Revised Fire Water Calculation-Pol Depot, Asoj: LPM/M LPM/M LPM/M LPM/M LPM/M

The document calculates the fire water requirements for 5 tanks - T1101, T1102, T1201, T1301, T1302 - located at a depot. It provides the tank details, fire water demand calculations for different scenarios of individual tanks on fire, and calculates the total critical water demand. Based on the calculations, it recommends providing 2 working fire water pumps with a capacity of 554 KLPH each and 1 standby pump with the same capacity, as well as 2 fire water storage tanks with a total capacity of the calculated critical water demand.

Uploaded by

Arindom
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
68 views1 page

Revised Fire Water Calculation-Pol Depot, Asoj: LPM/M LPM/M LPM/M LPM/M LPM/M

The document calculates the fire water requirements for 5 tanks - T1101, T1102, T1201, T1301, T1302 - located at a depot. It provides the tank details, fire water demand calculations for different scenarios of individual tanks on fire, and calculates the total critical water demand. Based on the calculations, it recommends providing 2 working fire water pumps with a capacity of 554 KLPH each and 1 standby pump with the same capacity, as well as 2 fire water storage tanks with a total capacity of the calculated critical water demand.

Uploaded by

Arindom
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

REVISED FIRE WATER CALCULATION-POL DEPOT, ASOJ 14/09/2001

Tank No. Class Cap. Dia Ht Area T1101 on fire T1102 on fire T1201 on fire T1301 on fire T1302 on fire
mtrs mtrs m2 lpm/m2 lpm lpm/m2 lpm lpm/m2 lpm lpm/m2 lpm lpm/m2 lpm

T1101 B 3000kl 17 14 748 3 2244 3 2244 1 748 1 748 1 748

T1102 B 3000kl 17 14 748 3 2244 3 2244 3 2244 3 2244 1 748

T1201 B 1500kl 13 12 490 1 490 3 1471 3 1471 3 1471 3 1471

T1301 A 1500kl 14 11.5 506 1 506 3 1518 3 1518 3 1518 3 1518

T1302 B 1500kl 14 11.5 506 1 506 1 506 3 1518 3 1518 3 1518

5990 7983 7499 7499 6003

CRITICAL WATER DEMAND (KLPH) 359 479 450 450 360

FOAM WATER REQUIREMENT

CASE-I 5lpm/sq.mtr 68.1

CASE-II 8.1lpm/sq.mtr 74.8 74.8

CASE-III 12lpm/sq. mtr 6.2455

TOTAL CRITICAL WATER DEMAND 554

HENCE PROVIDE 2 x -----------KLPH @ 105 MLC WORKING + 1 x -----------KLPH @ 105MLC S/B PUMPS

Storage capacity kl
FW Tanks = kl x2 nos

Provide 2 nos x ---------- kl capacity FW storage tanks