Installation of Split AC
Installation of Split AC
Overview
Installation Overview
3
INSTALLATION ORDER
Page 6
Indoor Unit Installation
4
Indoor Unit
Installation
Safety Precautions
WARNING CAUTION
• Install the indoor and outdoor units, cables and
• Securely install the indoor unit on a structure that
wires at least 1m from televisions or radios
can sustain its weight. If the structure is too weak
to prevent static or image distortion. Depending
the unit may fall causing personal injury, unit and
on the appliances, a 1m distance may not be
property damage or death.
• If the indoor unit is installed on a metal part of the
building, it must be electrically grounded.
Page 7
Indoor Unit Installation
4
Page 8
Indoor Unit Installation
4
Page 9
Indoor Unit Installation
4
Page 10
Outdoor Unit Installation
5
Outdoor Unit Installation Instructions
Outdoor Unit
Step 1: Select installation location. If the location is exposed to strong winds the unit
Installation
The outdoor unit should be installed in the location that must be placed against the wall to shelter it from
meets the following requirements: the wind.
Place the outdoor unit as close to the indoor unit as
possible.
Ensure that there is enough room for installation and
maintenance.
Strong wind
The air inlet and outlet must not be obstructed or
exposed to strong wind.
Ensure the location of the unit will not be subject to
Strong wind
snowdrifts, accumulation of leaves or other seasonal
debris. If possible, provide an awning for the unit. Fig. 5.1
Ensure the awning does not obstruct airflow.
The installation area must be dry and well ventilated.
There must be enough room to install the connecting
pipes and cables and to access them for maintenance.
Strong wind
Fig. 5.2
>60cm
CAUTION
• Be sure to remove any obstacles that
Fix with bolts may block air circulation.
• Make sure you refer to Length
Specifications to ensure there is
enough room for installation and
maintenance.
Fig. 5.3
Page 11
Outdoor Unit Installation Instructions
779 W3
Outdoor Unit
Installation
487 W1
300 D 770 W
70 W2
25 B1
D2 D3
D1
61.5 A2
H1
H2
12 A1
NOTE
Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a sling.
Never hold the inlet of the outdoor unit to prevent it from deforming.
Do not touch the fan with hands or other objects.
Do not lean it more than 45, and do not lay it sidelong.
Make concrete foundation according to the specifications of the outdoor units.
Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind.
Page 12
NOTE: The minimum distance between the outdoor Notes On Drilling Hole In Wall
unit and walls described in the installation guide does
not apply to airtight rooms. Be sure to keep the unit
unobstructed in at least two of the three directions (M,
N, P) (See Fig. 5.10) You must drill a hole in the wall for the refrigerant piping,
and the signal cable that will connect the indoor and
outdoor units.
above
Outdoor Unit
Installation
1. Determine the location of the wall hole based on the
60cm
cm
location of the outdoor unit.
30
2. Using a 65-mm core drill, drill a hole in the wall.
30cm
on le
ft
60cm
NOTE: When drilling the wall hole, make sure
on r
ight to avoid wires, plumbing, and other sensitive
m t components.
0c ron
20 in f
(A) (B)
Fig. 5.11
Page 15
Drainpipe Installation
6
Page 16
Refrigerant Piping Connection
7
WARNING Refrigerant Piping Connection Instructions
• All field piping must be completed by a licensed
technician and must comply with the local and Step1: Cut pipes
national regulations. When preparing refrigerant pipes, take extra care
• When the air conditioner is installed in a small to cut and flare them properly. This will ensure
room, measures must be taken to prevent the efficient operation and minimize the need for future
refrigerant concentration in the room from maintenance.
exceeding the safety limit in the event of 1. Measure the distance between the indoor and
refrigerant leakage. If the refrigerant leaks and outdoor units.
its concentration exceeds its proper limit, hazards 2. Using a pipe cutter, cut the pipe a little longer than
due to lack of oxygen may result. the measured distance.
• When installing the refrigeration system, ensure
that air, dust, moisture or foreign substances do
not enter the refrigerant circuit. Contamination
CAUTION
Refrigerant Piping
or injury.
An angle of more than 10° may cause malfunction.
• Ventilate the area immediately if there is • DO NOT install the connecting pipe until both
refrigerant leakage during the installation. Leaked indoor and outdoor units have been installed.
refrigerant gas is both toxic and flammable.
Ensure there is no refrigerant leakage after
completing the installation work.
Page 17
Refrigerant Piping Connection
7
CAUTION
DO NOT deform pipe while cutting. Be extra careful not
to damage, dent, or deform the pipe while cutting. This
1. After removing burrs from cut pipe, seal the ends
will drastically reduce the heating efficiency of the unit.
with PVC tape to prevent foreign materials from
entering the pipe.
2. Sheath the pipe with insulating material.
3. Place flare nuts on both ends of pipe. Make sure
1. Make sure that the pipe is cut at a perfect 90° they are facing in the right direction, because you
angle. Refer to Fig. 7.2 for examples of bad cuts can’t put them on or change their direction after
flaring. See Fig. 7.4
Flare nut
Refrigerant Piping
90°
Oblique Rough Warped
Connection
Copper pipe
Pipe
Reamer
Point down
Pipe
Fig. 7.5
Fig. 7.3
Step 3: Flare pipe ends
Proper flaring is essential to achieve an gas-tight seal
Page 18
6. Place flaring tool onto the form. Step 4: Connect pipes
7. Turn the handle of the flaring tool clockwise until Connect the copper pipes to the indoor unit first, then
the pipe is fully flared. Flare the pipe in accordance connect it to the outdoor unit. You should first connect the
with the dimensions shown in table 7-3. low-pressure pipe, then the high-pressure pipe.
8. Remove the flaring tool and flare form, then inspect 1. When connecting the flare nuts, apply a thin coat
the end of the pipe for cracks and even flaring. of refrigeration oil to the flared ends of the pipes.
2. Align the center of the two pipes that you will
connect.
CAUTION
Check to make sure there is no refrigerant leak after
completing the installation work. If there is a refrigerant
leak, ventilate the area immediately and evacuate Indoor unit tubing Flare nut Pipe
Refrigerant Piping
Page 19
Wiring
8
Follow these instructions to prevent distortion when the
Safety Precautions
compressor starts:
• The unit must be connected to the main outlet.
Normally, the power supply must have a low output
WARNING impedance of 32 ohms.
• Be sure to disconnect the power supply before • No other equipment should be connected to the
working on the unit. same power circuit.
• All electrical wiring must be done according to • The unit’s power information can be found on the
local and national regulations. rating sticker on the product.
• Electrical wiring must be done by a qualified
technician. Improper connections may cause NOTE: The fuse is made of ceramic.
electrical malfunction, injury and fire.
• An independent circuit and single outlet must
be used for this unit. If the
electrical circuit capacity is not enough or there Outdoor Unit Wiring
is a defect in the electrical work, it can lead to
shock, fire, unit and property damage.
Wiring
to do so can cause overheating at the connection
1. Prepare the cable for connection
points, fire, and electrical shock.
• Ensure that main supply connection is made
Cross-section area of power
through a switch that disconnects all poles, with
contact gap of a least 3mm. Rated Current of Nominal Cross-Sectional
Appliance (A) Area (mm²)
6 0.75
6 - 10 1
10 - 16 1.5
CAUTION 16 - 25 2.5
• Connect the outdoor wires before connecting the
25- 32 4
indoor wires.
32 - 45 6
• Make sure you ground the unit. The grounding
wire should be away from gas pipes, water pipes,
lightning rods, telephone or other grounding
wires. Improper grounding may cause electrical
shock.
• DO NOT connect the unit with the power source
until all wiring and piping is completed.
• Make sure that you do not cross your electrical
wiring with your signal wiring, as this can cause
distortion and interference.
Page 20
b. Using wire strippers, strip the rubber jacket from
both ends of signal cable to reveal about 15cm
of the wires inside. Terminal block
Wire cover
c. Strip the insulation from the ends of the wires.
d. Using a wire crimper, crimp u-lugs on the ends of
the wires.
Screw
NOTE: While connecting the wires, please strictly follow Cable clamp
the wiring diagram (found inside the electrical box cover).
2. Remove the electric cover of the outdoor unit.
If there is no cover on the outdoor unit, disassemble
the bolts from the maintenance board and remove the
protection board. (See Fig. 8.1, 8.2)
Fig. 8.1
Page 21
Pressure Test Instructions
9
Systems are pressure tested to ensure they are:
Safe – for this test a pressure above the system’s maximum allowable
pressure (PSi) is used
Leak tight – this test is at PSi.
The nitrogen used for pressure testing is an asphyxiant, so the area around
the system should be well-ventilated
High pressures are used, so all non-essential personal should be evacuated
from the area
Anyone carrying out the pressure testing should wear safety goggles.
Dry (oxygen free) nitrogen (OFN) is used to achieve the pressures required for the
pressure tests because it is inert. You must never use oxygen for pressure testing -
pure oxygen at high pressure reacts violently with oil and will explode.
Increase the pressure to approximately 5 bar g and check for leaks using leak
detection spray at this pressure initially – many leaks will be identified at this
pressure so you will not waste nitrogen and time. It is also safer to find leaks at a
lower pressure than the final test pressures.
Increase the pressure slowly to the strength test pressure and hold it for 15
minutes. Under the Pressure Equipment Regulation this strength test might need
to be witnessed by a notified body.
Page 24