Line Size Calculation For Cooling Water Pipes: Pipe Size Provided Is OK

This document contains calculations to determine the appropriate pipe size for cooling water pipes. It analyzes flow rate, viscosity, density, length, velocity, pipe diameter, head loss, total head, and power requirements. For the unloading pump, it determines that the provided 100mm pipe size is adequate. For the transfer pump, it determines that the provided 25mm pipe is adequate but the calculations show the total head is unsafe and a larger pipe is recommended.

Uploaded by

jitendra shinde
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
350 views40 pages

Line Size Calculation For Cooling Water Pipes: Pipe Size Provided Is OK

This document contains calculations to determine the appropriate pipe size for cooling water pipes. It analyzes flow rate, viscosity, density, length, velocity, pipe diameter, head loss, total head, and power requirements. For the unloading pump, it determines that the provided 100mm pipe size is adequate. For the transfer pump, it determines that the provided 25mm pipe is adequate but the calculations show the total head is unsafe and a larger pipe is recommended.

Uploaded by

jitendra shinde
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 40

Line Size Calculation for Cooling Water Pipes

Data Sheet No.:


Customer :- GSML Job No.: 1089 Doc. No.:
Date : 17-11-2007 Page No.: 1 Rev 0
LINE SIZE CALCULATION UNLOADING PUMP
DATA :-

1) Flow Rate (Q) = 27.600 m^3/hr = 0.00767 m^3/s CONSIDERING 15% EXTRA
2) Viscosity(u) = 10.20 Cp
3) Density(q) = 850.00 Kg/m^3
4) Length(L) = 30.00 m
5) Velocity of Liquid (V) = 0.9766 m/s
6) Outside Dia. of Pipe provided = 100.00 mm 0.100
7) gravational Acc. 9.81 m/s^2
8) Pressure 3.00 Kg/cm^2
9) head available (Z2) = 8.00 m
By Continuity Equation,

Q = AxV
A = Q/V

(3.14 / 4 )*d^2 = 0.01 /0.9766

d = (0.01 /0.9766 / (3.14 / 4 ))^0.5


= 0.1000 m
= 99.98 mm

Minimum Inside Dia. of Pipe required (d) = 99.9770 mm 0.1000


As per Sch. 20 & 6.4 mm Thk. OD of Pipe required = 112.78 mm

Pipe size provided is OK

DATA :-

1) Flow Rate (Q) = 27.60 m^3/hr = 0.008 m^3/s


2) Velocity of Liquid (V) = 0.977 m/s
3) Outside Dia. of Pipe provided = 100.00 mm 0.10
pressure aatm. 101325.00 N/m^2
By Calculation, Va= 665.12
By Continuity Equation,
V= 0.9766454352
Q = AxV
A = Q/V Za = 2

(3.14 / 4 )*d^2 = 0.01 /0.97664543524 l = 15

d = (0.01 /0.976645435244161 / (3.14 / 4 ))^0.5


= 0.1000 m
= 99.97 mm

Minimum Inside Dia. of Pipe Required (d) = 99.97 mm


As per Sch. 20 & 6.4 mm Thk. OD of Pipe required = 112.77 mm

Increase Pipe size


or Cooling Water Pipes

CONSIDERING 15% EXTRA Re = DVq / u


(0.1 x 0.9766 x 850)/10.2
8138.3333333333 Re < 2100 LAMINAR
Re > 2100 TURBULANT
f = 16 / Re
0.0019660045

f = 0.079 /Re 0.25

= 0.0083175079

0.0083175079

hf = 4 f l v2 / 2 g d

((4x0.0083x30x H13^2)/2x9.81x100)
0.4852 m
0.6899355165 Head loss due to friction

Total head = 8.5338 m

safe Distance betn. Inlet to outlet.(Z) =

power req. = (gxZ2+V^2/2+hf)/ n


Total Head (H) =
862.8290459909
0.863 KW
1.157 Hp
v = 0.9766454352 Power Required =

Diff.Pr. = 0.049 Kg/cm^2


2.951 Kg/cm^2

NPSH = (Pa-Pv)/q - hfs +gZa


Re = DVq / u
8138.711960368
f = 0.079 /Re 0.25 16 / Re
0.0083174112 0.001965913
0.0083174112
hfs = 4 f l v2 / 2 g d
0.2426131117

NPSH = 137.8007751235
14.0469699412
DIFF HEAD 8.2912 m
DIFFERIENTIAL PRESSURE= (32xMuxVxL)/D^2
URBULANT
Mu = 0.0102 poise

956.29 N/m^2
(P1-P2) = 0.096 N/cm^2
0.0097 Kg/cm^2 0.009748
0.141 psi
hf = 0.099 m

power required(loss) 0.00073 W


0.00000073 KW
0.00000098 KW

ead loss due to friction = (32xMuxVxL)/(qxgxD^2)


Mu = 0.0102 pa.s

hf = 0.115 m
Distance betn. Inlet to outlet.(Z) = 8.00 m

Total Head (H) = Z+V^2+hf Eff.(n) = 0.60

9.068 m

Power Required = (mxHxg)/n

m = 6.517 Kg/s

P = 966.2186373 W

0.966 KW

1.296 Hp
Line Size Calculation for Cooling Water Pipes
Data Sheet No.:
Customer :- GSML Job No.: 1089 Doc. No.:
Date : 17-11-2007 Page No.: 1 Rev 0
LINE SIZE CALCULATION TRANSFER PUMP
DATA :-

1) Flow Rate (Q) = 1.725 m^3/hr = 0.00048 m^3/s CONSIDERING 15% EXTRA
2) Viscosity(u) = 10.20 Cp
3) Density(q) = 850.00 Kg/m^3
4) Length(L) = 30.00 m
5) Velocity of Liquid (V) = 0.9766 m/s
6) Outside Dia. of Pipe provided = 25.00 mm 0.025
7) gravational Acc. 9.81 m/s^2
8) Pressure 4.00 Kg/cm^2
9) head available (Z2) = 8.00 m
By Continuity Equation,

Q = AxV
A = Q/V

(3.14 / 4 )*d^2 = 0 /0.9766

d = (0 /0.9766 / (3.14 / 4 ))^0.5


= 0.0250 m
= 24.99 mm

Minimum Inside Dia. of Pipe required (d) = 24.9942 mm 0.0250


As per Sch. 20 & 6.4 mm Thk. OD of Pipe required = 37.79 mm

Pipe size provided is OK

DATA :-

1) Flow Rate (Q) = 1.73 m^3/hr = 0.00048 m^3/s


2) Velocity of Liquid (V) = 0.382 m/s
3) Outside Dia. of Pipe provided = 40.00 mm 0.04
pressure aatm. 101325.00 N/m^2
By Calculation, Va= 665.12
By Continuity Equation,
V= 0.3815021231
Q = AxV
A = Q/V Za = 4.4

(3.14 / 4 )*d^2 = 0 /0.38150212314225 l = 30

d = (0 /0.38150212314225 / (3.14 / 4 ))^0.5


= 0.0400 m
= 39.99 mm

Minimum Inside Dia. of Pipe Required (d) = 39.99 mm


As per Sch. 20 & 6.4 mm Thk. OD of Pipe required = 52.79 mm

Increase Pipe size


or Cooling Water Pipes

CONSIDERING 15% EXTRA Re = DVq / u


(0.025 x 0.9766 x 850)/10.2
2034.5833333333 Re < 2100 LAMINAR
Re > 2100 TURBULANT
f = 16 / Re
0.007864018

f = 0.079 /Re 0.25

= 0.0117627325

0.007864018

hf = 4 f l v2 / 2 g d

((4x0.0079x30x H13^2)/2x9.81x25)
1.8349 m
2.6092745042 Head loss due to friction

Total head = 9.8835 m

unsafe Distance betn. Inlet to outlet.(Z) =

power req. = (gxZ2+V^2/2+hf)/ n


Total Head (H) =
54.8430492882
0.055 KW
0.074 Hp
v = 0.9766454352 Power Required =

Diff.Pr. = 0.183 Kg/cm^2


3.817 Kg/cm^2

NPSH = (Pa-Pv)/q - hfs -gZa


Re = DVq / u
1271.6737438075
f = 0.079 /Re 0.25 16 / Re
0.0132291873 0.012581843
0.0125818435
hfs = 4 f l v2 / 2 g d
0.2800015583

NPSH = 74.979386677
7.6431586827
DIFF HEAD 9.6035 m
DIFFERIENTIAL PRESSURE= (32xMuxVxL)/D^2
URBULANT
Mu = 0.0102 poise

15300.59 N/m^2
(P1-P2) = 1.530 N/cm^2
0.1560 Kg/cm^2 0.155969
2.262 psi
hf = 1.590 m

power required(loss) 0.00073 W


0.00000073 KW
0.00000098 KW

ead loss due to friction = (32xMuxVxL)/(qxgxD^2)


Mu = 0.0102 pa.s

hf = 1.835 m
Distance betn. Inlet to outlet.(Z) = 8.00 m

Total Head (H) = Z+V^2+hf Eff.(n) = 0.60

10.789 m

Power Required = (mxHxg)/n

m = 0.407 Kg/s

P = 71.8441828 W

0.072 KW

0.096 Hp
Line Size Calculation for Cooling Water Pipes
Data Sheet No.:
Customer :- GSML Job No.: 1089 Doc. No.:
Date : 17-11-2007 Page No.: 1 Rev 0
LINE SIZE CALCULATION PURIFICATION PUMP
DATA :-

1) Flow Rate (Q) = 6.900 m^3/hr = 0.00192 m^3/s CONSIDERING 15% EXTRA
2) Viscosity(u) = 10.20 Cp
3) Density(q) = 850.00 Kg/m^3
4) Length(L) = 30.00 m
5) Velocity of Liquid (V) = 1.5260 m/s
6) Outside Dia. of Pipe provided = 40.00 mm 0.040
7) gravational Acc. 9.81 m/s^2
8) Pressure 4.00 Kg/cm^2
9) head available (Z2) = 8.00 m
By Continuity Equation,

Q = AxV
A = Q/V

(3.14 / 4 )*d^2 = 0 /1.526

d = (0 /1.526 / (3.14 / 4 ))^0.5


= 0.0400 m
= 39.99 mm

Minimum Inside Dia. of Pipe required (d) = 39.9900 mm 0.0400


As per Sch. 20 & 6.4 mm Thk. OD of Pipe required = 52.79 mm

Pipe size provided is OK

DATA :- Calculation For Suction Line

1) Flow Rate (Q) = 6.90 m^3/hr = 0.00192 m^3/s


2) Velocity of Liquid (V) = 0.977 m/s
3) Outside Dia. of Pipe provided = 50.00 mm 0.05
pressure aatm. 101325.00 N/m^2
By Calculation, Va= 665.12
By Continuity Equation,
V= 0.9766454352
Q = AxV
A = Q/V Za = 4.4

(3.14 / 4 )*d^2 = 0 /0.98 l = 30

d = (0 /0.98 / (3.14 / 4 ))^0.5


= 0.0500 m
= 49.99 mm

Minimum Inside Dia. of Pipe Required (d) = 49.99 mm


As per Sch. 20 & 6.4 mm Thk. OD of Pipe required = 62.79 mm

Increase Pipe size


or Cooling Water Pipes

CONSIDERING 15% EXTRA Re = DVq / u


(0.04 x 1.526 x 850)/10.2
5086.6666666667 Re < 2100 LAMINAR
Re > 2100 TURBULANT
f = 16 / Re
0.0031454784

f = 0.079 /Re 0.25

= 0.0093544611

0.0093544611

hf = 4 f l v2 / 2 g d

((4x0.0094x30x H13^2)/2x9.81x40)
3.3308 m
4.7364143351 Head loss due to friction

Total head = 11.4495 m

unsafe Distance betn. Inlet to outlet.(Z) =

power req. = (gxZ2+V^2/2+hf)/ n


Total Head (H) =
225.3005802748
0.225 KW
0.302 Hp
v = 1.5260084926 Power Required =

Diff.Pr. = 0.333 Kg/cm^2


3.667 Kg/cm^2

NPSH = (Pa-Pv)/q - hfs -gZa


Re = DVq / u
4069.355980184
f = 0.079 /Re 0.25 16 / Re
0.0098911246 0.003931826
0.0098911246
hfs = 4 f l v2 / 2 g d
1.1540689547

NPSH = 74.1053192806
7.55405905
DIFF. HEAD 10.2954 m
DIFFERIENTIAL PRESSURE= (32xMuxVxL)/D^2
URBULANT
Mu = 0.0102 poise

9339.12 N/m^2
(P1-P2) = 0.934 N/cm^2
0.0952 Kg/cm^2 0.0952
1.380 psi
hf = 0.971 m

power required(loss) 0.00179 W


0.00000179 KW
0.00000240 KW

ead loss due to friction = (32xMuxVxL)/(qxgxD^2)


Mu = 0.0102 pa.s

hf = 1.120 m
Distance betn. Inlet to outlet.(Z) = 8.00 m

Total Head (H) = Z+V^2+hf Eff.(n) = 0.60

11.449 m

Power Required = (mxHxg)/n

m = 1.629 Kg/s

P = 304.9569515 W

0.305 KW

0.409 Hp
Line Size Calculation for Cooling Water Pipes
LINE SIZE CALCULATION TRANSFER PUMP TO GT
DATA :-

1) Flow Rate (Q) = ### = 0.03778 m^3/s CONSIDERING 15% EXTRA


2) Viscosity(u) = 10.20 Cp
3) Density(q) = 850.00 Kg/m^3
4) Length(L) = 150.00 m
5) Velocity of Liquid (V) = 3.0000 m/s
6) Outside Dia. of Pipe provided = 40.00 mm 0.040
7) gravational Acc. 9.81 m/s^2
8) Pressure 6.00 Kg/cm^2
9) head available (Z2) = 8.00 m
By Continuity Equation,

Q = AxV
A = Q/V

(3.14 / 4 )*d^2 = 0.04 /3

d = (0.04 /3 / (3.14 / 4 ))^0.5


= 0.1266 m
= 126.62 mm

Minimum Inside Dia. of Pipe required (d) = 126.6230 mm 0.0400


As per Sch. 20 & 6.4 mm Thk. OD of Pipe required = 139.42 mm

Increase Pipe size

DATA :-

1) Flow Rate (Q) = 6.90 m^3/hr = 0.00192 m^3/s


2) Velocity of Liquid (V) = 0.977 m/s
3) Outside Dia. of Pipe provided = 50.00 mm 0.05
pressure aatm. 101325.00 N/m^2
By Calculation, Va= 665.12
By Continuity Equation,
V= 0.9766454352
Q = AxV
A = Q/V Za = 4.4

(3.14 / 4 )*d^2 = 0 /0.98 l = 30

d = (0 /0.98 / (3.14 / 4 ))^0.5


= 0.0500 m
= 49.99 mm
Minimum Inside Dia. of Pipe Required (d) = 49.99 mm
As per Sch. 20 & 6.4 mm Thk. OD of Pipe required = 62.79 mm

Increase Pipe size


or Cooling Water Pipes

CONSIDERING 15% EXTRA Re = DVq / u


(0.04 x 3 x 850)/10.2
10000 Re < 2100 LAMINAR
Re > 2100 TURBULANT
f = 16 / Re
0.0016

f = 0.079 /Re 0.25

= 0.0079

0.0079

hf = 4 f l v2 / 2 g d

((4x0.0079x150x H13^2)/2x9.81x40)
54.3578 m
77.297 psi Head loss due to friction

Total head = 62.8165 m

unsafe Distance betn. Inlet to outlet.(Z) =

power req. = (gxZ2+V^2/2+hf)/ n


Total Head (H) =
7350.1154943935
7.350 KW
9.857 Hp
v = 30.0778485492 Power Required =

Diff.Pr. = 5.436 Kg/cm^2


0.564 Kg/cm^2

NPSH = (Pa-Pv)/q - hfs -gZa


Re = DVq / u
4069.355980184
f = 0.079 /Re 0.25 16 / Re
0.0098911246 0.003931826
0.0098911246
hfs = 4 f l v2 / 2 g d
1.1540689547

NPSH = 74.1053192806
7.55405905
DIFF HEAD 61.6624 m
DIFFERIENTIAL PRESSURE= (32xMuxVxL)/D^2
URBULANT
Mu = 0.0102 poise

91800.00 N/m^2
(P1-P2) = 9.180 N/cm^2
0.9358 Kg/cm^2 0.93578
13.569 psi
hf = 9.542 m

power required(loss) 0.34680 W


0.00034680 KW
0.00046506 KW

ead loss due to friction = (32xMuxVxL)/(qxgxD^2)


Mu = 0.0102 pa.s

hf = 11.009 m
Distance betn. Inlet to outlet.(Z) = 8.00 m

Total Head (H) = Z+V^2+hf Eff.(n) = 0.60

28.009 m

Power Required = (mxHxg)/n

m = 32.111 Kg/s

P = ###

14.705 KW

19.720 Hp
Line Size Calculation for Cooling Water Pipes
Data Sheet No.:
Customer :- GSML Job No.: 1089 Doc. No.:
Date : 17-11-2007 Page No.: 1 Rev 0
LINE SIZE CALCULATION PURIFIER PUMP
DATA :-

1) Flow Rate (Q) = 2.760 m^3/hr = 0.00077 m^3/s CONSIDERING 15% EXTRA
2) Viscosity(u) = 10.20 Cp
3) Density(q) = 850.00 Kg/m^3
4) Length(L) = 150.00 m
5) Velocity of Liquid (V) = 0.6104 m/s
6) Outside Dia. of Pipe provided = 40.00 mm 0.040
7) gravational Acc. 9.81 m/s^2
8) Pressure 6.00 Kg/cm^2
9) head available (Z2) = 8.00 m
By Continuity Equation,

Q = AxV
A = Q/V

(3.14 / 4 )*d^2 = 0 /0.6104

d = (0 /0.6104 / (3.14 / 4 ))^0.5


= 0.0400 m
= 39.99 mm

Minimum Inside Dia. of Pipe required (d) = 39.9900 mm 0.0400


As per Sch. 20 & 6.4 mm Thk. OD of Pipe required = 52.79 mm

Pipe size provided is OK

DATA :-

1) Flow Rate (Q) = 6.90 m^3/hr = 0.00192 m^3/s


2) Velocity of Liquid (V) = 0.977 m/s
3) Outside Dia. of Pipe provided = 50.00 mm 0.05
pressure aatm. 101325.00 N/m^2
By Calculation, Va= 665.12
By Continuity Equation,
V= 0.9766454352
Q = AxV
A = Q/V Za = 4.4

(3.14 / 4 )*d^2 = 0 /0.98 l = 15

d = (0 /0.98 / (3.14 / 4 ))^0.5


= 0.0500 m
= 49.99 mm

Minimum Inside Dia. of Pipe Required (d) = 49.99 mm


As per Sch. 20 & 6.4 mm Thk. OD of Pipe required = 62.79 mm

Increase Pipe size

LINE SIZE CALCULATION UNLOADING PUMP INLET(HSD)


DATA :-

1) Flow Rate (Q) = 55.200 m^3/hr = 0.01533 m^3/s CONSIDERING 15% EXTRA
2) Viscosity(u) = 10.20 Cp
3) Density(q) = 850.00 Kg/m^3
4) Length(L) = 30.00 m
5) Velocity of Liquid (V) = 1.2500 m/s
6) Outside Dia. of Pipe provided = 125.00 mm 0.125
7) gravational Acc. 9.81 m/s^2

By Continuity Equation,

Q = AxV
A = Q/V

(3.14 / 4 )*d^2 = 0.02 /1.25

d = (0.02 /1.25 / (3.14 / 4 ))^0.5


= 0.1250 m
= 124.97 mm

Minimum Inside Dia. of Pipe required (d) = 124.9736 mm 0.1250


As per Sch. 20 & 6.4 mm Thk. OD of Pipe required = 137.77 mm

Pipe size provided is OK

LINE SIZE CALCULATION TRANSFER PUMP


DATA :-

1) Flow Rate (Q) = 1.725 m^3/hr = 0.00048 m^3/s CONSIDERING 15% EXTRA
2) Viscosity(u) = 10.20 Cp
3) Density(q) = 850.00 Kg/m^3
4) Length(L) = 30.00 m
5) Velocity of Liquid (V) = 0.5900 m/s
6) Outside Dia. of Pipe provided = 32.00 mm 0.032
7) gravational Acc. 9.81 m/s^2
By Continuity Equation,

Q = AxV
A = Q/V

(3.14 / 4 )*d^2 = 0 /0.59

d = (0 /0.59 / (3.14 / 4 ))^0.5


= 0.0322 m
= 32.16 mm

Minimum Inside Dia. of Pipe required (d) = 32.1568 mm 0.0320


As per Sch. 20 & 6.4 mm Thk. OD of Pipe required = 44.96 mm

Increase Pipe size


or Cooling Water Pipes

CONSIDERING 15% EXTRA Re = DVq / u


(0.04 x 0.6104 x 850)/10.2
2034.6666666667 Re < 2100 LAMINAR
Re > 2100 TURBULANT
f = 16 / Re
0.0078636959

f = 0.079 /Re 0.25

= 0.0117626121

0.0078636959

hf = 4 f l v2 / 2 g d

((4x0.0079x150x H13^2)/2x9.81x40)
2.2400 m
3.18528 Head loss due to friction

Total head = 10.2590 m

unsafe Distance betn. Inlet to outlet.(Z) =

power req. = (gxZ2+V^2/2+hf)/ n


Total Head (H) =
87.8732249591
0.088 KW
0.118 Hp
v = 0.610403397 Power Required =

Diff.Pr. = 0.224 Kg/cm^2


5.776 Kg/cm^2

NPSH = (Pa-Pv)/q - hfs -gZa


Re = DVq / u
4069.355980184
f = 0.079 /Re 0.25 16 / Re
0.0098911246 0.003931826
0.0098911246
hfs = 4 f l v2 / 2 g d
0.5770344774

NPSH = 74.6823537579
7.6128800976

SD)

CONSIDERING 15% EXTRA

CONSIDERING 15% EXTRA


DIFFERIENTIAL PRESSURE= (32xMuxVxL)/D^2
URBULANT
Mu = 0.0102 poise

18678.24 N/m^2
(P1-P2) = 1.868 N/cm^2
0.1904 Kg/cm^2 0.1904
2.761 psi
hf = 1.941 m

power required(loss) 0.00143 W


0.00000143 KW
0.00000192 KW

ead loss due to friction = (32xMuxVxL)/(qxgxD^2)


Mu = 0.0102 pa.s

hf = 2.240 m
Distance betn. Inlet to outlet.(Z) = 8.00 m

Total Head (H) = Z+V^2+hf Eff.(n) = 0.60

10.613 m

Power Required = (mxHxg)/n

m = 0.652 Kg/s

P = 113.0744737 W

0.113 KW

0.152 Hp
Inputs THICKNESS CALCULATION

01) Design Pressure (P) = 4.00 Kg/cm^2 56.920 A106 Gr B


Allowable Stress (S) = 20000.00 psi 20000.00 psi
Design Temp. (T) = 60 Deg.oC
Joint Eff.(E) = 1.00
Material Coeff.(Y) = 0.4
Out Side Diameter of Pipe (Do) = 5.000 in
Thickenss of Pipe (t)
Corrosion Allowance = 0.0000 mm

t = PDo/(2(SE+PY))
0.1805 mm 0.0071 in
t = (t+CA)/0.875
0.2063 mm 0.008 in
Selected Sch From Table of 31.3
tm = 3.40 mm 0.134 in

MAWP = 2SEt/(Do-2tY)

t = (tmx0.875)-CA
2.9750 mm 0.1171 in
MAWP = 954.90
MAWP> OPERATING PRESSURE THEN IT IS SAFE

Selected Sch. For pipe = Sch. 20


A106 Gr B A312 TP304L
20000.00 psi 20000.00 psi
Inputs THICKNESS CALCULATION

01) Design Pressure (P) = 22.50 Kg/cm^2


Allowable Stress (S) = 20000.00 psi
Design Temp. (T) = 60 Deg.oC
Joint Eff.(E) = 1.00
Material Coeff.(Y) = 0.4
Out Side Diameter of Pipe (Do) = 219.00 mm
Thickenss of Pipe (t)
Corrosion Allowance = 1.6000 mm

t = PDo/(2(SE+PY))
0.0441 mm
t = (t+CA)/0.875
1.8790 mm
Silected Sch From Table of 31.3
tm = 6.35 mm

MAWP = 2SEt/(Do-2tY)

t = (tm-CA)x0.875
4.1563 mm
MAWP = 770.84
MAWP> OPERATING PRESSURE THEN IT IS SAFE
ULATION

2.50 Kg/cm^2 319.5 A106 Gr B A312 TP304L


psi 20000.00 psi 16700.00 psi

219.00 mm 0.2190 m

1.6000 mm 0.002 m

0.004156
A312 TP304L
16700.00 psi