VFD Efficiency
VFD Efficiency
FREQUENCY
DRIVES
Energy Efficiency
Reference Guide
DISCLAIMER: Neither CEATI International, the authors, nor any
of the organizations providing funding support for this work
(including any persons acting on the behalf of the
aforementioned) assume any liability or responsibility for any
damages arising or resulting from the use of any information,
equipment, product, method or any other process whatsoever
disclosed or contained in this guide.
1 INTRODUCTION
600V or less
IGBT PWM (pulse width modulated using insulated
gate bipolar transistors)
Commercially available
Project managers for VFD projects who are not familiar with
the technology often undervalue the importance of obtaining
the correct data, analysis and up-front engineering that is
necessary to thoroughly understand the system.
c. Economics
Economics is typically one of the most important factors
involved in selecting industrial equipment, but the method of
evaluation is not straightforward. Many important economic
considerations are often ignored in VFD evaluations.
1 Introduction
Electrical savings are important but there are also other factors
that should be included as part of an evaluation of the life-
cycle costs of the equipment. For example when pumps or fans 9
are operated at reduced speeds there are often significant
maintenance savings due to reduced wear on seals, bearings,
shafts, etc. The purchase price is typically less than 10% of the
life cycle costs when operating and maintenance costs are
considered. Productivity increases from reduced downtimes
and reduced waste from optimized process control should also
be quantified for significant life cycle cost economics.
Capital Costs
Variable Frequency Drive
The cost of Variable Frequency Drives can vary greatly,
depending on the options required.
speed controls,
start/stop controls,
engineering,
12 cable and conduit,
foundations,
spare parts and any related modifications.
Motor
The cost of an inverter duty motor should be considered for a
new system; however, if the system is being considered for an
upgrade to a VFD then the existing motor should be reviewed
for size, capacity and efficiency. Usually only high efficiency
motors should be considered.
Installation
Installation, labour and commissioning charges for the drive,
motor and power conditioning apparatus should be determined.
Torsional Analysis
A torsional analysis will define the vibration effects of inverter
harmonics in the drive train. This should be conducted for
large drive applications.
Space Requirements
This includes the cost of any indoor space requirements for the
drive and filters, as well as any outdoor space costs, such as
those associated with transformers, filters or reactors.
1 Introduction
Cooling
Additional cooling may be required for drive installation.
Water cooling may be a much more economical alternative for
large applications, although HVAC equipment is often used.
Capital Savings
Use of a VFD may avoid certain capital investments.
Examples are gear boxes, control valves, fluid
coupling/mechanical speed changing equipment and reduced
voltage starters.
16
Over-Speed Capability
The over-speed capability of variable frequency drives can
save considerable operating costs, as well as investment, if
increases in production levels occur. For example, the airflow
through an existing fan may be increased by retrofitting a VFD
to the fan motor, which will allow operation at a frequency
higher than an existing 60 Hz rating.
1 Introduction
2 CLASSIFICATIONS OF DRIVES
a. AC Drives
Variable Frequency Drives
Electronic VFDs are speed control devices which vary the
voltage and frequency to an induction motor using a technique
called Pulse Width Modulation (PWM). VFDs have become
the preferred way to achieve variable speed operation as they
are relatively inexpensive and very reliable.
b. Other AC Drives
Wound Rotor Motor Control
Wound rotor motors are a special type of induction motor with
copper windings on the rotor rather than typical aluminum,
squirrel cage rotor bars.
The energy removed from the rotor circuit during the starting
procedure is wasted in the resistors as heat.
Multi-Speed Motors
Multi-speed motors are induction motors with specially wound
stators that allow the number of magnetic poles to be changed
by reconnecting the windings of the motor.
Under reduced voltage, a motor will “slip” more and thus its
speed will be reduced.
2 Classifications of Drives
c. DC Drives
Direct current (DC) motors are inherently variable speed
machines. Speed and torque control is achieved by varying the
armature voltage, the field excitation, or both.
e. Advanced Motors
Advanced motors are generally classified as a group of motor
designs which require power electronics and microprocessor
control for operation. This concept was formulated many years
ago, but is only now practical with today’s electronics. All
advanced motors allow for variable speed operation.
3 PRINCIPLES OF OPERATION -
AC VFD DRIVES
a. AC Induction Motors
An AC induction motor is constructed with a rotor that has
windings which intersect the rotating magnetic field generated
by the stator windings.
At full load speed, the rotor turns slightly slower than the
synchronous speed of the motor. This is because the magnetic
field causes currents to flow in the rotor windings and
produces a torque which turns the rotor; so if the rotor turns at
the same speed as the magnetic field, there would be no
relative motion between the rotor and the magnetic field, and
no torque would be produced.
25
The amount of speed by which the rotor lags the rotating
magnetic field is known as the slip of the motor. The higher
the slip, the more torque is produced by the motor.
The shape of the bars and the resistance of the alloy used in
their construction influences the torque-speed characteristics of
the motor.
28
29
3 Principles of Operation – AC VFD Drives
30
4 Selection of VFD Drives
Harmonics
Harmonic distortion of voltage and current is produced in
electrical systems by non-linear loads such as VFDs, welders,
rectifiers, Uninterruptible Power Supplies (UPS), arc furnaces
etc. Harmonics cause electrical waveform distortion that can
propagate through the entire power system and even outside of
the plant.
Harmonic Components
33
Effects of Harmonics
Microprocessors, numerically controlled machines, and
process controllers all rely on accurate control signals. The
presence of harmonics can cause these devices to malfunction.
Harmonics can also cause interference with computers and
improper operation of electronic equipment. They can also
cause capacitor and fuse failure.
Separate Supply
Ideally, loads producing harmonics, and sensitive
loads, should be supplied from entirely separate
feeders and independent transformers.
Filters
Harmonic filters can be used to reduce the amplitude
of one or more fixed frequency currents to prevent
them from entering the rest of the system. Filters can
be custom designed to suit the electrical environment.
Cable Length
Cable length should be kept as short as possible, i.e., 35
less than 15 meters or 50 feet, wherever possible.
b. Motor Considerations
Motor Electrical Issues
Winding insulation systems are classified by their temperature
or thermal capabilities. Tests used to prove thermal properties
for low voltage systems do not stress the electrical insulation
beyond 600 volts.
4 Selection of VFD Drives
46
5 Application Considerations and Estimated Savings for VFD
Drives
5 APPLICATION
CONSIDERATIONS AND
ESTIMATED SAVINGS FOR VFD
DRIVES
Conveyors
Extruders
Mixers
Positive displacement pumps and compressors
50 In these applications:
51
Output Mechanical
Motor System Efficiency = x 100%
Input Electrical
5 Application Considerations and Estimated Savings for VFD
Drives
These are effective and simple controls, but severely affect the
efficiency of the system.
58
Figure 19: Fan Versus Inlet Vane Setting
Where: N = Speed
Q = Flow
P = Pressure
HP = Power
Note: when the flow and pressure laws are combined, the
result is a formula that matches the system curve formula:
59
2
SYSTEM Pressure CURVE P = K x (N) .
Thus the machine will follow the system curve when its speed
is changed.
Where: N = Speed
Q = Flow
P = Pressure
HP = Power
For most applications that a user will consider, the square law
approximation should be used. Only fans with little or no static
pressure, such as cooling tower fans and roof vent fans with
domes, or pumps with no static head like discharge pumps will
approximate a cube function.
5 Application Considerations and Estimated Savings for VFD
Drives
This allows the fan or pump to produce the desired results with
the minimum of input power.
61
The other two methods modify some system parameter which
generally results in a reduction of the machine’s efficiency.
This is why the power demand is greater than the adjustable-
speed method.
The fan will operate 8,000 hours per year. With no control
available and at an energy cost of $0.10/kWh, the annual
electricity cost will be:
Flow Duty
Cycle
100% 20%
75% 40%
50% 40%
Required Power
62
For each operating point, a required power from the fan curve
can be obtained (from the preceding curves for each control
scheme).
From the outlet damper curve (Figure 18), the weighted power
calculations for the outlet damper method are as follows:
The annual cost of operation for the three control methods are
as follows:
Dampers
Inlet Dampers $16,480 $3,520
VFD Control $10,400 $9,600
d. System Efficiency
System efficiency is defined as the ratio of the units of product
produced by that system to the electrical energy drawn by a
system. To determine any difference, subtract the old system
efficiency from the new.
e. Electrical Efficiency
The electrical efficiency improvement is determined by
comparing the base case measured electrical consumption with
the electrical use determined during the project evaluation
metering.
6 CASE STUDIES
Project Overview
The production process consists of drawing stainless steel
tubing through dies to reduce their diameter and/or wall
thickness. This drawing process is carried out on a drawbench. 69
Approach
The implementation team used data collected by the plant
engineering department to analyze the existing system. This
6 Case Studies
Project Implementation
A VFD using vector drive options was selected as it can
70 continuously monitor the current, voltage and angular position
of the AC induction motors. Prior to the development of vector
drive controls, only DC motors, which are less reliable and
required more maintenance than their AC counterparts, could
be used in applications requiring accurate torque and speed
control. Today, vector drive options are a regular feature of
VFDs.
Results
As a result of the changes implemented by the team, the
breaking drawbench now requires less energy to draw a tube,
even though the motor size was increased from 150 HP to . For
a typical draw, the eddy current coupling system required 190
HP to draw a tube, while the more efficient VFD drive requires
less than 90 HP. The projected total annual operating time was
also reduced by 623 hours as a result of the modifications,
since the greater horsepower available enabled many of the
tubes to be reduced to the desired size with a smaller number
of draws.
Project Overview
The ventilation system uses nine supply fans and nine return
fans to control and maintain proper ambient conditions, cool
process machinery and provide proper air quality to its
workers. Initially, a mixture of return air and fresh air is
cleaned, cooled and humidity adjusted by four air washers.
This air is then supplied to the facility by the nine supply fans
6 Case Studies
Approach
73
To determine how to improve ventilation system performance,
the company and VFD specialist collected base case system
data over two weeks to measure the performance of the
existing system. Motor power was electronically logged,
damper positions were manually recorded based on visual
inspection of the damper linkages and power was measured on
each fan at ten minute intervals. These data were analyzed and
the team then developed a load duty cycle to calculate energy
demand, operating hours (peak, and off-peak periods) and
annual energy consumption during this period for both the
return fans and supply fans. This data was later compared to
the new system data, collected from after installation.
6 Case Studies
Project Implementation
After determining that the ventilation system’s fans were
significantly oversized, the team retrofitted 15 of the 18 fans
with VFDs. The remaining fans always ran at full flow and did
not need VFDs. A power and energy measurement was
connected to each of the VFDs to gather load data for the new
system. The system logged each fan’s speed and power
consumption in 15 minute intervals and savings analysis
reports were generated. With the VFDs installed, damper
control was no longer necessary so the fan control dampers
were left fully opened.
Results
Installation of the VFDs reduced the ventilation system’s total
electricity demand from approximately 322 kW to 133 kW, a
74 59 percent reduction. The total annual energy consumption for
the fans similarly fell 59 percent from approximately
2,700,000 kWh to 1,100,000 kWh. The energy efficiency gains
were possible because the VFDs enabled plant personnel to
fully open the fan control dampers and reduced fan speed. This
resulted in a large drop in power consumption and allowed the
system to operate more efficiently. These electricity savings
translated to annual energy cost savings of about $101,000.
The cost of the project was $130,000 and included:
The simple payback for the project’s cost was 1.3 years.
6 Case Studies
Project Overview
Modern dairy milking systems used in dairy farms utilize a
vacuum for automatically milking the animals. In typical dairy
vacuum milking systems, several milking units are attached to
the animals with teat cups and a vacuum is introduced into the
milking lines by a vacuum pump which draws milk from the
teats into a storage tank.
Project Implementation
Using the recommendations provided, the farm decided to
76
implement a system which reduced the motor size and
operated with a VFD. The motor was replaced with a new,
energy efficient 20 HP motor. In addition, the farm installed a
VFD on the new motor to adjust the pumping system speed
based on the system load. The dairy could have installed a
larger VFD on the existing 30 HP motor, but that would have
increased the capital cost and missed the opportunity for a
more efficient motor.
Project Results
The implementation of the new vacuum pump system resulted
in energy savings and more efficient production for the farm.
While the original system drew 16 kW, the new system never
uses more than 4.5 kW, even during peak needs. The farm was
able to decrease the horsepower required by the vacuum
system by 30% of the system’s total capacity without any
6 Case Studies
78
Appendix A: Bibliography
APPENDIX A: BIBLIOGRAPHY
Canadian Electrical Code, Canadian Standards Association
80
Appendix B: Useful Web Sites
www1.eere.energy.gov/industry/
The Industrial Technologies Program works with U.S. industry
to improve industrial energy efficiency and environmental
performance.
www.ieee.org
A non-profit organization, IEEE is the world’s leading
professional association for the advancement of technology.
81
www.nema.org
NEMA is the trade association of choice for the electrical
manufacturing industry, and is the largest trade association for
manufacturers of electrical products in the United States.
www.electrofed.com/councils/EEMAC/
The Electrical Equipment Manufacturers Association of
Canada (EEMAC) is the meeting place for over 80 companies
involved in the manufacturing and sale of electrical products,
systems, and components in Canada. EEMAC focuses on the
economic well-being of the industry.
http://www.midamericanenergy.com/pdf/ee_VFD_manuf.pdf
Utility Case Studies, such as this one offers further examples
as the VFD installed in a rubber manufacturing plant.
Appendix B: Useful Web Sites
http://www.bchydro.com/business/investigate/investigate78
0.html
BC Hydro’s Power Smart program uses services such as
E Source to provide customer information, such as the one
above on Variable Speed Drives.
http://www.hydro.mb.ca/pop/pop_profile_whiteshell_labs.pdf
http://www.hydro.mb.ca/pop/pop_profile_prairie_forest.pdf
Utilities often provide case studies of the services that they
support, such as Manitoba Hydro’s case studies on a VFD
application. Contacting your utility may provide additional
support such as monitoring, system information, etc.
http://www.Energy-Efficiency.com
Presentations and useful references are available that support
the triple bottom line that energy efficiency provides, i.e.:
Economic Prosperity
82
Environmental Performance
Social Responsibility
http://oee.nrcan.gc.ca/industrial/equipment/vfd/index.cfm?
attr=24
Natural Resources Canada’s Office of Energy Efficiency offers
online help such as:
Description
Estimated Savings
Purchasing Tips
Other useful links including manufacturing.
http://oee.nrcan.gc.ca/Publications/infosource/Pub/ici/eii/M
92-242-2002-11E.pdf
Fact sheets such as the above provide additional support.
Appendix B: Useful Web Sites
http://www.pumpsystemsmatter.org/content_detail.aspx?id
=150
There are many more resources, such as the Hydraulic Institute
which is a market transformation initiative created to assist
North American pump system users gain a more competitive
business advantage through strategic, broad-based energy
management and pump system performance optimization. A
primary objective of the initiative is to change the decision-
making process for the purchase of pumping systems and
additional resources, such as the VFD is available.
http://www.ceati.com/eerg.php
Energy Efficiency Guides, such as this one, are available free
to download from the CEATI website.
83
Appendix B: Useful Web Sites
84
Appendix C: Industry Acronyms and Glossary of Terms
APPENDIX C: INDUSTRY
ACRONYMS AND GLOSSARY OF
TERMS
Industry Acronyms
AC = alternating current
ANSI = American National Standards Institute
ASD = adjustable speed drive
BHP = brakehorsepower
CFM = cubic feet per minute
CSA = Canadian Standards Association
CSI = current source inverter
DC = direct current
DSP = digital signal processor
ECC = eddy current coupling 85
FPM = feet per minute
GPM = gallon per minute
GTO = gate turnoff (thyristor)
HDF = harmonic distortion factor
IGBT = insulated gate bi-thermal thyristor
IEEE = Institute of Electrical and Electronics Engineers
LCI = load-commutated inverter
NEMA = National Electrical Manufacturers Association
NPV = net present value
PAM = pulse amplitude modulation
PLC = programmable logic controller
PWM = pulse width modulated (inverter)
SCR = silicon-controlled rectifier
SR = switched reluctance
THD = total harmonic distortion
V = voltage
Appendix C: Industry Acronyms and Glossary of Terms
Glossary of Terms
Alternating Current: The flow of electricity which changes
direction on a regular continuous cycle reaching a maximum in
one direction, decreasing to zero, then reversing to reach a
maximum in the opposite direction.
Air Gap: The space between the rotating and stationary part of
an electric motor. Magnetic energy is transferred across this
gap.
90
Appendix D: Useful Formulas
For Pumps
hp = [GPM x head (ft) x specific gravity]
[3960 x % eff. of pump]
Specific gravity of water = 1.0
1 ft3 per sec = 448 GPM
1 PSI = A head of 2.309 ft for water weighing 62.36 lb/ft 3 at 62°F
Appendix D: Useful Formulas
Centrifugal Pumps
Effect of speed on input brake horsepower
Horsepower Required
HP = [torque(lb-ft) x speed (RPM)]
5,250
HP = torque (lb-in) x speed (RPM)63,000
Torque (lb-ft) = [HP x 5,250]
speed (RPM)
Ohms Law
Amperes = volts
ohms
Appendix D: Useful Formulas
Ohms = volts
amperes
Volts = amperes x ohms
Power in DC Circuits
Horsepower = volts x amperes
746
Power in AC Circuits
Kilovolt-Amperes (kVA)
94 kVA (single-phase) = volts (line to line) x amperes (line to line)
1,000
kVA (three-phase) = volts (line to line) x amperes (line to line) x 1.73
1,000
Kilowatts (kW)
kW (single-phase) = volts (line to line) x amperes (line to line) x power factor
1,000
kW (three-phase) = volts (line to line) x amperes (line to line) x
1.73
1,000
Power factor (PF) = kW
kVA
Three-Phase AC Circuits
hp = volts(line to line) x amperes(line to line) x1.73 x EFF x PF
746
Appendix D: Useful Formulas
95
APPENDIX E: CONVERSION
FACTORS
Multiply By To Obtain
Length Meters 3.281 Feet
Meters 39.37 Inches
Inches 0.0254 Meters
Feet 0.3048 Meters
Torque Newton- 0.7376 lb-ft
Meters 1.3558 Newton-
lb-ft 0.0833 Meters
lb-in 12.00 lb-ft
lb-ft lb-in
Rotation RPM 6.0 Degrees/sec
RPM 0.1047 Rad/sec
Degrees/sec 0.16667 RPM
Rad/sec 9.549 RPM
2
Moment of Newton- 2.42 lb-ft
96 Inertia Meters2 0.000434 lb-ft
2
2 2
oz-in 0.00694 lb-ft
2 2
lb-in 32.17 lb-ft
2 2
Slug-ft 0.1675 lb-ft
2 2
oz-in-sec 2.68 lb-ft
2
lb-in-sec
Power Watts 0.00134 HP
lb-ft/min 0.0000303 HP
HP 746 Watts
HP 30300 lb-ft/min
Temperature Degree C = (Degree F-32) x 5/9
Degree F = (Degree C x 9/5) + 32