Product Data Sheet: Tesys Gv2 - Circuit Breaker - Magnetic - 25 A - Screw Clamp Terminals

1) The document provides product data and specifications for a TeSys GV2 circuit breaker with the model number GV2L22, rated for 25A and screw clamp terminals. 2) It is a 3-pole magnetic circuit breaker intended for motor applications on AC networks between 50/60Hz. 3) Key specifications include a breaking capacity of 10kA, rated operational voltage of 690V AC, and mechanical durability of 100,000 cycles.

Uploaded by

Johan Maya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
133 views

Product Data Sheet: Tesys Gv2 - Circuit Breaker - Magnetic - 25 A - Screw Clamp Terminals

1) The document provides product data and specifications for a TeSys GV2 circuit breaker with the model number GV2L22, rated for 25A and screw clamp terminals. 2) It is a 3-pole magnetic circuit breaker intended for motor applications on AC networks between 50/60Hz. 3) Key specifications include a breaking capacity of 10kA, rated operational voltage of 690V AC, and mechanical durability of 100,000 cycles.

Uploaded by

Johan Maya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Product data sheet GV2L22

Characteristics TeSys GV2 - Circuit breaker - magnetic - 25 A -


screw clamp terminals

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range TeSys
Product name TeSys GV2
Device short name GV2L
Device application Motor
Poles description 3P
Network type AC
Utilisation category AC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2
Network frequency 50/60 Hz conforming to IEC 60947-2
Breaking capacity 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit technology Magnetic
Magnetic tripping current 327 A

Complementary
Fixing mode Clipped on 35 mm symmetrical DIN rail
Screwed on panel (with 2 x M4 screws)
Operating position Any position
Motor power kW 11 kW at 400/415 V AC 50/60 Hz
11 kW at 500 V AC 50/60 Hz
15 kW at 500 V AC 50/60 Hz
9 kW at 400/415 V AC 50/60 Hz
18.5 kW at 690 V AC 50/60 Hz

Aug 16, 2019


1
Control type Rotary knob
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
Power dissipation per pole 1.8 W
Mechanical durability 100000 cycles
Electrical durability 100000 cycles for AC-3 at 415 V
Operating rate 40 cyc/h
Rated duty Continuous conforming to IEC 60947-4-1
Connections - terminals Screw clamp terminals 2 cable(s) 1...6 mm² solid
Screw clamp terminals 2 cable(s) 1.5...6 mm² flexible without cable end
Screw clamp terminals 2 cable(s) 1...4 mm² flexible with cable end
Tightening torque 1.7 N.m on screw clamp terminals
Mechanical robustness Shocks 30 Gn conforming to IEC 60068-2-27
Vibrations 5 Gn, 5...150 Hz conforming to IEC 60068-2-6
Suitability for isolation Yes conforming to IEC 60947-1
Phase failure sensitivity Yes
Height 89 mm
Width 45 mm
Depth 97 mm
Product weight 0.33 kg

Environment
Standards EN 60204
IEC 60947-1
IEC 60947-2
NF C 63-120
NF C 63-650
NF C 79-130
VDE 0113
VDE 0660
Product certifications BV
CCC
CSA
DNV
GL
LROS (Lloyds register of shipping)
RINA
Protective treatment TH
IK degree of protection IK04
Ambient air temperature for operation -20...60 °C
Ambient air temperature for storage -40...80 °C
Fire resistance 960 °C conforming to IEC 60695-2-1
Operating altitude 0...2000 m

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  0631  -  Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference contains SVHC above the threshold  -  Go to CaP for more details
Go to CaP for more details
Product environmental profile Available
Product Environmental Profile
Product end of life instructions Need no specific recycling operations

Contractual warranty
Warranty period 18 months

2
Product data sheet GV2L22
Performance Curves

Tripping Curves for GV2L or LE Combined with Thermal Overload Relay LRD or LR2K
Average Operating Times at 20 °C Related to Multiples of the Setting Current

1 3 poles from cold state


2 2 poles from cold state
3 3 poles from hot state

Current Limitation on Short-Circuit for GV2L and GV2LE Only (3-Phase 400/415 V)
Dynamic Stress
I peak = f (prospective Isc) at 1.05 Ue = 435 V

3
1 Maximum peak current
2 32 A
3 25 A
4 18 A
5 14 A
6 10 A
7 6.3 A
8 4 A
9 2.5 A
10 1.6 A
11 Limit of rated ultimate breaking capacity on short-circuit of GV2LE (14, 18, 23, and 25 A ratings).

Current Limitation on Short-Circuit for GV2L and GV2LE + Thermal Overload Relay LRD or LR2K (3-Phase 400/415
V)
Dynamic Stress
I peak = f (prospective Isc) at 1.05 Ue = 435 V

4
1 Maximum peak current
2 32 A
3 25 A
4 18 A
5 14 A
6 10 A
7 6.3 A
8 4 A
9 2.5 A
10 1.6 A
11 Limit of rated ultimate breaking capacity on short-circuit of GV2LE (14, 18, 23, and 25 A ratings).

Thermal Limit on Short-Circuit for GV2L Only


2
Thermal Limit in kA s in the Magnetic Operating Zone
2
Sum of I dt = f (prospective Isc) at 1.05 Ue = 435 V

5
1 25 A and 32 A
2 18 A
3 14 A
4 10 A
5 6.3 A
6 4 A
7 2.5 A
8 1.6 A

Thermal Limit on Short-Circuit for GV2L and GV2LE + Thermal Overload Relay LRD or LR2K
2
Thermal Limit in kA s in the Magnetic Operating Zone
2
Sum of I dt = f (prospective Isc) at 1.05 Ue = 435 V

6
1 32 A (GV2LE32)
2 25 A and 32 A (GV2L32)
3 18 A
4 14 A
5 10 A
6 6.3 A
7 4 A
8 2.5 A
9 1.6 A
10 Limit of rated ultimate breaking capacity on short-circuit of GV2 LE (14, 18, 23, and 25 A ratings).

7
Product data sheet GV2L22
Dimensions Drawings

GV2L
Dimensions

X1 Electrical clearance = 40 mm for Ue ≤ 415 V, or 80 mm for Ue = 440 V, or 120 mm for Ue = 500 and 690 V.
X2 = 40 mm.
GVAD, AM, AN, AU, AS

1 Maximum
GV2AK00

Mounting
On rail AM1 DE200, AM1 ED200 (35 x 15)

Panel mounted

On pre-slotted mounting plate AM1 PA

8
Adapter Plate GK2AF01

7.5 mm Height Compensation Plate GV1F03

Mounting
Mounting of External Operator GV2APN01, GV2APN02 or GV2APN04 for Motor Circuit Breakers GV2L

Door cut-out

(1) For IP65 only.


Mounting of External Operator GVAPH02 for Motor Circuit Breakers GV2L

Minimum Maximum

GV2 APN●● + GV APH02 151 250

GV2 APN●● + GV APH02 + GV APK11 250 445

9
Door cut-out

(1) For IP65 only.

GV2L and GV2LE


Sets of busbars GV2G445, GV2G454, GV2G472, with terminal block GV2G05

l p

GV2G445 (4 x 45 mm) 179 45

GV2G454 (4 x 54 mm) 206 54

GV2G472 (4 x 72 mm) 260 72

Number of tap-offs a

5 6 7 8

GV2G445 224 269 314 359

GV2G454 260 314 368 422

GV2G472 332 404 476 548


Sets of Busbars for GV2L and GV2LE
Sets of busbars GV2G●●● with terminal block GV1G09

Sets of busbars GV2G245, GV2G254, GV2GR272

GV2G245 (2 x 45 mm) 89

GV2G254 (2 x 54 mm) 98

GV2G272 (2 x 72 mm) 116

10
Set of busbars GV2G554

Sets of busbars GV2G345 and GV2G354

GV2G345 (3 x 45 mm) 134

GV2G354 (3 x 54 mm) 152

11
Product data sheet GV2L22
Connections and Schema

GV2L••

12