Valvula Solenoide Serie 344 Asco
Valvula Solenoide Serie 344 Asco
B A
E
4/2
pilot operated, high flow, heavy duty B A
P Series
single solenoid / dual solenoid E 344
1/4 to 1 P
FEATURES
• Rugged forged brass bodied solenoid valves (mono- or bistable function)
designed to provide maximum flow
• Solenoid valves have poppet type seats and discs to provide tight sealing
• Main valve discs are power driven in both directions by line pressure
(min. ∆P 0,7/1,7 bar)
• The solenoid valves satisfy all relevant EC Directives
GENERAL
Differential pressure 0,7/1,7 - 17 bar [1 bar = 100kPa]
Maximum viscosity 65cST (mm2/s)
Response times 100 - 1000 ms
fluids () temperature range (TS) seal material ()
air, inert gas, water -20 to +85°C NBR (nitrile)
BP
MP
RP
LP
Not Not
0,4W - 1,7W Available Available 6W - 11,6W
SPECIFICATIONS
operating pressure
flow prefix optional solenoids basic
pipe orifice differential (bar) power
coefficient catalogue
size size
kv
max. (PS) level NEMA ATEX / IECEx number
IP65
min. air () 7&9 Ex d Ex e mb Ex mb
NPT (mm) (m3/h) (l/min) ~ (1) = (2) ~/= EF NF EM PV SC brass stainless steel
Single Solenoid
1/4(3) 6,4 0,7 11,6 0,7 9,0 9,0 10,5/11,2 B344A070 -
1/4(3) 6,4 0,7 11,6 0,7 9,0 10,0 LP - B344A370 -
3/8(4) 9,5 1,9 31,6 0,7 9,0 9,0 10,5/11,2 B344A072 -
3/8(4) 9,5 1,2 20,0 0,7 9,0 10,0 LP - B344A372 -
1/2 9,5 1,9 31,6 0,7 9,0 9,0 10,5/11,2 B344A074 -
1/2 9,5 1,2 20,0 0,7 9,0 10,0 LP - B344A374 -
3/4(5) 19,0 4,8 80,0 0,7 9,0 9,0 10,5/11,2 B344A076 -
3/4(5) 19,0 4,5 75,0 0,7 9,0 10,0 LP - B344A376 -
80086GB-2017/R01
[email protected]
Zaragoza, 976 587 019
https://basesistemas.com/suministro-y-venta-de-elementos-de-instrumentacion-y-control-industrial/
SERIES 344
SPECIFICATIONS
operating pressure
flow prefix optional solenoids basic
pipe orifice differential (bar) power
coefficient catalogue
size size
kv
max. (PS) level NEMA ATEX / IECEx number
IP65
min. air () 7&9 Ex d Ex e mb Ex mb
NPT (mm) (m3/h) (l/min) ~ (1) = (2) ~/= EF NF EM PV SC brass stainless steel
Dual Solenoid
1/4(3) 6,4 0,7 11,6 0,7 17,0 9,0 6,0/9,7 B344 - 044 -
1/4(3) 6,4 0,7 11,6 0,7 10,0 10,0 LP - B344A344 -
3/8(4) 9,5 1,9 31,6 0,7 17,0 9,0 6,0/9,7 B344 - 080 -
3/8(4) 9,5 1,2 20,0 0,7 10,0 10,0 LP - B344A380 -
1/2 9,5 1,9 31,6 0,7 17,0 9,0 6,0/9,7 B344 - 082 -
1/2 9,5 1,2 20,0 0,7 10,0 10,0 LP - B344A382 -
3/4(5) 19,0 4,8 80,0 0,7 20,0 9,0 6,0/9,7 B344B054 -
3/4(5) 19,0 4,5 75,0 0,7 10,0 10,0 LP - B344A354 -
1 19,0 4,8 80,0 0,7 20,0 9,0 6,0/9,7 B344B056 -
1 19,0 4,5 75,0 0,7 10,0 10,0 LP - B344A356 -
● Available feature (1)
Single solenoid 9 bar on water and dual solenoid 14 bar on water 1/2" exhaust connection
(4)
[email protected]
Zaragoza, 976 587 019
https://basesistemas.com/suministro-y-venta-de-elementos-de-instrumentacion-y-control-industrial/
SERIES 344
EXPLANATION OF TEMPERATURE RANGES OF SOLENOID VALVES
Valve temperature range The valve temperature range (TS) is determined by the selected seal material, the temperature
range for proper operation of the valve and sometimes by the fluid (e.g. steam)
Operator ambient temperature range The operator ambient temperature range is determined by the selected power level and the
safety code
Total temperature range The temperature range of the complete solenoid valve is determined by the limitations of both
temperature ranges above
ELECTRICAL CHARACTERISTICS
Coil insulation class F
Connector Spade plug
Connector specification ISO 4400 (cable Ø 6-10 mm)
Electrical safety IEC 335
Standard voltages: DC (=) 24V - 48V; Allowable voltage variation +10%, -15%
AC (~) 24V - 48V - 115V - 230V/50Hz; Other voltages and 60Hz are available on request
power ratings operator electrical replacement coil / kit
prefix inrush holding hot/cold amb. temp. enclosure
range (TS)
safety code
protection ~ = type(2)
option ~ ~ =
(VA) (VA) (W) (W) (C°)(1) (EN 60529) 230 V/50 Hz 24V/DC
Basic power (BP)
SC 34,0 15,6 6,0 7,0/9,7 -40 to +75 EN 60730 IP65, moulded 400325-117 400325-142 02
SC 55,0 23,0 10,5 9,0/11,2 -40 to +75 EN 60730 IP65, moulded 400425-117 400425-142 01
WP/WS 34,0 15,6 6,0 7,0/9,7 -40 to +75 EN 60730 IP67, steel/SS 400305-117 400305-142 06
WP/WS 55,0 23,0 10,5 9,0/11,2 -40 to +75 EN 60730 IP67, steel/SS 400405-117 400405-142 05
NF/WSNF 55,0 23,0 10,5 - -60 to +25/40/60 II2G Ex d IIC Gb T6/T5/T4, II2D Ex tb IIIC Db IP66/67, alu./SS 400405-117 - 03/04
NF/WSNF - - - 9,0/11,2 -60 to +40/60/75 II2G Ex d IIC Gb T6/T5/T4, II2D Ex tb IIIC Db IP66/67, alu./SS - 400405-142 03/04
EM/WSEM 55,0 23,0 10,5 9,0/11,2 -40 to +40 II2G Ex e mb IIC Gb T3, II2D Ex tb IIIC Db IP66/67, steel/SS 400909-117 400913-142 05/06
PV 55,0 23,0 10,5 9,0/11,2 -40 to +65 II2G Ex mb IIC Gb T3(~)/T4(=),II2D Ex mb IIIC Db IP67, moulded - (3) - (3) 07/08
EF 30,0 16,0 6,1 7,0/10,6 -40 to +52/40 NEMA type 7 and 9 NEMA 4X 238214-057D 238314-006D 10
EF 50,0 25,0 10,1 9,0/11,6 -40 to +52/40 NEMA type 7 and 9 NEMA 4X 238614-057D 238714-006D 09
Low power (LP)
SC 1,5 1,5 1,5 1,7/1,7 -40 to +60 EN 60730 IP65, moulded 400925-097 400925-042 11/12
WP/WS 1,5 1,5 1,5 1,7/1,7 -40 to +60 EN 60730 IP67, steel/SS 400926-097 400926-042 13/14
EM/WSEM 1,5 1,5 1,5 1,7/1,7 -40 to +40/55 II2G Ex e mb IIC Gb T6/T5, II2D Ex tb IIIC Db IP66/67, steel/SS 400926-097 400926-042 13/14
PV - - - 1,7/1,7 -40 to +60 II2G Ex mb IIC Gb T6, II2D Ex mb IIIC Db IP67, moulded - - (3) 15/16
EF - - - 1,4/1,4 -40 to +60 NEMA type 7 and 9 NEMA 4X - 238714-902D 17/18
(1)
Temperature range can be limited by sealings (2)
Refer to the dimensional drawings on page 4 and 5 - Not available
(3)
Multiple coil-kits available under ATEX, contact us
ADDITIONAL OPTIONS
● Ex mb (prefix "PV") execution can be supplied in various cable lengths
● Compliance with "UL", "CSA" and other local approvals available on request
● 1/2" NPT (prefix "T") and M20 x 1,5 (prefix "ET") conduits (aluminium or 316 SS) available for steel solenoid housing
● Special moulded-in solid state components for peak voltage suppression and/or rectification (four diode bridge)
INSTALLATION
● Multi language installation/maintenance instructions are included with each valve
● The solenoid valves can be mounted in any position without affecting operation
● Important: a minimum operating pressure differential must be maintained between the pressure and exhaust ports. Supply
and exhaust piping must be full area and unrestricted
● For dual solenoid construction one of the solenoids may be energized momentarily or continuously.
Minimum on-time of coil is 0,3 second on air and 1,0 seconds on liquids.
80086GB-2017/R01
[email protected]
Zaragoza, 976 587 019
https://basesistemas.com/suministro-y-venta-de-elementos-de-instrumentacion-y-control-industrial/
SERIES 344
344 A070 / A370 / A072 / A372 / A074 / 344 - 044 / A344 / - 080 / - 082 / A380 /
A374 / A076 / A376 / A078 / A378 - 382 / B054 / A354 / B056 / A356
360° 360°
TYPE 03 TYPE 04
Aluminium, epoxy coated / AISI 316L SS Aluminium, epoxy coated / AISI 316L SS
NF / WSNF: EN/IEC 60079-1, 60079-31 NF / WSNF: EN/IEC 60079-1, 60079-31
344 A070 / A072 / A372 / A074 / A076 / A078 344 - 044 / - 080 / - 082 / A380 / - 382 / B054 / B056
360°
360°
TYPE 05 TYPE 06
Metal, epoxy coated / AISI 316 SS Metal, epoxy coated / AISI 316 SS
WP / WS: IEC 335 WP / WS: IEC 335
EM / WSEM: EN/IEC 60079-7+18+31 EM / WSEM: EN/IEC 60079-7+18+31
344 A070 / A370 / A072 / A372 / A074 / 344 - 044 / A344 / - 080 / - 082 / A380 /
A374 / A076 / A376 / A078 / A378 - 382 / B054 / A354 / B056 / A356
360°
360°
80086GB-2017/R01
[email protected]
Zaragoza, 976 587 019
https://basesistemas.com/suministro-y-venta-de-elementos-de-instrumentacion-y-control-industrial/
SERIES 344
344 A070 / A370 / A072 / A372 / A074 / 344 - 044 / A344 / - 080 / - 082 / A380 /
A374 / A076 / A376 / A078 / A378 - 382 / B054 / A354 / B056 / A356
360°
360°
TYPE 09 TYPE 10
Epoxy encapsulated Epoxy encapsulated
EF: ICS-6 ANSI / NEMA Type 7 and 9 EF: ICS-6 ANSI / NEMA Type 7 and 9
NOTE: applicable to solenoid only NOTE: applicable to solenoid only
344 G070 / G370 / G072 / G372 / G074 / 344 G044 / G344 / G080 / G082 / G380 /
G374 / G076 / G376 / G078 / G378 G382 / G054 / G354 / G056 / G356
360°
360°
TYPE 11 TYPE 12
Epoxy moulded Epoxy moulded
SC: IEC 335 / ISO 4400 SC: IEC 335 / ISO 4400
344 A070 / A370 / A072 / A372 / A074 / 344 - 044 / A344 / - 080 / - 082 / A380 /
A374 / A076 / A376 / A078 / A378 - 382 / B054 / A354 / B056 / A356
360°
360°
80086GB-2017/R01
[email protected]
Zaragoza, 976 587 019
https://basesistemas.com/suministro-y-venta-de-elementos-de-instrumentacion-y-control-industrial/
SERIES 344
344 A070 / A370 / A072 / A372 / A074 / 344 - 044 / A344 / - 080 / - 082 / A380 /
A374 / A076 / A376 / A078 / A378 - 382 / B054 / A354 / B056 / A356
360°
360°
TYPE 15 TYPE 16
Epoxy encapsulated Epoxy encapsulated
PV: EN/IEC 60079-18 PV: EN/IEC 60079-18
344 A070 / A370 / A072 / A372 / A074 / 344 - 044 / A344 / - 080 / - 082 / A380 /
A374 / A076 / A376 / A078 / A378 - 382 / B054 / A354 / B056 / A356
360°
360°
TYPE 17 TYPE 18
Epoxy encapsulated Epoxy encapsulated
EF: ICS-6 ANSI / NEMA Type 7 and 9 EF: ICS-6 ANSI / NEMA Type 7 and 9
NOTE: applicable to solenoid only NOTE: applicable to solenoid only
344 G070 / G370 / G072 / G372 / G074 / 344 G044 / G344 / G080 / G082 / G380 /
G374 / G076 / G376 / G078 / G378 G382 / G054 / G354 / G056 / G356
360°
360°
80086GB-2017/R01
[email protected]
Zaragoza, 976 587 019
https://basesistemas.com/suministro-y-venta-de-elementos-de-instrumentacion-y-control-industrial/
SERIES 344
SECTIONAL DRAWING
ø14 pilot top exhaust
single solenoid low power
ø14
20
80086GB-2017/R01
[email protected]
Zaragoza, 976 587 019
https://basesistemas.com/suministro-y-venta-de-elementos-de-instrumentacion-y-control-industrial/