WALL - 77.7
SRF(C0NS=WL-I/EX/0P/BS/AZM=0/SIZE^-8.65f8/0R6=19.72»34j0)
SRF<C0NS=WDW/EX/TR/SS/SIZE=5.0»4.17/0R6=2.35>3.5>-.17)
SRF(C0NS=WL-S/EX/0P/BS/AZM=0/SIZE=1.O6>8/ORG=11.O7»34 jO)
AFS(AREA=.022)
AFS(AREA=.020/ZS=8.)
$ FLOOR
SRF(CONS=FLR2-A/IN/OP/BS/TILT=180/SIZE=11.49»10/ZONE=FLR1)
SRF(C0NS=FLR2-T/IN/0P/BS/TILT=180/SIZE=1.41j10/Z0NE=FLR1)
AFS(AREA=.065)
i CEILING - 192.
SRF(C0NS=CLG2-I/IN/0P/BS/TILT=0/SIZE=11.9,10/Z0NE=ATTIC)
SRF(C0NS=CL62-T/IN/0P/BS/TILT=0/SIZE=.94»10/Z0NE=ATTIC)
AFS(AREA=.048/ZS=8.
% SCHEDULES
LIT(WS=LBW/CAP=.4/RAD=.8/VIS=.l)
CTRL<CWS=WINTER)
3
ZONE C
% BEDROOM *3
GE0M(NAME=BDRM3/Z=9.17/CLHT=^8)
i PARTITIONS - 80. 6» 82. 8» 92.8
SRF(C0NS=PTN-A/IN/0P/BS/AZM=180/SIZE^9.36»7.67/Z0NE=FLR1)
SRF<C0NS=PTN-S/IN/0P/BS/AZM=180/SIZE=1.15»7.67/Z0NE=FLR1)
AFS(AREA=.5/ZS^4)
SRF(C0NS=PTN-A/IN/0P/BS/AZM=90/SIZE=9.6»7.67/Z0NE=BDRM2)
SRF(C0NS=PTN-S/IN/0P/BS/AZM=90/SIZE=1.2»7.67/Z0NE=BDRM2)
AFS(AREA=.038/ZS=4)
SRF(C0NS=PTN-A/IN/0P/BS/AZM=270/SIZE=10.8j7.67)
SRF(C0NS=PTN-S/IN/0P/BS/AZM=270/SIZE=1.3>7.67)
% NORTH WALL - 77.7
SRF(C0NS=WL-I/EX/0P/BS/AZM=0/SIZE--8.63f8/0RG=10j34>0)
SRF(C0NS=WDW/EX/TR/SS/SIZE=5.0»4.17/0RG=2.35»3.5»-.17)
SRF(C0NS=WL-S/EX/0P/BS/AZM=0/SIZE-=1.06»8/0RG=1.35 j34j0)
AFS<AREA=.022)
AFS(AREA=.020/ZS=8.)
% FLOOR - 104.3
SRF(C0NS^FLR2-A/IN/0P/BS/TILT=180/SIZE=9.29j10/Z0NE=FLR1)
SRF(C0NS=FLR2-T/IN/0P/BS/TILT=180/SIZE=1.14>10/Z0NE=FLR1)
AFS(AREA=.080)
C-5
% CEILING - 104»3
SRF(C0NS=CLG2-I/IN/QP/BS/TILT^0/SIZE=9^67Jl0/Z0NE=ATTIC)
SRF(C0NS=CLG2-T/IN/0P/BS/TILT=0/SIZE=.76j10/Z0NE=ATTIC)
AFS(AREA=»039/ZS=8»
$ SCHEDULES
LIT(WS=LBW/CAP=,4/RAD=»8/UIS=»1)
CTRL(CWS=WINTER)
:
ZONE C
$ ATTIC
GE0M(NAME=ATTIC/Z=17.17/CLHT=2»2)
$ ATTIC FLOOR - 129»1j 256»4> 129»» 104*3
SRF(C0NS-^FLR3-I/IN/OP/BS/TILT = 18O/SIZE = ll*97f 10/Z0NE=FLR1)
SRF(C0NS=FLR3-T/IN/0P/BS/TILT=180/SIZE=,94»10/Z0NE=FLR3
AFS(AREA=*049)
SRF(CONS=FLR3-I/IN/OP/BS/TILT=180/SIZE=23*8>10/Z0NE=MBDRM)
SRF(C0NS^FLR3-T/IN/0P/BS/TILT=180/SIZE=1*87j10/Z0NE=MBDRM)
AFS(AREA=*096)
SRF(C0NS=FLR3-I/IN/0P/BS/TILT=180/SIZE=ll*9f 10/Z0NE=BDRM2)
SRF(C0NS:^FLR3-T/IN/OP/BS/TILT=180/SIZE=*94 j10/ZONE=BDRM2)
AFS(AREA=*048)
SRF(C0NS=FLR3-I/IN/0P/BS/TILT=180/SIZE=9*67»10/Z0NE=BDRM3)
SRF(C0NS=FLR3-T/IN/0P/BS/TILT=180/SIZE=*76j10/Z0NE=BDRM3)
AFS(AREA=*039)
SRF(CONS=RO0F-A/EX/OP/BS/AZM=O/TILT = 180/ORG=19*73 »34>0/SIZE=19*42»2)
AFS(AREA=2,/EXP=*5)
$ ROOF
SRF(C0NS=R00F-A/EX/0P/BS/AZM=180/TILT-22»6/SIZE=20f 18*8/0RG=0f0F0)
AFS(AREA=*35)
SRF(CONS=ROOF-A/EX/OP/BS/AZH=0/TILT=22*6/SIZE=20jl8,8/ORG=20»34fO)
AFS(AREA=*35)
$ NO SCHEDULES
:
C-6
21 JAN SMALL INTER-ROOM OPENINGS
6.7 m/s
-14.4°C
I
1.00 ach
I
I
7.34 kWh
8.2 sec/day
ii Fh
STANDARD OPENINGS
I. 02 ach
7.41 kWh
II. 1 sec/day
SINGLE ZONE
1.03 ach
7.42 kWh
4.6 sec/day
CASE 7d
AIR CHANGE METHOD; using same ach
gives same load
3.9 sec/day
NBS-114A (REV. 2-80
U.S. DEPT. OF COMM. 1, PUBLICATION OR 2. Performing Organ. Report No. 3. Publication Date
REPORT NO.
BIBLIOGRAPHIC DATA NBSIR 81-2404 December 1981
SHEET (See instructions)
4. TITLE AND SUBTITLE
5. AUTHOR(S)
George N. Walton 742.01
6. PERFORMING ORGANIZATION (if joint or other than NBS, see instructions) 7. Contract/Grant No.
9. SPONSORING ORGANIZATION NAME AND COMPLETE ADDRESS (Street. City, State, ZiP)
DEPARTMENT OF ENERGY
NBS and Passive and Hybrid Solar Energy Division
Office of Solar Heat Technologies
Washington, DC 20585
10. SUPPLEMENTARY NOTES
I I
Document describes a computer program; SF-185, FIPS Software Summary, is attached.
11. ABSTRACT (A 200-word or less factual summary of most significant information. If document includes a significant
bi bliography or literature survey, mention it here)
A model is presented for computing the infiltration and air flow between rooms of a
multi-room building in terms of basic principles of fluid mechanics. This model
has been incorporated into a comprehensive loads-predicting computer program.
Air flows, room temperatures, and heating loads for a typical townhouse under
different conditions of environment and with various construction features are
computed. These calculations show the feasibility of detailed multi-room air
movement analysis. They also indicate that when the inter-room openings of a low-
rise structure are large compared to the envelope openings, the infiltration and
total load can be accurately, and more quickly, computed by assuming no resistance
to air flow between rooms. This property will also allow simplified calculations
for high-rise buildings with many rooms. Methods are proposed for handling more
complex air flow phenomena.
12. KEY WORDS (Six to twelve entries; alphabetical order; capitalize only proper names; and separate key words by semicolon s)
building energy analysis; computer simulation; infiltration; natural ventilation
$6.50
Order From National Technical Information Service (NTIS), Springfield, VA. 22161
USCOMM-DC 6043-P80
1