Standard Technical Data Sheet (1.1 KV Grade Xlpe Power Cables)
Standard Technical Data Sheet (1.1 KV Grade Xlpe Power Cables)
b) Maximum Conductor temp. allowed for the short circuit duty (deg
C.) as stated above. : --------------------------------------250 oC------------------------------------------------
9 Conductor
a) Material Stranded Aluminium as per Class 2 of IS : 8130
b) Grade : ------------------------------------- H 2 (Electrolytic grade) -------------------------
c) Cross Section area (Sq.mm.) : 630 300/150
d) Number of wires(No.)minimum : 53 30/15
e) Form of Conductor Stranded compacted
Stranded and compacted circular
circular/sector shaped
f) Direction of lay of stranded layers : -------- Outermost layer shall be R.H lay & opposite in successive layers --------
10 Conductor resistance (DC) at 20 oC per km-maximum 0.0469 0.1 / 0.206
11 Insulation
a) Composition of insulation : -------------------------------------Extruded XLPE as per IS-7098 Part(1)-----------------
b) Nominal thickness of insulation(mm) : 2.8 1.8/1.4
c) Minimum thickness of insulation : 2.42 1.52/1.16
12 Inner Sheath
a) Material : --------------------------------Extruded PVC type ST-2 as per IS-5831-84-----------------
b) Calculated diameter over the laid up cores,(mm) : NA 52
c) Thickness of Sheath (minimum)mm : N.A 0.6
d) Method of extrusion NA Pressure/Vacuum extrusion
13 Armour
a) Type and material of armour Al. Wire[ H4
: Gal. Steel wire
grade]
b) Direction of armouring : ----------------------------------left hand--------------------------------------------------
c) Calculated diameter of cable over inner sheath (under armour), mm
: 33.9 53.2
b) Non standard drum lengths : Maximum one(1) non standard lengths of each cable size may be
supplied in drums only over & above the standard lengths as specified
above.(if required for completion of project).
17 Whether progressive sequential marking on outer sheath provided at
1 meter interval : ----------------------------------------- YES -------------------------------------------------
18 Identification of cores
a) colour of cores As per IS 7098 Part(1)
b) Numbering : ----------------------------------------- N.A ---------------------------------------------------
19 Whether Cables offered are ISI marked : ----------------------------------------- YES ---------------------------------------------------
20 Whether Cables offered are suitable for laying as per IS 1255
: ----------------------------------------- YES -----------------------------------------------------