Assignment
Assignment
Given:
Required:
1. For uniform flow, do you expect subcritical flow both in the trapezoidal and
rectangular sections?
2. Specify the rate of change of bed width with distance, using a 3rd-degree
polynomial, through the transition.
3. Specify the rate of change of side slope with distance through the transition.
4. Determine the elevation of the bed (invert) of the transition versus distance along
the transition so that the energy line has a constant slope through the transition,
matching the upstream and downstream uniform flow depths.
5. Make sure the water surface through the transition has a constant, uniform slope.
6. What is the total bed elevation change across the transition?
7. Show your results graphically, with a side view and a plan view of the transition.
BIE 5300/6300 Assignment #10
Drop Spillway Design
2 Dec 04 (due 7 Dec 04)
Given:
Required:
1. Design a drop spillway for the given conditions at the location of the 7.5-ft drop.
2. Use English units for the design.
3. Use the design procedure given in the lecture notes, but iterate to make the
basin area (b x L) as small as feasible at the design flow rate; however, if
possible, do not make the basin width, b, greater than the average base width of
the earthen canal.
4. Add 10% to the upstream normal depth for freeboard, determining the height of
the headwall at the upstream sides of the stilling basin.
5. Produce side view and plan view technical drawings of the drop spillway,
indicating the dimensions of the energy dissipation structure.
A Design Solution:
I. Uniform-Flow Depths
• From the ACA program, the following uniform-flow depths were found:
both of which are for the design flow rate of 120 cfs.
• hc = 2.20 ft
• xa = 9.17 ft
• xb = 1.76 ft
• xc = 3.84 ft
• L = 14.77 ft
• ht = 4.76 ft
• yend = 0.88 ft
• ydrop = -8.38 ft
• Some of the above values could be rounded up, but in this design they will
remain as calculated (other dimensions will be rounded, as shown below).
• Adding 10% to the upstream normal depth (as specified), the headwall height
should be 1.1(3.91) = 4.30 ft above the origin, which is at the crest height.
• There will need to be a converging section at the stilling basin inlet because the
stilling basin width is less than the upstream channel width. This is given a 45-
degree convergence, as shown in the plan view drawing (see below).
• According to design procedures, the wingwall height at the end sill is to be 0.85hc
= 0.85(2.20) = 1.87 ft above the tail water surface.
• The side walls should slope linearly from the headwall to the beginning of the
wingwalls over the length, L, of the stilling basin.
• Also according to design procedures, the wingwalls splay out at 45 degrees, and
the tops slope downward at 45 degrees.
• Extending the wingwalls to intersect with the base of the downstream channel
side slopes, the length of each wingwall will be:
2
⎛ 10.0 − 6.5 ⎞
L wing = 2⎜ ⎟ = 2.47 ft
⎝ 2 ⎠
• This design will follow the guidelines in which the floor blocks have the same
width and length, which is equal to:
Lblocks = 0.5hc = 0.5(2.20) = 1.10 ft
• Number of floor blocks for 50% occupation of the stilling basin width:
6.5
N= = 2.95
2(1.10)
6.50 − 3(1.10)
block spacing = = 0.80 ft
4
• Finally, the proportion of the stilling basin width occupied by the three floor blocks
will be:
⎛ 3(1.10) ⎞
occupied width = 100 ⎜ ⎟ = 50.8%
⎝ 6.50 ⎠
VI. Drawings
upstream 4.30 ft
1.87 ft
10.93 ft 3.84 ft
downstream
2.00 ft
1.10 ft
Side View
1.10 ft
10.00 ft
6.50 ft
Plan View
BIE 5300/6300 Assignment #11
Siphon Spillway Design
7 Dec 04 (due 10 Dec 04)
Given:
Required:
a. What is the depth of flow in the canal at the maximum discharge? Take this as
FSL (full supply level).
b. What siphon spillway crest elevation (referenced to msl) do you recommend?
c. What is the estimated available head, H, across the siphon spillway?
d. Is H < hatm, where hatm is mean atmospheric pressure head?
e. What are the barrel dimensions (b and D), given a rectangular barrel section
(according to USBR guidelines, D ≥ 2.0 ft)?
f. What are RCL, RC and RS?
g. What is the estimated full-pipe unit discharge, q, in the siphon spillway?
h. What is the estimated maximum unit discharge through the siphon spillway
(“vortex” equation)? Make sure this is more than the discharge calculated from
the “orifice equation,” otherwise the design is not acceptable.
i. What is the minimum required vent (siphon breaker) pipe inside diameter?
j. What is the required height of the outlet deflector sill (1.5D)?
k. What is the required height of the outlet ceiling, h2?
l. What is the hydraulic seal in the canal, above the top of the opening to the
siphon spillway, on the downhill canal back at Qmax? Is it greater than the
minimum values of 1.5hv +0.5 ft, or 1.0 ft (whichever is greater)?
m. Create a side-view drawing of your design, with Fig. 4-17 as a model.
Solution:
By iteration, the normal depth is found to be hn = 1.289 m at 4.0 m3/s, with C = 60.
This is taken to be the full supply level (FSL).
By USBR design guidelines, the crest elevation is 0.2 ft (0.061 m) above FSL.
Then, the crest elevation is: 239.000 + 1.289 + 0.061 = 240.350 m above msl.
c) Available head
The available head, H, is measured from the crest elevation to the downstream
water surface elevation (see Fig. 4-17). Taking the maximum downstream water
surface elevation: H = 240.350 – 238.500 = 1.850 m.
d) Is H < hatm?
e) Barrel dimensions
Try the minimum recommended barrel height, D = 2.0 ft (0.610 m). The width, b,
will be determined below.
f) RCL, RC and RS
Use the recommended ratio RCL/D = 2.0. Then, RCL = 2.0(0.610) = 1.22 m. RC =
RCL – ½D = 0.915 m. And, RS = RCL + ½D = 1.525 m.
⎛R ⎞
qmax = RC 2g(0.7h) ln ⎜ S ⎟
⎝ RC ⎠
⎛ 1.525 ⎞
= 0.915 2(9.81)(0.7)(10.05) ln ⎜ ⎟
⎝ 0.915 ⎠
= 5.49 m2 /s
Thus, qmax > q, as required. Then, the required barrel width is:
Q 4.00
b= = = 1.63 m
q 2.46
This is taken as 1/24th of the barrel area, or 0.992/24 = 0.0413 m2. For a circular
pipe cross section, this give an inside diameter of 0.229 m. Round up to the
nearest available steel pipe size.
(Q / b) ( 4.00 /1.63 )
2 2
hc =3 =3 = 0.850 m
g 9.81
The velocity at critical depth would be:
Q 4.00
Vc = = = 2.89 m/s
bhc (1.63)(0.850)
Vc2 (2.89)2
= = 0.425 m
2g 2(9.81)
Finally,
Using the minimum dimensions, the inlet along the side slope of the canal is b x 2D,
or 1.63 wide by 1.22 high (in meters). This gives a total inlet area of (1.63)(1.22) =
1.99 m2. Then, the maximum inlet velocity head is:
Q2 (4.00)2
hv = = = 0.206 m
2gA 2 2(9.81)(1.99)2
If the inlet begins at the base of the canal side slope (see Fig. 4-17), this hydraulic
seal corresponds to a vertical depth of:
The depth of water above the inlet is, then: 1.289 – 0.256 = 1.033 m, which exceeds
the hydraulic seal requirement of 0.461 m. Thus, the hydraulic seal is sufficient.
m) Side-view drawing
FSL
1.289 m
ft
1.85 m
1.5:1 2
0.
30o
m high
0.61 m
22
0.915 m
water
1.
2.49 m
1.2
2
sill
m
1.63 m
60o 1:1
0.61 m
1.525 m 3.100 m
ll all
Barrel
ff wa ff w
to uto
cu c
Lecture 2
Flumes for Open-Channel Flow Measurement
• If possible, you will want to specify the installation of a Parshall flume such
that it operates under free-flow conditions throughout the required flow range
• To do this, you need to specify the minimum elevation of the upstream floor of
the flume
• Follow these simple steps to obtain a free-flow in a Parshall flume, up to a
specified maximum discharge:
• In general, the floor of the flume should be placed as high in the canal as
grade and other conditions permit, but not so high that upstream free board is
compromised.
• The downstream water surface elevation will be unaffected by the installation
of the flume (at least for the same flow rate)
• As an example, a 0.61-m Parshall flume is shown in the figure below
• The transition submergence, St, for the 0.61-m flume is 66% (see table)
• The maximum discharge in the canal is given as 0.75 m3/s, which for free-
flow conditions must have an upstream depth of (see Eq. 3): hu =
(0.75/1.429)1/1.55 = 0.66 m
• With the transition submergence of 0.66, this gives a depth to the flume
floor of 0.66(0.660 m) = 0.436 m from the downstream water surface
• Therefore, the flume crest (elevation of hu tap) should be set no lower than
0.436 m below the normal maximum water surface for this design flow
rate, otherwise the regime will be submerged flow
• However, if the normal depth for this flow rate were less than 0.436 m, you
would place the floor of the flume on the bottom of the channel and still
have free flow conditions
• The approximate head loss across the structure at the maximum flow rate
will be the difference between 0.660 and 0.436 m, or 0.224 m
• This same procedure can be applied to other types of open-channel
measurement flumes
BIE 5300/6300 Lectures 19 Gary P. Merkley
II. Non-Standard Parshall Flume Calibrations
• Some Parshall flumes were incorrectly constructed or were intentionally built with
a non-standard size
• Others have settled over time such that the flume is out of level either cross-wise
or longitudinally (in the direction of flow), or both
• Some flumes have the taps for measuring hu and hd at the wrong locations (too
high or too low, or too far upstream or downstream)
• Some flumes have moss, weeds, sediment or other debris that cause the
calibration to shift from that given for standard conditions
• Several researchers have worked independently to develop calibration
adjustments for many of the unfortunate anomalies that have befallen many
Parshall flumes in the field, but a general calibration for non-standard flumes
requires 3-D modeling
• There are calibration corrections for out-of-level installations and for low-flow
conditions
• There have been reports by some researchers that hysteresis effects have been
observed in the laboratory under submerged-flow conditions in Parshall flumes
• The effect is to have two different flow rates for the same submergence, S, value,
depending on whether the downstream depth is rising or falling
• There is no evidence of this hysteresis effect in Cutthroat flumes, which are
discussed below
IV. Software
• You can use the ACA program to develop calibration tables for Parshall,
Cutthroat, and trapezoidal flumes
• Download ACA from:
http://www.engineering.usu.edu/bie/faculty/merkley/Software.htm
• You can also download the WinFlume program from:
http://www.usbr.gov/pmts/hydraulics_lab/winflume/index.html
1.0
0.8
hu
0.7
0.6
0.5
0.4
0.4 0.5 0.6 0.7 0.8 0.9 1.0
hd
hd hu Q S Regime
(m) (m) (m3/s)
0.15 0.714 0.999 0.210 free
0.20 0.664 0.999 0.301 free
0.25 0.634 0.999 0.394 free
0.30 0.619 1.000 0.485 free
0.35 0.615 1.002 0.569 free
0.40 0.619 1.000 0.646 free
0.45 0.631 1.000 0.713 submerged
0.50 0.650 1.001 0.769 submerged
0.55 0.674 1.000 0.816 submerged
0.60 0.703 1.000 0.853 submerged
0.65 0.736 1.000 0.883 submerged
0.70 0.772 0.999 0.907 submerged
0.75 0.811 1.001 0.925 submerged
0.80 0.852 1.004 0.939 submerged
0.85 0.894 1.000 0.951 submerged
0.90 0.938 1.002 0.959 submerged
• The dimensions of a Cutthroat flume are identified by the flume width and length
(W x L, e.g. 4” x 3.0’)
• The flume lengths of 1.5, 3.0, 4.5, 6.0, 7.5, 9.0 ft are sufficient for most
applications
• The most common ratios of W/L are 1/9, 2/9, 3/9, and 4/9
• The recommended ratio of hu/L is equal to or less than 0.33
Free-flow equation
• For Cutthroat flumes the free-flow equation takes the same general form as for
Parshall flumes, and other channel “constrictions”:
nf
Qf = Cf W (hu ) (1)
3 6
1 1
B = W + L/4.5
B = W + L/4.5
W Flow
Inlet Outlet
Section Section
Lu = 2L/9 Ld = 5L/9
Lin = L/3 Lout = 2L/3
Piezometer
Tap for hu
Top View Piezometer
Tap for hd
L
Side View
• For any given flume size, the flume wall height, H, is equal to hu for Qmax,
according to the above equation, although a slightly larger H-value can be used
to prevent the occurrence of overflow
• So, solve the above free-flow equation for hu, and apply the appropriate Qmax
value from the table below; the minimum H-value is equal to the calculated hu
• For Cutthroat flumes the submerged-flow equation also takes the same general
form as for Parshall flumes, and other channel constrictions:
Cs W(hu − hd )nf
Qs = ns
(2)
[ −(log10 S)]
Cf nf St Cs ns Discharge (m3/s)
W (m) L (m)
min max
0.051 0.457 5.673 1.98 0.553 3.894 1.45 0.0001 0.007
0.102 0.457 5.675 1.97 0.651 3.191 1.58 0.0002 0.014
0.152 0.457 5.639 1.95 0.734 2.634 1.67 0.0004 0.022
0.203 0.457 5.579 1.94 0.798 2.241 1.73 0.0005 0.030
0.102 0.914 3.483 1.84 0.580 2.337 1.38 0.0002 0.040
0.203 0.914 3.486 1.83 0.674 1.952 1.49 0.0005 0.081
0.305 0.914 3.459 1.81 0.754 1.636 1.57 0.0008 0.123
0.406 0.914 3.427 1.80 0.815 1.411 1.64 0.0011 0.165
0.152 1.372 2.702 1.72 0.614 1.752 1.34 0.0005 0.107
0.305 1.372 2.704 1.71 0.708 1.469 1.49 0.0010 0.217
0.457 1.372 2.684 1.69 0.788 1.238 1.50 0.0015 0.326
0.610 1.372 2.658 1.68 0.849 1.070 1.54 0.0021 0.436
0.203 1.829 2.351 1.66 0.629 1.506 1.30 0.0007 0.210
0.406 1.829 2.353 1.64 0.723 1.269 1.39 0.0014 0.424
0.610 1.829 2.335 1.63 0.801 1.077 1.45 0.0023 0.636
0.813 1.829 2.315 1.61 0.862 0.934 1.50 0.0031 0.846
0.254 2.286 2.147 1.61 0.641 1.363 1.28 0.0009 0.352
0.508 2.286 2.148 1.60 0.735 1.152 1.37 0.0019 0.707
0.762 2.286 2.131 1.58 0.811 0.982 1.42 0.0031 1.056
1.016 2.286 2.111 1.57 0.873 0.850 1.47 0.0043 1.400
0.305 2.743 2.030 1.58 0.651 1.279 1.27 0.0012 0.537
0.610 2.743 2.031 1.57 0.743 1.085 1.35 0.0025 1.076
0.914 2.743 2.024 1.55 0.820 0.929 1.40 0.0039 1.611
1.219 2.743 2.000 1.54 0.882 0.804 1.44 0.0055 2.124
(0.3048)1+nf
Cf (English) = 3
Cf (metric) (3)
(0.3048)
• The next table shows the calibration parameters for English units
Discharge (cfs)
W (ft) L (ft) Cf nf St Cs ns
min max
0.167 1.50 5.796 1.98 0.553 3.978 1.45 0.004 0.24
0.333 1.50 5.895 1.97 0.651 3.315 1.58 0.008 0.50
0.500 1.50 5.956 1.95 0.734 2.782 1.67 0.013 0.77
0.667 1.50 5.999 1.94 0.798 2.409 1.73 0.018 1.04
0.333 3.00 4.212 1.84 0.580 2.826 1.38 0.009 1.40
0.667 3.00 4.287 1.83 0.674 2.400 1.49 0.018 2.86
1.000 3.00 4.330 1.81 0.754 2.048 1.57 0.029 4.33
1.333 3.00 4.361 1.80 0.815 1.796 1.64 0.040 5.82
0.500 4.50 3.764 1.72 0.614 2.440 1.34 0.016 3.78
1.000 4.50 3.830 1.71 0.708 2.081 1.49 0.034 7.65
1.500 4.50 3.869 1.69 0.788 1.785 1.50 0.053 11.5
2.000 4.50 3.897 1.68 0.849 1.569 1.54 0.074 15.4
0.667 6.00 3.534 1.66 0.629 2.264 1.30 0.024 7.43
1.333 6.00 3.596 1.64 0.723 1.940 1.39 0.050 15.0
2.000 6.00 3.633 1.63 0.801 1.676 1.45 0.080 22.5
2.667 6.00 3.662 1.61 0.862 1.478 1.50 0.111 29.9
0.833 7.50 3.400 1.61 0.641 2.159 1.28 0.032 12.4
1.667 7.50 3.459 1.60 0.735 1.855 1.37 0.068 25.0
2.500 7.50 3.494 1.58 0.811 1.610 1.42 0.108 37.3
3.333 7.50 3.519 1.57 0.873 1.417 1.47 0.151 49.4
1.000 9.00 3.340 1.58 0.651 2.104 1.27 0.042 19.0
2.000 9.00 3.398 1.57 0.743 1.815 1.35 0.088 38.0
3.000 9.00 3.442 1.55 0.820 1.580 1.40 0.139 56.9
4.000 9.00 3.458 1.54 0.882 1.390 1.44 0.194 75.0
−0.3555
St = 0.9653(W / L)0.2760 L0.04322(W / L) (7)
ns
Cf ( − log10 St )
Cs = nf
(8)
(1 − St )
• Note that Eqs. 4-8 are for English units (L and W in ft; Q in cfs)
• The maximum percent difference in the Cutthroat flume calibration parameters is
less than 2%, comparing the results of Eqs. 4-8 with the calibration parameters
for the 24 standard Cutthroat flume sizes
• Trapezoidal flumes are often used for small flows, such as for individual furrows
in surface irrigation evaluations
• The typical standard calibrated flume is composed of five sections: approach,
converging, throat, diverging, and exit
• However, the approach and exit sections are not necessary part of the flume
itself
Gary P. Merkley
S
W P
F U
R S
W
Plan View
28
F Throat End View
A B C B D
F
P
Side View End View
• Trapezoidal flume calibrations are for free-flow regimes only (although it would
be possible to generate submerged-flow calibrations from laboratory data)
• The following equation is used for free-flow calibration
nft
Qf = Cft (hu ) (9)
where the calibration parameters for the above seven flume sizes are given in the
table below:
Flume Qmax
Cft nft
Number (cfs)
1 1.55 2.58 0.35
2 1.55 2.58 0.09
3 1.99 2.04 2.53
4 3.32 2.18 2.53
5 5.92 2.28 3.91
6 2.63 1.83 3.44
7 4.80 2.26 2.97
Note: for h u in ft and Q in cfs
V-Notch Flumes
• When the throat base width of a trapezoidal flume is zero (W = 0, usually for the
smaller sizes), these are called “V-notch flumes”
• Similar to the V-notch weir, it is most commonly used for measuring water with a
small head due to a more rapid change of head with change in discharge
• Flume numbers 1 and 2 above are V-notch flumes because they have W = 0
Free-flow:
So, applying Eq. 10 with measured pairs of Qf and hu, “a” is log Cf and “b” is nf
Submerged-flow:
⎡ Qs ⎤
log ⎢ n ⎥ = log(Cs W) − ns log [ −(logS)] (12)
⎢⎣ (hu − hd ) f ⎥⎦
Again, applying Eq. 10 with measured pairs of Qs and hu and hd, “a” is log Cs and
“b” is ns
• Straight lines can be plotted to show the relationship between log hu and log Qf
for a free-flow rating, and between log (hu-hd) and log QS with several degrees of
submergence for a submerged-flow rating
• If this is done using field or laboratory data, any base logarithm can be used, but
the base must be specified
• Multiple linear regression can also be used to determine Cs, nf, and ns for
submerged flow data only − this is discussed further in a later lecture
Free Flow
• Laboratory data for free-flow conditions in a flume are shown in the following
table
• Free-flow conditions were determined for these data because a hydraulic jump
was seen downstream of the throat section, indicating supercritical flow in the
vicinity of the throat
Q (cfs) hu (ft)
4.746 1.087
3.978 0.985
3.978 0.985
2.737 0.799
2.737 0.798
2.211 0.707
1.434 0.533
1.019 0.436
1.019 0.436
1.019 0.436
1.019 0.436
0.678 0.337
• Take the logarithm of Q and of hu, then perform a linear regression (see Eqs. 10
and 11)
• The linear regression gives an R2 value of 0.999 for the following calibration
equation:
Qf = 4.04h1.66
u (13)
• We could modify Eq. 13 to fit the form of Eq. 6, but for a custom flume calibration
it is convenient to just include the throat width, W, in the coefficient, as shown in
Eq. 13
• Note that the coefficient and exponent values in Eq. 13 have been rounded to
three significant digits each – never show more precision than you can justify
Submerged Flow
• Data were then collected under submerged-flow conditions in the same flume
• The existence of submerged flow in the flume was verified by noting that there is
not downstream hydraulic jump, and that any slight change in downstream depth
produces a change in the upstream depth, for a constant flow rate
• Note that a constant flow rate for varying depths can usually only be obtained in
a hydraulics laboratory, or in the field where there is an upstream pump, with an
unsubmerged outlet, delivering water to the channel
BIE 5300/6300 Lectures 31 Gary P. Merkley
• Groups of (essentially) constant flow rate data were taken, varying a downstream
gate to change the submergence values, as shown in the table below
• In this case, we will use nf in the submerged-flow equation (see Eq. 12), where nf
= 1.66, as determined above
• Perform a linear regression for ln[Q/(hu – hd)1.66] and ln[-log10S], as shown in Eq.
12, giving an R2 of 0.998 for
1.66
1.93 (hu − hd )
Qs = 1.45
(14)
( − log10 S )
where Qs is in cfs; and hu and hd are in ft
Abt, S.R., Florentin, C. B., Genovez, A., and B.C. Ruth. 1995. Settlement and submergence
adjustments for Parshall flume. ASCE J. Irrig. and Drain. Engrg. 121(5).
Abt, S., R. Genovez, A., and C.B. Florentin. 1994. Correction for settlement in submerged Parshall
flumes. ASCE J. Irrig. and Drain. Engrg. 120(3).
Ackers, P., White, W. R., Perkins, J.A., and A.J.M. Harrison. 1978. Weirs and flumes for flow
measurement. John Wiley and Sons, New York, N.Y.
Genovez, A., Abt, S., Florentin, B., and A. Garton. 1993. Correction for settlement of Parshall flume.
J. Irrigation and Drainage Engineering. Vol. 119, No. 6. ASCE.
Kraatz D.B. and Mahajan I.K. 1975. Small hydraulic structures. Food and Agriculture Organization of
the United Nations, Rome, Italy.
Parshall, R.L. 1950. Measuring water in irrigation channels with Parshall flumes and small weirs. U.S.
Department of Agriculture, SCS Circular No. 843.
Parshall R.L. 1953. Parshall flumes of large size. U.S. Department of Agriculture, SCS and
Agricultural Experiment Station, Colorado State University, Bulletin 426-A.
Robinson, A.R. 1957. Parshall measuring flumes of small sizes. Agricultural Experiment Station,
Colorado State University, Technical Bulletin 61.
Robinson A. R. and A.R. Chamberlain. 1960. Trapezoidal flumes for open-channel flow
measurement. ASAE Transactions, vol.3, No.2. Trans. of American Society of Agricultural
Engineers, St. Joseph, Michigan.
Skogerboe, G.V., Hyatt, M. L., England, J.D., and J. R. Johnson. 1965a. Submerged Parshall flumes
of small size. Report PR-WR6-1. Utah Water Research Laboratory, Logan, Utah.
Skogerboe, G.V., Hyatt, M. L., England, J.D., and J. R. Johnson. 1965c. Measuring water with
Parshall flumes. Utah Water Research Laboratory, Logan, Utah.
Skogerboe, G. V., Hyatt, M. L., Anderson, R. K., and K.O. Eggleston. 1967a. Design and calibration
of submerged open channel flow measurement structures, Part3: Cutthroat flumes. Utah Water
Research Laboratory, Logan, Utah.
Skogerboe, G.V., Hyatt, M.L. and K.O. Eggleston 1967b. Design and calibration of submerged open
channel flow measuring structures, Part1: Submerged flow. Utah Water Research Laboratory.
Logan, Utah.
Skogerboe, G.V., Hyatt, M. L., England, J.D., and J. R. Johnson. 1965b. Submergence in a two-foot
Parshall flume. Report PR-WR6-2. Utah Water Research Laboratory, Logan, Utah.
Skogerboe, G. V., Hyatt, M. L., England, J. D., and J. R. Johnson. 1967c. Design and calibration of
submerged open-channel flow measuring structures Part2: Parshall flumes. Utah Water
Research Laboratory. Logan, Utah.
Working Group on Small Hydraulic Structures. 1978. Discharge Measurement Structures, 2nd ed.
International Institute for Land Reclamation and Improvement/ILRI, Wageningen, Netherlands.
Many thanks are extended to USU engineering students, past and present,
whose numerous suggestions and corrections have been incorporated into these
lecture notes.
Copyright Notice
This material has been duplicated by special permission of the copyright holder.
It is not to be duplicated or used for purposes other than learning resource support for
Utah State University. Any violation of this agreement is punishable under existing
copyright laws.
These lecture notes are formatting for printing on both sides of the page, with odd-
numbered pages on the front. Each lecture begins on an odd-numbered page, so
some even-numbered pages are blank.
6.89 kPa/psi
1 cb = 1 kPa
10 mb/kPa, or 100 kPa/bar
2.308 ft/psi, or 9.81 kPa/m (head of water)
14.7 psi = 101.3 kPa = 10.34 m (head of water) = 1,013 mbar = 1 atm
62.4 lbs/ft3, or 1000 kg/m3 (max density of pure water at 4°C)
0.1333 kPa/mmHg
0.7457 kW/HP
1 langley = 1 cal/cm2
0.0419 MJ/m2 per cal/cm2
0.3048 m/ft
1.609 km/mile
2.471 acre/ha
43,560 ft2/acre
1,233 m3/acre-ft
57.2958 degrees/radian
π ≈ 3.14159265358979323846
e ≈ 2.71828182845904523536
ºC = (ºF – 32)/1.8
ºF = 1.8(ºC) + 32
Ratio of weight to mass at sea level and 45° latitude: g = 9.80665 m/s2
• The main references are Design of Small Canal Structures, USBR; and Water
Measurement Manual, USBR. At least one copy of each will be on reserve in the
library.
• Some material will also be referred to from Irrigation Fundamentals, by
Hargreaves & Merkley, as well as from other books and sources
• BIE 5300/6300 lecture notes by G.P. Merkley are required
II. Homework
III. Tests
• Flow measurement
• Open channels
• Full pipe flow
• Most flow measurement devices and techniques are based on the measurement
of head (depth or pressure) or velocity
• One exception to this is the salt dilution method (described below)
• Here, the term “flow rate” refers to volumetric rate, or volume per unit time
• Thus, we apply mathematical relationships between head and discharge, or take
products of velocity and cross-sectional area
• Strictly speaking, all open-channel and most pipe flow measurement techniques
cause head loss
• Perhaps the most accurate method for measuring flow rate is by timing the filling
of a container of known volume
• However, this is often not practical for large flow rates
• Typical flow measurement accuracies are from ±2% to ±20% of the true
discharge, but this range can be much greater
• Measurements of head, velocity, and area are subject to errors for a variety of
reasons:
1. Approach Conditions
3. Equipment Problems
4. Measurement Location
5. Human Errors
• The following are considered to be special methods, because they are mostly
simple and approximate, and because they are not usually the preferred methods
for flow measurement in open channels
1. Measurement by Observation
2. Measurement by Floats
float
wa
te
r su
r fa
ce
10 m
• It is a good idea to have more than one measurement point so that the
velocity can be averaged over a reach, and to lessen the chance of an error
• Then, a graph can be made of float travel distance versus time, with the slope
equal to the surface velocity of the water
• Select a location in which the channel is fairly straight, not much change in
cross-section, smooth water surface, and no abrupt changes in bed elevation
or longitudinal slope
• Note that wind can affect the velocity of the float, changing the relationship
between surface velocity and average flow velocity
• The float speed will be higher than the average flow velocity in the channel,
unless perhaps the float travels near one of the channel banks or is
obstructed by vegetation
• You can estimate the average velocity in the channel by reducing the float
speed by some fraction
• The following table is from the U.S. Bureau of Reclamation
• It gives coefficients to multiply by the measured float velocity, as a function of
average depth, to obtain the approximate average flow velocity in the channel
Average Depth
(ft) (m) Coefficient
1 0.30 0.66
2 0.61 0.68
3 0.91 0.70
4 1.22 0.72
5 1.52 0.74
6 1.83 0.76
9 2.74 0.77
12 3.66 0.78
15 4.57 0.79
>20 >6.10 0.80
• To obtain average depth, divide the cross-sectional area by the top width of
the water surface (do not use an area-weighted average of subsection
depths)
• The coefficients in the above table only give approximate results; you can
typically expect errors of 10 to 20% in the flow rate
• What happens to the above coefficient values when the average water depth
is below 1 ft (or 0.3 m)?
• Some hydrographers have used partially submerged wooden sticks which are
designed to approximate the mean flow velocity, precluding the need for
coefficients as in the above table
• One end of the stick is weighted so that is sinks further
• The stick will give the correct velocity only for a small range of water depths
• The float method is not precise because the relationship between float speed
and true average flow velocity is not well known in general
• Other methods should be used if an accurate measurement is desired
BIE 5300/6300 Lectures 5 Gary P. Merkley
Sample calculation:
The float method is applied in a rectangular channel with a base width of 0.94 m
and a uniform water depth of 0.45 m. Ten float travel times are recorded over a
distance of 5.49 m (18 ft), with calculated surface velocities:
3. Dye Method
or,
⎛ C − C2 ⎞
Q = q⎜ 1 ⎟ (2)
⎝ C2 − C0 ⎠
5. Uniform Flow
• In this method the channel bed slope, average cross-section, and average
depth are measured
• A roughness value is estimated, and the Manning or Chezy equation is
applied to calculate the discharge
• This method is valid only for steady uniform flow, and is severely limited by an
inability to accurately estimate the roughness value
• And because it is only valid for steady uniform flow, it cannot be
applied in general since these flow conditions are often not found
in open channels
• Ideally, both bed slope and water surface slope are measured to
verify whether the flow is uniform or not
• The discharge can be estimated by giving a range of probable flow
rates for maximum and minimum roughness values (also
estimated), based on the channel appearance and size
• The roughness can be estimated by experience, or by consulting
hydraulics handbooks which provide tables and figures, or photographs
V = 2gh (3)
• This method is best applied for higher flow velocities because it is difficult to
read the head differential at low velocities, in which large errors in the
estimation of velocity can result
• Many different flow measurement flumes have been designed and tested, but
only a few are commonly found in practice today
Short-throated flumes:
Long-throated flumes:
• Critical flow conditions are created in a region of parallel flow in the control
section, again, assuming free flow conditions
• These linear-stream flow conditions are much better theoretically defined;
thus, rating relations can be reasonably well predicted
• Generally, flows larger than 10 lps can be measured with an error of less
than ±2% in an appropriately dimensioned flume
• Broad-crested weirs are an example of long-throated flumes
Advantages
1. capable of operation with relatively small head loss, and a high transition
submergence value (compared to sharp-crested weirs)
2. capable of measuring a wide range of free-flow discharges with relatively
high tail-water depths, using a single water depth measurement
3. capable of measuring discharge under submerged flow conditions using
two water depth measurements
4. both sediment and floating debris tend to pass through the structure
5. no need for a deep and wide upstream pool to reduce the velocity of
approach
Disadvantages
• When critical flow occurs the flow rate through the flume is uniquely
related to the upstream depth, hu
• That is, the free flow discharge can be obtained with only a single water
depth measurement
Qf = f(hu ) (4)
• When the tail-water depth is increased such that the flume operates under
submerged-flow conditions, both upstream, hu, and downstream, hd, depth
measurements are required.
• Let S be the submergence ratio, or S = hd/hu. Then, Qs is a function of the
head differential, (hu - hd), and S
• The value of submergence which marks the change from free flow to submerged
flow, and vice versa, is referred to as the transition submergence, St.
• At this condition the discharge given by the free-flow equation is exactly
the same as that given by submerged-flow equation
• The Parshall flume is perhaps the most commonly used open-channel flow-
measuring device in irrigation systems in the U.S. and elsewhere
• It was developed at Colorado State University by Ralph Parshall from 1915-1922
• Some characteristics of this flume design are:
• The general forms of the free-flow and submerged-flow equations for flumes,
including the Parshall flume, are:
Free Flow
nf
Qf = Cf W (hu ) (6)
Submerged Flow
Cs W(hu − hd )nf
Qs = (7)
[ −(log10 S + C2 )]ns
• It is strongly recommended that you use the same units for W and depth (hu and
hd) in Eqs. 6 and 7 (i.e. don’t put W in inches and hu in feet)
• Below are two views of a Parshall flume
• Note that both hu and hd are measured from the upstream floor elevation, that is,
from a common datum
• This is in spite of the fact that the downstream tap is supposed to be located at
an elevation equal to H – Y below the upstream floor, as shown in the figure
below
• The diverging outlet section of the flume is not required when the structure is
placed at a drop in bed elevation, whereby it would always operate under free-
flow conditions
• The USBR (1974) discusses “modified Parshall flumes” which fit a particular
canal profile
• The following table gives dimensions (A-H, K, X & Y) and discharge ranges for
the 23 standard Parshall flume sizes (see the following figure showing the
dimensional parameters) in metric units
• It is noted that Parshall flumes were developed using English units, but these
days we often prefer metric units
• Anyway, many of the dimensions in English units were not even “round”
numbers, often being specified to the 32nd of an inch
• The next table shows Parshall flume dimensions for the same 23 standard sizes,
but in feet, rounded to the thousandth of a foot, with discharge ranges in cubic
feet per second
• The minimum flow rate values represent the limits of the validity of the free-flow
rating equation
• For submerged flow conditions, a minimum flow rate also applies because if it is
very low, the difference between hu and hd will be virtually indistinguishable
(perhaps 1 mm or less)
• The next table gives calibration parameters (Cf, Cs, nf, ns) and transition
submergence (St) for standard Parshall flume sizes (metric units)
• Use Eq. (3) or (4) to get flow rate in m3/s, where depths are in metres
• The C2 value in Eq. (4) is equal to about 0.0044 (dimensionless) for all of the
standard Parshall flume sizes
• Standard sizes were developed in English units, so the throat width values show
below are “odd” numbers, but the ft-inch equivalents are given in parentheses
• Note that St is transition submergence − the value tends to increase with the size
of the flume, up to a maximum of about 0.80
• Be aware that the St values in the table below are for the maximum flow rate; for
other flow rates it is different
• Also note that the values in the table below are for a base 10 logarithm in Eq. (4)
• In practice, under extreme submerged-flow conditions, the head differential, hu-
hd, can be less than 1 mm and no measurement is possible with the flume
Throat
Width (m) Cf Cs nf ns St
0.025 (1”) 2.38 2.10 1.55 1.000 0.56
0.051 (2”) 2.38 2.15 1.55 1.000 0.61
0.076 (3”) 2.32 2.14 1.55 1.000 0.64
0.152 (6”) 2.50 2.02 1.58 1.080 0.55
0.229 (9”) 2.34 1.91 1.53 1.060 0.63
0.305 (12”) 2.26 1.76 1.52 1.080 0.62
0.457 (18”) 2.32 1.71 1.54 1.115 0.64
0.610 (24”) 2.34 1.74 1.55 1.140 0.66
Metric Units
0.762 (30”) 2.36 1.70 1.56 1.150 0.67
0.914 (3’) 2.37 1.70 1.56 1.160 0.68
1.219 (4’) 2.40 1.66 1.57 1.185 0.70
1.524 (5’) 2.43 1.65 1.58 1.205 0.72
1.829 (6’) 2.46 1.62 1.59 1.230 0.74
2.134 (7’) 2.49 1.61 1.60 1.250 0.76
2.438 (8’) 2.49 1.59 1.60 1.260 0.78
3.048 (10’) 2.47 1.52 1.59 1.275 0.80
3.658 (12’) 2.43 1.50 1.59 1.275 0.80
4.572 (15’) 2.40 1.48 1.59 1.275 0.80
6.096 (20’) 2.37 1.46 1.59 1.275 0.80
7.620 (25’) 2.35 1.45 1.59 1.275 0.80
9.144 (30’) 2.33 1.44 1.59 1.275 0.80
12.192 (40’) 2.32 1.43 1.59 1.275 0.80
15.240 (50’) 2.31 1.42 1.59 1.275 0.80
• The following table gives calibration parameters (Cf, Cs, nf, ns) and transition
submergence (St) for standard Parshall flume sizes in English units
Throat
Width Cf Cs nf ns St
1 inches 4.06 3.59 1.550 1.000 0.56
2 inches 4.06 3.67 1.550 1.000 0.61
3 inches 3.97 3.66 1.550 1.000 0.64
6 inches 4.12 3.32 1.580 1.080 0.55
9 inches 4.09 3.35 1.530 1.060 0.63
12 inches 4.00 3.11 1.520 1.080 0.62
18 inches 4.00 2.95 1.540 1.115 0.64
24 inches 4.00 2.97 1.550 1.140 0.66
30 inches 4.00 2.89 1.555 1.150 0.67
English Units
3 feet 4.00 2.87 1.560 1.160 0.68
4 feet 4.00 2.78 1.570 1.185 0.70
5 feet 4.00 2.71 1.580 1.205 0.72
6 feet 4.00 2.64 1.590 1.230 0.74
7 feet 4.00 2.59 1.600 1.250 0.76
8 feet 4.00 2.55 1.600 1.260 0.78
10 feet 4.01 2.48 1.590 1.275 0.80
12 feet 3.96 2.45 1.590 1.275 0.80
15 feet 3.90 2.41 1.590 1.275 0.80
20 feet 3.85 2.38 1.590 1.275 0.80
25 feet 3.82 2.36 1.590 1.275 0.80
30 feet 3.80 2.34 1.590 1.275 0.80
40 feet 3.77 2.33 1.590 1.275 0.80
50 feet 3.75 2.32 1.590 1.275 0.80
• It is seen that nf, ns, and St are dimensionless, but Cf & Cs depend on the
units
• Also, the submerged-flow coefficient, Cs, is for a base-10 logarithm
• Note that, for 1 ft ≤ W ≤ 8 ft, the nf value can be approximated as:
where W is in ft
Abt, S.R., Florentin, C.B., Genovez, A., and Ruth, B.C. 1995. Settlement and Submergence
Adjustments for Parshall Flume. ASCE J. Irrig. and Drain. Engrg., 121(5):317-321.
Blaisdell, F.W. 1994. Results of Parshall Flume Tests. ASCE J. Irrig. and Drain. Engrg., 120(2):278-
291.
Brater, E.F., and King, H.W. 1976. Handbook of Hydraulics. McGraw-Hill Book Co., New York, N.Y.
Parshall, R.L. 1945. Improving the Distribution of Water to Farmers by Use of the Parshall Measuring
Flume. USDA Soil Conservation Service, in cooperation with the Colorado Agric. Exp. Station,
Colorado State Univ., Fort Collins, CO.
Parshall, R.L. 1953. Parshall Flumes of Large Size. USDA Soil Conservation Service, in cooperation
with the Colorado Agric. Exp. Station, Colorado State Univ., Fort Collins, CO.
Skogerboe, G.V., Hyatt, M.L., and Eggleston, K.O. 1967. Design & Calibration of Submerged Open
Channel Flow Measurement Structures, Part 1: Submerged Flow. Utah Water Research
Laboratory, Utah State Univ., Logan, UT.
Skogerboe, G.V., Hyatt, M.L., and Eggleston, K.O. 1967. Design & Calibration of Submerged Open
Channel Flow Measurement Structures, Part 2: Parshall Flumes. Utah Water Research
Laboratory, Utah State Univ., Logan, UT.
USBR. 1997. Water Measurement Manual. U.S. Bureau of Reclamation, Denver, CO. (also available
from Water Resources Publications, LLC, http://www.wrpllc.com/)
Wright, S.J., and Taheri, B. 1991. Correction to Parshall Flume Calibrations at Low Discharges.
ASCE J. Irrig. and Drain. Engrg., 117(5):800-804.
• If possible, you will want to specify the installation of a Parshall flume such
that it operates under free-flow conditions throughout the required flow range
• To do this, you need to specify the minimum elevation of the upstream floor of
the flume
• Follow these simple steps to obtain a free-flow in a Parshall flume, up to a
specified maximum discharge:
• In general, the floor of the flume should be placed as high in the canal as
grade and other conditions permit, but not so high that upstream free board is
compromised.
• The downstream water surface elevation will be unaffected by the installation
of the flume (at least for the same flow rate)
• As an example, a 0.61-m Parshall flume is shown in the figure below
• The transition submergence, St, for the 0.61-m flume is 66% (see table)
• The maximum discharge in the canal is given as 0.75 m3/s, which for free-
flow conditions must have an upstream depth of (see Eq. 3): hu =
(0.75/1.429)1/1.55 = 0.66 m
• With the transition submergence of 0.66, this gives a depth to the flume
floor of 0.66(0.660 m) = 0.436 m from the downstream water surface
• Therefore, the flume crest (elevation of hu tap) should be set no lower than
0.436 m below the normal maximum water surface for this design flow
rate, otherwise the regime will be submerged flow
• However, if the normal depth for this flow rate were less than 0.436 m, you
would place the floor of the flume on the bottom of the channel and still
have free flow conditions
• The approximate head loss across the structure at the maximum flow rate
will be the difference between 0.660 and 0.436 m, or 0.224 m
• This same procedure can be applied to other types of open-channel
measurement flumes
BIE 5300/6300 Lectures 19 Gary P. Merkley
II. Non-Standard Parshall Flume Calibrations
• Some Parshall flumes were incorrectly constructed or were intentionally built with
a non-standard size
• Others have settled over time such that the flume is out of level either cross-wise
or longitudinally (in the direction of flow), or both
• Some flumes have the taps for measuring hu and hd at the wrong locations (too
high or too low, or too far upstream or downstream)
• Some flumes have moss, weeds, sediment or other debris that cause the
calibration to shift from that given for standard conditions
• Several researchers have worked independently to develop calibration
adjustments for many of the unfortunate anomalies that have befallen many
Parshall flumes in the field, but a general calibration for non-standard flumes
requires 3-D modeling
• There are calibration corrections for out-of-level installations and for low-flow
conditions
• There have been reports by some researchers that hysteresis effects have been
observed in the laboratory under submerged-flow conditions in Parshall flumes
• The effect is to have two different flow rates for the same submergence, S, value,
depending on whether the downstream depth is rising or falling
• There is no evidence of this hysteresis effect in Cutthroat flumes, which are
discussed below
IV. Software
• You can use the ACA program to develop calibration tables for Parshall,
Cutthroat, and trapezoidal flumes
• Download ACA from:
http://www.engineering.usu.edu/bie/faculty/merkley/Software.htm
• You can also download the WinFlume program from:
http://www.usbr.gov/pmts/hydraulics_lab/winflume/index.html
1.0
0.8
hu
0.7
0.6
0.5
0.4
0.4 0.5 0.6 0.7 0.8 0.9 1.0
hd
hd hu Q S Regime
(m) (m) (m3/s)
0.15 0.714 0.999 0.210 free
0.20 0.664 0.999 0.301 free
0.25 0.634 0.999 0.394 free
0.30 0.619 1.000 0.485 free
0.35 0.615 1.002 0.569 free
0.40 0.619 1.000 0.646 free
0.45 0.631 1.000 0.713 submerged
0.50 0.650 1.001 0.769 submerged
0.55 0.674 1.000 0.816 submerged
0.60 0.703 1.000 0.853 submerged
0.65 0.736 1.000 0.883 submerged
0.70 0.772 0.999 0.907 submerged
0.75 0.811 1.001 0.925 submerged
0.80 0.852 1.004 0.939 submerged
0.85 0.894 1.000 0.951 submerged
0.90 0.938 1.002 0.959 submerged
• The dimensions of a Cutthroat flume are identified by the flume width and length
(W x L, e.g. 4” x 3.0’)
• The flume lengths of 1.5, 3.0, 4.5, 6.0, 7.5, 9.0 ft are sufficient for most
applications
• The most common ratios of W/L are 1/9, 2/9, 3/9, and 4/9
• The recommended ratio of hu/L is equal to or less than 0.33
Free-flow equation
• For Cutthroat flumes the free-flow equation takes the same general form as for
Parshall flumes, and other channel “constrictions”:
nf
Qf = Cf W (hu ) (1)
3 6
1 1
B = W + L/4.5
B = W + L/4.5
W Flow
Inlet Outlet
Section Section
Lu = 2L/9 Ld = 5L/9
Lin = L/3 Lout = 2L/3
Piezometer
Tap for hu
Top View Piezometer
Tap for hd
L
Side View
• For any given flume size, the flume wall height, H, is equal to hu for Qmax,
according to the above equation, although a slightly larger H-value can be used
to prevent the occurrence of overflow
• So, solve the above free-flow equation for hu, and apply the appropriate Qmax
value from the table below; the minimum H-value is equal to the calculated hu
• For Cutthroat flumes the submerged-flow equation also takes the same general
form as for Parshall flumes, and other channel constrictions:
Cs W(hu − hd )nf
Qs = ns
(2)
[ −(log10 S)]
Cf nf St Cs ns Discharge (m3/s)
W (m) L (m)
min max
0.051 0.457 5.673 1.98 0.553 3.894 1.45 0.0001 0.007
0.102 0.457 5.675 1.97 0.651 3.191 1.58 0.0002 0.014
0.152 0.457 5.639 1.95 0.734 2.634 1.67 0.0004 0.022
0.203 0.457 5.579 1.94 0.798 2.241 1.73 0.0005 0.030
0.102 0.914 3.483 1.84 0.580 2.337 1.38 0.0002 0.040
0.203 0.914 3.486 1.83 0.674 1.952 1.49 0.0005 0.081
0.305 0.914 3.459 1.81 0.754 1.636 1.57 0.0008 0.123
0.406 0.914 3.427 1.80 0.815 1.411 1.64 0.0011 0.165
0.152 1.372 2.702 1.72 0.614 1.752 1.34 0.0005 0.107
0.305 1.372 2.704 1.71 0.708 1.469 1.49 0.0010 0.217
0.457 1.372 2.684 1.69 0.788 1.238 1.50 0.0015 0.326
0.610 1.372 2.658 1.68 0.849 1.070 1.54 0.0021 0.436
0.203 1.829 2.351 1.66 0.629 1.506 1.30 0.0007 0.210
0.406 1.829 2.353 1.64 0.723 1.269 1.39 0.0014 0.424
0.610 1.829 2.335 1.63 0.801 1.077 1.45 0.0023 0.636
0.813 1.829 2.315 1.61 0.862 0.934 1.50 0.0031 0.846
0.254 2.286 2.147 1.61 0.641 1.363 1.28 0.0009 0.352
0.508 2.286 2.148 1.60 0.735 1.152 1.37 0.0019 0.707
0.762 2.286 2.131 1.58 0.811 0.982 1.42 0.0031 1.056
1.016 2.286 2.111 1.57 0.873 0.850 1.47 0.0043 1.400
0.305 2.743 2.030 1.58 0.651 1.279 1.27 0.0012 0.537
0.610 2.743 2.031 1.57 0.743 1.085 1.35 0.0025 1.076
0.914 2.743 2.024 1.55 0.820 0.929 1.40 0.0039 1.611
1.219 2.743 2.000 1.54 0.882 0.804 1.44 0.0055 2.124
(0.3048)1+nf
Cf (English) = 3
Cf (metric) (3)
(0.3048)
• The next table shows the calibration parameters for English units
Discharge (cfs)
W (ft) L (ft) Cf nf St Cs ns
min max
0.167 1.50 5.796 1.98 0.553 3.978 1.45 0.004 0.24
0.333 1.50 5.895 1.97 0.651 3.315 1.58 0.008 0.50
0.500 1.50 5.956 1.95 0.734 2.782 1.67 0.013 0.77
0.667 1.50 5.999 1.94 0.798 2.409 1.73 0.018 1.04
0.333 3.00 4.212 1.84 0.580 2.826 1.38 0.009 1.40
0.667 3.00 4.287 1.83 0.674 2.400 1.49 0.018 2.86
1.000 3.00 4.330 1.81 0.754 2.048 1.57 0.029 4.33
1.333 3.00 4.361 1.80 0.815 1.796 1.64 0.040 5.82
0.500 4.50 3.764 1.72 0.614 2.440 1.34 0.016 3.78
1.000 4.50 3.830 1.71 0.708 2.081 1.49 0.034 7.65
1.500 4.50 3.869 1.69 0.788 1.785 1.50 0.053 11.5
2.000 4.50 3.897 1.68 0.849 1.569 1.54 0.074 15.4
0.667 6.00 3.534 1.66 0.629 2.264 1.30 0.024 7.43
1.333 6.00 3.596 1.64 0.723 1.940 1.39 0.050 15.0
2.000 6.00 3.633 1.63 0.801 1.676 1.45 0.080 22.5
2.667 6.00 3.662 1.61 0.862 1.478 1.50 0.111 29.9
0.833 7.50 3.400 1.61 0.641 2.159 1.28 0.032 12.4
1.667 7.50 3.459 1.60 0.735 1.855 1.37 0.068 25.0
2.500 7.50 3.494 1.58 0.811 1.610 1.42 0.108 37.3
3.333 7.50 3.519 1.57 0.873 1.417 1.47 0.151 49.4
1.000 9.00 3.340 1.58 0.651 2.104 1.27 0.042 19.0
2.000 9.00 3.398 1.57 0.743 1.815 1.35 0.088 38.0
3.000 9.00 3.442 1.55 0.820 1.580 1.40 0.139 56.9
4.000 9.00 3.458 1.54 0.882 1.390 1.44 0.194 75.0
−0.3555
St = 0.9653(W / L)0.2760 L0.04322(W / L) (7)
ns
Cf ( − log10 St )
Cs = nf
(8)
(1 − St )
• Note that Eqs. 4-8 are for English units (L and W in ft; Q in cfs)
• The maximum percent difference in the Cutthroat flume calibration parameters is
less than 2%, comparing the results of Eqs. 4-8 with the calibration parameters
for the 24 standard Cutthroat flume sizes
• Trapezoidal flumes are often used for small flows, such as for individual furrows
in surface irrigation evaluations
• The typical standard calibrated flume is composed of five sections: approach,
converging, throat, diverging, and exit
• However, the approach and exit sections are not necessary part of the flume
itself
Gary P. Merkley
S
W P
F U
R S
W
Plan View
28
F Throat End View
A B C B D
F
P
Side View End View
• Trapezoidal flume calibrations are for free-flow regimes only (although it would
be possible to generate submerged-flow calibrations from laboratory data)
• The following equation is used for free-flow calibration
nft
Qf = Cft (hu ) (9)
where the calibration parameters for the above seven flume sizes are given in the
table below:
Flume Qmax
Cft nft
Number (cfs)
1 1.55 2.58 0.35
2 1.55 2.58 0.09
3 1.99 2.04 2.53
4 3.32 2.18 2.53
5 5.92 2.28 3.91
6 2.63 1.83 3.44
7 4.80 2.26 2.97
Note: for h u in ft and Q in cfs
V-Notch Flumes
• When the throat base width of a trapezoidal flume is zero (W = 0, usually for the
smaller sizes), these are called “V-notch flumes”
• Similar to the V-notch weir, it is most commonly used for measuring water with a
small head due to a more rapid change of head with change in discharge
• Flume numbers 1 and 2 above are V-notch flumes because they have W = 0
Free-flow:
So, applying Eq. 10 with measured pairs of Qf and hu, “a” is log Cf and “b” is nf
Submerged-flow:
⎡ Qs ⎤
log ⎢ n ⎥ = log(Cs W) − ns log [ −(logS)] (12)
⎢⎣ (hu − hd ) f ⎥⎦
Again, applying Eq. 10 with measured pairs of Qs and hu and hd, “a” is log Cs and
“b” is ns
• Straight lines can be plotted to show the relationship between log hu and log Qf
for a free-flow rating, and between log (hu-hd) and log QS with several degrees of
submergence for a submerged-flow rating
• If this is done using field or laboratory data, any base logarithm can be used, but
the base must be specified
• Multiple linear regression can also be used to determine Cs, nf, and ns for
submerged flow data only − this is discussed further in a later lecture
Free Flow
• Laboratory data for free-flow conditions in a flume are shown in the following
table
• Free-flow conditions were determined for these data because a hydraulic jump
was seen downstream of the throat section, indicating supercritical flow in the
vicinity of the throat
Q (cfs) hu (ft)
4.746 1.087
3.978 0.985
3.978 0.985
2.737 0.799
2.737 0.798
2.211 0.707
1.434 0.533
1.019 0.436
1.019 0.436
1.019 0.436
1.019 0.436
0.678 0.337
• Take the logarithm of Q and of hu, then perform a linear regression (see Eqs. 10
and 11)
• The linear regression gives an R2 value of 0.999 for the following calibration
equation:
Qf = 4.04h1.66
u (13)
• We could modify Eq. 13 to fit the form of Eq. 6, but for a custom flume calibration
it is convenient to just include the throat width, W, in the coefficient, as shown in
Eq. 13
• Note that the coefficient and exponent values in Eq. 13 have been rounded to
three significant digits each – never show more precision than you can justify
Submerged Flow
• Data were then collected under submerged-flow conditions in the same flume
• The existence of submerged flow in the flume was verified by noting that there is
not downstream hydraulic jump, and that any slight change in downstream depth
produces a change in the upstream depth, for a constant flow rate
• Note that a constant flow rate for varying depths can usually only be obtained in
a hydraulics laboratory, or in the field where there is an upstream pump, with an
unsubmerged outlet, delivering water to the channel
BIE 5300/6300 Lectures 31 Gary P. Merkley
• Groups of (essentially) constant flow rate data were taken, varying a downstream
gate to change the submergence values, as shown in the table below
• In this case, we will use nf in the submerged-flow equation (see Eq. 12), where nf
= 1.66, as determined above
• Perform a linear regression for ln[Q/(hu – hd)1.66] and ln[-log10S], as shown in Eq.
12, giving an R2 of 0.998 for
1.66
1.93 (hu − hd )
Qs = 1.45
(14)
( − log10 S )
where Qs is in cfs; and hu and hd are in ft
Abt, S.R., Florentin, C. B., Genovez, A., and B.C. Ruth. 1995. Settlement and submergence
adjustments for Parshall flume. ASCE J. Irrig. and Drain. Engrg. 121(5).
Abt, S., R. Genovez, A., and C.B. Florentin. 1994. Correction for settlement in submerged Parshall
flumes. ASCE J. Irrig. and Drain. Engrg. 120(3).
Ackers, P., White, W. R., Perkins, J.A., and A.J.M. Harrison. 1978. Weirs and flumes for flow
measurement. John Wiley and Sons, New York, N.Y.
Genovez, A., Abt, S., Florentin, B., and A. Garton. 1993. Correction for settlement of Parshall flume.
J. Irrigation and Drainage Engineering. Vol. 119, No. 6. ASCE.
Kraatz D.B. and Mahajan I.K. 1975. Small hydraulic structures. Food and Agriculture Organization of
the United Nations, Rome, Italy.
Parshall, R.L. 1950. Measuring water in irrigation channels with Parshall flumes and small weirs. U.S.
Department of Agriculture, SCS Circular No. 843.
Parshall R.L. 1953. Parshall flumes of large size. U.S. Department of Agriculture, SCS and
Agricultural Experiment Station, Colorado State University, Bulletin 426-A.
Robinson, A.R. 1957. Parshall measuring flumes of small sizes. Agricultural Experiment Station,
Colorado State University, Technical Bulletin 61.
Robinson A. R. and A.R. Chamberlain. 1960. Trapezoidal flumes for open-channel flow
measurement. ASAE Transactions, vol.3, No.2. Trans. of American Society of Agricultural
Engineers, St. Joseph, Michigan.
Skogerboe, G.V., Hyatt, M. L., England, J.D., and J. R. Johnson. 1965a. Submerged Parshall flumes
of small size. Report PR-WR6-1. Utah Water Research Laboratory, Logan, Utah.
Skogerboe, G.V., Hyatt, M. L., England, J.D., and J. R. Johnson. 1965c. Measuring water with
Parshall flumes. Utah Water Research Laboratory, Logan, Utah.
Skogerboe, G. V., Hyatt, M. L., Anderson, R. K., and K.O. Eggleston. 1967a. Design and calibration
of submerged open channel flow measurement structures, Part3: Cutthroat flumes. Utah Water
Research Laboratory, Logan, Utah.
Skogerboe, G.V., Hyatt, M.L. and K.O. Eggleston 1967b. Design and calibration of submerged open
channel flow measuring structures, Part1: Submerged flow. Utah Water Research Laboratory.
Logan, Utah.
Skogerboe, G.V., Hyatt, M. L., England, J.D., and J. R. Johnson. 1965b. Submergence in a two-foot
Parshall flume. Report PR-WR6-2. Utah Water Research Laboratory, Logan, Utah.
Skogerboe, G. V., Hyatt, M. L., England, J. D., and J. R. Johnson. 1967c. Design and calibration of
submerged open-channel flow measuring structures Part2: Parshall flumes. Utah Water
Research Laboratory. Logan, Utah.
Working Group on Small Hydraulic Structures. 1978. Discharge Measurement Structures, 2nd ed.
International Institute for Land Reclamation and Improvement/ILRI, Wageningen, Netherlands.
• Some recent models have proven to be both accurate and durable when used in
irrigation channels
• Electromagnetic current meters are available that contain a sensor with the point
velocity displayed digitally
• Some earlier models manifested considerable electronic noise under turbulent flow
conditions (even the latest models still have problems if near steel-reinforced
concrete infrastructure, such as bridge piers)
• Present models yield more stable velocity readings, with averaging algorithms
• However, recent lab tests have shown that the Price current meters are more
accurate than at least two types of electromagnetic meter throughout a range of
velocities, and significantly more accurate at low velocities (J.M. Fulford 2002)
40 0.092 0.175 0.258 0.342 0.425 0.508 0.674 0.840 1.007 1.339 1.672
41 0.090 0.171 0.252 0.333 0.415 0.496 0.658 0.820 0.982 1.307 1.631
42 0.088 0.167 0.247 0.326 0.405 0.484 0.642 0.801 0.959 1.276 1.592
43 0.086 0.164 0.241 0.318 0.396 0.473 0.628 0.782 0.937 1.246 1.556
44 0.085 0.160 0.236 0.311 0.387 0.462 0.614 0.765 0.916 1.218 1.520
45 0.083 0.157 0.231 0.305 0.378 0.452 0.600 0.748 0.896 1.191 1.487
46 0.081 0.154 0.226 0.298 0.370 0.443 0.587 0.732 0.876 1.166 1.455
47 0.080 0.151 0.221 0.292 0.363 0.434 0.575 0.716 0.858 1.141 1.424
48 0.078 0.148 0.217 0.286 0.355 0.425 0.563 0.702 0.840 1.117 1.394
49 0.077 0.145 0.213 0.280 0.348 0.416 0.552 0.688 0.823 1.095 1.366
50 0.076 0.142 0.209 0.275 0.342 0.408 0.541 0.674 0.807 1.073 1.339
51 0.074 0.139 0.205 0.270 0.335 0.400 0.531 0.661 0.791 1.052 1.313
52 0.073 0.137 0.201 0.265 0.329 0.393 0.521 0.648 0.776 1.032 1.288
53 0.072 0.135 0.197 0.260 0.323 0.385 0.511 0.636 0.762 1.013 1.264
54 0.071 0.132 0.194 0.255 0.317 0.378 0.502 0.625 0.748 0.994 1.241
55 0.070 0.130 0.190 0.251 0.311 0.372 0.493 0.614 0.735 0.976 1.218
56 0.068 0.128 0.187 0.247 0.306 0.365 0.484 0.603 0.722 0.959 1.197
57 0.067 0.126 0.184 0.242 0.301 0.359 0.476 0.592 0.709 0.942 1.176
58 0.066 0.124 0.181 0.238 0.296 0.353 0.468 0.582 0.697 0.926 1.156
59 0.065 0.122 0.178 0.234 0.291 0.347 0.460 0.573 0.685 0.911 1.136
60 0.064 0.120 0.175 0.231 0.286 0.342 0.452 0.563 0.674 0.896 1.117
Wading
Bridge
Cableway
• For very wide canals, or rivers, with water depths exceeding 150 cm, a cable is
placed above the water with vertical supports on each bank that are heavily
anchored for stability
• The cable supports a car (box) that travels underneath the cable using pulleys. This
car carries the hydrographer and the current meter equipment
• The cable has markers so that the location across the channel is known
• A hand line or a cable reel assembly is used depending on the size of the weight
that must be used
Fulford, J.M. 2002. Comparison of Price Meters to Marsh-McBirney and Swoffer Meters. WRD
Instrument News, March.
• The most complete method for establishing the mean velocity at a vertical section is
to take a series of current meter velocity measurements at various depths in the
vertical
• Often, the current meter is placed below the water surface at one-tenth of the water
depth and a velocity measurement is made, then the current meter is placed at two-
tenths of the water depth; this procedure is continued until the velocity has finally
been measured at nine-tenths below the water surface
• Of particular importance are the velocity measurements at relative water depths of
0.2, 0.6 and 0.8 because they are used in the simpler methods
• When the above field procedure has been completed for a number of verticals in the
cross section, the data are plotted
• The relative water depth, which varies from zero at the water surface to unity at the
channel bed, is plotted on the ordinate starting with zero at the top of the ordinate
scale and unity at the bottom of the ordinate scale
• Velocity is plotted on the abscissa
• A smooth curve can be fitted on the data points for each vertical, from which the
mean velocity for the vertical can be determined
• Also, the relative water depth(s) corresponding with the mean velocity on the
velocity profile can be compared between each vertical
• Because the field procedure and data analysis for this method
are time consuming, simpler methods are commonly used
• Some of the more common methods are described in the
following sections
• However, the vertical velocity method provides an opportunity to determine whether
or not the simpler procedures are valid, or if some adjustments are required
Two-Point Method
V0.2 + V0.8
V= (1)
2
Six-Tenths Method
• For shallow water depths, say less than 75 cm, the Six-
Tenths Method is used
• However, shallow is a relative term that is dependent on the
type (size) of current meter being used
• A single current meter measurement is taken at a relative
water depth of 0.6 below the water surface and the resulting
velocity is used as the mean velocity in the vertical
• In irrigation canals, this method is commonly used at the first vertical from each
bank, while the two points method is used at all of the other verticals in the cross-
section
• Frequently, the first vertical from each bank has a low velocity so the discharge in
each section adjacent to the left and right (looking downstream) banks represents a
very small portion of the total discharge in the cross-section
• In situations where shallow flow depths exist across most of the cross section, and
the six-tenths method must be used because of the type of current meter that is
available, then it is likely there will be considerable error in the velocity
measurement, perhaps more than ten percent
Three-Point Method
1 ⎛ V0.2 + V0.8 ⎞
V= ⎜ + V0.6 ⎟ (2)
2 ⎝ 2 ⎠
Integration Method
• In this approach, experienced hydrographers can slowly lower and raise the current
meter two or three times along a vertical line in the stream
• The resulting “integrated” velocity along the vertical is then used to determine the
flow rate in a cross-section
• This method is subject to large errors, however, and should only be used for quick
checks
Gary P. Merkley 46 BIE 5300/6300 Lectures
II. Velocity at Vertical Walls
• In such cases, visual observation will usually disclose that the velocity very near the
vertical wall is significantly greater than zero
• These data are given in the table below
• The mathematical relationship between the parameters is:
Vw Vw / VD
= (3)
Vx Vx / VD
and,
⎛ V / V ⎞ 0.65 Vx
Vw = Vx ⎜ w D ⎟ = (4)
⎝ Vx / VD ⎠ Vx / VD
where,
x/D Vx / VD
0.0 0.650
0.1 0.825
0.2 0.884
0.3 0.916
0.4 0.936
0.5 0.952
0.6 0.964
0.7 0.975
0.8 0.984
0.9 0.993
1.0 1.000
Vx 0.65 + 10.52 ( x / D )
= (5)
VD 1 + 10.676 ( x / D ) − 0.51431( x / D )2
1.00
0.95
0.90
0.85
Vx/VD
0.80
0.75
0.70
0.65
0.60
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
x/D
• The current meter is used to measure the mean velocity of each vertical in the cross
section
• In addition, the spacing of the verticals is used in determining the cross-sectional
area of each section, where a section is defined as the cross-sectional area of flow
between two verticals.
BIE 5300/6300 Lectures 49 Gary P. Merkley
• In natural channels, the measuring cross-section should be subdivided into twenty
(20) or more verticals for a relatively smooth channel bed; but for lined canals,
twenty verticals is usually excessive and unnecessary
• For an irregular channel bed, more verticals are needed, not only to better define
the cross-sectional area of flow, but also because an irregular bed causes more
variation in the velocity distribution
• Verticals do not need to be spaced closer than 0.3 m across the width of the
channel (Corbett et al. 1943), but for small canals the verticals can be closer than
that, especially when there are only 3 or 4 verticals across the section
• For concrete-lined trapezoidal cross-section canals of small and medium size, it is
typical to take verticals at the mid-points of the side slopes on each side, and at the
two vertices where the side slopes meet the canal bottom, then dividing the base
width into 3 to 5 equally-spaced verticals
• The most important verticals for defining the cross-sectional area of flow are shown
in this figure (for this example)
• The data from the above figure will be used below in sample calculations
• The water depth must be known at each vertical in order to calculate the cross-
sectional area of flow for two sections, one on each side of the vertical
• Accurately determining the flow areas is just as important as accurate velocity
measurements
• The greatest sources of error in measuring the depth of water are:
• Another source of error: water “piles up” on the upstream edge of the rod and is
lower on the downstream edge, requiring the hydrographer to sight across the rod,
looking both upstream and downstream to get a reading
Gary P. Merkley 50 BIE 5300/6300 Lectures
VI. Recording of Data
• There are various formats for recording current metering data, and various
computational procedures (all of which are similar)
• These days, it is usually convenient to transfer the data to a spreadsheet application
and do the computations therein
distance velocity
observed
revolu-
flow
mean
depth
depth
depth
width
tions
from
area
time
start at point mean mean rate
point in vertical in section
Hydrographers: ____________________________________________________________________
No. _____ of _____ page(s) Computations __________________________________________
Checked by: ________________________________________________________________________
• Because of the shallow water depth at 0.82 m, the six-tenths method was used in
making the current meter measurement, which resulted in a velocity of 0.208 m/s
• The discharge in this cross section is less than 0.5% of the total discharge
Distancia desde Profundidad Fracción de Velocidad (m/s) Profundidad Ancho Area Caudal
el inicio Profundidad del punto promedio de promedio de Promedio
(m) (m) los puntos subsección (m) (m) (m2) (m3/s)
derecha pared vertical: (0.93)(0.65)/0.893=
0.00 0.88 0.68 0.68
Sontek. 2003. 6837 Nancy Ridge Dr., Suite A, San Diego, CA. www.sontek.com
USBR. 1997. Water Measurement Manual. U.S. Government Printing Office, Denver, CO.
I. Introduction
• In this field exercise, we will check the dimensions of a flow measurement flume,
also applying the:
1. Observation method;
2. Float method;
3. Uniform flow method; and,
4. Dye method.
• You will write this up as a homework exercise with the following sections:
• Include a few digital photographs in the report (we will bring a camera)
• You may turn the report in by groups, if desired, but everyone in the group must
contribute significantly to the work
I. Introduction
• In this field exercise, we will do current metering in a canal, at the same locations
as the flume from the previous field work
• We will use three current meters:
• The results of the current metering will be compared to the known calibration of a
measurement flume
• You will write this up as a homework exercise with the following sections:
• Include a few digital photographs in the report (we will bring a camera)
• You may turn the report in by groups, if desired, but everyone in the group must
contribute significantly to the work
I. Introduction
Duckbill weir
Advantages
Disadvantages
1. Relatively large head required, particularly for free flow conditions. This
precludes the practical use of weirs for flow measurement in flat areas.
2. The upstream pool must be maintained clean of sediment and kept free of
weeds and trash, otherwise the calibration will shift and the measurement
accuracy will be compromised
• A weir with a sharp upstream corner, or edge, such that the water
springs clear of the crest
• Those most frequently used are sharp-crested rectangular, trapezoidal,
Cipoletti, and triangular or 90° V-notch weirs
• According to the USBR, the weir plate thickness at the crest edges
should be from 0.03 to 0.08 inches
• The weir plate may be beveled at the crest edges to achieve the
necessary thickness
• A rectangular weir whose notch (opening) sides are coincident with the
sides of the approach channel, also rectangular, which extend
unchanged downstream from the weir
• It is the lateral flow contraction that is “suppressed”
• The sides and crest of a weir are far away from the sides and bottom
of the approach channel
• The nappe will fully contract laterally at the ends and vertically at the
crest of the weir
• Also called an “unsuppressed” weir
• Calibration is slightly more complex than for a suppressed weir
• Large errors in flow measurement can occur because of poor flow conditions,
high-velocity and turbulence in the area just upstream of weir
• In general, the approaching flow should be the same as the flow in a long,
straight channel of the same size
• The upstream section of channel is sometimes called the “weir pool”
• For best flow measurement accuracy, the velocity of approach to a weir should
be less than 0.5 fps, or about 0.15 m/s
• This value is approximately obtained by dividing the maximum discharge by the
product of channel width and water depth (for a rectangular channel section),
which measured at the upstream point 4 to 6 times the weir head
• This point is the preferred staff gauge location upstream of the weir
• A tranquil flow condition should extend upstream from the weir a distance of 15
to 20 times the head on the weir
• The weir pool can be a wide channel section just upstream, thereby obtaining a
sufficiently low approach velocity
• Never place a weir in an open-channel reach with supercritical flow; a hydraulic
jump will form upstream and the water surface at the weir will not be tranquil
1. The weir should be set at the lower end of a long pool sufficiently wide and deep
to give an even, smooth flow
2. The centerline of the weir notch should be parallel to the direction of the flow
3. The face of the weir should be vertical, not leaning upstream nor downstream
4. The crest of the weir should be level, so the water passing over it will be of the
same depth at all points along the crest (does not apply to V-notch weirs, but the
centerline of the V-notch opening should be vertical)
5. The upstream edge should be sharp so that the nappe touches the crest only at
the leading (upstream) edge
6. Ideally, though not always practical, the height of the crest above the bottom of
the pool, P, should be at least three times the depth of water flowing over the
weir crest (check this condition for the maximum flow rate) – note that some
calibrations do not have this restriction, as described below
7. The sides of the pool should be at a distance from the sides of the crest not less
than twice the depth of the water passing over the crest (for unsuppressed
rectangular weirs):
8. For accurate measurements the depth over the crest should be no more than
one-third the length of the crest
9. The depth of water over the crest should be no less than two inches (50 mm), as
it is difficult to obtain sufficiently accurate depth readings with smaller depths
10. The crest should be placed high enough so water will fall freely below the weir,
leaving an air space under the over-falling sheet of water. If the water below the
weir rises above the crest, this free fall is not possible, and the weir is then
operating under submerged-flow conditions.
11. To prevent erosion by the falling and swirling water, the channel downstream
from the weir should be protected by loose rock or by other material
12. You can assume that the discharge measurement accuracy of a sharp-crested
weir under free-flow conditions is within ±2% under the best field conditions
13. Don’t design a weir in which the minimum measurable flow rate is less than 2%
of the maximum flow rate, because you will not be able to accurately measure
such small flows.
Vu2 V2
ht = h + = Cht + hL + v (2)
2g 2g
• Solving for the mean flow velocity at the vena contracta, Vv,
• From continuity, Q = AvVv, and expressing the area of the vena contracta in
terms of the weir opening, Av = CcA, where Cc is the contraction coefficient,
• Letting Cd = Cc C' 2g ,
Q = Cd A h t (6)
Q = Cd Lh ht ≈ CdLh3 / 2 (7)
⎛θ⎞ ⎛θ⎞
Q = Cd tan ⎜ ⎟ h2 ht ≈ Cd tan ⎜ ⎟ h5 / 2 (8)
⎝2⎠ ⎝2⎠
θ
• Letting Cdv = Cd tan ,
2
Q = Cdvh5 / 2 (9)
• For field calibrations it is useful to apply Eq. 7 for rectangular weirs and Eq. 9 for
triangular weirs
• These coefficients will include the effects of approach velocity, nappe shape, weir
opening contraction, and head loss
• Note that Eqs. 7 and 9 are dimensionally correct for either cfs or m3/s, given the
above definition for Cd
• Note also that Eq. 9 is of the same form as the free-flow calibration equation for
nonorifice open-channel constrictions
• The general form of Eq. 9 can be used to calibrate most weirs, regardless of
whether they are sharp-crested or not, when both the coefficient and the
exponent on the “h” term are taken to be calibration parameters (based on field
or lab data)
• A convenient method of including the variation in the velocity of approach and the
contraction of the water jet over the weir is to relate Cd to the ratio hu/P, where P
is the vertical distance from the upstream channel bed to the weir crest
• A larger discharge for a given hu would be passed when hu/P is large
• In other words, when hu/P is large, the influence of the vertical component is
relatively small, and there is less contraction
• This is done through a coefficient called “Ce”
Le = L + KL (11)
he = hu + KH (12)
hu
Ce = 3.22 + 0.40 (13)
P
for KH = 0.003 ft and KL = -0.003 ft, with Q in cfs and head in feet.
hu
Ce = 3.25 + 0.445 (14)
P
for KH = 0.012 ft and KL = 0, with Q in cfs and head in feet.
hu
Ce = 3.21 + 0.45 (15)
P
Gary P. Merkley 68 BIE 5300/6300 Lectures
for KH = 0.004 ft and KL = 0, with Q in cfs and head in feet.
hu
Ce = 3.22 + 0.44 (16)
P
for KH = 0.003 ft and KL = 0, with Q in cfs and head in feet.
4.0 4.0
0.010 0.010 hu in ft, Q in cfs
3.8 3.8
1.0
=
L/B 0.9
KL (ft) 0.005 0.005 Ce 3.6 L/B
= 3.6
= 0.8
L/B
3.4 3.4
6
0.000 0.000 L/B = 0.
L/B = 0.4
3.2 L/B = 0.2 3.2
0.004 0.004
0.003 0.003
0.002 0.002
KL (m)
0.001 0.001
0.000 0.000
-0.001 -0.001
-0.002 -0.002
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
L/B
2.30 2.30
2.25 2.25
2.20 2.20
2.10 2.10
1.90 1.90
0.7
L /B =
1.85 .6 1.85
L/B = 0
1.70 1.70
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4
hu/P
⎛h ⎞
Ce = αce ⎜ u ⎟ + βce (17)
⎝P⎠
where Ce is for Q in m3/s, and,
⎛L⎞
βce = 1.724 + 0.04789 ⎜ ⎟ (18)
⎝B⎠
and,
⎛L⎞
−0.00470432 + 0.030365 ⎜ ⎟
αce = ⎝B⎠ (19)
2
⎛L⎞ ⎛L⎞
1 − 1.76542 ⎜ ⎟ + 0.879917 ⎜ ⎟
⎝B⎠ ⎝B⎠
where KL is in meters
I. Cipoletti Weirs
Q = CL h3 / 2 (1)
⎛ ⎛2⎞ ⎞
Q = ⎜ 0.63 ⎜ ⎟ 2g ⎟ L h3 / 2 = Ccip L h3 / 2 (2)
⎝ ⎝3⎠ ⎠
where L is the weir length (equal
to the width of the bottom of the
crest, as shown above); and h is
the upstream head, measured
from the bottom (horizontal part)
of the weir crest
X. V-Notch Weirs
Q = Ch5/2 (3)
dQ 5 3 / 2
= Ch (4)
dh 2
• Dividing Eq. 4 by Eq. 3 and rearranging,
dQ 5 dh
= (5)
Q 2 h
• It is seen that the variation of discharge is around 2.5 times the change in head
for a V-notch weir
• Thus, it can accurately measure the discharge, even for relatively small flows
with a small head: h is not too small for small Q values, but you still must be able
to measure the head, h, accurately
• A rectangular weir can accurately measure small flow rates only if the length, L,
is sufficiently small, because there is a minimum depth value relative to the crest;
but small values of L also restrict the maximum measurable flow rate
• The general equation for triangular weirs is:
hu
⎛θ⎞
Q = Cd 2 2g tan ⎜ ⎟
⎝2⎠
∫ (hu − hx ) hx dh (6)
0
because,
dA = 2x dh (7)
x
= tan(θ / 2) (8)
hu − hx
dQ = Cd 2gh dA (9)
8 ⎛θ⎞
Q = Cd 2g tan ⎜ ⎟ hu2.5 (10)
15 ⎝2⎠
• For a given angle, θ, and assuming a constant value of Cd, Eq. 10 can be
reduced to Eq. 3 by clumping constant terms into a single coefficient
8 ⎛θ⎞
Q= 2g Ce tan ⎜ ⎟ he5 / 2 (11)
15 ⎝2⎠
where,
he = hu + K h (12)
• The curves in the two figures below can be closely approximated by the following
equations:
for θ in radians
• Of course, you multiply a value in degrees by π/180 to obtain radians
• Some installations have an insertable metallic V-notch weir that can be placed in
slots at the entrance to a Parshall flume to measure low flow rates during some
months of the year
Kh (inches)
2 0.075
Kh (mm)
0.050
1
0.025
0
20 40 60 80 100
Notch Angle, θ (degrees)
0.60
0.59
Ce
0.58
0.57
20 40 60 80 100
Notch Angle, θ (degrees)
Q f = k + αhβ (15)
where k = 0 for the V-notch and rectangular weirs, but not for the Sutro; and β is
as defined below:
Single Curve
0.385
⎛ ⎛ h ⎞nf ⎞
Qs = Qf ⎜ 1 − ⎜ d ⎟ ⎟ = K sQ f (16)
⎜ ⎝ hu ⎠ ⎟
⎝ ⎠
• For hd ≤ 0, Ks = 1.0 and the flow is free
• For hd > hu, there will be backflow across the weir
• For hu = hd, the value of Qs becomes zero (this is logical)
• The value of Qf is calculated from a free-flow weir equation
• The exponent, nf, is that which corresponds to the free-flow equation (usually, nf
= 1.5, or nf = 2.5)
• The figure below shows that in applying Eq. 16, hu & hd are measured from the
sill elevation
• Eq. 16 is approximately correct, but may give errors of more than 10% in the
calculated flow rate, especially for values of hd/hu near unity
where Q is the flow rate; Cf and nf are calibration parameters for free-flow
conditions; L is the “length” of the crest; Hu is the total upstream hydraulic head
with respect to the crest elevation; and Ks is a coefficient for submerged flow, as
defined above. As before, the coefficient Ks is equal to 1.0 (unity) for free flow
and is less than 1.0 for submerged flow. Thus,
K s ≤ 1.0 (18)
hu Hu
hd
flow
weir
5hu
• The coefficient Ks can be defined by a family of curves based on the value of
Hu/P and hd/Hu
• Each curve can be approximated by a combination of an exponential function
and a parabola
• The straight line that separates the exponential and parabolic functions in the
graph is defined herein as:
• Below the straight line (Eq. 19) the function from Eq. 20 is applied
• And, Eq. 21 is applied above the straight line
• In Eq. 19, let A = 0.2 y B = 0.8 (other values could be used, according to
judgment and data analysis)
• In any case, A+B should be equal to 1.0 so that the line passes through the point
(1.0, 1,0) in the graph (see below).
1.0
0.9
0.8
0.7
0.6
0.2 < Hu/P < 2.0
0.20
K 0.5
0.40
0.60
0.4 0.80
1.00
0.3 1.20
1.40
1.60
0.2 1.80
2.00
0.1
0.0
-0.20 0.00 0.20 0.40 0.60 0.80 1.00
hd/Hu
• This curve is defined by Eq. 20, but the values of α and β depend on the value of
Hu/P
Gary P. Merkley 80 BIE 5300/6300 Lectures
• The functions are based on a separate analysis of the laboratory results from
Scoresby (ibid) and are the following:
α = 0.24
FG H IJ + 0.76
HPK
t
(22)
FH I
β = 0.014 G J + 0.23
HPK
t
(23)
• The point at which the two parts of the curves join is calculated in the following:
F hI F hI
AG J + B = αG1 − J
β
(24)
HH Kt H HK t
β
⎛h ⎞ ⎛ h ⎞
F = A ⎜ d ⎟ + B − α ⎜1− d ⎟ = 0 (25)
⎝ Hu ⎠ ⎝ Hu ⎠
β−1
∂F ⎛ h ⎞
= A + αβ ⎜ 1 − d ⎟ (26)
⎛h ⎞ ⎝ Hu ⎠
∂⎜ d ⎟
⎝ Hu ⎠
• With Eqs. 25 and 26, a numerical method can be applied to determine the value
of hd/Hu
• Then, the value of Ks can be determined as follows:
⎛h ⎞
Ks = A ⎜ d ⎟ + B (27)
⎝ Hu ⎠
• The resulting values of hd/Hu and Ks define the point at which the two parts of the
curves join together on the graph
hu
L
P
θ
hinge
• The calibration equations presented below for overshot gates are based on the
data and analysis reported by Wahlin & Replogle (1996)
• The representation of overshot gates herein is limited to rectangular gate leafs in
rectangular channel cross sections, whereby the specified leaf width is assumed
to be the width of the cross section, at least in the immediate vicinity of the gate;
this means that weir end contractions are suppressed
2 2g
Q = K s Ca Ce Gwh1.5
e (28)
3
where Q is the discharge; θ is the angle of the opening (10° ≤ θ ≤ 65°), measured
from the horizontal on the downstream side; Gw is the width of the gate leaf; and
he is the effective head
• The value of P can be calculated directly based on the angle of the gate opening
and the length of the gate leaf (P = L sinθ, where L is the length of the gate)
• The coefficient Ca is a function of the angle setting, θ, and can be adequately
described by a parabola:
where θ is in degrees
C2
⎡ ⎛ h ⎞1.5 ⎤
K s = C1 ⎢1 − ⎜ d ⎟ ⎥ (31)
⎢⎣ ⎝ hu ⎠ ⎥⎦
where,
C1 = 1.0666 − 0.00111 θ for θ < 60
(32)
C1 = 1.0 for θ ≥ 60
and,
C2 = 0.1525 + 0.006077 θ − 0.000045 θ2 (33)
in which θ is in degrees
P
θ
flow
• The issue of approach velocity was raised above, but there is another standard
way to compensate for this
• The reason this is important is that all of the above calibrations are based on
zero (or negligible) approach velocity, but in practice the approach velocity may
be significant
• To approximately compensate for approach velocity, one approach (ha ha!)
method is to add the upstream velocity head to the head term in the weir
equation
• For example, instead of this…
nf
Qf = Cf ( hu ) (34)
which means it is an iterative solution for Qf, which tends to complicate matters a
lot, because the function is not always well-behaved
• For known hu and A, and known Cf and nf, the solution to Eq. 36 may have
multiple roots; that is, multiple values of Qf may satisfy the equation (e.g. there
may be two values of Qf that are very near each other, and both positive)
• There may also be no solution (!*%&!#@^*) to the equation
• Conclusion: it is a logical way to account for approach velocity, but it can be
difficult to apply
• One of the possible flow measurement errors is the effect of siltation upstream of
the weir
• This often occurs in a canal that carries a medium to high sediment load
• Some weirs have underflow gates which can be manually opened from time to
time, flushing out the sediment upstream of the weir
• The effect is that the discharge flowing over the weir can be increased due to a
higher upstream “apron”, thus producing less flow contraction
• The approximate percent increase in discharge caused by silting in front of a
rectangular weir is given below:
0.50 3% 4% 5% 6% 6%
0.75 1% 2% 2% 3% 3%
1.00 zero
P
W
X
• W is the value of P when there is no sediment deposition upstream of the weir
• X is the horizontal distance over which the sediment has been deposited
upstream of the weir – if X is very large, use the top of the sediment for
determining P, and do not make the discharge correction from the previous table
• The reason for the increase in discharge is that there is a change in flow lines
upstream of the weir
• When the channel upstream of the weir becomes silted, the flow lines tend to
straighten out and the discharge is higher for any given value of hu
Addison. 1949.
Kindsvater and Carter. 1957.
Flinn, A.D., and C.W.D. Dyer. 1894. The Cipoletti trapezoidal weir. Trans. ASCE, Vol. 32.
Scoresby, P. 1997. Unpublished M.S. thesis, Utah State Univ., Logan, UT.
Wahlin T., and J. Replogle. 1996.
I. Introduction
• When operating under free-flow conditions, critical flow will occur over the crest
(sill), and the discharge is uniquely related to the upstream flow depth – in this
case, the downstream conditions do not affect the calibration
• The broad-crested weir can be calibrated in the field or laboratory; however, a
major advantage of the structure is that it can be accurately calibrated based on
theoretical equations without the need for independent laboratory measurements
• The flow depth upstream of the measurement structure must always be higher
than it would be in the absence of the structure because there is always some
head loss
• Downstream of the structure the depth will not be affected; so, the required head
loss is manifested (in one way) as an increase in the upstream depth
hu 2zu - 3zu L
II. Transition Submergence
• This means that the broad-crested weir can usually function as a free-flow
measurement device with less increase in the upstream water depth, which can be
a significant advantage
Advantages
1. the design and construction of the structure is simple, thus it can be relatively
inexpensive to install
2. a theoretical calibration based on post-construction dimensions can be obtained,
and the accuracy of the calibration is such that the discharge error is less that two
percent (this is assuming correct design and installation of the structure)
3. as with other open-channel flow measurement structures operating under free-flow
(modular) conditions, a staff gauge which is marked in discharge units can be
placed upstream; this allows a direct reading of the discharge without the need for
tables, curves, or calculators
4. the head loss across the structure is usually small, and it can be installed in
channels with flat slopes without greatly affecting existing upstream flow depths
5. floating debris tends to pass over and through the structure without clogging
Disadvantages
1. for water supplies with sediment, there will be deposition upstream of the structure
2. the upstream water depth will be somewhat higher than it was without the structure
3. farmers and other water users tend to oppose the installation of this structure
because they believe that it significantly reduces the channel flow capacity.
Although this is a false perception for a correctly designed broad-crested weir, it
Gary P. Merkley 88 BIE 5300/6300 Lectures
does represent an important disadvantage compared to some other flow
measurement devices
• The channel upstream of the broad-crested weir should be fairly straight and of
uniform cross-section
• The flow regime in the upstream section should be well into the subcritical range so
that the water surface is stable and smooth (Fr2 < 0.20, if possible). For this reason
it is best to avoid locating the structure just downstream of a canal gate or turnout,
for example, because the water surface is often not stable enough for an accurate
staff gauge reading
• The use of a stilling well and float assembly (or other water level sensing device) to
measure water level can partially compensate for fluctuating water levels, although
it involves additional cost
• Preferably, there are no gates or channel constrictions downstream of the structure
which would cause non-modular flow
• In fact, it is desirable to locate the structure just upstream of an elevation drop if
possible
• The presence of adjustable gates downstream complicates the design even more
than for fixed constrictions because the depth will depend on both discharge and
gate setting
• Other factors involved in the site selection are the stability of the channel bed and
side slopes in the upstream direction (in the case of earthen canals), and the
accessibility for measurement readings and maintenance
• If the upstream channel is not stable, the calibration may change significantly, and
sediment can accumulate rapidly at the structure, also affecting the calibration
V. Design Considerations
Sill Height
• One of the most important design parameters is the height of the sill above the
upstream channel bed
• This height should be sufficient to provide modular flow for the entire range of
discharges that the broad-crested weir is intended to measure; however, it should
not be higher than necessary because this would cause undue increases in the
upstream water level after installation
• Thus, a design objective is to determine the minimum crest height for which
modular flow can be obtained, and not to exceed this minimum height
• Excessively tall broad-crested weirs are not a problem in terms of water
measurement or calibration, they are only troublesome with respect to
unnecessarily raising the upstream water level
• The lower limit on sill height is based on the Froude number in the upstream
channel section (Fr2 < 0.20)
• The converging upstream ramp should have a slope of between 2:1 and 3:1 (H:V).
If flatter, the ramp is longer than necessary and there will be additional hydraulic
losses which detract from the calibration accuracy
• If the ramp is steeper than 2:1, unnecessary turbulence may be created in the
converging section, also causing addition head loss
• The diverging ramp at the downstream end of the crest should have a slope of
between 4:1 and 6:1 (H:V), or should be truncated (non-existent). The 6:1 ratio is
preferred in any case, and this same ratio is used in the diverging sections of other
flow measurement devices, in both open-channel and pipe flow, to minimize head
losses from turbulence
• If the 6:1 ratio causes an excessively long downstream ramp, then the length
should be abruptly truncated (see the figure below), not rounded off
DS ramp
flow truncated
hu
hc
zu
hu 2zu - 3zu L zd
hd
• The side slope in the throat section of the broad-crested weir is usually the same
as that in the upstream section, but it does not need to be the same
• In very wide and earthen channels it is common practice to reduce the width of the
throat section and design for a zero side slope (i.e. a rectangular section)
• When the side slope is reduced it is usually because the vertical flow contraction
obtained by the crest height is insufficient to induce modular flow conditions.
Therefore, in some cases lateral flow contraction is also required
Ratio of hu/L
• For existing channels with a straight section downstream of the broad-crested weir,
and without hydraulic controls such as sluice gates, the value of hd can be
determined according to normal flow conditions. That is, for a given discharge, the
value of hd can be calculated using the Manning or Chezy equations
• In the case of a downstream control which causes a backwater effect at the broad-
crested weir, the issue becomes complicated since the actual submergence ratio
across the structure depends not only on the discharge, but also on the control
setting (which creates an M1 profile upstream toward the broad-crested weir). This
is a common situation because the water surface profile in most irrigation channel
reaches is affected by downstream flow control structures
• For this reason, it is preferable to have a drop in elevation immediately
downstream of the broad-crested weir, or to have a straight canal section without
any nearby control structures in the downstream direction
• The modular limit will vary according to discharge for a given installation, and its
calculation can be summarized as follows:
(1) The specific energy of the flow upstream of the broad-crested weir can be set
equal to the specific energy over the crest (or sill) of the structure. The energy
balance can be expressed mathematically as follows:
Vu2 V2
hu + zu + = hc + zu + c (1)
2g 2g
where hu is the upstream flow depth, referenced from the sill elevation; Vu is the
average velocity in the upstream section, based on a depth of (hu + zu); zu is the
height of the sill above the upstream bed; hc is the depth over the crest where
critical flow is assumed to occur; and Vc is the average velocity in the critical flow
section over the crest.
Recognizing that Q = VA, where Q is the volumetric flow rate (discharge) and A is
the area of the flow cross-section,
Q2 Q2
hc − hu + − =0 (2)
2g A c2 2g A u2
Q2 ⎛ 1 1 ⎞
hc − hu + ⎜⎜ 2 − 2 ⎟⎟ = 0 (3)
2g ⎝ A c A u ⎠
g A 3c
Q2 = (4)
Tc
where Tc is the width of the water surface over the crest. This last equation for Q2
can be combined with the equation for energy balance to produce the following:
A 3c ⎛ 1 1 ⎞
hc − hu + ⎜⎜ 2 − 2 ⎟⎟ = 0 (5)
2 Tc ⎝ A c Au ⎠
This last equation can be solved by trial-and-error, or by any other iterative method,
knowing hu, zu, and the geometry of the upstream and throat cross-sections. The
geometry of the sections defines the relationship between hc and Ac, and between
hu and Au (important: if you look carefully at the above equations, you will see that
Au must be calculated based on a depth of hu + zu). The solution to Eq. 5 gives the
value of hc.
(3) The final step is to calculate the discharge corresponding to the value of Ac,
which is calculated directly from hc. This is done using the following form of the
Froude number equation:
g A 3c
Q= (6)
Tc
This process is repeated for various values of the upstream flow depth, and in the
end a table of values for upstream depth and discharge will have been obtained.
From this table a staff gauge can be constructed. This simple calibration assumes
that the downstream flow level is not so high that non-modular flow exists across
the structure.
interface
uses
Windows, Messages, SysUtils, Classes, Graphics, Controls, Forms, Dialogs,
StdCtrls, Buttons;
type
TWmain = class(TForm)
btnStart: TBitBtn;
procedure btnStartClick(Sender: TObject);
private
function NewtonRaphson(hu:double):double;
function EnergyFunction(hc:double):double;
function Area(h,b,m:double):double;
function TopWidth(h,b,m:double):double;
end;
var
Wmain: TWmain;
implementation
{$R *.DFM}
const
g = 9.810; // weight/mass (m/s2)
bu = 2.000; // base width upstream (m)
mu = 1.250; // side slope upstream (H:V)
zu = 1.600; // upstream sill height (m)
bc = 6.000; // base width at control section (m)
mc = 1.250; // side slope at control section (H:V)
L = 1.500; // sill length (m)
var
hu,Au,hc: double;
function TWmain.NewtonRaphson(hu:double):double;
//-----------------------------------------------------------------------------
// Newton-Raphson method to solve for critical depth. Returns flow rate.
//-----------------------------------------------------------------------------
var
i,iter: integer;
dhc,F,Fdhc,change,Ac,Tc: double;
begin
result:=0.0;
hc:=0.1*i*hu;
dhc:=0.0001*hc;
F:=EnergyFunction(hc);
Fdhc:=EnergyFunction(hc+dhc);
change:=Fdhc-F;
if abs(change) < 1.0E-12 then break;
change:=dhc*F/change;
hc:=hc-change;
function TWmain.EnergyFunction(hc:double):double;
//-----------------------------------------------------------------------------
// Energy balance function (specific energy), equal to zero.
//-----------------------------------------------------------------------------
var
Ac,Tc: double;
begin
Ac:=Area(hc,bc,mc);
Tc:=TopWidth(hc,bc,mc);
result:=hc-hu+0.5*Ac*Ac*Ac*(1.0/(Ac*Ac)-1.0/(Au*Au))/Tc;
end;
function TWmain.Area(h,b,m:double):double;
//-----------------------------------------------------------------------------
// Calculates cross-section area for symmetrical trapezoidal shape.
//-----------------------------------------------------------------------------
begin
result:=h*(b+m*h);
end;
function TWmain.TopWidth(h,b,m:double):double;
//-----------------------------------------------------------------------------
// Calculates top width of flow for symmetrical trapezoidal shape.
//-----------------------------------------------------------------------------
begin
result:=b+2.0*m*h;
end;
humin:=0.075*L;
humax:=0.75*L;
hu:=humin;
hu:=hu+0.03;
if hu > humax then break;
end;
CloseFile(F);
end;
end.
Head loss in the throat (where the critical flow control section is assumed to be
located) can be estimated according to some elements from boundary layer theory.
The equation is (Schlichting 1960):
CF L Vc 2
(hf )throat = (7)
2gR
where L is the length of the sill; Vc is the average velocity in the throat section; and R is
the hydraulic radius of the throat section. The values of V and R can be taken for
critical depth in the throat section. The drag coefficient, CF, is estimated by assuming
the sill acts as a thin flat plat with both laminar and turbulent flow, as shown in the
figure below (after Bos, Replogle and Clemmens 1984).
The drag coefficient is calculated by assuming all turbulent flow, subtracting the
turbulent flow portion over the length Lm, then adding the laminar flow portion for the
length Lm. Note that CF is dimensionless.
⎛m⎞ ⎛m⎞
CF = CT,L − ⎜ ⎟ CT,m + ⎜ ⎟ CL,m (8)
⎝L⎠ ⎝L⎠
where CL,m is the thin-layer laminar flow coefficient over the distance m, which
begins upstream of the weir crest:
1.328
CL,m = (9)
(Re )m
When (Re)L < (Re)m, the flow is laminar over the entire crest and CF = CL,L, where
CL,L is defined by Eq. 9.
where x is equal to L or m, for CT,L and CT,m, respectively; Re is the Reynolds number;
and k is the absolute roughness height. All values are in m and m3/s. Below are some
sample values for the roughness, k.
Material Roughness, k
and Condition (mm)
Glass 0.001 to 0.01
Smooth Metal 0.02 to 0.1
Rough Metal 0.1 to 1.0
Wood 0.2 to 1.0
Smooth Concrete 0.1 to 2.0
Rough Concrete 0.5 to 5.0
Vx
(R e ) x = (11)
ν
ν⎛ L⎞
m= ⎜ 350,000 + ⎟ (12)
V⎝ k⎠
Diverging Section
2
ξ ( Vc − Vd )
(hf )ds = (13)
2g
where (hf)ds is the head loss in the diverging section (m); Vc is the average velocity in
the control section, at critical depth (m/s); and Vd is the average velocity in the
downstream section (m/s), using hd referenced to the downstream channel bed
elevation (not the sill crest).
Gary P. Merkley 100 BIE 5300/6300 Lectures
The coefficient ξ is defined as:
Converging Section
After having calculated the CF drag coefficient for the throat section, and assuming the
same roughness value for the channel and structure from the gauge location to the
control section, the upstream losses can be estimated. These are the losses from the
gauge location to the beginning of the sill.
For the section from the gauge to the beginning of the upstream ramp, the head loss is
estimated as:
⎛ CF Lgauge ⎞ Vu2
(hf )gauge =⎜ ⎟ (15)
⎝ R u ⎠ 2g
where Lgauge is the distance from the gauge to the beginning of the upstream ramp; Vu
is the average velocity in the upstream section (at the gauge); and Ru is the hydraulic
radius at the gauge. All values are in metric units (m and m/s).
For the upstream ramp, the same equation can be used, but the hydraulic radius
changes along the ramp. Therefore,
1 ⎛ CF Lu ⎞ ⎛ Vu2 Vr2 ⎞
(hf )us = ⎜ ⎟⎜ + ⎟ (16)
2 ⎝ 2g ⎠ ⎜⎝ Ru Rr ⎟⎠
where the values of Vr and Rr, at the entrance to the throat section (top of the ramp),
are estimated by calculating the depth at this location:
Advantages
Disadvantages
Free Flow
n
Qf = Cf hu f (1)
where the subscript f denotes free flow; Qf is the free-flow discharge; Cf is the
free-flow coefficient; and nf is the free-flow exponent
• The value of Cf increases as the size of the constriction increases, but the
relationship is usually not linear
• The value of nf is primarily dependent upon the geometry of the constriction with
the theoretical values being 3/2 for a rectangular constriction and 5/2 for a
triangular constriction
• Sample field data for developing the discharge rating for a rectangular open-
channel constriction are listed in the table below
• The discharge rate in the constriction was determined by taking current meter
readings at an upstream location, and again at a downstream location
• The free-flow equation for the flow depths measured below the benchmark (at
411.201 m) is:
1.55
Qf = 0.74 ( hu ) x (2)
• The “Tape Measurement” in the above table is for the vertical distance from the
benchmark down to the water surface
• If a regression analysis is performed with the free-flow data using the theoretical
value of nf = 3/2,
1.5
Qf = 0.73 ( hu )sw (3)
or,
1.5
Qf = 0.75 ( hu ) x (4)
• The error in the discharge resulting from using nf = 3/2 varies from -1.91% to
+2.87%.
nf
Cs ( hu − hd )
Qs = ns
(5)
( − logS )
where the subscript s denotes submerged flow, so that Qs is the submerged-flow
discharge, Cs is the submerged-flow coefficient, and ns is the submerged-flow
exponent
• Base 10 logarithms have usually been used with Eq. 5, but other bases could be
used, so the base should be specified when providing calibration values
• Note that the free-flow exponent, nf, is used with the term hu - hd
• Consequently, nf is determined from the free-flow rating, while Cs and ns must be
evaluated using submerged-flow data
• The theoretical variation in ns is between 1.0 and 1.5
• Note that the logarithm term in the denominator of Eq. 5 can be estimated by
taking the first two or three terms of an infinite series (but this is not usually
necessary):
1 2 1 3 1 4
loge (1 + x) = x − x + x − x +… (6)
2 3 4
• Draw a straight line through the five data points and extend this line to –log10S =
1.0 (as shown above)
• The value on the ordinate at –log10S = 1.0 is Cs
• The slope of the line is –ns (measured with a linear scale)
• You might not prefer to use this method unless you have no computer
• Multiple regression analysis can be used to arrive directly at all three values (Cs,
nf, and ns) without free-flow data
• This can be done by taking the logarithm of Eq. 5 as follows:
• In this example, a nearly constant discharge was diverted into the irrigation
channel and a check structure with gates located 120 m downstream was used
to incrementally increase the flow depths
• Each time that the gates were changed, it took 2-3 hours for the water surface
elevations upstream to stabilize
• Thus, it took one day to collect the data for a single flow rate
• The data listed in the table below were collected in two consecutive days
nf
Cs (hu − hd )
Qs
=
( − logS )ns = (hu − hd )
nf
(8)
n
Q∆h=1 Cs (1) f
( − logS )ns
then,
nf
Qs = Q∆h=1.0 (hu − hd ) (9)
or,
Qs
Q∆h=1.0 = nf
(10)
(hu − hd )
where Q∆h=1.0 has a different value for each value of the submergence, S
• Using the term Q∆h=1.0 implies that hu - hd = 1.0 (by definition); thus, Eq. 10
reduces to:
1.55
0.367 ( hu − hd )
Qs = 1.37
(12)
( − logS )
Transition Submergence
Cs (1 − St ) f hnuf
n
Cf hnuf = (13)
( − logSt ) ns
then,
f ( St ) = Cf ( − logSt )
ns
− Cs (1 − St )
nf
=0 (14)
1.37 1.55
0.74 ( − logS ) = 0.367 (1 − S ) (15)
or,
1.55
0.367 ( hu − hd )
0.74h1.55
u = (16)
( − logS )1.37
and,
1.37 1.55
0.74 ( − logS ) = 0.367 (1 − S ) (17)
• Equation 18 can be solved to determine the value of St, which in this case is 0.82
• Thus, free flow exists when S < 0.82 and submerged flow exists when the
submergence is greater than 82%
• The table below gives the submergence values for different values of Qs/Qf for
the sample constriction rating
S Qs/Qf S Qs/Qf
0.82 1.000 0.91 0.9455
0.83 0.9968 0.92 0.9325
0.84 0.9939 0.93 0.9170
0.85 0.9902 0.94 0.8984
0.86 0.9856 0.95 0.8757
0.87 0.9801 0.96 0.8472
0.88 0.9735 0.97 0.8101
0.89 0.9657 0.98 0.7584
0.90 0.9564 - -
1.55
Qs 0.367 ( hu − hd ) 1
= = (19)
Qf ( − logS )1.37 0.74h1.55
u
1.337
S= = 0.935 (21)
1.430
• Thus, for this condition submerged flow exists in the example open-channel
constriction
• In practice, there may only be a “trivial” solution for transition submergence, in
which St = 1.0. In these cases, the value of Cs can be slightly lowered to obtain
another mathematical root to the equation. This is a “tweaking” procedure.
• Note that it is almost always expected that 0.50 < St < 0.92. If you come up with
a value outside of this range, you should be suspicious that the data and or the
analysis might have errors.
• A constant-head orifice, or
CHO, is a double orifice
gate, usually installed at
the entrance to a lateral or
tertiary canal
• This is a design promoted
for years by the USBR,
and it can be found in
irrigation canals in many
countries
• The idea is that you set
the downstream gate as a
meter, and set the
upstream gate as
necessary to have a
constant water level in the
mid-gate pool
• It is kind of like the double
doors in the engineering building at USU: they are designed to act as buffers
whereby the warm air doesn’t escape so easily when people enter an exit the
building
• But, in practice, CHOs are seldom used as intended; instead, one of the gates is
left wide open and the other is used for regulation (this is a waste of materials
because one gate isn’t used at all)
• Note the missing wheel in the upstream gate, in the above figure
• Few people know what CHOs are for, and even when they do, it is often
considered inconvenient or impractical to operate both gates
• But these gates can be calibrated, just as with any other gate
• It is safe to assume that the exponent on the head for orifice flow (free and
submerged) is 0.50, so it is not necessary to treat it as an empirically-determined
calibration parameter
• The basic relationship for orifice flow can be derived from the Bernoulli equation
• For orifice flow, a theoretical contraction coefficient, Cc, of 0.611 is equal to π/(π+2),
derived from hydrodynamics for vertical flow through an infinitely long slot
• Field-measured discharge coefficients for orifice flow through gates normally range
from 0.65 to about 0.9 − there is often a significant approach velocity
• Radial gates can be field calibrated using the same equation forms as vertical
sluice gates, although special equations have been developed for them
• If the water level on the upstream side of the gate is above the bottom of the
gate, then the flow regime is probably that of an orifice
• In this case, the momentum function (from open-channel hydraulics) can be used
to determine whether the flow is free or submerged
• In some cases it will be obviously free flow or obviously submerged flow, but the
following computational procedure is one way to distinguish between free orifice
and submerged orifice flow
• In the figure below, h1 is the depth just upstream of the gate, h2 is the depth just
downstream of the gate (depth at the vena-contracta section) and h3 is the depth
at a section in the downstream, a short distance away from the gate
Q2
M = A hc + (22)
gA
where A is the cross-sectional area and hc is the depth to the centroid of the area
from the water surface
• The following table shows the values of A and Ahc for three different channel
sections
Rectangular bh bh2
2
⎡ ⎛ m1 + m2 ⎞ ⎤ ⎡ b ⎛ m1 + m2 ⎞ ⎤ 2
Trapezoidal ⎢b + ⎜ 2 ⎟ h⎥ h ⎢2 + ⎜ 6 ⎟ h⎥ h
⎣ ⎝ ⎠ ⎦ ⎣ ⎝ ⎠ ⎦
−1 ⎛ 2h ⎞
• For circular sections, θ is defined as: θ = 2cos ⎜1 − ⎟
⎝ D⎠
• There are alternate forms of the equations for circular sections, but which yield
the same calculation results.
• The depth h2 can be determined in the either of the following two ways:
• Another (simpler) criteria for the threshold between free- and submerged-orifice
flow is:
CcGo = hd (23)
• The threshold between orifice and nonorifice flow can be defined as:
Cohu = Go (24)
• Note that if Co = 1.0, then when hu = Go, the water surface is on the verge of
going below the bottom of the gate (or vice-versa), when the regime would
clearly be nonorifice
• However, in moving from orifice to nonorifice flow, the transition would begin
before this point, and that is why Co must be less than 1.0
• It seems that more research is needed to better defined the value of Co
• In practice, the flow can move from any regime to any other at an underflow
(gate) structure:
Free Submerged
Orifice FO SO
Non-orifice FN SN
• If the downstream water level is also above the top of the opening, submerged
conditions exist and the discharge equation becomes:
Qs = CdCv A 2g ( hu − hd ) (27)
• For a rectangular gate having a gate opening, Go, and a gate width, W, the free-
flow discharge equation can be obtained from Eq. 26 of the previous lecture,
assuming that the dimensionless velocity head coefficient is equal to unity:
(
Qf = CdGoGw 2g hu − CgGo ) (1)
where Go is the vertical gate opening; Gw is the gate width; GoGw is the area, A,
of the gate opening; and, Cg is between 0.5 and 0.61
• The upstream flow depth, hu, can be measured anywhere upstream of the gate,
including the upstream face of the gate
• The value of hu will vary only a small amount depending on the upstream location
chosen for measuring hu
• Consequently, the value of the coefficient of discharge, Cd, will also vary
according to the location selected for measuring hu
• One of the most difficult tasks in calibrating a gate structure is obtaining a highly
accurate measurement of the gate opening, Go
• For gates having a threaded rod that rises as the gate opening is increased, the
gate opening is read from the top of the hand-wheel to the top of the rod with the
gate closed, and when set to some opening, Go
• This very likely represents a measurement of gate opening from where the gate
is totally seated, rather than a measurement from the gate lip; therefore, the
measured value of Go from the thread rod will usually be greater than the true
gate opening, unless special precautions are taken to calibrate the thread rod
• Also, when the gate lip is set at the same elevation as the gate sill, there will
undoubtedly be some flow or leakage through the gate
• This implies that the datum for measuring the gate opening is below the gate sill
• In fact, there is often leakage from a gate even when it is totally seated because
of inadequate maintenance
• An example problem will be used to illustrate the procedure for determining an
appropriate zero datum for the gate opening
Sample Calibration
• Calibration data (listed in the table below) were collected for a rectangular gate
structure
• The data reduction is listed in the next table, where the coefficient of discharge,
Cd, was calculated from Eq. 27
BIE 5300/6300 Lectures 123 Gary P. Merkley
Discharge, Qf Gate Opening, Go Upstream Benchmark
(m3/s) (m) Tape Measurement (m)
0.0646 0.010 0.124
0.0708 0.020 1.264
0.0742 0.030 1.587
0.0755 0.040 1.720
0.0763 0.050 1.787
0.0767 0.060 1.825
Qf Go hu
Cd
(m3/s) (m) (m)
0.0646 0.010 1.838 0.756
0.0708 0.020 0.698 0.677
0.0742 0.030 0.375 0.654
0.0755 0.040 0.242 0.635
0.0763 0.050 0.175 0.625
0.0767 0.060 0.137 0.620
Note: The discharge coefficient, Cd, was calculated
using the following equation:
⎛ G ⎞
Qf = CdGoGw 2g ⎜ hu − o ⎟
⎝ 2 ⎠
• A rectangular coordinate plot of Cd versus the gate opening, Go, is shown in the
figure below
0.76
0.74
Coefficient of discharge, Cd
0.72
0.70
0.68
0.66
0.64
0.62
0.01 0.02 0.03 0.04 0.05 0.06
Gate opening, Go (m)
⎛ G + ∆Go ⎞
Qf = Cd ( Go + ∆Go ) Gw 2g ⎜ (hu )∆G − o ⎟ (2)
⎝ o 2 ⎠
where ∆Go is a measure of the zero datum level below the gate sill, and
• Assuming values of ∆Go equal to 1 mm, 2 mm, 3 mm, etc., the computations for
determining Cd can be made from Eq. 3
• The results for ∆Go equal to 1 mm, 2 mm, 3 mm, 4 mm, 5 mm, 6 mm, 7 mm, 8
mm and 12 mm (gate seated) are listed in the table below
• The best results are obtained for ∆Go of 3 mm − the results are plotted in the
figure below, which shows that Cd varies from 0.582 to 0.593 with the average
value of Cd being 0.587
• For this particular gate structure, the discharge normally varies between 200 and
300 lps, and the gate opening is normally operated between 40-60 mm, so that a
constant value of Cd = 0.587 can be used when the zero datum for Go and hu is
taken as 3 mm below the gate sill
• Another alternative would be to use a constant value of Cd = 0.575 for ∆Go = 4
mm and Go greater than 30 mm
• Assuming that the dimensionless velocity head coefficient in Eq. 27 is unity, the
submerged-flow discharge equation for a rectangular gate having an opening,
Go, and a width, W, becomes:
Qs Go hu hd h u - hd
Cd
(m3/s) (m) (m) (m) (m)
0.079 0.102 0.823 0.643 0.180 0.676
0.095 0.121 0.819 0.633 0.187 0.674
0.111 0.139 0.816 0.620 0.196 0.668
0.126 0.162 0.813 0.626 0.187 0.666
0.141 0.179 0.810 0.615 0.195 0.660
0.155 0.198 0.808 0.615 0.193 0.659
• As in the case of the free-flow orifice calibration in the previous section, a trial-
and-error approach can be used to determine a more precise zero datum for the
gate opening
• In this case, the submerged flow equation would be rewritten as:
Qs Go h u - hd Cd
Note: The discharge coefficient, Cd, was calculated from Eq. 32:
• As before, the criteria for determining ∆Go is to obtain a nearly constant value of
the discharge coefficient, Cd
• The above table has the example computational results for determining the
discharge coefficient, Cd, according to adjusted gate openings, Go, under
submerged flow conditions
• A different form of the submerged-flow rating equation has been used with
excellent results on many different orifice-type structures in medium and large
canals
• The differences in the equation involve consideration of the gate opening and the
downstream depth as influential factors in the determination of the discharge
coefficient
• The equation is as follows:
Qs = Cs hs Gw 2g (hu − hd ) (6)
and,
β
⎛G ⎞
Cs = α ⎜ o ⎟ (7)
⎝ hs ⎠
where hs is the downstream depth referenced to the bottom of the gate opening,
α and β are empirically-fitted parameters, and all other terms are as described
previously
• The next table shows some example field calibration data for a large canal gate
operating under submerged-flow conditions
• The solution to the example calibration is: α = 0.796, and β = 1.031
• This particular data set indicates an excellent fit to Eqs. 6 and 7, and it is typical
of other large gate structures operating under submerged-flow conditions
Data Discharge Go ∆h hs
Go/hs Cs
Set (m3/s) (m) (m) (m)
1 8.38 0.60 3.57 2.205 0.272 0.206
2 9.08 0.70 3.00 2.010 0.348 0.268
3 5.20 0.38 3.31 1.750 0.217 0.168
4 4.27 0.30 3.41 1.895 0.158 0.125
5 5.45 0.40 3.43 2.025 0.198 0.149
6 12.15 0.95 2.63 2.300 0.413 0.334
7 5.49 0.38 3.72 1.905 0.199 0.153
8 13.52 1.10 2.44 2.405 0.457 0.369
9 14.39 1.00 3.84 2.370 0.422 0.318
10 16.14 1.13 3.79 2.570 0.440 0.331
11 6.98 0.50 3.70 1.980 0.253 0.188
12 11.36 0.58 7.64 2.310 0.251 0.183
13 7.90 0.42 6.76 2.195 0.191 0.142
14 7.15 0.38 6.86 2.110 0.180 0.133
15 7.49 0.51 3.98 2.090 0.244 0.184
16 10.48 0.70 3.92 2.045 0.342 0.266
17 12.41 0.85 3.76 2.205 0.385 0.298
18 8.26 0.55 3.91 2.065 0.266 0.208
Note: the data are for two identical gates in parallel, both having the
same opening for each data set, with a combined opening width of 2.20
m.
-0.6
-0.8
alpha = 0.796
-1.0
beta = 1.031
-1.2
-1.4
ln(Cs)
-1.6
-1.8
-2.0
-2.2
-2.4
-2.0 -1.8 -1.6 -1.4 -1.2 -1.0 -0.8 -0.6
ln(Go/hs)
• This structure type includes radial (or “Tainter”) gates as calibrated by the USBR
(Buyalski 1983) for free and submerged orifice-flow conditions
• The calibration of the gates follows the specifications in the USBR “REC-ERC-
83-9” technical publication, which gives calibration equations for free and
submerged orifice flow, and corrections for the type of gate lip seal
• The calibration requires no field measurements other than gate dimensions, but
you can add another coefficient to the equations for free flow and orifice flow in
an attempt to accommodate calibration data, if available
• Three gate lip seal designs (see figure below) are included in the calibrations:
• The gate lip seal is the bottom of the gate leaf, which rests on the bottom of the
channel when the gate is closed
• The discharge coefficients need no adjustment for the hard-rubber bar gate lip,
which is the most common among USBR radial gate designs, but do have
correction factors for the other two lip seal types
• These are given below for free and submerged orifice flow
Gr
hu
Go P hd
• The gate radius divided by the pinion height should be within the range 1.2 ≤ Gr/P
≤ 1.7
• The upstream water depth divided by the pinion height should be less than or
equal to 1.6 (hu/P ≤ 1.6)
• If these and other limits are observed, the accuracy of the calculated flow rate
from Buyalski’s equations should be within 1% of the true flow rate
Eccentricity
⎛ ⎛ Gr ⎞ ⎞
2
AFE = 0.00212 ⎜ 1.0+31.2 ⎜ − 1.6 ⎟ ⎟ + 0.901
⎜ ⎝ P ⎠ ⎟⎠
⎝ (9)
⎛ ⎛ Gr ⎞ ⎞
2
BFE = 0.00212 ⎜ 1.0+187.7 ⎜ − 1.635 ⎟ ⎟ − 0.079
⎜ ⎝ P ⎠ ⎟⎠
⎝ (10)
⎛G ⎞
FE = AFE − BFE ⎜ o ⎟
⎝ P ⎠ (11)
where Gr is the gate radius (m or ft); and P is the pinion height (m or ft)
Directrix
⎛ ⎛ Gr ⎞ ⎞
2
AFD = 0.788 − 0.04 ⎜ 1.0+89.2 ⎜ − 1.619 ⎟ ⎟ (12)
⎜ ⎝ P ⎠ ⎟⎠
⎝
⎛ ⎛ Go ⎞ ⎞
2
FD = 0.472 − BFD ⎜ 1.0- ⎜ − AFD ⎟ ⎟ (14)
⎜ ⎝ P ⎠ ⎟⎠
⎝
Focal Distances
⎛G ⎞ Go
FX1 = 1.94 ⎜ o ⎟ − 0.377 ≤ 0.277
⎝ P ⎠ P
(15)
⎛G ⎞ Go
FX1 = 0.18 ⎜ o ⎟ + 0.111 > 0.277
⎝ P ⎠ P
⎛G ⎞
FY1 =0.309 − 0.192 ⎜ o ⎟ (16)
⎝ P ⎠
and,
hu
FXV = − FX1 (17)
P
The correction on Cfcda for the “music note” gate lip seal design is:
⎛G ⎞
Ccorrect = 0.125 ⎜ o ⎟ + 0.91 (music note) (18)
⎝ P ⎠
The correction on Cfcda for the “sharp edge” gate lip seal design is:
⎛G ⎞
Ccorrect = 0.11⎜ o ⎟ + 0.935 (sharp edge) (19)
⎝ P ⎠
For the hard-rubber bar gate lip seal design, Ccorrect = 1.0. The preceding corrections
on Cfcda for the “music note” and “sharp edge” gate lip seal designs were chosen
from the linear options proposed by Buyalski (ibid).
⎛ ⎞
Cfcda = Ccorrect ⎜ FE2 (FD + FXV ) − FXV 2 + FY1 ⎟
2
(20)
⎝ ⎠
where Cscda is the submerged-flow discharge coefficient; and all other terms
are as previously defined; both Cscda and Cds are dimensionless
• Note that the square-root term does not include the downstream depth, hd,
but it is included in the lengthy definition of Cscda
• As in the free-flow case, Cscda is determined according to a series of conic
equations:
Directrix
−1
⎛ ⎛G ⎞ ⎞
ADA = ⎜ 11.98 ⎜ r ⎟ − 26.7 ⎟ (22)
⎝ ⎝ P ⎠ ⎠
−1
⎛ ⎛G ⎞ ⎞
AD = ⎜ ADA ⎜ o ⎟ + ADB ⎟ (24)
⎝ ⎝ P ⎠ ⎠
⎛G ⎞
BDA = 0.025 ⎜ r ⎟ − 2.711 (25)
⎝ P ⎠
⎛G ⎞
BDB = 0.071 − 0.033 ⎜ r ⎟ (26)
⎝ P ⎠
⎛G ⎞
BD = BDA ⎜ o ⎟ + BDB (27)
⎝ P ⎠
⎛h ⎞
DR = AD ⎜ d ⎟ + BD (28)
⎝P⎠
D = DR −1.429 (29)
Eccentricity
⎛G ⎞
AEA = 0.06 − 0.019 ⎜ r ⎟
⎝P ⎠ (30)
⎛G ⎞
AEB = 0.996 + 0.0052 ⎜ r ⎟
⎝P ⎠ (31)
−1
⎛ ⎛G ⎞ ⎞
AE = ⎜ AEA ⎜ o ⎟ + AEB ⎟
⎝ ⎝ P ⎠ ⎠ (32)
⎛ ⎛ Go ⎞ ⎞
2
BE = BEK + 0.255 ⎜ 1.0 + 1.429 ⎜ − 0.44 ⎟ ⎟ (34)
⎜ ⎝ P ⎠ ⎟⎠
⎝
ER = AE (D ) + BE
(35)
⎛ ER ⎞
E = ln ⎜ ⎟
⎝ D ⎠ (36)
Vector V1
E (D )
V1 = (37)
1.0 + E
Focal Distance
⎛P⎞
AFA = 0.038 − 0.158 ⎜ ⎟ (38)
⎝ Gr ⎠
⎛G ⎞
AFB = 0.29 − 0.115 ⎜ r ⎟ (39)
⎝ P ⎠
⎛G ⎞
AF = AFA ⎜ o ⎟ + AFB (40)
⎝ P ⎠
⎛P ⎞
BFA = 0.0445 ⎜ ⎟ − 0.321 (41)
⎝ Gr ⎠
⎛ P ⎞
BF = BFA ⎜ ⎟ + BFB (43)
⎝ Go ⎠
AF (hd )
FY = BF − (44)
P
hu h
VX = − V1 − d − FX (46)
P P
The correction on Cscda for the “music note” gate lip seal design is:
⎛G ⎞
Ccorrect = 0.39 ⎜ o ⎟ + 0.85 (music note) (47)
⎝ P ⎠
The correction on Cscda for the “sharp edge” gate lip seal design is:
⎛G ⎞
Ccorrect = 0.11⎜ o ⎟ + 0.9 (sharp edge) (48)
⎝ P ⎠
• For the hard-rubber bar gate lip seal design, Ccorrect = 1.0
• The preceding corrections on Cscda for the “music note” and “sharp edge” gate
lip seal designs were chosen from the linear options proposed by Buyalski
(ibid)
Finally,
Buyalski, C.P. 1983. Discharge algorithms for canal radial gates. Technical Report REC-ERC-83-9.
U.S. Bureau of Reclamation, Denver, CO. 232 pp.
Brater, E.F., and H.W. King. 1976. Handbook of hydraulics. 6th edition. McGraw-Hill Book Company,
New York, N.Y. 583 pp.
Buyalski, C.P. 1983. Discharge algorithms for canal radial gates. Technical Report REC-ERC-83-9.
U.S. Bureau of Reclamation, Denver, CO. 232 pp.
Chow, V.T. 1959. Open-channel hydraulics. McGraw-Hill Book Company, New York, N.Y. 680 pp.
Daugherty, R.L., and J. B. Franzini. 1977. Fluid mechanics with engineering applications. 7th edition.
McGraw-Hill Book Company, New York, N.Y. 564 pp.
Davis, C.V. and K.E. Sorensen (eds.). 1969. Handbook of applied hydraulics. McGraw-Hill Book
Company, New York, N.Y.
French, R.H. 1985. Open-channel hydraulics. McGraw-Hill Book Company, New York, N.Y. 705 pp.
Hu, W.W. 1973. Hydraulic elements for USBR standard horseshoe tunnel. J. of the Transportation
Engrg. Div., ASCE, 99(4): 973-980.
Hu, W.W. 1980. Water surface profile for horseshoe tunnel. Transportation Engrg. Journal, ASCE,
106(2): 133-139.
Press, W.H., S. A. Teukolsky, W. T. Vetterling, and B. P. Flannery. 1992. Numerical recipes in C: the
art of scientific computing. 2nd Ed. Cambridge Univ. Press, Cambridge, U.K. 994 pp.
Shen, J. 1981. Discharge characteristics of triangular-notch thin-plate weirs. Water Supply Paper
1617-B. U.S. Geological Survey.
Skogerboe, G.V., M.L. Hyatt, R.K. Anderson, and K.O. Eggleston. 1967. Cutthroat flumes. Utah Water
Research Laboratory Report WG31-4. 37 pp.
Skogerboe, G.V., L. Ren, and D. Yang. 1993. Cutthroat flume discharge ratings, size selection and
installation. Int’l Irrig. Center Report, Utah State Univ., Logan, UT. 110 pp.
Uni-Bell Plastic Pipe Association. 1977. Handbook of PVC pipe: design and construction. Uni-Bell
Plastic Pipe Association, Dallas, TX.
Villamonte, J.R. 1947. Submerged-weir discharge studies. Engrg. News Record, p. 866.
I. Introduction
• There are a wide variety of methods for measuring discharge and velocity in
pipes, or closed conduits
• Many of these methods can provide very accurate measurements
• Others give only rough estimates
• But, in general, it is easier to obtain a given measurement accuracy in pipes
when compared to measurement in open channels
• Some of the devices used are very expensive and are more suited to industrial
and municipal systems than for agricultural irrigation systems
• The pitot tube is named after Henri Pitot who used a bent glass tube to measure
velocities in a river in France in the 1700s
• The pitot tube can be used not only for measuring flow velocity in open channels
(such as canals and rivers), but in closed conduits as well
• There are several variations of pitot tubes for measuring flow velocity, and many
of these are commercially available
• The measurement from a pitot tube can be accurate to ±1% of the true velocity,
even if the submerged end of the tube is up to ±15% out of alignment from the
flow direction
• The velocity reading from a pitot tube must be multiplied by cross-sectional area
to obtain the flow rate (it is a velocity-area method)
• Pitot tubes tend to become clogged unless the water in the pipe is very clean
• Also, pitot tubes may be impractical if there is a large head, unless a manometer
is used with a dense liquid like mercury
• Venturis
• Nozzles
• Orifices
• Flow rate
• Fluid properties
• Element geometry
• The principle of this flow measurement device was first documented by J.B.
Venturi in 1797 in Italy
• Venturi meters have only a small head loss, no moving parts, and do not clog
easily
Head
loss
∆h
21º 5º - 7º
Flow
D1 D2 D1
2g ∆h(sg − 1)
Q = C A2 (1)
4
1− β
V. Flow Nozzles
• Flow nozzles operate on the same principle as venturi meters, but the head loss
tends to be much greater due to the absence of a downstream diverging section
• There is an upstream converging section, like a venturi, but there is no
downstream diverging section to reduce energy loss
Gary P. Merkley 144 BIE 5300/6300 Lectures
• Flow nozzles can be less expensive than venturi meters, and can provide
comparable accuracy
• The same equation as for venturi meters is used for flow nozzles
• The head differential across the nozzle can be measured using a manometer or
some kind of differential pressure gauge
• The upstream tap should be within ½D1 to D1 upstream of the entrance to the
nozzle
• The downstream tap should be approximately at the outlet of the nozzle (see the
figure below)
Head
loss
HGL
Flow D1
D2
• The space between the nozzle and the pipe walls can be filled in to reduce the
head loss through the nozzle, as seen in the following figure
Head
loss
HGL
Flow D1
D2
• These devices use a thin plate with an orifice, smaller than the pipe ID, to create
a pressure differential
• The orifice opening is usually circular, but can be other shapes:
• Square
• Oval
• Triangular
• Others
• The pressure differential can be measured, as in venturi and nozzle meters, and
the same equation as for venturi meters can be used
• However, the discharge coefficient is different for orifice meters
• It is easy to make and install an orifice meter in a pipeline – easier than a nozzle
• Orifice meters can give accurate measurements of Q, and they are simple and
inexpensive to build
• But, orifice meters cause a higher head loss than either the venturi or flow nozzle
meters
• As with venturi meters and flow nozzles, orifice meters can provide values within
±1% (or better) of the true discharge
• As with venturi meters, there should be a straight section of pipe no less than 10
diameters upstream
• Some engineers have used eccentric orifices to allow passage of sediments –
the orifice is located at the bottom of a horizontal pipe, not in the center of the
pipe cross section
upstream downstream
½D1 30 to 45 deg
0.005D1
to 0.02D1 ½D2
CL
Gary P. Merkley 146 BIE 5300/6300 Lectures
• The upstream head is usually measured one pipe diameter upstream of the thin
plate, and the downstream head is measured at a variable distance from the
plate
• Standard calibrations are available, providing C values from which the discharge
can be calculated for a given ∆h value
• In the following, the coefficient for an orifice plate is called “K”, not “C”
• The coefficient values depend on the ratio of the diameters and on the Reynold’s
number of approach; they can be presented in tabular or graphical formats
Head loss
∆h
vena contracta
Flow D1
D2
0.5D1
D1
An Orifice Meter in a Pipe
• In the figure below, the Reynold’s number of approach is calculated for the pipe
section upstream of the orifice plate (diameter D1, and the mean velocity in D1)
• Note also that pipe flow is seldom laminar, so the curved parts of the figure are
not of great interest
• An equation for use with the curves for K:
⎡⎛ P ⎞ ⎛P ⎞⎤
Q = KA 2 2g ⎢⎜ u + zu ⎟ − ⎜ d + zd ⎟ ⎥ (2)
⎣⎝ γ ⎠ ⎝ γ ⎠⎦
• The above equation is the same form as for canal gates operating as orifices
• The ratio β is embedded in the K term
• Note that zu equals zd for a horizontal pipe (they are measured relative to an
arbitrary elevation datum)
• Note that Pu/γ is the same as hu (same for Pd/γ and hd)
• Also, you can let ∆h = hu - hd
0.69
0.68
0.67
0.66
0.65
K
0.64
0.63
0.62
0.61
0.60
0.30 0.35 0.40 0.45 0.50 0.55 0.60 0.65 0.70
D2/D1
2g∆h(sg − 1)
Q = Cd A 2 (3)
1− β 4
D2
β= (4)
D1
where D2 is the diameter of the circular orifice opening; and, D1 is the inside
diameter of the upstream pipe
• In Eq. 3, “sg” is the specific gravity of the manometer fluid, and the constant “1”
represents the specific gravity of pure water
• The specific gravity of the manometer liquid must be greater than 1.0
• Thus, if a manometer is used to measure the head differential across the orifice
plate, the term “∆h(sg - 1)” represents the head in depth (e.g. m or ft) of water
• If both ends of the manometer were open to the atmosphere, and there’s no
water in the manometer, then you will see ∆h = 0
• But if both ends of the manometer are open to the atmosphere, and you pour
some water in one end, you’ll see ∆h > 0, thus the need for the “(sg – 1)” term
• Note that the specific gravity of water can be slightly different than 1.000 when
the water is not pure, or when the water temperature is not exactly 5°C
• See the figure below
• Note also that the manometer liquid must not be water soluble!
Head of water =
∆h(sg - 1)
sg = 1 ∆h
sg > 1
in which T°C is the water temperature in °C; (D1)meas is the measured inside pipe
diameter; and αp is the coefficient of linear thermal expansion of the pipe material
(1/°C)
• The coefficient of linear thermal expansion is the ratio of the change in length per
degree Celsius to the length at 0°C
• See the following table for linear thermal expansion values
Metal
Copper 0.0000176
Brass 0.0000188
Aluminum 0.0000230
Zinc 0.0000325
PVC 0.0000540
Plastic
ABS 0.0000990
PE 0.0001440
Glass 0.0000081
Other
Wood 0.0000110
Concrete 0.0000060 – 0.0000130
• For the range 0 to 100 °C, the following two equations can be applied for the
density and kinematic viscosity of water
• The density of pure water:
1
ν= (7)
83.9192 T + 20,707.5 T + 551,173
2
where αop is the coefficient of linear thermal expansion of the orifice plate
material (1/°C); and (D2)meas is the measured orifice diameter
• Note that the water temperature must be substantially different than 20°C for the
thermal expansion corrections to be significant
• The coefficient of discharge is defined by Miller (1996) for a circular pipe and
orifice plate in which the upstream tap is located at a distance D1 from the plate,
and the downstream tap is at a distance ½D1:
BIE 5300/6300 Lectures 151 Gary P. Merkley
Cd = 0.5959 + 0.0312β2.1 − 0.184β8
0.039β 4 91.71β2.5 (9)
+ − 0.0158β +
3
1 − β4 R0e.75
• Similar Cd equations exist for other orifice plate configurations, and for venturis
• The Cd expression for venturis is much simpler than that for orifice plates
• The Reynold’s number is a function of the flow rate, so the solution is iterative
• The calculated value of Cd is typically very near to 0.6, so if this is taken as the
initial value, usually only one or two iterations are needed:
Miller, R.W. 1996. Flow measurement engineering handbook. 3rd Ed. McGraw-Hill Book Co., New
York, N.Y.
USBR. 1996. Flow measurement manual. Water Resources Publications, LLC. Highlands Ranch,
CO.
I. Elbow Meters
3.5
Head differential (inches of Hg)
3.0
2.5
2.0
1.5
1.0
0.5
0.0
0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.14
Discharge (cfs)
• Note that the outside walls are usually transparent to allow direct readings by eye
a t2
x = vot + (1)
2
where x is the distance; vo is the initial velocity at time 0; t is the elapsed time;
and a is the acceleration
• Flow emanating from a horizontal pipe will fall a height y over a distance x
• The horizontal component (x-direction) has almost no acceleration, and the
vertical component (y-direction) has an initial velocity of zero
• The vertical acceleration is equal to the ratio of weight to mass, or g = 9.81 m/s2
(32.2 ft/s2)
• Therefore,
gt 2
x = v ot and, y = (2)
2
π D2 x
Q= (3)
2y
4
g
x
Q = 3.151CD2 (4)
y
where C is a coefficient to adjust the calculated discharge value when the ratios
of x/D or y/D are smaller than 8 and 5, respectively (otherwise, C equals unity)
• This method can also be used for pipes flowing partially full (i.e. A < πD2/4), and
experimental data are available to assist in the estimation of discharge for these
conditions
1.88
⎛ a⎞
Q = 8.69 ⎜ 1 − ⎟ D2.48 (5)
⎝ D⎠
where a and D are defined in the figure below (ft); and Q is discharge in cfs
• As with pipes discharging horizontally into the air, there is a method to measure
the flow rate from vertical pipes
• This is accomplished by assuming a translation of velocity head into the
measurable height of a column of water above the top of the pipe
• Thus, to estimate the flow rate from pipes discharging vertically into the air it is
only necessary to measure the:
• This is a nice idea on “paper,” but in practice, it can be difficult to measure the
height of the column of water because of sloshing, surging, and splashing
• Also, the act of measuring the height of the column can significantly alter the
measured value
• The table below gives flow rate values in gpm for several pipe diameters in
inches
• The vortex shedding meter can be accurate to within ±½% to ±1% of the true
discharge
• The basic principal is that an object placed in the flow will cause turbulence and
vortices in the downstream direction, and the rate of fluctuation of the vortices
can be measured by detecting pressure variations just downstream
• This rate increases with increasing velocity, and it can be used to give an
estimate of the discharge
• This requires calibration for a particular pipe material, pipe size, element shape
and size, fluid type, and temperature
• It is essentially a velocity-area flow measurement method, but it is calibrated to
give discharge directly
1. Doppler
2. Transit-time
a) Flow velocity
b) Beam orientation (angle)
c) Speed of sound through the liquid medium
• Collins meters
• Commercial propeller flow meters
• Electromagnetic flow meters
• Volumetric tank
• Historically, flow rate capacity and construction cost have been the dominant
design criteria, but it is better to take into account all of the above factors before
finalizing a design
• This is not to say that you necessarily have to dwell on an issue like aesthetics,
for example
BIE 5300/6300 Lectures 161 Gary P. Merkley
• However, issues such as dynamic operation, maintenance requirements and
need for spillways have often been given only cursory attention during the design
phase, requiring subsequent post-construction modifications to the infrastructure
• Water management and operational needs are very similar
• Secondary uses can
include things like
navigation (large canals),
clothes washing, other
domestic uses, aquatic
production, bathing, and
many others
• Remember that every
design has both common
and unique (site-specific)
features, compared to
other canals
• In earthen canals, and for canals in general, the most efficient cross section is a
secondary consideration to erodibility, maintenance, safety, and convenience
• The ratio of flow depth, h, to canal bottom width, b, usually varies from 1:2 to 1:4
for small canals, and from 1:4 to 1:8 in large canals
• Freeboard can be designed into the canal size at ¼ of the maximum water depth
plus one foot (maximum of 6 ft)
• Less freeboard is required if the canal is carefully controlled during operation
• Top width of the bank should allow for a vehicle to pass on one side; the other
side can be more narrow
• A primary concern in the layout of the system is that it serves the purpose of
conveying and distributing water to key locations in the area of service
• Another concern is that the excavation and earthen fill volumes not be excessive
• When large volumes of excavation and or fill are required, the construction costs
can increase tremendously
• In fill areas, compaction of the soil material is very important, to avoid settlement
problems and possible structural failure
• In bends, the radius of curvature should usually be between 3 and 7 times the
top width of flow at maximum design discharge (larger radius for larger canals)
• For a known design discharge, known longitudinal bed slope, and selected cross-
sectional shape, the Manning or Chezy equation can be solved for the required
depth
• Or, for a known design discharge, known longitudinal bed slope, and specified
maximum depth, the Manning equation can be solved for the required base width
of a rectangular section
• In general, the equation can be solved for any “unknown”, where all other
parameters are specified
• You can also go to the field and measure everything but roughness under
steady, uniform flow conditions, then calculate the value of n
• Avoid critical flow at or near design discharge (unstable water surface)
V. Manning Equation
• The Manning equation has been used to size canals all over the world
• It is an empirical equation for approximating uniform flow conditions in open
channels
• A roughness factor, n, is used in the equation
• In Metric units:
1
Q= AR2 / 3 So (1)
n
where Q is in m3/s; A is cross-section flow area (m2); R is hydraulic radius (m),
equal to A divided by wetted perimeter; and So is the longitudinal bed slope
(dimensionless)
1
≈ 1.49 (2)
(0.3048 m / ft)1/ 3
• In English units:
1.49
Q= AR2 / 3 So (3)
n
where Q is in cfs; A is in ft2; and R is in (ft)
Q = CA RSo (4)
R1/ 6
C= (5)
n
• The relationship between C and the Darcy-Weisbach f is:
8g
C≈ (6)
f
• Thus, C can be defined as a function of relative roughness (ε/R) and Reynold’s
number, and the resulting graph looks much like the Moody diagram, vertically
inverted
• Reynold’s number can be defined like this:
4RV
NR = (7)
ν
where R is the hydraulic radius (m), A/Wp; V is the mean flow velocity in a cross
section (m/s); and ν is the kinematic viscosity of water (m2/s)
C = 1.107 NR (9)
• For turbulent smooth flow (NR > 2000 & ε ≈ 0) and units of m and m3/s:
⎛ 0.28C ⎞
C = −17.7 log10 ⎜ ⎟ (10)
⎝ NR ⎠
• For turbulent transitional flow (NR > 2000 & ε > 0) and units of m and m3/s:
⎛ ε / R 0.28C ⎞
C = −17.7 log10 ⎜ + ⎟ (11)
⎝ 12 NR ⎠
• For turbulent rough flow (NR > 20,000 & ε > 0), where C is no longer a function of
NR, and units of m and m3/s:
⎛ 12 ⎞
C = 17.7 log10 ⎜ ⎟ (12)
⎝ ε /R ⎠
which gives the flat (horizontal) lines for fully turbulent flow
• To determine the threshold between turbulent transition and turbulent rough flow
for a given ε/R ratio, first determine C from Eq. 11, then calculate NR as:
75C
NR = (13)
ε /R
0.3048
= 2.006 (14)
0.3048
• Note that for all but laminar flow, you must iterate to solve for C
• This can be done quickly and easily in a computer program, and the results can
be presented as in the graph above
• Epsilon (roughness height) values depend on channel lining material type &
condition:
Davis, C.V. and K.E. Sorensen (eds.). 1969. Handbook of applied hydraulics. McGraw-Hill Book
Company, New York, N.Y.
Labye, Y., M.A, Olsen, A. Galand, and N. Tsiourtis. 1988. Design and optimization of irrigation
distribution networks. FAO Irrigation and Drainage Paper 44, Rome, Italy. 247 pp.
USBR. 1974. Design of small canal structures. U.S. Government Printing Office, Washington, D.C.
435 pp.
• For trapezoidal cross sections, the inverse side slope (H:V) is usually
between zero and 2.0
• Common inverse side slopes are zero (rectangular section), 1.0 and 1.5
• There are tradeoffs between low and high values of side slope:
1. canals with low inverse side slopes occupy less land area
2. high inverse side slopes are more stable and may require
less maintenance
3. high inverse side slopes are safer, if animals or people could
fall into the canal, because it is easier to climb out
4. rectangular cross sections can be simpler to build, when lined
with concrete (especially for small cross sections)
5. it may be easier to build and install structures and transitions
for rectangular sections
6. medium-range side slopes correspond to greater hydraulic
efficiency
• Freeboard means the extra depth of a canal section, above the water surface for
100% flow rate capacity, usually for uniform-flow conditions
• A freeboard value should be added to the maximum expected depth to allow for:
• Thus, with freeboard, under maximum flow conditions (full supply level, FSL),
canal overflow is not impending
• If the canal starts to overflow, enormous erosive damage can occur in just a few
minutes
• According to Murphy’s Law, these things usually happen about 3:00 am, when no
one is around. Then, everyone finds out at about 6:30 am after it has been
spilling for hours.
• Many reaches of canal in many countries are routinely operated with virtually no
freeboard, and disasters often occur
BIE 5300/6300 Lectures 173 Gary P. Merkley
A canal which is overtopping the banks and spilling water.
Symmetrical section:
A = h ( b + mh )
(16)
T = b + 2mh (17)
Wp = b + 2h m2 + 1
(18)
Gary P. Merkley 176 BIE 5300/6300 Lectures
w = h m2 + 1 (19)
T −b
m=
4w 2 − (T − b)2 (20)
h2 ⎛ 2hm ⎞
hc = ⎜b + ⎟ (21)
2A ⎝ 3 ⎠
h2 ⎛ 4hm ⎞
h= ⎜b + ⎟ (22)
2A ⎝ 3 ⎠
where h is the depth from the bottom (or “invert”) of the cross section up to the
centroid of the cross-sectional area; and hc is the depth from the water surface
down to the area centroid:
hc = h − h (23)
A = h [b + 0.5(m1 + m2 )h]
(24)
T = b + h ( m1 + m2 )
(25)
Wp = b + h ⎛⎜ m12 + 1 + m22 + 1 ⎞⎟
⎝ ⎠ (26)
w = h m12 + 1 or h m22 + 1
(27)
BIE 5300/6300 Lectures 177 Gary P. Merkley
h2 ⎡ h ⎤
hc = ⎢b + ( m1 + m2 ) ⎥ (28)
2A ⎣ 3 ⎦
h2 ⎡ 2h ⎤
h= ⎢
2A ⎣
b + ( m1 + m2 ) ⎥ (29)
3 ⎦
T
β
hc
h
h
⎛ 2h ⎞
β = 2cos −1 ⎜ 1 − ⎟ (30)
⎝ D⎠
D2
A= (β − sinβ ) (31)
8
or,
⎡ h−r ⎞ π⎤
A = (h − r) 2hr − h2 + r 2 ⎢sin−1 ⎛⎜ ⎟+ (32)
⎣ ⎝ r ⎠ 2 ⎥⎦
βD
Wp =
2 (34)
D⎛ β⎞
h= ⎜ 1 − cos ⎟
2⎝ 2⎠ (35)
D 2
h= − (hD − h2 )3 / 2 (36)
2 3A
hc = h − h (37)
beta 0.45
6.0 Top Width
Wetted Perimeter
5.0
0.35
Hydraulic Radius
Depth to Centroid
Beta, T, A, Wp
0.30
4.0
0.25
3.0
0.20
0.15
2.0
0.10
1.0
0.05
0.0 0.00
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Depth
r
r/2 h3
h2
h1
⎡ ⎛ 1 + 7 ⎞⎤
h1 = r ⎢1 − ⎜⎜ ⎟⎟ ⎥ (38)
⎢⎣ ⎝ 4 ⎠ ⎥⎦
then,
r
h2 = − h1
2 (39)
and,
r
h3 =
2 (40)
2
T = 2r 1 − ⎛⎜ 1 − ⎞⎟
h
(41)
⎝ r⎠
⎛ 2 ⎞ ⎛ 2
r⎞
⎛ r ⎞ r ⎛ r ⎞
T = ⎜ r − ⎜h − ⎟ − ⎟ − ⎜ − r − ⎜h − ⎟ + ⎟
2 2
(42)
⎜ ⎝ 2⎠ 2⎟ ⎜ ⎝ 2⎠ 2⎟
⎝ ⎠ ⎝ ⎠
or,
2
⎛ r⎞
T = 2 r − ⎜h − ⎟ − r
2
⎝ 2⎠ (43)
2
T = r 1 − ⎜⎛ 1 −
2h ⎞
⎟ (44)
⎝ r ⎠
and T = 0 when h = 0 or h = r
Cross-sectional area:
• For 0 ≤ h ≤ h1:
⎡ h−r ⎞ π⎤
A = (h − r) h ( 2r − h ) + r 2 ⎢sin−1 ⎛⎜ ⎟+ (45)
⎣ ⎝ r ⎠ 2 ⎥⎦
⎛ 1 ⎞
A = r 2 ⎜ α 2 − α1 − [cot (α1 ) − cot (α 2 )] ⎟ − A a + A b + A1 (46)
⎝ 4 ⎠
2
⎛r ⎞
r − ⎜ − h⎟
2
⎝2 ⎠
ϕ2 = (48)
r
−h
2
α1 = tan−1 ( ϕ1 )
(49)
α 2 = tan−1 ( ϕ2 )
(50)
2
1 ⎛⎜ 2 ⎛ r r ⎞⎟
2
⎞
Aa = r − ⎜ − h⎟ − (51)
ϕ2 ⎜ ⎝2 ⎠ 2⎟
⎝ ⎠
and,
2
1⎛ r⎞
Ab = ⎜ r 2 − h22 − ⎟ (52)
ϕ1 ⎝ 2⎠
y2 y2 ⎛ r 2⎞
A = 2∫ x dy + A1 = 2 ∫ 2
⎜ − + r − y ⎟ dy + A1 (53)
y1 y1 ⎝ 2 ⎠
y
⎡ 2 2 2 −1 ⎛ y ⎞ ⎤
2
A = ⎢ −r y + y r − y + r sin ⎜ ⎟ ⎥ + A1 (54)
⎣ ⎝ r ⎠ ⎦ y1
r C1
y1 = (56)
2
where,
⎛ 1+ 7 ⎞
C1 = 1 − ⎜⎜ ⎟⎟ (57)
⎝ 2 ⎠
and,
C1 ⎛⎜ C12 ⎞
⎟ − sin−1 ⎛⎜ C1 ⎞⎟
C2 = 1− 1− (58)
2 ⎜ 4 ⎟ ⎝ 2 ⎠
⎝ ⎠
⎛ 2⎞
2⎡ −1 ⎛ 2h − r ⎞ ⎤
⎛ r ⎞⎜ 2 ⎛ r⎞ ⎟
A = r ⎢C2 + sin ⎜ ⎟ ⎥ − ⎜ h − ⎟ ⎜ r − r − ⎜ h − ⎟ ⎟ + A1 (59)
⎣ ⎝ 2r ⎠⎦ ⎝ 2⎠ ⎝ 2⎠
⎝ ⎠
• Equation 59 is preferred over Eq. 46 because it is simpler and yields the same
result for h1 < h ≤ r/2
⎛ r⎞ r2 2h − r ⎞
A = ⎜ h − ⎟ h ( r − h ) + sin−1 ⎛⎜ ⎟ + A2 (60)
⎝ 2⎠ 4 ⎝ r ⎠
• For 0 ≤ h ≤ h1:
r3
h=
A
⎡π −1 ⎛ h ⎞⎤
⎢ 2 − sin ⎜ 1 − r ⎟ ⎥ −
⎣ ⎝ ⎠⎦
h(2r − h)
3A
(
hr − 2h2 + 3r 2 ) (61)
Mx = ∫ ( yx ) dy = ∫ y ⎛⎜ −r + 2 r 2 − y 2 ⎞⎟ dy
⎝ ⎠
Mx = −r ∫ y dy + 2∫ y r 2 − y 2 dy (62)
y2
⎡ ry 2 2 2 3/2⎤
Mx = ⎢ −
⎢⎣ 2 3
− r − y2( ) ⎥
⎥⎦ y
1
where y1 and y2 are integration limits, exactly as defined above for cross-
sectional area. Applying the integration limits:
2 3/2
r⎛ r⎞ 2⎡ 2⎤
Mx = r C3 − ⎜ h − ⎟ − ⎢r 2 − ⎜⎛ h − r ⎟⎞ ⎥
3
(63)
2⎝ 2⎠ 3⎣ ⎝ 2⎠ ⎦
where,
3/2
C12 2 ⎛ C12 ⎞
C3 = + ⎜1 − ⎟ (64)
8 3 ⎜⎝ 4 ⎟⎠
r Mx
hx = + (65)
2 Ax
⎛ 2⎞
2⎡ −1 ⎛ 2h − r ⎞ ⎤
⎛ r ⎞⎜ 2 ⎛ r⎞ ⎟
A x = r ⎢C2 + sin ⎜ ⎟⎥ − ⎜ h − ⎟ ⎜ r − r − ⎜ h − ⎟ ⎟ (66)
⎣ ⎝ 2r ⎠ ⎦ ⎝ 2⎠ ⎝ 2⎠
⎝ ⎠
⎛r M ⎞
A x ⎜ + x ⎟ + A1h1
h= ⎝ 2 Ax ⎠ (67)
A x + A1
r3 2
− [h(r − h)]
3/2
Mx = (68)
12 3
2
r ⎛ 2h − r ⎞
A x = ⎜⎛ h − ⎟⎞ h(r − h) + sin−1 ⎜
r
⎟ (69)
⎝ 2⎠ 4 ⎝ r ⎠
• The composite value of h must account for the calculations up to h = r/2, so for
depths from r/2 to r, the following area-weighted relationship is used to obtain the
exact depth to the area centroid:
⎛r M ⎞
A x ⎜ + x ⎟ + A 2h2
h= ⎝ 2 Ax ⎠ (70)
A x + A2
where A2 and h 2 are the values corresponding to h = r/2 (Eqs. 59 and 67)
Wetted perimeter:
• For 0 ≤ h ≤ h1:
⎛ h⎞
Wp = 2r cos−1 ⎜ 1 − ⎟ (71)
⎝ r⎠
where C1 is as defined in Eq. 57; and Wp1 is the wetted perimeter corresponding
to h = h1 (Eq. 71)
⎡ ⎛ 2h ⎞ π ⎤
Wp = r ⎢cos−1 ⎜ 1 − ⎟ − 2 ⎥ + Wp 2 (73)
⎣ ⎝ r ⎠ ⎦
0.9 4.5
0.8 4.0
Top width
0.7 3.5
Area
T/r, A/r , and hbar/r
Centroid depth
0.6 3.0
Wetted perimeter
Wp/r
0.5 2.5
2
0.4 2.0
0.3 1.5
0.2 1.0
0.1 0.5
0.0 0.0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Depth, h/r
• The increase in area with the standard horseshoe cross section (compared to a
circular section with a diameter of r) is only about 5.6% for a full section
Wp = b + 2h m2 + 1 (2)
A
Wp = − mh + 2h m2 + 1 (4)
h
2. Differentiate Wp with respect to h (A and m constant) and equate to zero (to
minimize Wp for a given area):
∂Wp −A
= 2
− m + 2 m2 + 1 = 0 (5)
∂h h
A = h2 ⎛⎜ 2 m2 + 1 − m ⎞⎟ (6)
⎝ ⎠
h2 ⎛⎜ 2 m2 + 1 − m ⎞⎟
R= ⎝ ⎠ (7)
b + 2h m2 + 1
5. Now, manipulate Eq. 7
bh + 2h2 m2 + 1 − bh − mh2
R= (8)
2
b + 2h m + 1
h ⎛⎜ b + 2h m2 + 1 ⎞⎟ − h ( b + mh )
R= ⎝ ⎠ (9)
b + 2h m2 + 1
hWp − A
R= = h−R (10)
Wp
A bh h
R= = = (12)
Wp b + 2h 2
8. For the most efficient trapezoidal section we will get Wp = T + b, where T is the
top width of flow (b+2mh), which for a symmetrical trapezoid means that the
length of each side slope (for depth h) is T/2. It also means that b = T/2, and this
corresponds to half of a regular six-sided polygon, or a hexagon. The interior
angle of a hexagon is 120 degrees, so m = 1/tan(60°) = 0.577.
h = Kx 2 (13)
h h h 2h3 / 2
A = ∫ x dh = ∫ dh = (14)
0 0 K 3 K
2
∑
2
Wp = lim ⎡⎣ f ( x + ∆x ) − f ( x ) ⎤⎦ + ( ∆x ) (15)
∆x →0
or,
1/ 2
⎛ 2 ⎞
Wp =
∫ ⎜ ⎛ df ⎞ + 1⎟
⎜ ⎜⎝ dx ⎟⎠
⎝
⎟
⎠
dx (16)
2 2
∆s ≈ ⎡⎣ f ( x + ∆x ) − f ( x ) ⎤⎦ + ( ∆x ) (17)
• Then,
h/K
Wp = ∫ 4K 2 x 2 + 1 dx (19)
0
• After integration (using integration tables), the wetted perimeter for half of the
parabolic section is:
h⎛h 1 ⎞ 1 ⎡ ⎛ h h 1 ⎞⎤
Wp = K + + ln ⎢ 2K ⎜ + + ⎟⎟ ⎥ (20)
K ⎜⎝ K 4K 2 ⎟⎠ 4K ⎢⎣ ⎜⎝ K K 4K 2 ⎠ ⎥⎦
• An analysis of the hydraulic radius for such a parabolic section shows that the
hydraulic radius decreases monotonically as K increases from an infinitesimally
small value, so there is no “most efficient” value of K
• Chow (1959) has some equations (exact and approximate) for various channel
section shapes, including the parabola defined in this case
Davis, C.V. and K.E. Sorensen (eds.). 1969. Handbook of applied hydraulics. McGraw-Hill Book
Company, New York, N.Y.
Hu, W.W. 1973. Hydraulic elements for USBR standard horseshoe tunnel. J. of the Transportation
Engrg. Div., ASCE, 99(4): 973-980.
Hu, W.W. 1980. Water surface profile for horseshoe tunnel. Transportation Engrg. Journal, ASCE,
106(2): 133-139.
Labye, Y., M.A, Olsen, A. Galand, and N. Tsiourtis. 1988. Design and optimization of irrigation
distribution networks. FAO Irrigation and Drainage Paper 44, Rome, Italy. 247 pp.
USBR. 1963. Linings for irrigation canals. U.S. Government Printing Office, Washington, D.C. 149 pp.
I. General
1. Kennedy Formula
2. Lacey Method
3. Maximum Velocity Method
4. Tractive-Force Method
1. Kennedy Formula
( )
C2
Vo = C1 havg (1)
where Vo is the velocity (fps); and havg is the mean water depth (ft)
C1 Material
0.56 extremely fine soil
0.84 fine, light sandy soil
0.92 coarse, light sandy soil
1.01 sandy, loamy silt
1.09 coarse silt or hard silt debris
Gary P. Merkley 192 BIE 5300/6300 Lectures
C2 Sediment Load
0.64 water containing very fine silt
0.50 clear water
Kennedy Formula
(clear water: C2 = 0.50)
1.2
C1 = 0.56
C1 = 0.84
1.0
C1 = 0.92
C1 = 1.01
C1 = 1.09
0.8
Velocity, V o (m/s)
0.6
0.4
0.2
0.0
0.0 0.5 1.0 1.5 2.0 2.5 3.0
Depth, db (m)
Figure 1. Velocity values versus water depth for the Kennedy formula with
clear water.
2. Lacey Method
• Developed by G. Lacey in the early part of the 20th century based on data from
India, Pakistan, Egypt and elsewhere
• Supports the “Lindley Regime Concept”, in which Lindley wrote:
“when an artificial channel is used to convey silty water, both bed and
banks scour or fill, changing depth, gradient and width, until a state of
balance is attained at which the channel is said to be in regime”
and, dm is the mean diameter of the bed and side slope materials (mm); V is the
mean velocity over the cross-section (fps); Wp is the wetted perimeter (ft); R is
the hydraulic radius (ft); S is the longitudinal bed slope (ft/ft); and Q is discharge
(cfs)
V = 0.00124 d11/
m
12
/S (7)
and,
V = 0.881 Q1/ 6d1/
m
12
(8)
• A weakness in the above method is that it considers particle size, dm, but
not cohesion & adhesion
1.346 0.75
V= R S (9)
Na
• This method gives the maximum permissible mean velocity based on the type of
bed material and silt load of the water
• It is basically a compilation of field data, experience, and judgment
• Does not consider the depth of flow, which is generally regarded as an important
factor in determining velocity limits
Velocity (fps)
Clear Water with
Material water colloidal silt
Fine sand, colloidal 1.5 2.5
Sandy loam, non-colloidal 1.75 2.5
Silt loam, non-colloidal 2 3
Alluvial silt, non-colloidal 2 3.5
Firm loam soil 2.5 3.5
Volcanic ash 2.5 3.5
Stiff clay, highly colloidal 3.75 5
Alluvial silt, colloidal 3.75 5
Shales and hard "pans" 6 6
Fine gravel 2.5 5
Coarse gravel 4 6
Cobble and shingle 5 5.5
Ws tanθ (11)
where θ is the angle of repose of the bed material and Ws is the weight of a soil
particle
40 Very angular
Moderately angular
38 Slightly angular
Slightly rounded
36
Angle of repose (degrees)
Moderately rounded
34 Very rounded
32
30
28
26
24
22
20
1 10 100
Soil particle size (mm)
aTbed (12)
where “a” is the effective particle area and Tbed (lbs/ft2 or N/m2) is the shear
stress exerted on the particle by the flow of water in the channel
Ws tan θ
Tbed = (14)
a
Ws sinφ (15)
where φ is the angle of the side slope, as defined in the figure below
⎛ 1⎞
φ = tan−1 ⎜ ⎟ (16)
⎝m⎠
• The force on the side slope particles in the direction of water flow is:
aTside (17)
where Tside is the shear stress (lbs/ft2 or N/m2) exerted on the side slope particle
by the flow of water in the channel
• The resistance to particle movement on the side slopes is due to the orthogonal
component of Eq. 15, Wscosφ, as shown in the above figure, multiplied by the
coefficient of friction, tan θ
• Thus, when particle movement is impending on the side slopes:
Ws
Tside = cos2 φ tan2 θ − sin2 φ (20)
a
Ws tan2 φ
Tside = cos φ tan θ 1 − (21)
a tan2 θ
or,
Ws sin2 φ
Tside = tan θ 1 − (22)
a sin2 θ
Tside
K= (23)
Tbed
where Tside and Tbed are the critical (threshold) values defined in Eqs. 4 & 9-11
• Then:
sin2 φ tan2 φ
K = 1− = cos φ 1 − (24)
sin2 θ tan2 θ
Step 0
Step 1
• Determine the critical shear stress, Tc (N/m2 or lbs/ft2), based on the type
of material and particle size from Fig. 3 or 4 (note: 47.90 N/m2 per lbs/ft2)
• Fig. 3 is for cohesive material; Fig. 4 is for non-cohesive material
• Limit φ according to θ (let φ ≤ θ)
Step 2
Step 3
Lean clay
Clay
Heavy clay
Sandy clay
T c (N/m2)
10
1
0.1 1.0 10.0
Void Ratio
Figure 4. Permissible value of critical shear stress, Tc, in N/m2, for cohesive
earthen material (adapted from USBR Hyd Lab Report Hyd-352).
About Figure 4: The “void ratio” is the ratio of volume of pores to volume of solids.
Note that it is greater than 1.0 when there is more void space than that occupied
by solids. The void ratio for soils is usually between 0.3 and 2.0.
Clear water
Low content of fine sediment
High content of fine sediment
Coarse, non-cohesive material
Tc (N/m2)
10
1
0.1 1.0 10.0 100.0
Figure 5. Permissible value of critical shear stress, Tc, in N/m2, for non-
cohesive earthen material (adapted from USBR Hyd Lab Report Hyd-352).
• The three curves at the left side of Fig. 5 are for the average particle diameter
• The straight line at the upper right of Fig. 5 is not for the “average particle
diameter,” but for the particle size at which 25% of the material is larger in size
• This implies that a gradation (sieve) analysis has been performed on the earthen
material
particle gradation
75% 25%
smallest largest
Clear water:
Low sediment:
High sediment:
Coarse material:
Tc = 2.17d0.75 (28)
0.153
⎛b⎞
Kbed ≅ 0.792 ⎜ ⎟ for 1 ≤ b / h ≤ 4
⎝h⎠ (29)
⎛b⎞
Kbed ≅ 0.00543 ⎜ ⎟ + 0.947 for 4 ≤ b / h ≤ 10
⎝h⎠
AB + C (b / h)
D
K side ≅ (30)
B + (b / h)
D
where,
A = −0.0592 (m ) + 0.347 (m ) + 0.193
2
(31)
−0.000311(m)
7.23
B = 2.30 − 1.56e (32)
−0.00143 (m )
5.63
C = 1.14 − 0.395e (33)
−3.29
−35.2 (m )
D = 1.58 − 3.06e (34)
• Equations 29 give Kbed to within ±1% of the values from the USBR data for 1 ≤
b/h ≤ 10
• Equations 30-34 give Kside to within ±2% of the values from the USBR data for 1
≤ m ≤ 3 (where the graphed values for m = 3 are extrapolated from the lower m
values)
• The figure below is adapted from the USBR, defining the inverse side slope, and
bed width
• The figure below also indicates locations of measured maximum tractive force on
the side slopes, Kside, and the bed, Kbed
• These latter two are proportional to the ordinate values of the above two graphs
(Figs. 6 & 7)
KTc
hmax = (35)
KbedγSo
KTc
hmax = (36)
K side γSo
• Note that K, Kbed, Kside, and So are all dimensionless; and Tc/γ gives units
of length (ft or m), which is what is expected for h
• The smaller of the two hmax values from the above equations is applied to
the design (i.e. the “worst case” scenario)
Step 5
• Take the smaller of the two depth, h, values from Eqs. 35 & 36
• Use the Manning or Chezy equations to calculate the flow rate
• If the flow rate is sufficiently close to the desired maximum discharge
value, the design process is finished
• If the flow rate is not the desired value, change the side slope, m, and or
bed width, b, checking the m and b/h limits you may have set initially
• Return to Step 3 and repeat calculations
• There are other ways to attack the problem, but it’s almost always iterative
Tc ≅ γhSo (37)
Carter, A.C. 1953. Critical tractive forces on channel side slopes. Hydraulic Laboratory Report No.
HYD-366. U.S. Bureau of Reclamation, Denver, CO.
Chow, V.T. 1959. Open-channel hydraulics. McGraw-Hill Book Co., Inc., New York, NY.
Davis, C.S. 1969. Handbook of applied hydraulics (2nd ed.). McGraw-Hill Book Co., Inc., New York,
NY.
Labye, Y., M.A. Olson, A. Galand, and N. Tsiourtis. 1988. Design and optimization of irrigation
distribution networks. FAO Irrigation and Drainage Paper 44, United Nations, Rome, Italy. 247
pp.
Lane, E.W. 1950. Critical tractive forces on channel side slopes. Hydraulic Laboratory Report No.
HYD-295. U.S. Bureau of Reclamation, Denver, CO.
Lane, E.W. 1952. Progress report on results of studies on design of stable channels. Hydraulic
Laboratory Report No. HYD-352. U.S. Bureau of Reclamation, Denver, CO.
Smerdon, E.T. and R.P. Beasley. 1961. Critical tractive forces in cohesive soils. J. of Agric. Engrg.,
American Soc. of Agric. Engineers, pp. 26-29.
• Design an earthen canal section in an alluvial soil such that the wetted
boundaries do not become eroded
• The canal will follow the natural terrain at an estimated So = 0.000275 ft/ft with a
preliminary design side slope of 1.5:1.0 (h:v)
• The bed material has been determined to be a non-cohesive “coarse light sand”
with an average particle diameter of 10 mm, 25% of which is larger than 15 mm
• Thus, 15 mm will be used to determine Tc in Fig. 5
• Tests have shown that the angle of repose for the bed material is approximately
34°, measured from the horizontal
• For the Manning equation, use a roughness value of 0.030
• Design the section using a trapezoidal shape with a bed width to depth ratio, b/h,
of between 1.0 and 5.0
• The design should also be such that the canal bed and sides do not erode
• Adjust the side slope if necessary, but keep it within the range 0.5:1 to 2.0:1 (h:v)
• Note that φ < θ must be true to allow for a stable side slope
• The critical tractive force can be estimated from Figure 5 (see above)
• The material is non-cohesive, and 25% of the particles are larger than 15 mm
• This gives Tc ≈ 16.3 N/m2 (0.34 lbs/ft2) for the 15 mm abscissa value
T sin2 φ
K = side = 1− 2
= 1 − 3.2sin2 φ (1)
Tbed sin θ
• Design requirements for this example call for a side slope between 0.5 & 2.0
• Actually, the range is restricted to 1.5 to 2.0 because the preliminary design
side slope of 1.5:1 corresponds to an angle φ = 33.7°
• This is less than the angle of repose, θ = 34°, but it is very close
• Make a table of K values:
m φ K
1.5 33.7° 0.122
1.6 32.0° 0.318
1.7 30.5° 0.419
1.8 29.1° 0.493
1.9 27.8° 0.551
2.0 26.6° 0.599
• From Figure 7 (see above), the maximum shear stress fraction for sides, Kside,
is approximately equal to 0.74 in the range 1.0 < (b/h) < 5.0, and for side
slopes from 1.5 to 2.0
• Take Kside as a constant for this problem: Kside ≈ 0.74
• The maximum shear stress fraction on the channel bed, Kbed, will fall on the
curve for trapezoidal sections, and will vary from 0.79 to 0.97 within the
acceptable range1.0 < (b/h) < 5.0
• Make a table of Kbed values according to b/h ratio (from Figure 6):
b/h Kbed
1 0.79
2 0.90
3 0.94
4 0.96
5 0.97
• In Table 4 it is seen that the bed width must be less than 35 ft, otherwise the
required b/h ratio will be greater than 5.0
• Also, it can be seen that bed widths less than 10 ft will have problems
because the b = 10 and m = 1.5 combination gives b/h < 1.0
• Taking Kside from Figure 7, the maximum allowable depth according to the
tractive force method for side slopes is:
m φ hmax
1.5 33.7° 3.3
1.6 32.0° 8.5
1.7 30.5° 11.2
1.8 29.1° 13.2
1.9 27.8° 14.8
2.0 26.6° 16.0
• From the above table it is seen that the side slope must now be between 1.6
and 2.0, otherwise the required flow depths will exceed the limit imposed by
the tractive force method for side slopes
Again, taking Kbed from Figure 6, the maximum allowable depth according to the
tractive force method for the channel bed is:
side slope, m
b (ft)
1.5 1.6 1.7 1.8 1.9 2.0
10 n/a 8.00 10.50 12.40 13.80 15.00
15 n/a 7.20 9.70 11.20 12.50 13.60
20 n/a 6.80 8.90 10.60 11.90 12.90
25 n/a 6.60 8.70 10.30 11.50 12.50
30 n/a 6.50 8.60 10.10 11.30 12.30
Note: bold depth values are not acceptable.
• The allowable depths according to the bed criterion are all less than the
allowable depths (for the same m values) from the side slope criterion
• Therefore, use the bed criterion as the basis for the design
• The permissible values for m = 2.0 are all much higher than those from the
Manning equation
• Permissible values for m = 1.9, 1.8, and 1.7 are also higher than those
from the Manning equation
• For m = 1.6, only the b = 30 ft bed width is within limits (less than that
required by the Manning equation for 650 cfs)
3. Kennedy Formula
0.64
Vo = CDm = 0.92 ( 7.91) = 3.5 fps (5)
• This is more than the tractive force design velocity of 2.5 fps. (OK)
4. Lacey Method
• This is also more than the tractive force design velocity of 2.5 fps. (OK)
• From Table 1, the maximum permissible velocity for “coarse light sand”, say
“fine gravel”, is 5.0 fps for water transporting colloidal silt
• For the same material and clear water, the maximum is 2.5 fps -- a large
difference based on a fairly subjective determination
• Also, from the given information of this example problem, an exact match the
materials listed in Table 1 is not possible
• From Table 2, for “coarse sand”, the maximum permissible velocity is 1.8 fps
• Design an earthen canal section using the tractive force method such that the
bed and side slopes are stable
• The design flow rate is 90 m3/s and the water is clear
• The earthen material is non-cohesive fine sand with average particle size of 0.5
mm and an angle of repose of 27°
• Assume that the inverse side slope is fixed at m = 3.0 for this design. Use a
Manning’s n of 0.02
• Determine the minimum bed width, b
• Determine the maximum longitudinal bed slope, So
• Recommend a freeboard value for the design discharge
• Make a sketch to scale of the channel cross section and the water surface at the
design discharge
• From Figure 5, for non-cohesive material, with an average particle size of 0.5
mm and clear water, Tc ≈ 0.03 lb/ft2
• Arbitrarily limit b/h to a minimum of 1 and maximum of 9 (note that b/h < 1 is
usually not reasonable or feasible for an earthen channel)
• This is a very wide range of b/h values anyway
• The table below shows Kbed and Kside for 1 ≤ b/h ≤ 9
• The Kside values are extrapolated from the curves for 1 ≤ m ≤ 2 because in our
case, m = 3
BIE 5300/6300 Lectures 215 Gary P. Merkley
b/h Kbed Kside
1 0.79 0.78
2 0.90 0.81
3 0.94 0.83
4 0.97 0.83
5 0.98 0.83
6 0.98 0.84
7 0.99 0.84
8 0.99 0.84
9 1.00 0.84
• Calculate uniform flow depths for various b and So values, using n = 0.02 and
the Manning equation
• Note that b will have to be fairly large because it is an earthen channel and
the design discharge is rather large itself
• The uniform flow calculations are done in a computer program and the results
are given in the table below
Uniform flow depths (in ft) for varying b & So (Manning; n = 0.02)
Longitudinal bed slope, So
b (ft)
0.00001 0.00002 0.00003 0.00004 0.00005 0.00006 0.00007 0.00008 0.00009 0.00010
30 23.750 20.379 18.609 17.437 16.573 15.894 15.340 14.874 14.473 14.122
40 22.479 19.161 17.426 16.278 15.434 14.773 14.233 13.780 13.390 13.050
50 21.317 18.063 16.367 15.250 14.429 13.787 13.264 12.825 12.448 12.119
60 20.256 17.074 15.423 14.337 13.541 12.920 12.415 11.991 11.628 11.312
70 19.289 16.184 14.579 13.527 12.757 12.158 11.671 11.263 10.913 10.609
80 18.406 15.382 13.825 12.806 12.063 11.485 11.016 10.623 10.287 9.995
90 17.602 14.659 13.149 12.164 11.446 10.889 10.437 10.059 9.737 9.456
100 16.867 14.005 12.542 11.589 10.896 10.359 9.923 9.560 9.250 8.980
110 16.194 13.413 11.994 11.073 10.404 9.885 9.465 9.115 8.816 8.557
120 15.578 12.874 11.499 10.607 9.960 9.459 9.054 8.717 8.429 8.179
• Calculate b/h values for each of the uniform-flow depths in the above table
• Values in the following table are shown in bold where greater than the
specified maximum of 9
• The following two tables are interpolated Kbed and Kside values
• Values shown in bold (following two tables) are greater than 1.0 and
considered to be infeasible
• Using the interpolated max shear stress fractions, apply the following
equations to calculate maximum water depth:
and,
KTc
hmax =
K side γSo
where the smaller of the two values is taken for the design
• Bold values in the following two tables have a uniform flow depth which
exceeds the calculated maximum depth, and are removed from consideration
• It is clear that the bed slope must be less than So = 0.00003 ft/ft
• This is a very small slope
• But there is a large range of possible bed widths
• The lower b values will result in great depths, and the higher b values will take
up a wide “swath” of land. Most feasible will probably be a compromise
between these extremes, perhaps 60 < b < 90 ft.
• To complete one design possibility, recommend b = 80 ft & So = 0.00002 ft/ft
• This corresponds to a uniform flow depth of h = 15.4 ft (see above)
• Using the freeboard curves from the previous lecture, with Q = 3,178 cfs, the
height of the bank above the water surface should be about 4.5 ft
• Then, the depth of the channel is 15.4 + 4.5 = 19.9 ft. Round up to 20 ft.
20.0 ft 15.4 ft 1
3
80.0 ft
References & Bibliography
Carter, A.C. 1953. Critical tractive forces on channel side slopes. Hydraulic Laboratory Report No.
HYD-366. U.S. Bureau of Reclamation, Denver, CO.
Chow, V.T. 1959. Open-channel hydraulics. McGraw-Hill Book Co., Inc., New York, NY.
Davis, C.S. 1969. Handbook of applied hydraulics (2nd ed.). McGraw-Hill Book Co., Inc., New York,
NY.
Labye, Y., M.A. Olson, A. Galand, and N. Tsiourtis. 1988. Design and optimization of irrigation
distribution networks. FAO Irrigation and Drainage Paper 44, United Nations, Rome, Italy. 247
pp.
Lane, E.W. 1950. Critical tractive forces on channel side slopes. Hydraulic Laboratory Report No.
HYD-295. U.S. Bureau of Reclamation, Denver, CO.
Lane, E.W. 1952. Progress report on results of studies on design of stable channels. Hydraulic
Laboratory Report No. HYD-352. U.S. Bureau of Reclamation, Denver, CO.
Smerdon, E.T. and R.P. Beasley. 1961. Critical tractive forces in cohesive soils. J. of Agric. Engrg.,
American Soc. of Agric. Engineers, pp. 26-29.
• The most common and (usually) most important reason is to reduce seepage
losses (and this may be for a variety of reasons)
• The assumption that lining will solve seepage problems is often unfounded,
simply because poor maintenance practices (especially with concrete linings) will
allow cracking and panel failures, and tears and punctures in flexible membranes
• Seepage losses from canals can be beneficial in that it helps recharge aquifers
and makes water accessible to possibly larger areas through groundwater
pumping. The extent of aquifers is more continuous than that of canals and
canal turnouts. But, pumping ($energy$) is usually necessary with groundwater,
unless perhaps you are downhill and there is an artesian condition (this is the
case in some places).
• “Administrative losses” and over-deliveries can add up to a greater volume of
water than seepage in many cases (that means that canal lining is not always the
most promising approach to saving water in the distribution system)
• Sometimes, only the bottom of a canal is lined when most of the seepage has
been found to be in the vertical direction
• It may be advisable to perform soil compaction testing under concrete linings to
determine if steps need to be taken to avoid subsequent settlement of the canal
• Lining to decrease maintenance costs can backfire (costs may actually increase)
• Concrete pipe is an alternative to lined canals, but for large capacities the pipes
tend to cost more
• Many billions of dollars have been spent world-wide during the past several
decades to line thousands of miles of canals
BIE 5300/6300 Lectures 221 Gary P. Merkley
II. Some Types of Lining and Costs
1. Soil
• Lime
• Bentonite clay
• “High-swell” Bentonite & coarse clay or other “bridging material”
• Geosynthetic clay liner (“Bentomat”)
• Soil mixed with portland cement
• Thin compacted earth (6 - 12 inches)
• Thick compacted earth (12 - 36 inches)
5. Plastic
6. Asphalt (bituminous)
7. Synthetic Rubber
Earthen Linings
1. protection
• ozone “attack” and UV radiation
• puncture due to maintenance machinery
and animal feet, etc.
• vandalism
2. anchoring
• flotation of the lining (high water table)
• resist gravity force along side slope
• wind loading
• Plastic linings are typically 10 to 20 mil (0.010 to 0.020 inches, or 0.25 to 0.5 mm)
-- thicker membranes are usually recommendable because of increased
durability, and because the overall installation costs only increase by about 15%
for a doubling in thickness
• The USBR previously used 10 mil plastic linings, but later changed most
specifications to 20 mil linings
• Plastic linings of as low as 8 mil (PE), and up to 100 mil have been used in
canals and retention ponds
• Low density polyethylene (LDPE) is made of nearly the same material as
common trash bags (such as “Hefty” and “Glad” brands), but these trash bags
have a thickness of only 1.5 - 2 mils
• Plastic canal linings are manufactured in rolls, 5 to 7 ft in width, then seamed
together in a factory or shop to create sheets or panels of up to 100 ft (or more)
in width
• Rubber membrane linings can have a thickness ranging from 20 to 60 mil
• Flexible plastic and synthetic rubber linings are susceptible to damage
(punctures, tears) both during and after installation
• Flatter than normal side slopes (say 3:1) are sometimes preferred with plastic
linings to help prevent the possible migration of the lining down the slope, and to
help prevent uncovering of the lining by downward movement of soil
Gary P. Merkley 226 BIE 5300/6300 Lectures
• Correctly installed plastic and synthetic rubber linings are completely impervious,
provided they have not been damaged, and provided that the flow level in the
channel does not exceed the height of the lining
• Plastic liners will “age” and lose plasticizer, causing a loss of flexibility and
greater potential for damage. Increased plasticizer during fabrication has been
shown to be effective in this regard
plas-ti-ciz-er (plas'tuh sie zuhr) n. a group of substances that are used in plastics to
impart viscosity, flexibility, softness, or other properties to the finished product
• Some canals in central Utah have had plastic linings for more than 30 years, and
most of it is still in good condition (measured seepage is essentially zero in the
lined sections, but some evidence of puncture/tearing has been found)
• Plastic lining material is sometimes used to retrofit existing concrete-lined canals
after the concrete lining canal fails and or continued maintenance is considered
infeasible
Preparing a canal section for buried
membrane lining (courtesy R.W. Hill)
• In the former Soviet Union, thin PE lining has been placed under precast slabs of
concrete lining in some canals
• In India, some canals have been lined with plastic (PE) on the bottom, and bricks
or tiles on the side slopes
• Polyethylene (PE) is the lowest cost geomembrane material, PVC is next lowest.
Some newer materials such as polyolefin are more expensive
• Exposed membrane linings have been tried, but tend to deteriorate quickly for
various reasons
• Exposed membrane linings have recently been installed in some full (operating)
canals
Fly Ash
• Fly ash is a fine dust particulate material (roughly the size of silt) produced by
coal-burning power plants, usually in the form of glassy spheres
• Fly ash contains mostly SiO2 (silicon dioxide), Al2O3 (aluminum oxide), and Fe2O3
(iron oxide)
• Fly ash is often mixed with soil to form canal linings, the mixture being more
dense and less permeable than soil alone
• Fly ash is sometimes mixed with both soil and portland cement
I. Introduction
980
970
960
950
Relative Elevation (m)
940
930
910
900
890
880
870
Cebadas River
860
0 200 400 600 800 1000
Distance (m)
1. Pipe
• A siphon in the Narmada canal in India was recently built to carry 40,000 cfs
(1,100 m3/s) across a depression; it has multiple rectangular conduits in parallel
Gary P. Merkley 230 BIE 5300/6300 Lectures
• The Central Arizona Project (CAP) has four large siphons with 21-ft diameter pre-
stressed concrete pipe; some of these have already been replaced because of
corrosion and subsequent structural failure
2. Transitions
Concrete pipe repairs on
• Transitions for siphons are the an inverted siphon
inlet and outlet structures
• Most siphons have inlet and
outlet structures to reduce head
loss, prevent erosion and piping,
and maintain submergence
(“hydraulic seal”)
• It can be very hazardous to omit
inlet and outlet structures
because these locations are
often at steep embankments that
would erode very quickly in the
event of a breach or overflow
• An emergency spillway is
sometimes located just upstream
of a siphon inlet
• Transitions in smaller siphons may be of the same design at the inlet and outlet,
and standard designs can be used to reduce costs
• With larger siphons, it may be desirable to do a “site-specific” transition design,
possibly with different designs for the inlet and outlet
• Operation of a gate at the entrance of a siphon may ensure hydraulic seal, but
will not ensure full pipe flow in the downhill section(s) of pipe at discharges below
the design value
• It is not common to install a gate at the outlet of a siphon (this is never done in
USBR designs)
4. Collars
• Collars may be used, as with culverts, to prevent “piping” and damage due to
burrowing animals
• However, with siphons they are not always necessary because the inlet and
outlet structures should be designed and built to direct all water into the entrance
and exit all water to the downstream channel
BIE 5300/6300 Lectures 231 Gary P. Merkley
5. Blowoff and Vent Structures
• A “blow-off” structure is a valved outlet on top of the pipe at a low point in the
siphon
• Smaller siphons often do not have a blow-off structure
• These structures are used to help drain the siphon in an emergency, for routine
maintenance, or for winter shut-down
• Blow-off structures may have man holes (or “person access holes”) on large
siphons to allow convenient entry for manual inspection
• Blow-off structures can be used to periodically remove sediment from the pipe
• Continuous-acting vents are installed in some siphons to remove air during
operation (this is usually an after thought when “blow-back” (surging) problems
are manifested)
• Others have simple vertical pipes to vent air from the pipe, but these can have
the opposite effect
• Air can become trapped, especially in long siphons, during filling; filling of the
siphon should be gradual, not sudden
• Some blow-off structures are of the “clamshell” type, with top and bottom leafs off
of a tee at the bottom of the siphon
• Clamshell blow-offs are not so common, but have definite advantages in terms of
avoiding cavitation (handling high velocity flows at large heads) compared to
butterfly valves, for example
6. Canal Wasteways
7. Safety Features
• The design of siphons has many similarities to the design of culverts; however,
unlike the design of culverts:
• USBR siphon designs are generally for an assumed 50-year useful life
2. Head Losses
• Culverts are usually designed for full pipe flow from inlet to outlet (the outlet is
almost always submerged, and it is highly unlikely that open channel flow would
prevail throughout the siphon – the change in elevation is usually too great)
• Total head loss is the sum of: inlet, outlet, pipe, and minor head losses
• Convergence losses at the entrance are usually negligible, but divergence losses
at the exit (outlet) can be significant
• Most of the loss in a siphon is from pipe friction
• Outlet losses are typically about twice the inlet losses
• Minor losses in pipe bends are usually insignificant
• Most siphons are designed to carry the full design discharge without causing an
“M1” profile (backwater) in the upstream channel – to achieve this, it is important
to carefully estimate head losses
• If the total siphon head loss at the design discharge exceeds available head
(difference in upstream and downstream canal elevations and water depths) the
siphon will operate at a lower discharge and cause the upstream water level to
increase
• A hydraulic jump in the descending part of the siphon (upstream side) will greatly
increase the head loss, and may cause problems of surging and “blow-back”
• Blow-back occurs when air is entrained into the water due to a hydraulic jump in
the pipeline, or due to movement of a hydraulic jump within the pipe; water and
air periodically surge backwards through the inlet
3. Hydraulic Seal
• The “hydraulic seal” is the minimum required upstream head, relative to the
upper edge of the siphon pipe at the siphon inlet, to prevent the entrainment of
air at that location
• The hydraulic seal recommended by the USBR is equal to 1.5∆hv, where ∆hv is
the difference in velocity heads in the upstream open channel and in the pipe
(when flowing full)
• For a more conservative value of the hydraulic seal, use 1.5hpipe, where hpipe is
the velocity head in the siphon pipe when flowing full
hydraulic seal
siphon
inlet
4. Design Steps
• What is the maximum pressure in the inverted siphon pipe? This must be
calculated at the design stage so that a suitable pipe is selected.
• The maximum pressure is equal to the maximum of:
• In any case, the maximum pressure will be at, or very near, the location of
minimum elevation in an inverted siphon
• If a gate or valve is at the siphon exit, and it is completely closed, the maximum
pressure will be according to #2, without subtracting friction loss (i.e. full pipe,
zero flow condition); otherwise, the zero flow condition pertains to #1
• Note that the above assumes that an open channel is upstream of the siphon
entrance, and an open channel is at the siphon exit
• Note that in order to calculate friction loss, you need to assume a pipe diameter
(ID) and a pipe material
• Due to possible water surging in the pipe, the pressure may be somewhat higher
than that calculated above, so consider adding a 10% safety factor
USBR. 1978. Design of small canal structures. U.S. Government Printing Office, Washington, D.C.
435 pp.
I. Cross-Drainage Structures
• Cross-drainage is required when a canal will carry water across natural drainage
(runoff) channels, or across natural streams; otherwise, the canal may be
damaged
• In some cases, cross-drainage flows are collected in a small channel paralleling
the canal, with periodic cross-drainage structures over or under the canal; this is
especially prevalent where there are poorly defined natural drainage channels
• In culvert design for carrying runoff water, usually one of the big questions is
what the capacity should be
• When the canal capacity is less than the natural channel capacity, it may be
economical to build an inverted siphon so the canal crosses the natural channel
• With siphon crossings, it is not nearly as important to accurately estimate the
maximum flow in the natural channel because the structure is for the canal flow
• In other cases, it may be more economical to provide cross-drainage by building
a culvert to accommodate natural flows after the canal is constructed
• In these cases, the cross-drainage structure does one of the following:
1. Culverts
• These are often appropriate where natural flows cross a fill section of the
canal
• Culverts may tend to clog with weeds, debris, rock, gravel, and or
sediments, especially at or near
the inlet
2. Over-chutes
3. Drain Inlets
• With these structures, the flow of the natural channel is directed into the
canal
• These may be appropriate where the natural flows are small compared
to the canal capacity, and or when the natural flows are infrequent
• These may be appropriate when the canal traverses a steep slope, and
cross-drainage might cause excessive downhill erosion, compromising
the canal
• These may be less expensive than over-chute or culvert structures, but
may require more frequent maintenance of the canal
• Drain inlets may be problematic insofar as rocks, sediment and other
debris can clog the inlet and or fill the canal near the inlet, obstructing
the canal flow
II. Alignment
• Align the culvert along natural open channels where possible so that the natural
runoff pattern is not disturbed any more than necessary
• If the natural drainage channel is not perpendicular to the canal, it is best to have
a skewed alignment of the culvert
• One or more bends in the culvert can be used to help follow the natural channel,
especially in longer culverts
• If there is no apparent natural runoff channel, consider using the shortest straight
path from inlet to outlet
• In some cases it may be unnecessary or undesirable to follow a natural channel
• Knowing the inlet and outlet locations will determine the length and slope of the
culvert
• The invert of the inlet and outlet should correspond approximately to the natural
ground surface elevations at the two respective locations -- otherwise,
sedimentation and or erosion will likely occur, requiring maintenance
• However, a compound slope may be needed if:
1. With energy
dissipation structure
2. Without energy
dissipation structure
• Culverts are typically designed for full- Culvert with collars (USBR)
pipe flow in the barrel at the design
discharge value
• This means that pressurized pipe flow is
impending at the design discharge, but
at lower flow rates open-channel flow
exists in the barrel
• The upper limit on barrel velocity is
usually specified at about 10 fps, or
perhaps 12 fps with an energy
dissipation structure at the outlet
• For full pipe flow without inlet and outlet
structures, in which case the culvert is
simply a buried pipe, you can use a limit
of 5 fps
• Discharge capacity can be checked using the Manning (or Chezy) equation for a
circular section running full (again, impending pressurization)
• For new pre-cast concrete pipe, the Manning “n” value is about 0.013, but for
design purposes you can use a higher value because the pipe won’t always be
new
• The head loss through a typical inlet structure with inlet control can be estimated
as a “minor loss” by:
V2
hf = K (2)
2g
where the coefficient K may vary from 0.05 for a smooth, tapered inlet transition,
flush with the culvert barrel, to 0.90 for a projecting, sharp-edged barrel inlet
• Note that the inlet and or outlet losses may or may not be “minor” losses when
dealing with culverts, especially when the barrel is short
• For outlet control, the head loss is estimated as in the above equation for inlet
control, except that there will also be expansion losses downstream
• For barrel control, the head loss is the sum of the inlet, barrel, and outlet losses
USBR. 1978. Design of small canal structures. U.S. Government Printing Office, Washington, D.C.
435 pp.
• Design a concrete culvert using the procedures given by the USBR (Design of
Small Canal Structures, USBR 1978)
• The culvert will go underneath a concrete-line canal as shown in the figure below,
perpendicular to the canal alignment (shortest path across)
• The outside slope of the canal banks is 1.5:1.0 on both sides (H:V)
• The inside side slope of the concrete lining is 1:1 (both sides)
• The concrete lining thickness is 0.05 m
• Elevation of the top of the canal banks is given as 134.00 m, with elevations of
the original ground surface at intersections with canal banks given in the figure
• The berm on both banks is 3.0 m wide
• The depth of the canal from the bottom to the top of the berms is 4.0 m, with the
upper 30 cm unlined
• The barrel will be pre-cast circular concrete pipe, and the inlet and outlet
structures can be specified as Type 1, 2, 3, or 4, as given by the USBR
• The available concrete pipe has an inside diameter of: 60, 70, 80, and 90 cm
• You must select from one of these diameters for the culvert barrel
• Length of the pipe is 1.5 m per section
• The upstream and downstream natural channels are wide and poorly defined in
cross-section, and no effort will be made to develop prismatic channels upstream
of the culvert inlet, nor downstream of the culvert outlet
• The horizontal distance from the culvert inlet to the pipe outlet is (from left to
right):
1.5*(134.00-132.12)+3.0+4.0+5.5+4.0+3.0+1.5*(134.00-128.06) = 31.23 m
4Q 4(2.4)
D= = = 1.01 m (1)
πV π(3.0)
• The largest available pipe size is 90 cm; therefore, two or more pipes are needed
in parallel for this culvert design
• For half the design discharge, 1.2 m3/s, the required diameter is:
4Q 4(1.2)
D= = = 0.71 m (2)
πV π(3.0)
• Then, we can use two 80-cm ID pipes at a full pipe flow velocity of 2.39 m/s
• It would also be possible to use three 60-cm ID pipes at a full pipe flow velocity of
2.83, which is closer to the maximum velocity of 3.0 m/s
• But, choose two 80-cm ID pipes because it will simplify installation, require less
excavation work, and may reduce the overall pipe cost
• With the full pipe flow impending, the energy loss gradient can be estimated by
the Manning equation for open-channel flow
• Use a Manning n value of 0.015 for new concrete pipe, with a slight safety factor
for aging (typical useful life is estimated as 40 to 50 years)
• Use half the design discharge because two 80-cm ID pipes will be installed in
parallel
2 2 4/3
Sf =
Q2n2 Wp4 / 3
=
(1.2 ) ( 0.015 ) ( 2.51)
= 0.011 m / m (3)
A10 / 3 ( 0.503 )10 / 3
Q 2T
Fr2 = = 1.0 (4)
gA 3
⎛ 2h ⎞
β = 2cos−1 ⎜ 1 − ⎟ (5)
⎝ D⎠
⎛β⎞ βD
T = D sin ⎜ ⎟ and, Wp = (6)
⎝2⎠ 2
D2
A= (β − sin β ) (7)
8
• Solve for depth, h, such that Fr2 = 1.0 for Q = 1.2
m3/s and D = 0.80 m
• Using the Newton method, hc = 0.663 m
2 2 4/3
(1.2 ) ( 0.015 ) (1.83 )
( Sf )crit = = 0.011 m / m (8)
( 0.445 )10 / 3
• This is essentially the same loss gradient as for impending full pipe flow, but
note that the critical flow depth is 83% of the pipe ID
• If the slope of the pipe is 0.011 m/m or greater, critical flow can occur
• The upstream pipe will be situated so as to begin at Elev 132.12, and just
clear the canal base at the left side
• The elevation of the canal base is 134.00 - 4.0 = 130.00 m
• The horizontal distance from the culvert inlet to the left side of the canal base
is 1.5*(134.00-132.12)+3.0+4.0 = 9.82 m
• The pipe must drop at least 132.12-130.00+0.05+0.2 = 2.37 m over this
horizontal distance
• This corresponds to a pipe slope of 2.37/9.82 = 0.24 m/m (24%)
• The critical slope is 1.1% (< 24%), so the culvert will have inlet flow for the
design discharge (and for lower discharge values)
• At the design discharge, we will expect a hydraulic jump in the pipe upstream
of the bend, because the pipe slope will be lower in the remaining
(downstream) portion of the culvert
• It is necessary to check that the slope of the downstream pipe does not
exceed the critical slope
• The downstream part of the culvert barrel will travel a horizontal distance of
31.23 - 9.82 = 21.41 m
• The change in elevation over this distance will be 129.75 - 128.06 = 1.69 m
• Then, the slope of the downstream part of the pipe will be 1.69/21.41 = 0.079
m/m (7.9%)
• This slope is greater than the critical slope, and is not acceptable because it
would cause supercritical flow throughout, from inlet to outlet, causing erosion
downstream (unless erosion protection is used)
• Use the USBR recommended downstream slope of 0.005 (0.5%), which is
less than the critical slope of 1.1%
• To accomplish this, the upstream (steep) portion of the culvert pipe can be
extended further in the downstream direction (to the right)
• Equations can be written for the tops of the upstream and downstream pipes:
• Use the standard USBR culvert design, calling for two collars under the downhill
canal bank, and one collar under the uphill bank
• The distance between the two collars under the downhill bank will be
approximately 3.0 m plus 2.0 ft, or 3.61 m
• Then, the Y value is X/1.2, or Y = 3.61/1.2 = 3.0 m
• This gives very large collars
• There are other methods for determining collar size, but in this case the Y value
can be taken as 1.0 m, which would be only about one meter below the uphill
canal berm
• More information about the site and soil would be required to verify the adequacy
of the collar design
• Many culverts don’t have collars anyway, and in some cases they are
problematic because they impede effective soil compaction – “piping” may be
worse with the collars
USBR. 1978. Design of small canal structures. U.S. Government Printing Office, Washington, D.C.
435 pp.
I. Open-Channel Definitions
Canal Open channel of mild slope (subcritical flow) and relatively long;
could be lined or unlined
Flume A channel built above the natural ground surface, usually of mild
slope and rectangular or circular cross section, crossing a
depression or running along the contour of a hillside
Chute Like a flume, but having a steep slope (supercritical flow; Fr2 > 1.0)
and usually with some type of energy dissipation structure on the
downstream side (outlet)
Culvert One or more circular or rectangular pipes/conduits in parallel,
crossing under a road, canal, or other structure, either flowing full
(pressurized) or part full (open-channel flow); often used as a
cross-drainage structure
Prismatic This means a constant cross-sectional shape with distance,
constant and uniform bed slope, and straight channel alignment,
applied to any of the above
• The classification of the hydraulic behavior of culverts can take several forms
• Three primary groupings can be used to describe the hydraulics of culverts
• These groups are based on the three parts of the culvert that exert primary
control on culvert performance and capacity:
• Usually, one of these three primary controls determines the performance and
capacity of the culvert
• An example of this is a projecting, square-edged inlet with the barrel on a
steep slope (Fr2 > 1.0) and flowing partly full: if the inlet is not submerged, the
upstream water level (headwater) is determined by the inlet characteristics
alone
• In other cases, two or even all three primary controls can simultaneously
affect the performance and discharge capacity
• For example, if the inlet and outlet are submerged and the barrel is full, then a
designer can determine the headwater elevation by adding the outlet losses,
the barrel friction losses, and the inlet losses to the tailwater (downstream)
elevation (assuming the same specific energy in both the upstream &
downstream open channels)
• For example, each type of inlet will have a different effect on the culvert
performance
• Many of the items listed in the table are inter-related, which further
complicates an already difficult problem
• For instance, the depth of the flow just inside the culvert entrance depends on
the inlet geometry
• If this depth is less than the normal depth of flow, a water surface profile must
be computed beginning with the contracted depth of flow to determine the
flow depth at the culvert outlet
BARREL CONTROL
C. Length
1. Short
2. Long
D. Slope
1. Mild
i. Barrel slope less than critical slope
a. Part full, normal depth greater than critical depth
b. Full, not applicable
ii. Barrel slope less than friction slope
a. Part full, depth increases along barrel
b. Full, barrel under pressure
2. Steep
i. Barrel slope steeper than critical slope
a. Part full, normal depth less than critical depth
b. Full, not applicable
ii. Barrel slope steeper than friction slope
a. Part full, depth decreases along barrel (increases if
the inlet causes the depth inside the inlet to be less
than normal depth)
b. Full, barrel under suction
E. Discharge
1. Partially Full (Free-Surface Open-Channel Flow)
2. Slug and Mixture (Unsteady Flow)
3. Full (Closed Conduit Flow)
OUTLET CONTROL
• If the computed outlet depth exceeds the barrel height, the culvert is hydraulically
long, the barrel will fill, and the control will be the inlet, the barrel, and the outlet
• If the computed depth at the outlet is less than the barrel height, the barrel is only
part full and the culvert is considered hydraulically short, will not fill, and the
control will remain at the inlet
• Whether a culvert is hydraulically long or short depends on things such as the
barrel slope and the culvert material
• For example, changing from corrugated pipe to concrete pipe can change the
hydraulic length of a culvert from long to short
• A similar effect could result from a change in the inlet geometry
• Flow in culverts is also controlled by the hydraulic capacity of one section of the
installation
• The discharge is either controlled at the culvert entrance or at the outlet, and is
designated inlet control and outlet control, respectively
• In general, inlet control will exist as long as the ability of the culvert pipe to carry
the flow exceeds the ability of water to enter the culvert through the inlet
• Outlet control will exist when the ability of the pipe barrel to carry water away
from the entrance is less than the flow that actually enters the inlet
• The location of the control section will shift as the relative capacities of the
entrance and barrel sections change with increasing or decreasing discharge
• This means that it cannot be assumed that a given culvert will always operate
under the same hydraulic regime
Inlet Control
• Inlet control means that the discharge capacity of a culvert is controlled at the
culvert entrance by the depth of headwater and the entrance geometry, including
the barrel shape and cross-sectional area
• With inlet control, the roughness and length of the culvert barrel, as well as outlet
conditions (including depth of tailwater), are not factors in determining culvert
capacity
• An increase in barrel slope reduces the headwater (inlet) depth, and any
correction for slope can be neglected for conventional or commonly used culverts
operating under inlet control
Barrel Control
• Under barrel control, the discharge in the culvert is controlled by the combined
hydraulic effects of the entrance (inlet), barrel length & slope, and roughness of
the pipe barrel
• The characteristics of the flow do not always identify the type of flow
• It is possible, particularly at low flows, for length, slope, and roughness to control
the discharge without causing the pipe to flow full
Gary P. Merkley 252 BIE 5300/6300 Lectures
• But, this is not common at design discharges for most culverts
• The usual condition for this type of flow at the design discharge is one in which
the pipe cross section flows full for a major portion (but not all) of the length of
the culvert
• The discharge in this case is controlled by the combined effect of all hydraulic
factors
Outlet Control
• Culverts flowing with outlet control can have the barrel full of water or partly full
for either all or part of the barrel length
• If the entire cross section of the barrel is filled with water for the total length of the
barrel, the culvert is said to be flowing full
Type I Flow Inlet control. Critical depth occurs at or near the inlet:
(a) The slope of the culvert barrel is greater than the critical slope
(b) The downstream water surface elevation is lower than the elevation of the
water surface where critical flow occurs at the inlet
(c) The upstream water depth is less than approximately 1.5 times the barrel
height (or diameter)
Type II Flow Outlet control. Critical depth occurs at or near the outlet:
(a) The slope of the culvert barrel is less than critical slope
(b) The downstream water surface elevation is lower than the elevation of the
water surface where critical flow occurs at the outlet
(c) The upstream water depth is less than approximately 1.5 times the barrel
height (or diameter)
Type III Flow Barrel control. Subcritical barrel flow, a gradually-varied flow
profile:
(a) The downstream water surface elevation is less than the height (or
diameter) of the barrel, but is more than the critical depth at the outlet
(b) The upstream water depth is less than approximately 1.5 times the barrel
height (or diameter)
Type V Flow Inlet control. The barrel flows partially full and supercritical flow
occurs in the barrel downstream of the inlet:
(a) The slope of the culvert barrel is greater than the critical slope
(b) The upstream water depth is greater than approximately 1.5 times the
barrel height (or diameter)
(a) The upstream water depth is greater than approximately 1.5 times the
barrel height (or diameter)
(b) The outlet is unsubmerged (downstream depth less than the barrel height
or diameter)
Lindeburg, M.R. 1999. Civil engineering reference manual. 7th Ed. Professional Publications, Inc.,
Belmont, CA.
• As noted in a previous lecture, the hydraulic efficiency of the cross section may
be a consideration, semi-circular sections being the most efficient
• Inlet and outlet water levels may be a consideration in the flume design
• For example, the flume may be connected to a reservoir with a specified range of
water surface elevation
• As in any open-channel, avoid flume designs that would produce near-critical
flow conditions at the design capacity; attempt to arrive at a design with Fr < 0.9
• Consider USBR and or other guidelines for the inclusion of freeboard at the
design discharge
• Note that an overflow could quickly cause severe erosion under the flume
0.25
0.20
Height (m)
0.15
0.10
0.05
0.00
0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40
Distance (m)
• Transitions at pipe, flume, and canal outlets (ends) often have energy dissipation
structures included or added to the design
• Transitions are typically made of concrete or earth, the latter often having some
sort of riprap protection
• Earthen transitions between open-channel and pipe flow (culverts and siphons)
are often acceptable when the velocity in the pipe is less than about 3.5 fps (1
m/s)
• Transitions can have both lateral and vertical (bed) contraction or expansion
• It is very difficult to design transitions that work well over a wide range of flows
• Consequently, transitions are often designed for specified maximum flow rates
• Standard designs are selected for many small transitions because the time and
effort to design a special transition for a particular case may not be justified, and
because the engineer may not know how to go about designing a transition
based on the application of hydraulic equations
• The most common type of transition used in small canal structures by the USBR
is called “broken back” (Type I), which has vertical walls on the
converging/diverging sides
• For small structures (about 100 cfs or less), the USBR usually applies one of five
standard transition designs
• Standard USBR transitions are given in Chapter VII of the “Design of Small
Canal Structures” (1978) book and other publications and design reports
• More sophisticated transitions may be designed for larger flow rates
• Many of the USBR transitions are inlet and outlet structures for pipes, not
transitions between channel cross section changes
• Many open-channel-to-pipe transition designs call for a transition length (in the
direction of flow) of about three times the diameter of the pipe
• Inlet transitions to inverted siphons are generally designed such that the top of
the pipe is below the upstream open-channel water surface for the design
discharge (this is to help prevent the continuous entry of air into the siphon,
which reduces capacity)
• The USBR calls the difference in elevation between water surface and top of pipe
opening the “hydraulic seal”
• Inlet transitions for culverts are generally designed such that inlet control occurs,
possibly causing supercritical flow and a downstream hydraulic jump inside the
pipe (barrel)
• The head loss in inlet transitions is typically taken to be about 0.1∆hv, where ∆hv
is the change in velocity head from upstream to downstream across the transition
• For outlet transitions, the loss is usually about double this, or 0.2∆hv
• In some cases, these losses may be twice these values, or more, but ∆hv is
usually very small anyway, compared to the specific energy
• The second parabola is the same as the first, but inverted vertically & horizontally
I. Introduction
• The base widths and uniform flow depths for the upstream and downstream
channels are shown in the figure above; these were determined during the
design procedures for the respective channels (canal & flume)
• These calculations can be confirmed by applying the Manning or Chezy
equations
• The reduction in bottom width of the channel will be accomplished with a reverse
parabola, from b = 2.5 m to b = 2.0 m
• The reduction in side slope from m = 1 to m = 0 will be done linearly across the
length L of the transition
BIE 5300/6300 Lectures 265 Gary P. Merkley
III. Confirm Subcritical Flow
• In the upstream channel, for uniform flow, the squared Froude number is:
• In the downstream channel (flume), for uniform flow, the squared Froude number
is:
• Therefore, Fr2 < 1.0 for both the upstream canal and downstream flume
• Then, the flow regime in the transition should also be subcritical
• It would probably also be all right if the flow were supercritical in the flume, as
long as the flow remained subcritical upstream; a hydraulic jump in the transition
would cause a problem with our given design criterion
• For uniform flow, the slope of the water surface equals the slope of the channel
bed
• Then, the slope of the upstream water surface is 0.000516, and for the
downstream water surface it is 0.00292
• Since the mean velocity is constant for uniform flow, the respective energy lines
will have the same slopes as the hydraulic grade lines (HGL), upstream and
downstream
• For our design criterion of no GVF profiles, we will make the slope of the energy
line through the transition equal to the average of the US and DS energy line
slopes:
0.000516 + 0.00292
SEL = = 0.001718 (3)
2
Q2 Q2
hu + + ∆z = hd + + ∆E (5)
2gA u2 2gA d2
where hu is the upstream depth (m); Q is the design flow rate (m3/s); Au is the
upstream cross-sectional flow area (m2); ∆z is the total net change in canal invert
across the transition (m); hd is the downstream depth (m); Ad is the downstream
cross-sectional flow area (m2); and ∆E is the hydraulic energy loss across the
transition (m)
• The ∆z value is unknown at this point, but the slope of the water surface across
the transition should be equal to:
hu + ∆z − hd
S ws = (6)
L
where Sws is the (constant) slope of the water surface across the transition
(m/m); and L is the length of the transition (m)
Q2 ⎛ 1 1 ⎞
⎜⎜ 2 − 2 ⎟⎟ + ∆E
2g ⎝ A d A u ⎠
S ws = (7)
L
(15)2 ⎛ 1 1 ⎞
⎜ − ⎟ + 0.0137
2(9.81) ⎝ (4.3)2 (8.172)2 ⎠
S ws = = 0.0578 (8)
8.0
• The side slope will change linearly from 1 to 0 over the length of the transition
• The equation for m, with x = 0 at the upstream end of the transition, is:
m = 1 − 0.125 x (9)
where 0 ≤ x ≤ 8 m
• The bed width decreases from 2.5 to 2.0 m over the length of the transition
• This reduction is specified to be a reverse parabola, defined over L/2 = 4.0 m
• Specific criteria could be used to define the shape of the parabola, but a
reduction of 0.5 m in bed width over an 8.0-m distance can be accomplished in a
simpler way
• Define the bed width, b, for the first half of the transition as follows:
x2
b = 2.5 − (10)
64
where 0 ≤ x ≤ 4 m
(x − 8)2
b = 2.0 + (11)
64
where 4 ≤ x ≤ 8 m
b = Ax3 + Bx 2 + Cx + D (12)
where x = 0 and x = 8
2.50
2.45
Two parabolas
2.40
3rd-degree polynomial
2.35
Base width, b (m)
2.30
2.25
2.20
2.15
2.10
2.05
2.00
0 1 2 3 4 5 6 7 8
Distance, x (m)
V2 Q2 (15)2
= + x(S ws − SEL ) = + 0.0561x (14)
2g 2gA 2 2(9.81)(8.172)2
or,
Q
A= = h(b + mh) (16)
2g ( 0.172 + 0.0561x )
−b + b2 + 4mA
h= (17)
2m
• Use Eq. 16 to calculate A as a function of x, then insert A into Eq. 17 and solve
for h at each x value
• Using an arbitrary invert elevation of 2.0 m at the transition inlet, the relationship
between depth of water, h, and canal bed elevation, z, across the 8-m transition
is:
• Once h is known, use Eq. 18 to solve for z, then go to the next x value
• The graph below shows the results of calculations using the above equations
• The numerical results are shown in the table below
• Note that the sum “z+h” decreases linearly through the transition (the water
surface has a constant slope)
• Note that the velocity head increases linearly through the transition
• Note that the summation, z+h+V2/2g, in the last column of the table (to the right)
decreases linearly at the rate of 0.001718 m per meter of distance, x, as we have
specified (see Eq. 3): the energy line has a constant slope
2.0
1.5
m (m/m)
b (m)
1.0 h (m)
z (m)
0.5
0.0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0
Distance (m)
9.0 4.050
4.035
4.0
3.0 4.030
2.0
4.025
1.0
0.0 4.020
0.0 2.0 4.0 6.0 8.0
Distance (m)
I. Introduction
Upstream Downstream
subcritical
critical depth
supercritical depth
depth
conjugate depths
• Energy loss can be calculated based on measurements of depth and flow rate
• In designs, hydraulic jump energy loss is unknown, so you must apply the
momentum function to determine a conjugate depth, then apply Eq. 1
• For a given Froude number, flow rate, and upstream depth:
• Cross sections with sloping sides provide more pronounced secondary currents
(essentially orthogonal to the stream-wise direction), which also help dissipate
hydraulic energy
• Thus, hydraulic jumps in trapezoidal cross sections give energy dissipation
magnitudes somewhere between the extremes of rectangular and triangular
cross-sectional shapes
• Some important hydraulic jump parameters, such as jump length and location,
are determined experimentally, not theoretically
• Thus, design procedures for hydraulic jump energy dissipaters always include
empirical equations
• The length of the “roller,” Lr, is always less than the length of the jump, Lj
Figure 2. Another side view of a hydraulic jump (flow is from left to right)
1.01
L j ≈ 9.75hu (Fus − 1.0 ) (2)
where Fus is the Froude number on the upstream side of the jump
V. Drop Spillways
• Drop spillways (also known as “drop structures”) are abrupt decreases in channel
bed elevation with a downstream stilling basin, used to dissipate hydraulic energy
in open channels
• Drop spillways often combine both hydraulic jump and impact features, although
not all design situations are associated with a hydraulic jump
• Much research and experimentation has been done on drop spillways in efforts
to adequately define design procedures and parameters
• Part of the reason for this is that, when incorrectly dimensioned, drop spillways
can actually worsen an erosion problem in the downstream channel
• Most drop spillways have the following basic features:
1. Inlet section
2. Drop section
3. Rectangular stilling basin
4. Outlet section
1. Floor blocks
2. End sill at DS of basin
3. Turbulence in the “tail water”
4. Hydraulic jump (in some cases)
• The following drop structure design elements are adapted principally from
Donnelly & Blaisdell (1965) and involve mostly empirically-determined
relationships
• How long does the stilling basin need to be for effective energy dissipation?
• According to experimental results, a series of simple iterative calculations are
needed to answer this question
• Base dimensions on a design discharge and critical depth in a rectangular basin:
• Consider the following figure where flow goes from left to right (note that the
coordinate origin is located at the brink of the overfall):
spillway crest
y
x
ht+ydrop
xt
ydrop
headwall
ht
su
free
bm
basin floor
xf
xa
xs
Figure 3. Side view of a drop spillway showing the free and submerged nappes
(flow is from left to right)
xf ⎛ ydrop ⎞
= −0.406 + 3.195 − 4.386 ⎜ ⎟ (4)
hc ⎝ hc ⎠
where hc is as defined in Eq. 3; and the other variables are defined in Fig. 3
2
⎛x ⎞ ydrop
0.691 + 0.228 ⎜ t ⎟ −
xs
= ⎝ hc ⎠ hc
(5)
hc ⎛x ⎞
0.185 + 0.456 ⎜ t ⎟
⎝ hc ⎠
• The variable xt is the distance to where the upper nappe surface plunges into the
tail water
• The nappe plunge location, xt, is defined by an equation which is similar to Eq. 4
for the free nappe:
xt ⎛ ht + ydrop ⎞
= −0.406 + 3.195 − 4.386 ⎜ ⎟ (6)
hc ⎝ hc ⎠
where ht is the tail water depth in the stilling basin, as seen in Fig. 3, and is
referenced to the stilling basin floor
• The term in parentheses in Eq. 6 will be positive in those cases in which the tail
water is above the spillway crest
• To avoid a negative square root term in Eq. 6, limit (ht + ydrop)/hc to a maximum of
0.7 when applying Eq. 6
• This is not a significant restriction because the required stilling basin length is not
affected when:
• All water depths (including hc and ht) are greater than zero
• All “x” values downstream of the spillway crest are greater than zero
• But all “y” values are negative below the spillway crest, positive above (this
follows the convention introduced by Donnelly and Blaisdell), as seen in Fig. 3
• The average of the results from Eqs. 4 and 5 are used for drop structure design:
xa =
( x f + xs ) (8)
2
where the value of xa is can be determined mathematically (preferred) or
graphically, as shown in the following plot (Fig. 4) of the above equations
• The stilling basin length, L, will always be greater than xa (L > xa)
ht + ydrop = 0.7 0.65 0.6 0.55 0.5 0.4 0.3 0.2 0.1 0.0
10
-0.2
9
-0.5
8 -1.0
-2.0
7
-4.0
-8.0
6
xa/h c
1
0 1 2 3 4 5 6 7 8 9 10
-ydrop/hc
Figure 4. Plot of drop spillway design equations for determining the value of xa
• Floor blocks are usually included in drop structure designs to help dissipate
hydraulic energy before the flow exits the stilling basin
• There is a required minimum distance from xa to the blocks so the flow becomes
parallel to the floor before impinging on the upstream face of the blocks
• If the blocks are too close to the location of xa, water splashes (“boils”) off the
blocks, and may go over the sides of the stilling basin
floor
blocks
ydrop
xa xb
Figure 5. Side view of a drop spillway showing the recommended location of floor
blocks (flow is from left to right)
• If xb < ½hc, the floor blocks are mostly ineffective in terms of energy dissipation
• Thus, for stilling basin design, let
xb = 0.8hc (9)
Longitudinal Sills
• Longitudinal sills are sometimes placed on the floor of the stilling basin, parallel
to the basin walls, as seen in a plan-view (Fig. 6)
longitudinal sill
end sill
b
longitudinal sill
w
in
gw
L
al
l
Figure 6. Plan view of a drop spillway showing longitudinal sills and square floor
blocks (flow is from left to right)
1. Proportioned
2. Spaced
• There is a minimum distance from the floor blocks to the end sill, which is located
at the downstream end of the stilling basin
• This minimum distance is intended to maximize the energy dissipation from both
the floor blocks and the end sill
• For design purposes, let:
x c ≥ 1.75hc (10)
xa xb xc
stilling basin length, L
Figure 7. Side view of a drop spillway showing the location of the end sill and the
total basin length (flow is from left to right)
L = x a + xb + x c (11)
or,
L = x a + 2.55hc (12)
L
Figure 8. Side view of a drop spillway showing the height of the end sill
• The top of the end sill should be at or slightly above the invert (bottom) elevation
of the downstream channel (or downstream channel transition), as shown in the
following figure
floor invert of
blocks DS channel
end sill
ht
ydrop hds
L
Figure 9. Side view of a drop spillway showing the downstream channel invert
ht ≥ 2.15hc (14)
where ht is from the downstream water surface to the stilling basin floor, as seen
in Fig. 9
BIE 5300/6300 Lectures 285 Gary P. Merkley
• In most drop spillway designs, let
ht = 2.15hc (15)
• Note that the recommended ratio of ht/hc (= 2.15) is independent of the drop
height, ydrop
• There may be a hydraulic jump up to the tail water depth, in some cases
• If the tail water depth, ht, is too low (i.e. ht < 2.15 hc)
1. Increase the stilling basin width, b, which will decrease hc; or,
2. Increase |ydrop|, deepening the stilling basin floor
• Note that the depth from the spillway crest to the stilling basin floor can be
increased not only by deepening the basin floor, but also by providing a weir at
the overfall location
• This solution can be convenient for the drop structure design, but care must be
taken with the freeboard in the upstream channel because increasing the
spillway crest height will result in a corresponding upstream water depth increase
• The tops of the sidewalls should be at least 0.85dc above the tail water surface
• Wing walls are DS of the end sill, at 45º angle, and with a top slope of 1:1
• Wing wall length depends on the width of the DS channel section
• Wing walls are not necessary if the DS channel is a lined canal
e
headwall
su
1
rf a
ht
ce
0.4hc wingwall
xa xb xc
L
Figure 10. Side view of a drop spillway showing footings and wing walls
• The best design procedure depends on the given site conditions and
requirements for a particular location
• However, in general, the following procedure can be applied
1. Define the total available bed elevation change at the proposed drop
structure location.
2. Define the design discharge, Q.
Given:
Solution:
(9 / 5)
2
hc = 3
= 0.691 m
9.81
ht = 2.076 m
2.15hc = 2.15 ( 0.691) = 1.486 m
Thus,
ht > 2.15hc
⎡ ⎛ −2.526 ⎞ ⎤
x f = 0.691⎢ −0.406 + 3.195 − 4.386 ⎜ ⎟ ⎥ = 2.75 m
⎣⎢ ⎝ 0.691 ⎠ ⎦⎥
⎡ ⎛ 2.076 − 2.526 ⎞ ⎤
x t = 0.691⎢ −0.406 + 3.195 − 4.386 ⎜ ⎟ ⎥ = 1.42 m
⎢⎣ ⎝ 0.691 ⎠ ⎥⎦
xa =
( 2.75 + 3.27 ) = 3.01 m
2
14. Calculate xb (Eq. 9):
L = x a + x b + x c = 4.77 m
0.5b 2.5
N= = = 7.1 blocks
0.35 0.35
Round up to N = 8 blocks, giving a percent area of 56%. Placing a block against
each side wall of the stilling basin, the uniform spacing between the blocks will
be:
b − 0.35N
spacing = = 0.314 m
N −1
18. The height of the headwall, from the basin floor to the top, should be:
Aletraris, S.S. 1983. Energy dissipation parameters for small vertical drop structures. Unpublished
M.S. thesis, BIE department, Utah State Univ., Logan, UT.
Donnelly, C.A., and Blaisdell, F.W. 1965. Straight drop spillway stilling basin. ASCE J. Hydraulics
Div., HY 3:101-131 (May 1965).
Peterka, A.J. 1964. Hydraulic design of stilling basin and energy dissipaters. Engr. Monograph 25.
USBR, Denver, CO. (September).
Rand, W. 1955. Flow geometry at straight drop spillways. ASCE J. Hydraulics Div., 81:1-13.
Schwartz, H.I., and Nutt, L.P. 1963. Projected nappes subject to transverse pressure. ASCE J.
Hydraulics Div., 89(HY4):97-104.
White, M.P. 1943. Energy loss at the base of a free overfall. ASCE Trans., 108:1361-1364.
(discussion of paper 2204).
I. Introduction
• A wasteway weir is a sharp- or blunt-crested weir located along one bank of the
canal
• An air vent is located just downstream of the top of the siphon spillway to break
suction when the upstream water level in the canal drops below a certain level
• This location is about 15° (from vertical) downstream of the top of the siphon
pipe, as shown in Figure 4-17 of the USBR Small Canal Structures book
• The upstream end of the vent is open at the normal water surface level (or FSL)
of the canal
• A potential operating problem with this type of structure is that when the suction
is broken, the discharge will suddenly cease, and this can cause surges in the
canal
• A pan can be attached to the upstream end of the vent to help prevent the vent
from acting as a siphon itself, possibly causing the water level in the canal to
drop below full supply level
• The pan helps reduce the amount of water level fluctuation in the canal
w
flo
FSL
road
FSL
1.5:1
1.25:1 ft
2
0.
6.36 ft
6.16 ft
30o
ft high
2.00 ft
00 water
297
4.
4.0
2.00 ft 0f
t
sill
8.30 ft
2.00 ft
5.00 ft 10.00 ft
Barrel ll all
f wa f w
utof tof
c cu
Gary P. Merkley
Deflector at the Downstream Side of the Siphon
• A small angled deflector can be installed in the downstream end of the siphon to
help direct water up to the top of the barrel under non-full-flow conditions
• This helps to mix air and water and cause the siphon to prime to full flow quicker
• The roof of the siphon structure at the outlet should be above the expected
downstream water surface elevation
• This helps to evacuate air from the siphon
This design example is adapted from an example given by the USBR (1978)
Given:
Suppose there is a canal with a design discharge of 120 cfs in which an in-line pump
station is used to lift the water up to a downstream reach. The canal is trapezoidal in
cross-section, with a base width of 8.0 ft, side slope of 1½:1 (H:V).
The canal is at an elevation of about 6000 ft above msl. The available head across
the siphon spillway, H, is 6.0 ft.
Solution:
(b) Full Pipe Discharge Estimate the full pipe discharge by assuming: (1) orifice flow;
and (2) a discharge coefficient of 0.65. This will give a flow rate per “unit width” of
the barrel:
Note that this is an estimate, using an assumed Cd value, and D instead of area.
(c) Maximum Possible Discharge Now, estimate the discharge per unit width
according to the “vortex” equation, which takes into account the atmospheric
pressure available to “push” the water up over the invert of the siphon crest. The so-
called vortex equation looks like this:
⎛R ⎞
qmax = RC 2g(0.7h) ln ⎜ S ⎟ (2)
⎝ RC ⎠
where h is the available atmospheric pressure head, based on the density of water;
and qmax is the flow rate per foot of barrel width (cfs/ft).
Gary P. Merkley 298 BIE 5300/6300 Lectures
The change in average atmospheric pressure with elevation can be approximated by
the following linear relationship:
where Patm is in psi and Elev is the elevation above mean sea level, in ft. For 6000-ft
of elevation, the atmospheric pressure is about 11.9 psi, or h = 27.6 ft of head
(water).
⎛ 5.0 ⎞
qmax = (3.0) 2g(0.7)(27.6) ln ⎜ ⎟ = 54.1 cfs / ft (4)
⎝ 3.0 ⎠
This means that the previously-calculated unit discharge of 25.6 cfs/ft (from the
orifice equation) is acceptable. If q were greater than qmax, it would have been
necessary to decrease H or change RCL.
Q 120 cfs
b= = = 4.7 ft (5)
q 25.6 cfs / ft
This value could be rounded up to provide a margin of safety, but we will leave it at
4.7 ft (at least for now).
(e) Vent Diameter The diameter of the siphon breaker pipe, Dp, should be such that
the cross-sectional area is at least 1/24th of the cross-sectional area of the barrel
(according to USBR guidelines). This gives an area of (2.0)(4.7)/24 = 0.39 ft2. The
corresponding ID is 0.70 ft, or 8.5 inches. Thus, use whatever pipe size would be
closest to this diameter (perhaps 9-inch nominal size), noting that steel pipe is
usually used (for strength).
(f) Outlet Sill Height The height of the deflector sill at the outlet of the siphon is given
as 1.5D, or 3.0 ft in our case.
(g) Outlet Ceiling Height The ceiling of the outlet is defined as h2. Referring to Figure
4-17, this is given by:
where Ecritical is the specific energy for critical flow conditions, in feet. This is how the
dimensions are defined in the USBR design procedures.
Q2 (120)2
yc = 3 2
=3 2
= 2.7 ft (7)
gb (32.2)(4.7)
The velocity is Q/A = 120/(2.7*4.7) = 9.5 fps, so the velocity head is:
V2 (9.5)2
= = 1.4 ft (8)
2g 2(32.2)
Then, Ecritical is 2.7 + 1.4 = 4.1 ft. And, h2 = 1.5(2.0) + 4.1 + 1.0 = 8.1 ft.
(h) Other Design Details The inlet structure from the canal can be designed with a
height along the side slope of 2D (minimum). The inlet structure should provide a
minimum submergence of 1.5hv + 0.5 ft, where hv is the velocity at the inlet, and the
inlet area is at least 2Db.
• Canals and related infrastructure can be very dangerous to people and animals
• People drown in canals, inverted siphons and other facilities every year
• One of the most important considerations is the number of people that might be
exposed to dangerous facilities (canals, siphons, etc.) at a given site
• It is difficult to determine generally applicable design standards for safety
features because of many factors that should be considered
• Note that design engineers can be held legally liable for mishaps & accidents
• The kind of safety protection applied to a given canal and canal structures
normally depends on the safety classification:
1. Preventative
• Fencing
• Sign Posting
• Guard Railings and other Barriers
• Safety Nets
• Ladders
• Cables with Floats
• Pipe Inlet Racks
Show your work neatly on this or separate pages. Show units for
all calculated values. Make note of any important assumptions.
Name_______________________________
2. (15 pts) Current metering data is given below for an open channel with a top width
of 3.03 m. Complete the calculations to estimate the total flow rate in m3/s.
Totals:
1 of 7
3. (15 pts) You need to design a suppressed, rectangular sharp-crested weir for a
rectangular channel with a base width of 2.10 m, and a Qmax of 4.5 m3/s. A normal
depth of 0.678 m at Qmax was measured in the field. Manning roughness is 0.014.
Design the weir, specifying crest height, P, provided the conditions are appropriate.
4. (25 pts) A BCW, operating under free-flow conditions, has a flow rate of 17.00 m3/s
when hu (referenced from the sill) is 1.813 m. At this same flow rate, hd (referenced
from the downstream bed elevation) is 2.661 m. The upstream and throat sections
are rectangular with a width of 3.75 m. The sill height is zu = zd = 1.15 m. This BCW
has a downstream ramp with a 6:1 slope.
5. (25 pts) A circular pipe has a circular, sharp-edged orifice plate (D2 = 5.50 inches),
centered in the pipe cross section, which has an inside diameter of D1 = 7.90 inches.
Taps at D1 (upstream) and ½D1 (downstream) are connected to a manometer with
mercury, from which a head differential of 186 mm is measured. Water temperature
is 13°C. Ignoring thermal expansion adjustments:
2 of 7
Solutions:
For 50 cfs, select the W = 3 ft, L = 9 ft Cutthroat flume from the table in the
lecture notes, with Qmax = 56.9 cfs.
(c) Determine the minimum height (in feet) of the flume floor with
respect to the channel bed such that the flume operates under
free-flow conditions at Qmax.
1/ nf 1/1.55
⎛ Q ⎞ ⎛ 50.0 ⎞
hu = ⎜ f ⎟ =⎜ ⎟ = 2.77 ft
⎝ Cf W ⎠ ⎝ (3.442)(3.0) ⎠
Then,
(hd )max = Sthu = (0.820)(2.77) = 2.27 ft
Finally, the minimum floor height with respect to the channel bed is:
US Cutthroat flume DS
2.77 ft 2.27 ft
2.40 ft
0.13 ft
3 of 7
2. (15 pts) Current metering data is given below for an open channel with a top width
of 3.03 m. Complete the calculations to estimate the total flow rate in m3/s.
Note that there is a vertical wall at the 3.08 distance from the edge
(otherwise, the depth would be zero at this location). The ratio x/D is:
x (3.08 − 3.00)
= = 0.0762
D 1.05
Then,
Vx 0.65 + 10.52(0.0762)
= = 0.802
VD 1 + 10.676(0.0762) − 0.51431(0.0762)2
and,
0.65(0.210)
Vw = = 0.170 m/s
0.802
The rest of the calculations are simple and are given in the table below.
4 of 7
3. (15 pts) You need to design a suppressed, rectangular sharp-crested weir for a
rectangular channel with a base width of 2.10 m, and a Qmax of 4.5 m3/s. A normal
depth of 0.678 m at Qmax was measured in the field. Manning roughness is 0.014.
Design the weir, specifying crest height, P, provided the conditions are appropriate.
Q2 T (4.5)2 (2.10)
F =
2
= = 1.50
gA 3 (9.81) [(2.10)(0.678)]3
r
4. (25 pts) A BCW, operating under free-flow conditions, has a flow rate of 17.00
m3/s when hu (referenced from the sill) is 1.813 m. At this same flow rate, hd
(referenced from the downstream bed elevation) is 2.661 m. The upstream and
throat sections are rectangular with a width of 3.75 m. The sill height is zu = zd =
1.15 m. This BCW has a downstream ramp with a 6:1 slope.
Q2
Eu = hu + =
2gAu2
(17.0)2
(1.813 + 1.15) + = 3.082 m
2(9.81) [(1.813 + 1.15)(3.75)]
2
(b) Determine hc (referenced from the sill) for this flow rate.
Q2 T (17.0)2 (3.75)
F = 2
= =1
gA 3 9.81( 3.75hc )3
r
whereby hc = 1.280 m.
(c) Estimate the hydraulic head loss in the diverging section, (hf)ds.
5 of 7
log10 ⎡114.6 tan−1 (1/ 6 )⎤ − 0.165
ξ= ⎣ ⎦ = 0.638
1.742
The velocity at the critical-flow section is Vc = 17.0/((3.75)(1.280)) = 3.54 m/s.
The velocity at the DS section is Vd = 17.0/((3.75)(2.661)) = 1.70 m/s. Then,
5. (25 pts) A circular pipe has a circular, sharp-edged orifice plate (D2 = 5.50 inches),
centered in the pipe cross section, which has an inside diameter of D1 = 7.90
inches. Taps at D1 (upstream) and ½D1 (downstream) are connected to a
manometer with mercury, from which a head differential of 186 mm is measured.
Water temperature is 13°C. Ignoring thermal expansion adjustments:
D2 5.50
β= = = 0.696
D1 7.90
1
ν= = 1.198(10)−6 m2 /s
83.9192(13) + 20,707.5(13) + 551,173
2
This requires one or two iterations. The diameter of the orifice is: D2 =
0.3048(5.50/12) = 0.140 m. The cross-sectional area of the orifice opening is:
πD2 π(0.140)2
A2 = = = 0.0154 m2
4 4
Start with Cd = 0.6.
2g(0.186)(13.6 − 1)
Q1 = 0.6(0.0154) = 0.6(0.1194) = 0.0716 m3 /s
1 − (0.696)4
Then,
6 of 7
4Q 4(0.0716)
Re = = = 543,500
πDν π(0.140)(0.000001198)
and,
1 − (0.696)4 (543,500)0.75
37.06
= 0.607 + 0.75
Re
= 0.609
The adjusted flow rate is:
Q2 = 0.609(0.1194) = 0.0727 m3 /s
Re = 551,900
Q = 0.0727 m3/s
7 of 7
BIE 6300
Fall Semester 2004
Exam #2 – 14 Dec 04
Show your work neatly on this or separate pages. Show units for all
calculated values. Make note of any important assumptions.
Name_________________________________
An inverted siphon with a single barrel of circular concrete pipe (2.25-ft inside diameter) has a total
length of 635 ft. The descending part of the barrel has a length of 185 ft. The inlet and outlet
structures are ungated Type 1 USBR transitions. See the side view (profile) figure below:
upstream downstream
983.300 ft elev
975.950 ft elev
954.445 ft elev
The inverted siphon connects upstream and downstream open canals which have the same
trapezoidal in cross section: base width is b = 4.0 ft; inverse side slope is 1.00; and, longitudinal
bed slope is 0.000212 ft/ft. The Manning roughness is estimated to be n = 0.015 in the open
canals. Assume uniform-flow conditions in the open channels both upstream and downstream of
the inverted siphon.
a) Estimate the flow rate through the inverted siphon pipe under steady-state
flow conditions. Use the Darcy-Weisbach equation with friction factor “f”
defined by the Swamee-Jain equation:
0.25
f= 2
⎡ ⎛ ε 5.74 ⎞ ⎤
⎢log10 ⎜ + 0.9 ⎟ ⎥
⎣ ⎝ 3.75D NR ⎠ ⎦
where the roughness height is ε = 0.001 ft; and the kinematic viscosity of the
water is ν = 1.2(10)-5 ft2/s.
b) Calculate the maximum pressure in the inverted siphon pipe for steady-state
flowing conditions.
c) Calculate the maximum pressure in the inverted siphon pipe for non-flowing
conditions.
d) Calculate the uniform-flow depth in the upstream open canal.
e) Is the hydraulic seal sufficient at the inverted siphon entrance? (the barrel
invert has the same elevation as the canal invert at the siphon entrance).
Solution:
• Recognize that the open canals US and DS of the inverted siphon have the same cross-
section, longitudinal bed slope, and roughness. Thus, if uniform-flow conditions prevail US
and DS of the inverted siphon, the depth just US of the siphon must be the same as the
depth just DS. This means that the head differential on the siphon is equal to the
difference in entrance and exit elevations:
• Under steady-state flow conditions, the velocity heads are the same in the open channels
just US and just DS of the inverted siphon. This means that the hydraulic energy loss
through the siphon under these conditions is very nearly equal to ∆Elev. Then,
∆Elev = hf
where hf is determined from Darcy-Weisbach and Swamee-Jain (English units):
L V 2 8 f LQ2 8 f (635)Q2
hf = f = = = 0.277 f Q2
D 2g gπ D 2 5
(32.2)π (2.25)
2 5
0.25 0.25
f= 2
= 2
⎡ ⎛ 0.001 5.74 ⎞ ⎤ ⎡ ⎛ 5.74 ⎞ ⎤
⎢log10 ⎜ + 0.9 ⎟ ⎥ ⎢log10 ⎜ 0.000119 + 0.9 ⎟ ⎥
⎣ ⎝ 3.75(2.25) NR ⎠ ⎦ ⎣ ⎝ NR ⎠ ⎦
VD 4Q 4Q
NR = = = −5
= 4.72(10)4 Q
ν νπD 1.2(10) π(2.25)
• Then:
0.25
f=
( )
2
⎡log10 0.000119 + 0.000357Q−0.9 ⎤
⎣ ⎦
• Combine the above equation with the equation for hf:
0.0693Q2
hf = = 7.350 ft
( )
2
⎡log10 0.000119 + 0.000357Q−0.9 ⎤
⎣ ⎦
where the only unknown is Q (cfs). Rearrange as follows:
(
Q = −10.3 log10 0.000119 + 0.000357Q−0.9 )
• Using the above equation, make an initial guess of 10 cfs (for example), then iterate to
determine the solution to the equation:
Q next Q
(cfs) (cfs)
10.00 38.99
38.99 39.95
39.95 39.96
• From the above table, Q = 40.0 cfs (to three significant digits). This gives f = 0.0166.
[h(4.0 + h)]
5/3
1.49
40.0 = 0.000212
0.015 ⎡ 4.0 + 2h 1 + 1⎤ 2 / 3
⎣ ⎦
or,
[h(4.0 + h)]
5/3
27.7 =
[4.0 + 2.83h]
2/3
• Solving the above equation by iteration: h = 2.89 ft (to three significant digits).
• In this case, the maximum pressure will occur at the lowest point in the inverted siphon, at
the end of the descending portion of the barrel. This pressure is equal to the change in
elevation from the US free water surface to the end of the descending part of the barrel,
minus the friction loss. Using Darcy-Weisbach for hf:
8f(185)(40.0)2
hmax = ( 2.89 + 983.300 − 954.445 ) −
(32.2)π2 (2.25)5
or,
hmax = 31.7 − 129 f
• Note that f is the same as previously calculated (same D, same Q, etc.): f = 0.0166. Then,
• In this case, the maximum pressure will again occur at the lowest point in the inverted
siphon. For zero flow, there is zero friction loss.
• Assuming zero depth in the downstream channel:
• The hydraulic seal is the difference in elevation between the US free water surface and the
crown (highest point) of the barrel inlet. In our case, this is approximately equal to:
• According to USBR design criteria, the required hydraulic seal is 1.5 times the difference
in velocity heads between the pipe and the open canal:
⎛ V2 ⎞ 8(40.0 cfs)2
⎜ ⎟ = = 1.57 ft
( )
2
⎝ 2g ⎠pipe (32.2) π(2.25)2
⎛ V2 ⎞ (40.0 cfs)2
⎜ ⎟ = = 0.0627 ft
⎝ 2g ⎠canal 2(32.2) ( 2.89(4 + 2.89) )
2
• Then,
• Thus, the actual hydraulic seal is much less than the required hydraulic seal.
BIE 5300/6300 Assignment #1
Simple Flow Measurement and Flumes
02 Sep 04 (due 07 Sep 04)
I. A float test was conducted in a straight reach of open channel. The rectangular
cross section had a base width of 1.55 m. A small piece of a wooden twig was
timed with a stopwatch over a distance of 10 m, and the three trials produced
transit times of: 7.42, 7.58, and 7.49 s. The depth of water in the center of the
channel was 1.32 m. Apply the float method to estimate the discharge in m3/s.
II. You have field data for a concrete-lined, rectangular irrigation canal. The base
width is 3.04 m. The data show that the channel is prismatic (straight in
alignment, with constant cross-sectional shape and size) and the water depth
was constant at 2.15 m along a 2.23-km reach. The water depth had not
changed over a period of two hours before the measurements were taken. If the
longitudinal bed slope of the channel is 0.00012 m/m, what is the estimated
discharge range (min & max), in m3/s, for this canal reach? (use the Manning
and or Chezy equations).
III. Data were taken using the dye method in an earthen canal. A slug of dye was
injected into the center of the stream and the leading (front) edge traveled a
distance of 12 m in 9.05 s, while the trailing edge crossed the 12-m distance in
10.11 s. If the cross-sectional area of the channel was 5.13 m2, what is the
estimated discharge in m3/s?
IV. The table below has free-flow calibration data for a Cutthroat flume with L = 3.0
ft and W = 8 inches. Analyze the data to determine the values of Cf and nf and
compare these values to those published in the lecture notes.
Q (cfs) hu (ft)
2.688 1.003
2.688 1.003
2.686 1.003
2.687 1.003
2.687 1.003
1.865 0.811
1.865 0.811
3.375 1.095
2.263 0.907
1.461 0.696
1.122 0.611
1.123 0.611
1.123 0.611
1.123 0.611
0.844 0.518
V. The table below has submerged-flow calibration data for a Cutthroat flume with L
= 3.0 ft and W = 8 inches. Analyze the data to determine the values of Cs and
ns, using the nf value from the previous calibration for the same flume size.
Compare these values to those published in the lecture notes.
(a) Select an appropriate Cutthroat flume size, in English units, from the table in
the lecture notes.
(b) Determine the minimum height of the Cutthroat flume floor, relative to the
existing canal bed, such that free-flow conditions prevail up to the maximum
discharge of 40 cfs. Do not specify a floor elevation below the existing canal
bed.
(c) Will the upstream canal banks need to be raised if the Cutthroat flume is
installed for free-flow conditions?
Solutions:
I. The average transit time of the three trials is: (7.42 + 7.58 + 7.49)/3 = 7.50 s.
The average estimated surface velocity is: 10 m/7.50 s = 1.33 m/s.
Alternatively, the average surface velocity can be taken as (10/7.42 + 10/7.58 +
10/7.49)/3 = 1.33 m/s (same result). The cross-sectional area of the channel is:
A = (1.55)(1.32) = 2.05 m2
The average depth in the channel is 1.32 m (because the section is rectangular).
Interpolating linearly (which is the simplest option, and probably as valid as
anything else in this case) in the table from the lecture notes, the surface
velocity coefficient is:
which gives C = 0.73. The average velocity in the cross section is estimated as:
(0.73)(1.33 m/s) = 0.97 m/s. Finally, the flow rate is estimated to be:
( )
AV = 2.05 m2 ( 0.97 m/s ) ≈ 2.0 m3 /s
II. For this channel cross section size and type of lining, the Manning “n” value
might be in the range 0.012 < n < 0.018, depending on the condition of the
concrete lining and the presence (or absence) of vegetation and sediment. It
probably won’t be less than 0.012, but could be greater than 0.018.
The cross-sectional area is: A = (3.04 m)(2.15 m) = 6.54 m2. The wetted
perimeter is: Wp = 3.04 + 2(2.15) = 7.34 m. Applying the Manning equation:
1 ( 6.54 )
5/3
1 A5 / 3
Q= S = 0.00012 ≈ 5.5 m3 /s
0.012 ( 7.34 )
2/3 o 2/3
n Wp
at the lower range. Applying the equation again for n = 0.018, we get Q ≈ 3.7
m3/s. Thus, by the Manning equation, you might agree that: 3.7 < Q < 5.5 m3/s.
Note that the Manning “n” value has no more than two significant digits in this
case, so Q can have no more than that. You could also apply the Chezy
equation. These two equations will be discussed further in a future lecture.
III. With this method, you don’t apply a coefficient to the measured velocity, which in
this case is:
12 m
V= = 1.25 m/s
0.5 ( 9.05 + 10.11)
( )
Q = AV = 5.13 m2 (1.25 m/s) ≈ 6.4 m3 /s
IV. The free-flow data were analyzed as shown in the table below, giving Cf = 2.71
and nf = 1.78. Three significant digits are the most that can be justified for this
kind of calibration. Note the high coefficient of determination, R2, of 0.998.
These results were done in MS Excel®, using the LINEST spreadsheet function.
Predicted Percent
Q (cfs) hu (ft) ln(Q) ln(hu) Q (cfs) Difference Linear Regression
2.688 1.003 0.9888 0.0025 2.7234 -1.31 1.7805 0.9974
2.688 1.003 0.9888 0.0025 2.7234 -1.31 0.0212 0.0070
2.686 1.003 0.9881 0.0025 2.7234 -1.38 0.9982 0.0198
2.687 1.003 0.9884 0.0025 2.7234 -1.35
2.687 1.003 0.9884 0.0025 2.7234 -1.35 Cf= 4.07
1.865 0.811 0.6233 -0.2097 1.8665 -0.08 nf= 1.78
1.865 0.811 0.6233 -0.2097 1.8665 -0.08
3.375 1.095 1.2164 0.0908 3.1868 5.74
2.263 0.907 0.8167 -0.0980 2.2773 -0.63
1.461 0.696 0.3791 -0.3626 1.4215 2.74
1.122 0.611 0.1151 -0.4929 1.1272 -0.46
1.123 0.611 0.1160 -0.4929 1.1272 -0.37
1.123 0.611 0.1160 -0.4929 1.1272 -0.37
1.123 0.611 0.1160 -0.4929 1.1272 -0.37
0.844 0.518 -0.1696 -0.6587 0.8390 0.59
Note: L = 3.0 ft and W = 8 inches
Thus,
Qf = 4.07 W h1.78
u
V. The submerged-flow data were analyzed as shown in the table below, also in a
spreadsheet application, giving Cs = 1.60 and ns = 1.31. Three significant digits
are the most that can be justified for this kind of calibration. The free-flow
exponent, nf, was used in this calibration. Note the coefficient of determination,
R2, of 0.999.
Predicted Percent Linear Regression
Q (cfs) hu (ft) hd (ft) S=hd/hu hu-hd LHS RHS Q (cfs) Difference -1.311555 0.468977
2.687 1.005 0.575 0.572 0.430 2.356 -1.417 2.61 2.85 0.007212 0.019525
2.687 1.008 0.602 0.597 0.406 2.449 -1.497 2.64 1.75 0.999184 0.030379
2.687 1.009 0.627 0.621 0.383 2.545 -1.575 2.66 1.01
2.687 1.011 0.660 0.653 0.351 2.685 -1.687 2.68 0.42 Cs= 2.40
2.687 1.013 0.689 0.680 0.324 2.813 -1.787 2.69 0.04 ns= 1.31
2.687 1.021 0.739 0.724 0.282 3.041 -1.965 2.70 -0.46
2.687 1.030 0.781 0.758 0.249 3.240 -2.118 2.71 -0.71
2.685 1.055 0.863 0.818 0.192 3.664 -2.441 2.70 -0.66
2.685 1.083 0.931 0.859 0.153 4.034 -2.720 2.69 -0.19
2.685 1.120 0.993 0.887 0.127 4.335 -2.954 2.71 -0.86
2.683 1.183 1.093 0.925 0.089 4.903 -3.380 2.68 0.09
1.865 0.813 0.581 0.715 0.232 2.992 -1.926 1.87 -0.22
1.865 0.815 0.606 0.743 0.209 3.158 -2.049 1.86 0.10
1.865 0.820 0.639 0.779 0.181 3.394 -2.224 1.85 0.82
1.865 0.828 0.673 0.812 0.156 3.635 -2.402 1.84 1.51
1.863 0.840 0.702 0.835 0.138 3.827 -2.549 1.84 1.44
1.863 0.905 0.826 0.913 0.079 4.731 -3.225 1.80 3.21
1.86 0.870 0.763 0.877 0.107 4.246 -2.868 1.83 1.55
1.86 0.953 0.893 0.937 0.060 5.178 -3.567 1.80 3.06
1.86 1.077 1.025 0.952 0.052 5.421 -3.846 2.04 -9.31
1.858 1.015 0.968 0.954 0.047 5.584 -3.890 1.83 1.32
1.123 0.613 0.443 0.723 0.170 2.987 -1.959 1.18 -5.20
1.123 0.617 0.468 0.759 0.148 3.207 -2.124 1.18 -4.79
1.123 0.618 0.485 0.784 0.133 3.380 -2.249 1.17 -3.88
1.123 0.623 0.523 0.838 0.101 3.833 -2.569 1.13 -0.52
1.123 0.638 0.560 0.877 0.078 4.242 -2.867 1.11 1.24
1.123 0.666 0.608 0.914 0.058 4.743 -3.238 1.09 2.63
1.123 0.698 0.658 0.944 0.039 5.365 -3.685 1.05 6.27
1.12 0.828 0.805 0.972 0.023 6.201 -4.389 1.15 -2.47
Notes: "LHS" is ln(Qs) - nf ln(hu-hd). "RHS" is ln(-log10(S))
Thus,
2.40 W ( hu − hd )
1.78
Qs =
( − log10 S )
1.31
VI. Referring to the Cutthroat flume table for English units in the lecture notes, and
the Cutthroat flume top view figure, it is seen that the width of the flume is B = W
+ L/4.5.
(a) In the table, the smallest Cutthroat flume with a capacity of at least 40 cfs is
for W = 3.333 ft and L = 7.50 ft. This gives B = 3.333 + 7.50/4.5 = 5.0 ft,
which is the same as the base width of the rectangular canal. This works out
just right in this case, so choose the W = 3.333 ft and L = 7.50 ft size. Note
that W/L = 4/9.
(b) From the calibration table (English units), St = 0.873 for our selected flume
size. Free-flow conditions at Qmax give:
1/ nf 1/1.57
⎛Q ⎞ ⎛ 40 ⎞
hu = ⎜ max ⎟ =⎜ ⎟ = 2.18 ft
⎝ Cf W ⎠ ⎝ (3.519)(3.333) ⎠
Then, Sthu = (0.873)(2.18) = 1.90 ft, which is the maximum downstream
depth with respect to the upstream floor elevation.
Using the ACA program to determine the normal depth corresponding to the
given conditions, at Q = 40 cfs, it is found that the downstream depth would
be 3.07 ft. Thus, the floor of the flume must be at least 3.07 – 1.90 = 1.17 ft
above the existing canal bed. See the side view figure below.
(c) The depth of the concrete lining is given as 3.7 ft. The upstream depth at 40
cfs with the Cutthroat flume in place will be 2.18 + 1.17 = 3.35 ft, which is
less than 3.7 ft by a margin of 0.35 ft, which may be enough freeboard in this
case. The upstream canal banks do not need to be raised.
BIE 5300/6300 Assignment #2
Current Metering Calculations
09 Sep 04 (due 14 Sep 04)
II. You are given the electromagnetic current metering measurements below.
Calculate the total flow rate in the channel using a spreadsheet. Plot the cross-
section profile in a graph.
0.60
0.50
0.40
0.30
0.20
0.10
0.00
0.000 0.200 0.400 0.600 0.800 1.000 1.200 1.400
II. Again, the calculations were performed in a spreadsheet, applying the algorithm
for vertical walls (see the lecture notes), and the results are:
Note: Never show open-channel current metering results with more than two or
three significant digits – four or more significant digits cannot be justified.
BIE 5300/6300 Assignment #3
Weir Calculations
24 Sep 04 (due 28 Sep 04)
(a) Do the stated conditions meet all the guidelines for setting and
operating weirs, as given in the lecture notes? If no, which are
violated?
(b) You are required to estimate the discharge over the weir for the stated
conditions. Assuming negligible approach velocity, estimate Qf in cfs.
(c) Estimate the discharge, Qf, without assuming a negligible approach
velocity (hint: use Hu instead of hu in the calibration equation).
(d) Now suppose hd = 0.31 ft and everything else is the same as given
above. Estimate Qs in cfs.
IV. An overshot gate with L = 8.0 ft and Gw = 12.0 ft is installed in a canal. At the
downstream side of the gate is a reservoir with a constant water surface
elevation which is 0.29 ft above the gate hinge. The irrigation district needs you
to develop and plot calibration curves for gate openings of: θ = 15, 20, 25, 30,
35, 40, 45, 50, 55, and 60 degrees. The plot should have hu on the abscissa
and Q on the ordinate. Both the abscissa and ordinate must start at zero. Each
curve on the plot must be labeled with its corresponding gate opening angle.
V. A new trapezoidal concrete canal with a base width of 2.0 m and inverse side
slopes of 1.5 has a total lined depth of 2.5 m. The bed slope of the canal is
0.00015 m/m and the length is 2.35 km, all straight in alignment (no curves or
bends). At the end of the section there is a sudden drop in the bed elevation of
3.5 m, then the same channel cross section continues downstream, with the
same bed slope. Design a sharp-crested weir, just upstream of the elevation
drop, for a maximum flow rate of 7.0 m3/s. Make sure the canal lining won’t be
overtopped upstream of the weir.
BIE 5300/6300 Assignment #5
Open-Channel Constriction Calibrations
06 Oct 04 (due 12 Oct 04)
I. Develop a free-flow rating for this constriction using the following equation:
Qf = Cf hnuf
II. Develop a submerged-flow rating for this constriction using the following
equation:
Cs (hu − hd )
nf
Qs =
( − log10 S )
ns
III. Solve for transition submergence, St, for the above calibration.
Cs (hu − hd )
ns1
Qs =
( − log10 S )
ns 2
(a) Determine Cs, ns1 and ns2 based only on the submerged-flow data.
(b) Make a graph with plotted symbols for (Qs)measured vs. (Qs)calculated. The
ordinate range should be the same as the abscissa range, with a
diagonal line representing (Qs)measured/(Qs)calculated = 1.0.
(c) Comment on the data fit, using correlation or other such indices, as
appropriate.
(d) Comment on the data fit using this equation, as opposed to using the Qs
equation from (II) above.
Solutions:
I. Develop a free-flow rating for this constriction using the following equation:
Qf = Cf hnuf
Make two new columns for ln(Qf) and ln(hu) in the spreadsheet. Do a linear
regression using the LINEST spreadsheet function. The regression gives:
Cf= 5.57
nf = 1.61
The R2 value is 0.999, indicating a very good fit, and this is also seen in the
comparison graph:
7.0
6.0
5.0
(Qf)calculated
4.0
3.0
2.0
1.0
0.0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0
(Qf)measured
II. Develop a submerged-flow rating for this constriction using the following
equation:
Cs (hu − hd )
nf
Qs =
( − log10 S )
ns
Make two new columns for ln(Qs/(hu-hd)nf) and ln(-log10S) in the spreadsheet.
Do a linear regression using the LINEST spreadsheet function. The regression
gives:
Cs= 2.62
ns = 1.43
The R2 value is 0.999, indicating a very good fit, and this is also seen in the
comparison graph:
7.0
6.5
6.0
5.5
(Qs)calculated
5.0
4.5
4.0
3.5
3.0
2.5
2.0
2.0 3.0 4.0 5.0 6.0 7.0
(Qs)measured
III. Solve for transition submergence, St, for the above calibration.
Use the equation for f(St) = 0, as shown in the lecture notes. This equation is
derived by setting Qf = Qs. Make a table of St versus f(St), then plot the results.
The only solution is for St = 1.00, which is mathematically correct, but physically
impossible.
5.0
4.0
f(St)
3.0
2.0
1.0
0.0
0.0 0.2 0.4 0.6 0.8 1.0
St
0.016
0.014
0.012
0.010
f(St)
0.008
Solution at
0.006 St = 0.79
0.004
0.002
0.000
0.65 0.70 0.75 0.80 0.85 0.90 0.95 1.00
St
IV. Re-do the submerged-flow rating using the following equation:
Cs (hu − hd )
ns1
Qs =
( − log10 S )
ns 2
Make three new columns for ln(Qs), ln(hu-hd), and ln(-log10S) in the spreadsheet.
Do a multiple linear regression using the LINEST spreadsheet function. The
regression gives:
Cs= 2.78
ns1 = 1.54
ns2 = 1.36
The R2 value is 0.996, indicating a very good fit, and this is also seen in the
comparison graph, which is very similar to the previous plot:
7.0
6.5
6.0
5.5
(Qs)calculated
5.0
4.5
4.0
3.5
3.0
2.5
2.0
2.0 3.0 4.0 5.0 6.0 7.0
(Qs)measured
Even though the R2 value is slightly lower than for the previous form of the
submerged-flow equation, the sum of absolute deviations in measured and
calculated discharges is less in this case.
BIE 5300/6300 Assignment #6
Pipe Flow Measurement
13 Oct 04 (due 18 Oct 04)
I. You use a simple Pitot tube to measure the total head at the center of a circular
pipe with an inside diameter of 336 mm. The tip of the tube points in the
upstream direction. You find a total head of 42.35 m of water when connecting
the Pitot tube to a manometer. Separately, you measure the pressure in the
pipe at the same location, obtaining P = 413 kPa.
(a) Estimate the velocity in the pipe at the center of the cross section.
(b) Estimate the flow rate in the pipe, in liters per second.
II. You have a venturi connected to a manometer with mercury, whereby the
manometer is connected to an upstream tap, and to a tap just at the throat of the
venturi. The head differential on the mercury is 456 mm. The diameters are: D1
= 100 mm (upstream), and D2 = 50 mm (throat). The calibration coefficient for a
“machined inlet” is C = 0.995. Calculate the flow rate through the venturi.
III. You have a sharp-crested circular orifice at a gasketed pipe flange fitting. The
upstream pipe ID is D1 = 12.0 inches and the orifice diameter is 9.05 inches.
The orifice opening is centered in the pipe cross section. The upstream tap is at
a distance D1 upstream of the orifice plate, and the downstream tap is at a
distance ½D1 downstream of the plate. When the taps are connected to a
manometer with “blue” fluid (sg = 1.75), the head differential is observed to be
0.519 m. The water temperature is measured and found to be 8°C. Calculate
the flow rate to three significant digits, taking into account the Reynold’s number.
IV. You have to estimate the discharge from a partially-full horizontal pipe which
discharges freely into a canal. The end of the pipe is 20 cm above the water
surface in the canal. The pipe inside diameter is 35 cm, and the depth of water
at the pipe end is measured, giving 13 cm. Estimate the discharge in m3/s.
1
Solutions:
I. You use a simple Pitot tube to measure the total head at the center of a circular
pipe with an inside diameter of 336 mm. The tip of the tube points in the
upstream direction. You find a total head of 42.35 m of water when connecting
the Pitot tube to a manometer. Separately, you measure the pressure in the
pipe at the same location, obtaining P = 413 kPa.
Pipe area:
π(0.336)2
A= = 0.08867 m2
4
Pressure head:
P 413 kPa
= = 42.1 m
γ 9.81
Velocity head:
V2
= 42.35 − 42.1 = 0.25 m
2g
or, 196 lps. The true flow rate is probably slightly lower than this
because the velocity at the center of the cross section is greater than
the average velocity, even for fully turbulent flow.
II. You have a venturi connected to a manometer with mercury, whereby the
manometer is connected to an upstream tap, and to a tap just at the throat of the
venturi. The head differential on the mercury is 456 mm. The diameters are: D1
= 100 mm (upstream), and D2 = 50 mm (throat). The calibration coefficient for a
“machined inlet” is C = 0.995. Calculate the flow rate through the venturi.
2
D2 50
β= = = 0.50
D1 100
π(0.05)2
A2 = = 0.001963 m2
4
The flow rate is:
2g∆h(sg − 1)
Q = Cd A 2 =
1 − β4
2g(0.456)(13.6 − 1)
0.995(0.001963) = 0.0214 m3 /s
1 − (0.50)4
III. You have a sharp-crested circular orifice at a gasketed pipe flange fitting. The
upstream pipe ID is D1 = 12.0 inches and the orifice diameter is 9.05 inches.
The orifice opening is centered in the pipe cross section. The upstream tap is at
a distance D1 upstream of the orifice plate, and the downstream tap is at a
distance ½D1 downstream of the plate. When the taps are connected to a
manometer with “blue” fluid (sg = 1.75), the head differential is observed to be
0.519 m. The water temperature is measured and found to be 8°C. Calculate
the flow rate to three significant digits, taking into account the Reynold’s number.
π(9.05 /12)2
A2 = = 0.4467 ft 2
4
or, 0.04150 m2.
1
ν= = 1.385(10)−6 m2 /s
83.9192(8) + 20,707.5(8) + 551,173
2
3
Assume that the linear expansion due to pipe and element temperature is
negligible (which it probably is). Next, assume a starting Cd value of 0.6.
2g(0.519)(1.75 − 1)
Q1 = 0.6(0.0415) = 0.0837 m3 /s
1 − (0.7542)4
4Q 4(0.0837)
Re = = = 334,700
πDν π(0.2299)(0.000001385)
1 − (0.7542)4 (334,700)0.75
= 0.609
The updated flow rate is:
2g(0.519)(1.75 − 1)
Q2 = 0.609(0.0415) = 0.0850 m3 /s
1 − (0.7542) 4
4Q 4(0.0850)
Re = = = 339,900
πDν π(0.2299)(0.000001385)
1 − (0.7542)4 (339,900)0.75
= 0.609
Thus, the coefficient has converged to within three significant digits after only
one iteration. The flow rate is 0.0850 m3/s (3.00 cfs).
4
IV. You have to estimate the discharge from a partially-full horizontal pipe which
discharges freely into a canal. The end of the pipe is 20 cm above the water
surface in the canal. The pipe inside diameter is 35 cm, and the depth of water
at the pipe end is measured, giving 13 cm. Estimate the discharge in m3/s.
a/D = (35 - 13)/35 = 0.629 (which is greater than 0.45… OK), and
2.48
1.88 ⎛ 0.35 ⎞
Q = 8.69 (1 − 0.629 ) ⎜ 0.3048 ⎟ = 1.90 cfs
⎝ ⎠
5
BIE 5300/6300 Assignment #7
Earthen Canal Design
28 Oct 04 (due 2 Nov 04)
Show your calculations in an organized and neat format, including all relevant
calculations. Indicate any assumptions or relevant comments.
Given:
Required:
• Design the earthen channel section by applying the tractive force method
• Compare your results with those using the assumption of a very wide channel, in
which the critical tractive force is γhSo
• Compare your design with the velocity as obtained from the Kennedy formula
• Compare your design with the velocity as obtained from the Lacey method
• Compare your design with the velocity as obtained from the maximum velocity
method, both for values by Fortier and Scobey, and by the USBR
A Design Solution:
• The critical tractive force is taken from Fig. 5 (non-cohesive material) of the lecture
notes, using the curve labeled “low content of fine sediment.”
• Instead of reading the graph by eye, use the appropriate equation from the lecture
notes:
1
Angle of Repose
T sin2 φ
K = side = 1− 2
= 1 − 5.20 sin2 φ
Tbed sin θ
• Design requirements for this example call for a side slope between 0.0 & 3.5
• Then,
⎛ 1 ⎞
φmin = tan−1 ⎜ ⎟ = 15.9D
⎝ 3.5 ⎠
• Make a table of tractive force ratio, K, values for the acceptable range of φ:
φ (deg) m K
16 3.487 0.778
17 3.271 0.745
18 3.078 0.710
19 2.904 0.670
20 2.747 0.626
21 2.605 0.576
22 2.475 0.520
23 2.356 0.454
24 2.246 0.374
25 2.145 0.267
26 2.050 0.027
• These are hmax based on: (1) bed; and, (2) side slopes
• For water, use γ = 9,810 N/m3
• The following table has hmax values based on Kbed:
b/h
m 2.0 2.4 2.8 3.2 3.6 4.0 4.4 4.8 5.2 5.6 6.0
3.487 3.28 3.19 3.11 3.05 3.00 2.98 2.97 2.97 2.96 2.95 2.95
3.271 3.14 3.05 2.98 2.92 2.87 2.85 2.85 2.84 2.84 2.83 2.82
3.078 2.99 2.91 2.84 2.78 2.73 2.72 2.71 2.71 2.70 2.69 2.69
2.904 2.82 2.75 2.68 2.63 2.58 2.57 2.56 2.55 2.55 2.54 2.54
2.747 2.64 2.56 2.50 2.45 2.41 2.40 2.39 2.39 2.38 2.38 2.37
2.605 2.43 2.36 2.31 2.26 2.22 2.21 2.20 2.20 2.19 2.19 2.18
2.475 2.19 2.13 2.08 2.04 2.00 1.99 1.99 1.98 1.98 1.97 1.97
2.356 1.91 1.86 1.82 1.78 1.75 1.74 1.74 1.73 1.73 1.72 1.72
2.246 1.58 1.53 1.50 1.47 1.44 1.43 1.43 1.43 1.42 1.42 1.42
2.145 1.12 1.09 1.07 1.05 1.03 1.02 1.02 1.02 1.02 1.01 1.01
2.050 0.11 0.11 0.11 0.11 0.10 0.10 0.10 0.10 0.10 0.10 0.10
Note: values in italics are hmax based on Kbed
3
b/h
m 2.0 2.4 2.8 3.2 3.6 4.0 4.4 4.8 5.2 5.6 6.0
3.487 3.63 3.64 3.65 3.66 3.66 3.67 3.67 3.68 3.68 3.68 3.69
3.271 3.44 3.43 3.43 3.43 3.42 3.42 3.42 3.42 3.41 3.41 3.41
3.078 3.26 3.24 3.23 3.22 3.21 3.20 3.20 3.19 3.18 3.18 3.17
2.904 3.08 3.06 3.05 3.03 3.02 3.01 3.00 2.99 2.98 2.98 2.97
2.747 2.90 2.88 2.86 2.85 2.84 2.83 2.82 2.81 2.80 2.79 2.79
2.605 2.70 2.68 2.67 2.65 2.64 2.63 2.62 2.62 2.61 2.61 2.60
2.475 2.47 2.45 2.44 2.42 2.42 2.41 2.40 2.40 2.39 2.39 2.38
2.356 2.18 2.17 2.15 2.15 2.14 2.13 2.13 2.12 2.12 2.12 2.11
2.246 1.82 1.81 1.80 1.79 1.78 1.78 1.77 1.77 1.77 1.77 1.77
2.145 1.31 1.30 1.30 1.29 1.29 1.28 1.28 1.28 1.28 1.28 1.28
2.050 0.13 0.13 0.13 0.13 0.13 0.13 0.13 0.13 0.13 0.13 0.13
Note: values in italics are hmax based on Kside
• The above two tables show that hmax from Kside is greater for every combination
of b/h and m (within the given ranges)
• Therefore, use only the table for hmax from Kside to determine the maximum
allowable depth of water
• Note that the full range of “m” and the full range of “b/h” is represented in the
above two tables
• Calculate the uniform flow (normal) depth for values of “m” from 2.050 to 3.487
(as shown in the above tables), and various values of base width, “b.”
• Next, divide the base width by each respective depth, over the range of inverse
side slope values, giving a table of b/h ratios:
4
base width, b (m)
m 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0
3.487 2.07 2.39 2.73 3.08 3.44 3.82 4.22 4.63 5.05 5.49 5.94
3.271 2.04 2.35 2.69 3.04 3.40 3.78 4.17 4.58 5.00 5.44 5.89
3.078 2.00 2.32 2.65 3.00 3.36 3.73 4.13 4.53 4.95 5.39 5.84
2.904 1.98 2.29 2.62 2.96 3.32 3.70 4.08 4.49 4.91 5.34 5.79
2.747 1.95 2.26 2.59 2.93 3.29 3.66 4.05 4.45 4.87 5.30 5.75
2.605 1.92 2.23 2.56 2.90 3.25 3.62 4.01 4.41 4.83 5.26 5.71
2.475 1.90 2.21 2.53 2.87 3.22 3.59 3.98 4.38 4.80 5.23 5.68
2.356 1.88 2.18 2.50 2.84 3.19 3.56 3.95 4.35 4.76 5.20 5.64
2.246 1.85 2.16 2.48 2.81 3.16 3.53 3.92 4.32 4.73 5.16 5.61
2.145 1.83 2.14 2.45 2.79 3.14 3.51 3.89 4.29 4.70 5.13 5.58
2.050 1.81 2.11 2.43 2.76 3.11 3.48 3.86 4.26 4.68 5.11 5.55
Note: values in italics are ratios of b/h, using h from the Manning equation
• These calculations show that the range of base widths is limited (approximately)
as follows (with b in meters):
4<b<9
whereby b < 4 gives b/h less than the minimum of 2, and b > 9 gives b/h greater
than the maximum of 6, as specified for this problem
Ratios of h to hmax
• The above table shows that acceptable inverse side slopes for this design
problem are (rounding to two significant digits):
5
2.3 < m < 3.5
• The above table also shows that the base width can be any value between 4
and 9 m
• These ranges of base width and inverse side slope represent the domain of
feasible design solutions for this channel
• It would often be best to limit the width of the channel, possibly choosing a value
of b = 4, and accepting a somewhat greater depth of water for uniform flow
Tc 3.64
hmax = = = 3.71 m
γSo 9,810(0.0001)
• The largest hmax value based on Kside, for the acceptable range of m and b, is
3.69 m (see the above table)
• Therefore, the “very wide channel” solution is less restrictive than the previous
solution and will not have any bearing on the range of feasible m and b values
Kennedy Formula
where Vo is the “regime” velocity (m3/s); and h is depth (m) from the Manning
equation
A = h(b + mh)
• The following table gives Q values (m3/s) based on depths from the Manning
equation and Vo from the Kennedy formula for the previously-established range
of acceptable b and m values:
6
base width, b (m)
m 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 8.5 9.0
3.487 17.3 17.1 16.9 16.6 16.4 16.2 16.1 15.9 15.7 15.6 15.5
3.271 17.3 17.0 16.8 16.6 16.4 16.2 16.0 15.8 15.7 15.5 15.4
3.078 17.2 17.0 16.7 16.5 16.3 16.1 15.9 15.8 15.6 15.4 15.3
2.904 17.2 16.9 16.7 16.5 16.3 16.1 15.9 15.7 15.5 15.4 15.2
2.747 17.2 16.9 16.7 16.4 16.2 16.0 15.8 15.6 15.5 15.3 15.2
2.605 17.1 16.9 16.6 16.4 16.2 15.9 15.8 15.6 15.4 15.3 15.1
2.475 17.1 16.8 16.6 16.3 16.1 15.9 15.7 15.5 15.4 15.2 15.1
2.356 17.1 16.8 16.6 16.3 16.1 15.9 15.7 15.5 15.3 15.2 15.0
2.246 17.1 16.8 16.5 16.3 16.0 15.8 15.6 15.4 15.3 15.1 15.0
2.145 17.1 16.8 16.5 16.2 16.0 15.8 15.6 15.4 15.2 15.1 14.9
2.050 17.1 16.8 16.5 16.2 16.0 15.8 15.6 15.4 15.2 15.1 14.9
Note: values in italics are flow rate (m3/s) based on Vo from Kennedy (Q = VoA)
• Note that all flow rates in the above table are greater than Qmax (12 m3/s)
• This means that channel scouring would not be expected, at the design
discharge, according to the Kennedy formula
• However, some sediment deposition might occur, assuming the Kennedy
formula is correct for these site-specific conditions
• Recall that the Kennedy formula is 100% empirical
Lacey Method
f = 1.76 2 = 2.49
⎛ f2/ 3 ⎞ ⎛ 2.492 / 3 ⎞
S = 0.000547 ⎜ 1/ 6 ⎟ = 0.000547 ⎜ = 0.00037
⎜Q ⎟ ⎜ (12 * 35.31)1/ 6 ⎟⎟
⎝ ⎠ ⎝ ⎠
• In this case, all average velocity values within the feasible range (tractive force)
of m and b are below 0.76 m/s
• Thus, no scouring is to be expected, although perhaps some sediment
deposition might occur, according to Fortier & Scobey
• Again, the maximum velocity method is 100% empirical and will not provide
accurate results in all cases
• From the USBR, an average particle diameter of 2 mm falls under the “coarse
sand” category, giving a maximum velocity of Vmax = 1.8 fps (0.55 m/s)
• This is more restrictive than the Vmax from Fortier & Scobey, and also exceeds
almost all of the velocity values from the above table, but not by very much
8
BIE 5300/6300 Assignment #8
Culvert Design
16 Nov 04 (due 23 Nov 04)
Given:
The natural channel (a gulch) which carries the cross-drainage flow has a well-
defined and fairly stable cross-section.
The alignment of the gulch is orthogonal to the canal alignment.
The design flow rate for the culvert will be 100 cfs.
Circular concrete pipe will be used for the culvert barrel, and it comes with inside
diameters of 2.0 and 3.0 ft.
Let the upper top of the inlet to the culvert barrel be located at or just below
elevation 1,257.70 ft (this will require some excavation work just upstream of the
culvert inlet, but you don’t have enough information here to know how much
excavation will be needed).
Let the upper top of the outlet from the culvert barrel be located at or just below
elevation 1,249.63 ft.
Required:
Solution:
4Q 4(100)
D= = = 3.57 ft (1)
πV π(10)
0.5(100 cfs)
V= = 15.9 fps (2)
⎛ π(2)2 ⎞
⎜ 4 ⎟
⎝ ⎠
0.5(100 cfs)
V= = 7.07 fps (3)
⎛ π(3)2 ⎞
⎜ 4 ⎟
⎝ ⎠
which is acceptable. Therefore, use two 3-ft pipes for this culvert design, giving
two barrels.
• With the full pipe flow impending, the energy loss gradient can be estimated by
the Manning equation for open-channel flow, in which h = D
• Use a Manning n value of 0.015 for new concrete pipe, with a slight safety factor
for aging:
πD2 π(3.0)2
A= = = 7.069 ft (5)
4 4
2⎛ Wp4 / 3 ⎞ ⎛ (50)(0.015) ⎞2 ⎛ (9.425)4 / 3 ⎞
⎛ Qn ⎞ ⎜ ⎟=
Sf = ⎜ ⎟ ⎟ ⎜⎜ 10 / 3 ⎟⎟
= 0.00744
⎜ A10 / 3 ⎟ ⎜⎝
(6)
⎝ 1.49 ⎠ ⎝ ⎠
1.49 ⎠ ⎝ (7.069) ⎠
Q2Tc
Fr2 = = 1.0 (7)
gA3c
⎛ 2h ⎞
βc = 2cos −1 ⎜ 1 − c ⎟ (8)
⎝ D ⎠
⎛β ⎞
Tc = Dsin ⎜ c ⎟ (9)
⎝ 2⎠
D2
Ac = (βc − sinβc ) (10)
8
• Solve for depth, h, such that Fr2 = 1.0 for Q = 50 cfs and D = 3.0 ft (for English
units, g ≈ 32.2 ft/s2)
• Using the Newton method, βc = 4.268 rad, and hc = 2.301 ft
• Calculate the energy loss gradient (critical slope) corresponding to this depth
• For a depth of 2.301 ft, the flow cross-sectional area is 5.818 ft2, and the
wetted perimeter is 6.402 ft
• Applying the Manning equation:
2⎛ 4/3 ⎞
⎛ (50)(0.015) ⎞ ⎜ ( 6.402 )
( Sf )crit =⎜ ⎟ ⎟ = 0.00850 (11)
⎝ 1.49 ⎠ ( 5.818 )
⎜ 10 / 3 ⎟
⎝ ⎠
• If the slope of the pipe is 0.00850 or greater, critical flow can occur
• According to USBR guidelines, the top of the culvert barrel (pipe) should clear
the bottom of the canal by at least 0.5 ft
• Note that if more information were provided about the uphill topography, it
would also be possible to move the culvert inlet uphill, away from the canal
berm
• The elevation of the inside top of the barrel at the culvert inlet is 1,257.70 ft,
as specified above
• Assume a pipe thickness of 2 inches
• Recall the 2.5-inch canal lining thickness (specified)
• The elevation of the inside top of the barrel at the right canal base:
• The horizontal distance of the steep descending part of the culvert barrel:
• The minimum slope of the steep descending part of the culvert barrel:
• The flatter downstream part of the culvert barrel would traverse a horizontal
distance of:
• The change in elevation over this distance will be 1,251.93 - (1,249.63 - 2/12)
= 1,251.93 - 1,249.46 = 2.47 ft (where the 2/12 value is the assumed 2 inches
of pipe wall thickness)
• Then, the slope of the flatter downstream part of the barrel would be
2.47/21.53 = 0.115
• Also, the total horizontal distance is, then: 18.07 + 21.53 = 39.60 ft
• This slope is greater than the critical slope, and is not acceptable because it
would cause supercritical flow throughout, from inlet to outlet, causing erosion
downstream (unless erosion protection is used)
• This is the distance from the outlet at which the inside top of the upstream
pipe intersects the inside top of the downstream pipe
• The elevation of the intersection point is y = 0.319(13.98) + 1,245.07 =
1,249.53 ft, and the steep part of the barrel has the same slope as before
• Below, a profile of the inside top of the culvert barrel is shown
1259
1258
Both steep
1257
Downstream mild
1256
Elevation (ft)
1255
1254
1253
1252
1251
1250
1249
0 5 10 15 20 25 30 35 40
Horizontal distance (ft)
• The inlet and outlet can be USBR Type 1 (well-defined earthen section)
• The capacity of the downstream (mild) part of the barrel at impending full pipe
flow (but assuming open-channel flow) is approximated as:
1.49 (7.069)5 / 3
Q= 0.005 = 41 cfs (18)
0.015 (9.425)2 / 3
• Then, at the design capacity of 50 cfs (per barrel), the downstream portion of the
barrel would flow full and there would be a hydraulic jump inside the upstream
(steep) part of the barrel
• The outlet velocity would be approximately 7.07 fps (see Eq. 3 above)
• An energy dissipation structure at the outlet is not needed (because the outlet
velocity will be < 15 fps)
• The standard USBR culvert design, calling for two collars under the downhill
canal bank, and one collar under the uphill bank, is not appropriate in this design
because of the downstream retaining wall
• Use a single collar under the upstream canal bank, with Y = ½D = 1.5 ft, and a
thickness of 6 inches
• Note that some excavation will be required at the downhill side of the retaining
wall because the top of the culvert barrel has been set at the elevation of
1,249.63 (the inside top is about 2 inches lower, in this design)
r face
ground su
original barr
e l
13.98 ft
39.60 ft
Sprinkle & Trickle Irrigation
Lecture Notes
BIE 5110/6110
Fall Semester 2004
Copyright Notice
These lecture notes are formatting for printing on both sides of the page, with
odd-numbered pages on the front. Each lecture begins on an odd-numbered
page, so some even-numbered pages are blank.
Sprinkle Irrigation
1 Course Introduction.................................................................................... 9
2 Types of Sprinkler Systems; Soil-Water-Plant Relationships;
Planning Factors ...................................................................................... 11
3 Sprinkler Characteristics; Application Rates ............................................ 25
4 Set Sprinkler Uniformity & Efficiency........................................................ 39
5 Layout of Laterals & Mainline for Set Sprinklers; Pipe Hydraulics............ 51
6 Economic Pipe Selection Method............................................................. 59
7 Set Sprinkler Lateral Design .................................................................... 71
8 Set Sprinkler Lateral Design & Analysis................................................... 85
9 Mainline Pipe Design ............................................................................. 101
10 Minor Losses, Pressure Requirements & Pumps................................... 111
11 Pumps & System Curves; Affinity Laws & Cavitation ............................. 123
12 Center Pivot Design & Operation ........................................................... 145
13 Center Pivot Nozzling & Hydraulic Analysis ........................................... 155
14 Center Pivot Uniformity Evaluation; Linear Move Systems .................... 169
15 Maximizing Linear Move Field Length; Design Example ........................ 179
Trickle Irrigation
16 Components & Layout; Pressure Control & Flow Regulation ................. 189
17 Filtration for Trickle Irrigation Systems ................................................... 197
18 Trickle Irrigation Planning Factors; Salinity in Trickle Irrigation .............. 207
19 Water Requirements; Coefficient of Variation & System Capacity ......... 215
20 Emitter Selection & Design; Design Approach & Example ..................... 225
21 Pipe Specifications & Lateral Design; Manifold Location ....................... 231
22 Numerical Solution for Manifold Location; Derivations ........................... 241
23 Manifold Hydraulic Design ..................................................................... 253
24 Hydraulic Design of Mainline & Supply Line........................................... 275
6.89 kPa/psi
1 cb = 1 kPa
10 mb/kPa, or 100 kPa/bar
2.308 ft/psi, or 9.81 kPa/m (head of water)
14.7 psi = 101.3 kPa = 10.34 m (head of water) = 1,013 mbar = 1 atm
62.4 lbs/ft3, or 1000 kg/m3 (max density of pure water at 4°C)
0.1333 kPa/mmHg
0.7457 kW/HP
1 langley = 1 cal/cm2
0.0419 MJ/m2 per cal/cm2
0.3048 m/ft
1.609 km/mile
2.471 acre/ha
43,560 ft2/acre
1,233 m3/acre-ft
57.2958 degrees/radian
π ≈ 3.14159265358979323846
e ≈ 2.71828182845904523536
ºC = (ºF – 32)/1.8
ºF = 1.8(ºC) + 32
Ratio of weight to mass at sea level and 45° latitude: g = 9.80665 m/s2
I. Course Overview
V. Units
Important Advantages
Important Disadvantages
Hand-Move
End-Tow
Side-Roll
Side-Move
• almost the same as side-roll, but lateral pipe is not axle: it is mounted on A frames
with two wheels each
• clearance is higher than for side-roll
• not as common as side-roll sprinklers
Gun
Boom
• have big gun sprinklers mounted on rotating arms, on a trailer with wheels
• arms rotate due to jet action from nozzles
• arms supported by cables
• large water drops; commonly used on pastures, but also on other crops
• Perforated Pipe
• Hose-Fed Sprinklers
• Orchard Sprinklers
Traveler
Center Pivot
• cost is typically $35,000 ($270/ac or $670/ha), plus $15,000 for corner system
• easily automated
• typical maximum (fastest) rotation is about 20 hrs
• don’t rotate in 24-hr increment because wind & evaporation effects will concentrate
• returns to starting point after each irrigation
• typical lateral length is 1320 ft (400 m), or ¼ mile (quarter “section” area)
• laterals are about 10 ft above the ground
• typically 120 ft per tower (range: 90 to 250 ft) with one horsepower electric motors
(geared down)
• IPS 6” lateral pipe is common (about 6-5/8 inches O.D.); generally 6 to 8 inches, but
can be up to 10 inches for 2640-ft laterals
• typical flow rates are 45 - 65 lps (700 to 1000 gpm)
• typical pressures are 140 - 500 kPa (20 to 70 psi)
• older center pivots can have water driven towers (spills water at towers)
• end tower sets rotation speed; micro switches & cables keep other towers aligned
• corner systems are expensive; can operate using buried cable; corner systems don’t
irrigate the whole corner
• w/o corner system, π/4 = 79% of the square area is irrigated
• for 1320 ft (not considering end gun), area irrigated is 125.66 acres
• with corner system, hydraulics can be complicated due to end booster pump
• center pivots are ideal for allowing for effective precipitation
• ignore soil water holding capacity (WHC)
• requires almost no labor; but must be maintained, or it will break down
• can operate on very undulating topography
• known to run over farmers’ pickups (when they leave it out there)!
• many variations: overhead & underneath sprinklers; constant sprinkler spacing;
varied sprinkler spacing; hoses in circular furrows, etc.
• sprinkler nearest the pivot point may discharge only a fine spray; constant radial
velocity but variable tangential speeds (fastest at periphery)
• some center pivots can be moved from field to field
Linear Move
I. Irrigation Depth
MAD
dx = Wa Z (1)
100
where dx is the maximum net depth of water to apply per irrigation; MAD is
management allowed deficit (usually 40% to 60%); Wa is the water holding
capacity, a function of soil texture and structure, equal to FC – WP (field
capacity minus wilting point); and Z is the root depth
• For most agricultural soils, field capacity (FC) is attained about 1 to 3 days
after a complete irrigation
• The dx value is the same as “allowable depletion.” Actual depth applied may
be less if irrigation frequency is higher than needed during peak use period.
• MAD can also serve as a safety factor because many values (soil data, crop
data, weather data, etc.) are not precisely known
• Assume that crop yield and crop ET begins to decrease below maximum
potential levels when actual soil water is below MAD (for more than one day)
• Water holding capacity for agricultural soils is usually between 10% and 20%
by volume
• Wa is sometimes called “TAW” (total available water), “WHC” (water holding
capacity), “AWHC” (available water holding capacity)
• Note that it may be more appropriate to base net irrigation depth calculations
on soil water tension rather than soil water content, also taking into account
the crop type – this is a common criteria for scheduling irrigations through the
use of tensiometers
dx
fx = (2)
Ud
• The value of ET during the peak use period depends on the crop type and on
the weather. Thus, the ET can be different from year to year for the same
crop type.
• Some crops may have peak ET at the beginning of the season due to land
preparation requirements, but these crops are normally irrigated by surface
systems.
• When a system is to irrigate different crops (in the same or different
seasons), the crop with the highest peak ET should be used to determine
system capacity.
• Consider design probabilities for ET during the peak use period, because
peak ET for the same crop and location will vary from year-to-year due to
weather variations.
Merkley & Allen Page 16 Sprinkle & Trickle Irrigation Lectures
• Consider deficit irrigation, which may be feasible when water is very scarce
and or expensive (relative to the crop value). However, in many cases
farmers are not interested in practicing deficit irrigation.
• Leaching may be necessary if annual rains are not enough to flush the root
zone, or if deep percolation from irrigation is small (i.e. good application
uniformity and or efficiency).
• If ECw is low, it may not be necessary to consider leaching in the design
(system capacity).
• Design equation for leaching:
EC w
LR = (4)
5ECe − EC w
dn
LR ≤ 0.1: d= (5)
Ea
0.9 dn
LR > 0.1 d= (6)
(1 − LR)Ea
• When LR < 0.0 (a negative value) the irrigation water is too salty, and the
crop would either die or suffer severely
• Standard salinity vs. crop yield relationships (e.g. FAO) are given for
electrical conductivity as saturation extract
• Obtain saturation extract by adding pure water in lab until the soil is
saturated, then measure the electrical conductivity
• Here are some useful conversions: 1 mmho/cm = 1 dS/m = 550 to 800 mg/l
(depending on chemical makeup, but typically taken as 640 to 690). And, it
can usually be assumed that 1 mg/l ≈ 1 ppm, where ppm is by weight (or
mass).
Suppose ECw = 2.1 mmhos/cm (2.1 dS/m) and ECe for 10% reduction in crop
yield is 2.5 dS/m. Then,
EC w 2.1
LR = = = 0.20 (7)
5ECe − EC w 5(2.5) − 2.1
Thus, LR > 0.1. And, assuming no loss of water due to application nonuniformity,
the gross application depth is related to the net depth as follows:
dn
d = dn + (LR)d = (8)
1 − LR
and,
dn
d= = 1.25dn (9)
1 − 0.20
• The authors of the textbook only devote a few paragraphs to this topic, but it
is one of great importance
• A complete understanding of the distinctions between farm and field systems
comes only through years of experience
• Variability in design, operation and management conditions is limitless
• visit the field site personally if at all possible, and talk with the farmer
• get data on soil, topography, water supply, crops, farm schedules, climate, energy,
etc.
• be suspicious of parameter values and check whether they are within reasonable
ranges
• this step is unnecessary for automated fixed systems and center pivots
(a) determine Se, qa, nozzle size, and P for optimum application rate
(Tables 6.4 to 6.7)
(b) determine number of sprinklers to operate simultaneously to meet Qs
(Nn = Qs/qa) (Chapter 7)
(c) decide upon the best layout of laterals and mainline (Chapter 7)
(d) Adjust f, d, and/or Qs to meet layout conditions
(e) Size the lateral pipes (Chapter 9)
(f) Calculate the maximum pressure required for individual laterals
9. Calculate the mainline pipe size(s), then select from available sizes
10. Adjust mainline pipe sizes according to the “economic pipe selection method”
(Chapter 10)
Sprinkle & Trickle Irrigation Lectures Page 19 Merkley & Allen
11. Determine extreme operating pressure and discharge conditions (Chapter 11)
12. Select the pump and power unit (Chapter 12)
13. Draw up system plans and make a list of items with suggestions for operation
III. Summary
• Note that MAD is not a precise value; actual precision is less than two
significant digits; this justifies some imprecision in other values (don’t try to
obtain very precise values for some parameters when others are only rough
estimates)
• Why use f to determine Qs but f’ to determine net application depth?
(because Qs must be based on gross requirements; not irrigating 24 hrs/day
and 7 days/week does not mean that the crop will not transpire water 7
days/week)
• When determining the seasonal water requirements we subtract Pe from U.
However, to be safe, the value of Pe must be reliable and consistent from
year to year, otherwise a smaller (or zero) value should be used.
• Note that lateral and sprinkler spacings are not infinitely adjustable: they
come in standard dimensions from which designers must choose. The same
goes for pipe diameters and lengths.
• Note that design for peak Ud may not be appropriate if sprinklers are used
only to germinate seeds (when later irrigation is by a surface method).
Given:
Crop is alfalfa. Top soil is 1.0 m of silt loam, and subsoil is 1.8 m of clay loam.
Field area is 35 ha. MAD is 50% and ECw is 2.0 dS/m. Application efficiency is
estimated at 80%, and the soil intake rate is 15 mm/hr. Lateral spacing is 15 m and
lateral length is 400 m. Assume it takes ½ hour to change sets. Seasonal effective
rainfall is 190 mm; climate is hot. Assume one day off per week (irrigate only 6
days/week).
Hot climate, table 3.3 gives............Ud = 7.6 mm/day, and U = 914 mm/season
Top soil, table 3.1 gives ...........................................................Wa = 167 mm/m
Sub soil, table 3.1 gives ...........................................................Wa = 183 mm/m
Root depth, table 3.2 gives .........................................Z = (1.2 + 1.8)/2 = 1.5 m
Salinity for 10% yield reduction, table 3.5 gives ........................ECe = 3.4 dS/m
1. Average water holding capacity in root zone:
MAD ⎛ 50 ⎞
dx = Wa Z = ⎜ ⎟ (172.3 )(1.5 ) = 129.2 mm (11)
100 ⎝ 100 ⎠
dx 129.2 mm
fx = = = 17.0 days (12)
Ud 7.6 mm/day
17 days is just over two weeks, and depending on which day is off, there
could be 3 off days in this period. So, with one day off per week, we will
design the system capacity to finish in 17 - 3 = 14 days. Thus, f = 14 days.
But, remember that we still have to apply 17 days worth of water in these 14
days (we irrigate 6 days/week but crop transpires 7 days/week)
ECw 2.0
LR = = = 0.13 (15)
5ECe − ECw 5 ( 3.4 ) − 2.0
With 167.1 mm to apply and a soil intake rate of 15 mm/hr, this gives 11.14
hrs minimum set time (so as not to exceed soil intake rate). Then, we can
make the nominal set time equal to 11.5 hours for convenience. With 0.5 hrs
to move each set, there are a total of 12.0 hrs/set, and the farmer can
change at 0600 and 1800 (for example).
At this point we could take the lateral spacing, Sl, sprinkler spacing, Se, and
actual application rate to determine the flow rate required per sprinkler.
From the above, we can see that there would be two sets/day.
35 ha
= 2.08 laterals (17)
16.8 ha/lateral
Normally we would round up to the nearest integer, but because this is so
close to 2.0 we will use two laterals in this design.
U − Pe 914 mm - 190 mm
= = 5.6 irrigations (18)
dn 129.2 mm/irrig
with 11.5 hours operating time per set and two sets per day, the system runs
23 hrs/day...
Qs = 2.78
Ad
= 2.78
( 35 ha )(167.1 mm ) = 50.5 lps (800 gpm)
fT (14 days )( 23 hrs/day ) (19)
1. Sprinkler selection
2. Design of the system layout
3. Design of the laterals
4. Design of the mainline
5. Pump and power unit selection
• Rotating sprinklers have lower application rates because the water is only
wetting a “sector” (not a full circle) at any given instance...
• For the same pressure and discharge, rotating sprinklers have larger wetted
diameters
• Impact sprinklers always rotate; the “impact” action on the stream of water is
designed to provide acceptable uniformity, given that much of the water
would otherwise fall far from the sprinkler (the arm breaks up part of the
stream)
• Check out Web sites such as www.rainbird.com
Sprinkle & Trickle Irrigation Lectures Page 25 Merkley & Allen
III. Precipitation Profiles
• Typical examples of low, correct, and high sprinkler pressures (see Fig 5.5).
Pressure is OK
1. nozzle pressure
2. nozzle shape & size
3. sprinkler head design
4. presence of straightening vanes
5. sprinkler rotation speed
6. trajectory angle
7. riser height
8. wind
uniform! uniform!
lateral
lateral
lateral
• When winds are consistently recurring at some specific hour, the system can
be shut down during this period (T in Eq. 5.4 is reduced)
• For center pivots, rotation should not be a multiple of 24 hours, even if there
is no appreciable wind (evaporation during day, much less at night)
• If winds consistently occur, special straightening vanes can be used
upstream of the sprinkler nozzles to reduce turbulence; wind is responsible
for breaking up the stream, so under calm conditions the uniformity could
decrease
• For periodic-move systems, laterals should be moved in same direction as
prevailing winds to achieve greater uniformity (because Se < Sl)
• Laterals should also move in the direction of wind to mitigate problems of salt
accumulating on plant leaves
• Wind can be a major factor on the application uniformity on soils with low
infiltration rates (i.e. low application rates and small drop sizes)
• In windy areas with periodic-move sprinkler systems, the use of offset
laterals (½Sl) may significantly increase application uniformity
• Alternating the time of day of lateral operation in each place in the field may
also improve uniformity under windy conditions
• Occasionally, wind can help increase uniformity, as the randomness of wind
turbulence and gusts helps to smooth out the precipitation profile
0-3 mph wind: reduce manufacturer’s listed diameter of throw by 10% for an
effective value (i.e. the diameter where the application of
water is significant)
⎣ (
diam = diammanuf ⎡0.9 − 0.025 windmph − 3 ⎤
⎦ ) (21)
or,
diam = diammanuf ⎡⎣0.9 − 0.056 ( windm / s − 1.34 ) ⎤⎦ (22)
80 ft - (0.10)(0.80) = 72 ft (23)
• Equation 5.1:
q = Kd P (26)
P V2 q2
= = (27)
γ 2g 2gA 2
2gA 2P
= Kd P = q (28)
ρg
where the elevations are the same (z1 = z2) and the conversion through the
nozzle is assumed to be all pressure to all velocity
• Kd can be separated into an orifice coefficient, Ko, and nozzle bore area, A:
q = KoA P (29)
whereby,
Ko = 2 / ρ (30)
where the value of Ko is fairly consistent across nozzle sizes for a specific
model and manufacturer
4q
d= (31)
πK o P
3. Some sprinkler companies have invested much into the design of such
devices for low-pressure sprinkler nozzles
4. Low-pressure nozzles can be more expensive, possibly with reduced
uniformity and increased application rate, but the trade-off is in operating cost
dn
d= , for LR ≤ 0.1 (33)
Epa
where Epa is the “designer” application efficiency (decimal; Eq. 6.9). And,
0.9 dn
d= , for LR > 0.1 (34)
(1 − LR)Epa
• The gross application depth is the total equivalent depth of water which must
be delivered to the field to replace (all or part of) the soil moisture deficit in
the root zone of the soil, plus any seepage, evaporation, spray drift, runoff
and deep percolation losses
• The above equations for d presume that the first 10% of the leaching
requirement will be satisfied by the Epa (deep percolation losses due to
application variability). This presumes that areas which are under-irrigated
during one irrigation will also be over-irrigated in the following irrigation, or
that sufficient leaching will occur during non-growing season (winter) months.
• When the LR value is small (ECw ≤ ½ECe), leaching may be accomplished
both before and after the peak ET period, and the first equation (for LR ≤ 0.1)
can be used for design and sizing of system components. This will reduce
the required pipe and pump sizes because the “extra” system capacity during
the non-peak ET periods is used to provide water for leaching.
Ad
Qs = K (35)
fT
where,
Qs = system capacity;
T = hours of system operation per day (obviously, T≤ 24; also, t = fT)
K = coefficient for conversion of units (see below)
d = gross application depth (equals Ud/Eff during f’ period)
f = time to complete one irrigation (days); equal to f’ minus the days
off
A = net irrigated area supplied by the discharge Qs
3600qR e
I= (36)
SeSl
where I is the application rate (mm/hr); q is the flow rate (lps); Se is the
sprinkler spacing (m); Sl is the lateral spacing (m); and Re is the fraction of
water emitted by the nozzle that reaches the soil (takes into account the
evaporative/wind loss)
• If the velocity in the vertical direction at the nozzle, Vy, is taken as zero at
time t1, then,
( Vy )t
1
= V0 sin α − g t1 = 0 (39)
where V0 is the velocity of the stream leaving the nozzle (m/s); α is the angle
of the nozzle; t1 is the time for a drop to travel from the nozzle to the highest
point in the trajectory (s); and g is the ratio of weight to mass (9.81 m/s2)
• Note that the term Vosin α in Eq. 37 is the initial velocity component in the
vertical direction, and the term gt1 is the downward acceleration over time t1
• The above equation can be solved for t1
• The initial velocity, V0, can be calculated based on the sprinkler discharge
and the nozzle diameter
• Values of α can be found from manufacturers’ information
Merkley & Allen Page 36 Sprinkle & Trickle Irrigation Lectures
• Now, what is the highest point in the trajectory?
• First, solve for t1 in the previous equation:
Vo sin α
t1 = (40)
g
then,
x1 = V0 cos α t1 (42)
solving for h2,
gt 22
h2 = hr + h1 = Vy t 2 +
2 (43)
where hr is the riser height (m); t2 is the time for a drop of water to travel from
the highest point in the trajectory to impact on the ground; and Vy = 0
• Then, x2 is defined as:
2 (hr + h1 )
x 2 = V0 cos α t 2 = V0 cos α (44)
g
R j = x1 + x 2
(45)
• In summary, if air resistance is ignored and the sprinkler riser is truly vertical,
the theoretical value of Rj is a function of:
1. Angle, α
2. Nozzle velocity (qa/A)
3. Riser height, hr
• And, qa is a function of P
1. Application uniformity
2. Losses (deep percolation, evaporation, runoff, wind drift, etc.)
⎛
⎜ ∑
n
j=1 (
abs z j − m ) ⎟⎞
CU = 100 1.0 − (47)
⎜ ⎟
∑
n
⎜ z ⎟
⎝ j=1 j ⎠
where z are the individual catch-can values (volumes or depths); n is the
number of observations; and m is the average of all catch volumes.
⎛ σ 2⎞
CU = 100 ⎜ 1.0 − ⎟⎟ (49)
⎜ m π
⎝ ⎠
∑ z − m = nσ 2/ π (50)
• By the way, the ratio σ/m is known in statistics as the coefficient of variation
• Following is the approximate relationship between CU and DU:
• These equations are used in evaluations of sprinkler systems for both design
and operation
• Typically, 85 to 90% is the practical upper limit on DU for set systems
• DU > 65% and CU > 78% is considered to be the minimum acceptable
performance level for an economic system design; so, you would not
normally design a system for a CU < 78%, unless the objective is simply to
“get rid of water or effluent” (which is sometimes the case)
• For shallow-rooted, high value crops, you may want to use DU > 76% and
CU > 85%
CUa ≈ 10 CU
(53)
DUa ≈ 10 DU
• The above are also valid for “double” alternate sets (Sl/3)
• Use of alternate sets is a good management practice for periodic-move
systems
• The use of alternate sets approaches an Sl of zero, which simulates a
continuous-move system
V. System Uniformity
• The uniformity is usually less when the entire sprinkler system is considered,
because there tends to be greater pressure variation in the system than at
any given lateral position.
⎡1
( ⎤
system CU ≈ CU ⎢ 1 + Pn / Pa ⎥
⎣2 ⎦
) (54)
⎡1
( ⎤
system DU ≈ DU ⎢ 1 + 3 Pn / Pa ⎥
⎣4 ⎦
) (55)
where Pn is the minimum sprinkler pressure in the whole field; and Pa is the
average sprinkler pressure in the entire system, over the field area.
2Pn + Px
Pa = (56)
3
Design Efficiency:
Epa = DEpaReOe
(57)
• The design efficiency, Epa, is used to determine gross application depth (for
design purposes), given the net application depth
• In most designs, it is not possible to do a catch-can test and data analysis –
you have to install the system in the field first; thus, use the “design
efficiency”
• The subscript “pa” represents the “percent area” of the field that is
adequately irrigated (to dn, or greater) – for example, E80 and DE80 are the
application and distribution efficiencies when 80% of the field is adequately
irrigated
• Question: can “pa” be less than 50%?
U
80% of area overirrigated
C
w
Lo
Relative Applied Depth
h CU
Hig
100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0%
Area Receiving at Least the Desired Application
• These losses are typically from 5% to 10%, but can be higher when the air is
dry, there is a lot of wind, and the water droplets are small
• Effective portion of the applied water, Re. This is defined as the percentage
of applied water that actually arrives at the soil surface of the irrigated field.
• This is based on:
• climatic conditions
• wind speed
• spray coarseness
⎛ P1.3 ⎞
CI = 0.032 ⎜
⎜ B ⎟⎟
(58)
⎝ ⎠
where P is the nozzle pressure (kPa) and B is the nozzle diameter (mm)
CI > 17 17 ≥ CI ≥ 7 CI < 7
fine spray between fine and coarse coarse spray
• Allen and Fisher (1988) developed a regression equation to fit the curves in
Fig. 6.8:
Epa = DEpaReOe
(61)
where DEpa is in percent; and Re and Oe are in fraction (0 to 1.0). Thus, Epa
is in percent.
1. Compute the average catch depth over the wetted area (if a single
sprinkler), or in the area between four adjacent sprinklers (if in a
rectangular grid)
2. Multiply the sprinkler flow rate by the total irrigation time to get the volume
applied, then divide by the wetted area to obtain the gross average
application depth
3. Divide the two values to determine the effective portion of the applied
water
• In Chapter 6 of the textbook there are several tables that provide guidelines
for nozzle sizes for different:
• Wind conditions
• Application rates
• Sprinkler spacings
• For selected values of wind, application rate, and spacing, the tables provide
recommended nozzle sizes for single and double-nozzle sprinklers,
recommended sprinkler pressure, and approximate uniformity (CU)
• Recall that the maximum application rate is a function of soil texture, soil
structure, and topography (Table 5.4)
• For a given spacing and application rate, the sprinkler discharge, qa, can be
determined from Eq. 5.5
I ( SeSl ) d S SO
qa = = n e l e (62)
3600 3600EpaSto
where qa is in lps; I is in mm/hr; dn is in mm; Sto is the operating time for each
set, in hours; and Sl and Se are in m
• Why is the Oe term included in the above equation? (because Epa includes
Oe, as previously defined, and must be cancelled out when considering an
individual sprinkler)
• After calculating the system capacity and the design flow rate for sprinklers,
the number of sprinklers that will operate at the same time is:
Qs
Nn = (63)
qa
1. friction loss
2. elevation change
• The fundamental basis upon which sprinkler laterals are designed is:
• This is a design assumption that has been used for many years, and is
based on a great deal of experience
• The 20% for pressure variation is not an “exact” value; rather, it is based on
judgment and some cost comparisons
• A designer could change this value, but it would affect system performance
(uniformity), initial system cost, operating cost, and possibly other factors
• Computer programs could be written to search for an “optimal” percent
pressure variation according to initial and operating costs, and according to
crop value -- such an “optimal” value would vary from system to system
1. both friction loss and elevation are working to reduce pressure toward
the end of the lateral, and length is more restricted if the 20% rule is
still used
2. However, for small slopes, running laterals uphill may be required to
reduce the total length of the mainline pipe
• Note that V2/2g in the lateral pipe is normally converted into total head as the
water flows through the nozzle body. Therefore, the velocity head (and EL)
should normally be considered in lateral design. However, since a portion of
the velocity head is lost during deceleration of the water at the entrance into
risers and as turbulence inside the sprinkler head, and since V2/2g in a
lateral pipe is typically small (< 1 ft of head, or 0.2 psi, or 0.3 m head, or 3
kPa), it is normally neglected during design, and the HGL is used.
• Aside from limits on pressure variation, laterals should be oriented so that
they move in the direction of the prevailing winds -- this is because of salinity
problems and application uniformity
Qs 532
Ns = = = 111 sprinklers
qa 4.78 (65)
• Number of laterals,
1320 ft / lateral
= 33 sprinklers / lateral
40 ft / sprinkler (66)
111 sprinklers
= 3.36 laterals
33 sprinklers / lateral (67)
14 sets
f= = 7 days (69)
2 sets / day
⎛ 8 days ⎞
Qs = ⎜ ⎟ (532 gpm) = 608 gpm (71)
⎝ 7 days ⎠
• You might say that we are “effectively” finishing in somewhat less than 7
days, because the last set has only two laterals in operation, giving a system
capacity of 608 instead of 631
• Consider this calculation: there are 2 x 13 + 2 x 14 = 54 sets, but the last 2
sets have only 2 laterals. So, (52/54) x 631 = 608 gpm, as calculated above.
• Which is correct?
I. Review
0.25
f= 2
(72)
⎡ ⎛ ε 5.74 ⎞ ⎤
⎢log10 ⎜ + 0.9 ⎟ ⎥
⎣ ⎝ 3.75D NR ⎠ ⎦
which is valid for turbulent flow in the range: 4,000 ≤ NR ≤ 1.0(10)8. The ratio
ε/D is called “relative roughness.” The roughness height, ε, varies widely
• We will also use the Blasius equation (Eq. 8.6) to determine the value of “f,”
in some cases, for “smooth pipes”
total
minimum
total
Cost
Energy costs =
annualized fixed costs
fixed energy
• To balance these costs and find the minimum cost we will annualize the fixed
costs, compare with annual energy (pumping) costs
• We can also graph the results so that pipe diameters can be selected
according to their maximum flow rate
• We will take into account interest rates and inflation rates to make the
comparison
• This is basically an “engineering economics” problem, specially adapted to
the selection of pipe sizes
1. Determine the equivalent annual cost for purchasing each available pipe
size
2. Determine the annual energy cost of pumping
Sprinkle & Trickle Irrigation Lectures Page 59 Merkley & Allen
3. Balance the annual costs for adjacent pipe sizes
4. Construct a graph of system flow rate versus section flow rate on a log-
log scale for adjacent pipe sizes
• We will use the method to calculate “cut-off” points between adjacent pipe
sizes so that we know which size is more economical for a particular flow
rate
• We will use HP and kW units for power, where about ¾ of a kW equals a HP
• Recall that a Watt (W) is defined as a joule/second, or a N-m per second
• Multiply W by elapsed time to obtain Newton-meters (“work”, or “energy”)
1. Select a period of time over which comparisons will be made between fixed
and annual costs. This will be called the useful life of the system, n, in years.
2. For several different pipe sizes, calculate the uniform annual cost of pipe per
unit length of pipe.
where P is the cost per unit length of pipe; i is the annual interest rate
(fraction); and n is the number of years (useful life)
• Of course, i could also be the monthly interest rate with n in months, etc.
• Make a table of UAC values for different pipe sizes, per unit length of pipe
• The CRF value is the same for all pipe sizes, but P will change depending
on the pipe size
• Now you have the equivalent annual cost for each of the different pipe
sizes
• Note that the maximum possible value of Ot is 8,760 hrs/year (for 365
days)
• Note also that the “gross depth” is annual, so if there is more than one
growing season per calendar year, you need to include the sum of the
gross depths for each season (or fraction thereof)
• The total plant efficiency is the product of pump efficiency, Epump, and
motor efficiency, Emotor
Ep = EpumpEmotor
(76)
QH
WHP = (77)
102
where Q is in lps; H is in m of head; and WHP is in kilowatts (kW)
• Note that for fluid flow, “power” can be expressed as ρgQH = γQH
• Observe that 1,000/g = 1,000/9.81 ≈ 102, for the above units (other
conversion values cancel each other and only the 102 remains)
• The denominator changes from 102 to 3,960 for Q in gpm, H in ft, and
WHP in HP
OtCf
E=
Ep
(78)
• For electricity, the value of Cf is usually in dollars per kWh, and the value
used in the above equation may need to be an “average” based on
potentially complex billing schedules from the power company
• For example, in addition to the energy you actually consume in an electric
motor, you may have to pay a monthly fee for the installed capacity to
delivery a certain number of kW, plus an annual fee, plus different time-
of-day rates, and others
• Fuels such as diesel can also be factored into these equations, but the
power output per liter of fuel must be estimated, and this depends partly
on the engine and on the maintenance of the engine
• The units of E are dollars per WHP per year, or dollars per kW per year;
so it is a marginal cost that depends on the number of kW actually
required
Merkley & Allen Page 62 Sprinkle & Trickle Irrigation Lectures
6. Determine the marginal equipment cost:
• Note that Cf can include the “marginal” cost for the pump and power unit
(usually an electric motor)
• In other words, if a larger pump & motor costs more than a smaller pump,
then Cf should reflect that, so the full cost of friction loss is considered
• If you have higher friction loss, you may have to pay more for energy to
pump, but you may also have to buy a larger pump and/or power unit
(motor or engine)
• It sort of analogous to the Utah Power & Light monthly power charge,
based solely on the capacity to deliver a certain amount of power
Cf ($/kWh) = energy cost + marginal cost for a larger pump & motor
• This is not really an “energy” cost per se, but it is something that can be
taken into account when balancing the fixed costs of the pipe (it falls
under the operating costs category, increasing for decreasing pipe costs)
• That is, maybe you can pay a little more for a larger pipe size and avoid
the need to buy a bigger pump, power unit and other equipment
MAC =
(
CRF $big − $small )
(
Ot kWbig − kWsmall ) (79)
where MAC has the same units as Cf; and $big -$small is the difference in
pump+motor+equipment costs for two different capacities
• The difference in fixed purchase price is annualized over the life of the
system by multiplying by the CRF, as previously calculated
• The difference in pump size is expressed as ∆BHP, where ∆BHP is the
difference in brake horsepower, expressed as kW
• To determine the appropriate pump size, base the smaller pump size on a
low friction system (or low pressure system)
• For BHP in kW:
QsHpump
BHP =
102Ep
(80)
⎡ (1 + e )n − (1 + i )n ⎤ ⎡ i ⎤
EAE = ⎢ ⎥⎢ ⎥ (81)
⎢ e −i ⎥ ⎢ (1 + i )n − 1⎥
⎣ ⎦⎣ ⎦
where e is the annual inflation rate (fraction), i is the annual interest rate
(fraction), and n is in years
• Recall that the velocity limit is usually taken to be about 5 fps, or 1.5 m/s
9. Determine the difference in WHP between adjacent pipe sizes by equating the
annual plus annualized fixed costs for two adjacent pipe sizes:
∆WHPs1−s2 =
(UACs2 − UACs1)
E' (84)
10. Determine the difference in friction loss gradient between adjacent pipe sizes:
⎛ ∆WHPs1− s2 ⎞
∆Js1− s2 = 102 ⎜ ⎟
⎝ Qs ⎠ (85)
• This is the head loss difference needed to balance fixed and annual costs
for the two adjacent pipe sizes
• The coefficient 102 is for Qs in lps, and ∆WHP in kW
• You can also put Qs in gpm, and ∆WHP in HP, then substitute 3,960 for
102, and you will get exactly the same value for ∆J
• As before, ∆J is a head loss gradient, in head per 100 units of length (m
or ft, or any other unit)
• Thus, ∆J is a dimensionless “percentage”: head, H, can be in m, and
when you define a unit length (e.g. 100 m), the H per unit meter becomes
dimensionless
• This is why you can calculate ∆J using any consistent units and you will
get the same result
11. Calculate the flow rate corresponding to this head loss difference:
∆J =
800 f q2
gπ 2 (Ds1−5 − Ds2−5 ) (87)
0.54
⎡ ⎤
∆J
q = C⎢ ⎥
( )
(88)
⎢ 16.42(10)6 D−4.87 − D−4.87 ⎥
⎣ s1 s2 ⎦
• This is the flow rate for which either size (Ds1 or Ds2) will be the most
economical (it is the balancing point between the two adjacent pipe sizes)
• For a larger flow rate you would choose size Ds2, and vice versa
12. Repeat steps 8 through 11 for all other adjacent pipe sizes.
13. You can optionally create a graph with a log-log scale with the system flow
rate, Qs, on the ordinate and the section flow rate, q, on the abscissa:
• Find the needed flow rate in a given section of the pipe, q, make an
intersection with the maximum system capacity (Qs, on the ordinate), then
see which pipe size it is
• You can use the graph for different system capacities, assuming you are
considering different total irrigated areas, or different crop and or climate
values
• Otherwise, you can just skip step 13 and just do the calculations on a
spreadsheet for the particular Qs value that you are interested in
• The graph is perhaps didactic, but doesn’t need to be constructed to
apply this economic pipe selection method
1. If any of the economic factors (interest rate, inflation rate, useful life of the
system) change, the lines on the graph will shift up or down, but the slope
remains the same (equal to the inverse of the velocity exponent for the head
loss equation: 1.852 for Hazen-Williams and 2.0 for Darcy-Weisbach).
2. Computer programs have been developed to use this and other economic
pipe selection methods, without the need for constructing a graphical solution
on log-log paper. You could write such a program yourself.
5. Note that the equivalent annual pipe cost considers the annual interest rate,
but not inflation. This is because financing the purchase of the pipe would be
done at the time of purchase, and we are assuming a fixed interest rate. The
uncertainty in this type of financing is assumed by the lending agency.
6. This method is not normally used for designing pipe sizes in laterals. For
one thing, it might recommend too many different sizes (inconvenient for
operation of periodic-move systems). Another reason is that we usually use
different criteria to design laterals (the “20%” rule on pressure variation).
7. Other factors could be included in the analysis. For example, there may be
certain taxes or tax credits that enter into the decision making process. In
general, the analysis procedure in determining pipe sizes can get as
complicated as you want it to – but higher complexity is better justified for
larger, more expensive irrigation systems.
• It is often a good idea to apply more than one pipe selection method and
compare the results
• For example, don’t accept a recommendation from the economic selection
method if it will give you a flow velocity of more than about 10 ft/s (3 m/s),
otherwise you may have water hammer problems during operation
• However, it is usually advisable to at least apply the economic selection
method unless the energy costs are very low
• In many cases, the same pipe sizes will be selected, even when applying
different methods
4Q
D= (89)
πV
• The following tables show maximum flow rates for specified average velocity
limits and different pipe inside diameters
• The basic design criterion is to size lateral pipes so that pressure variation
along the length of the lateral does not exceed 20% of the nominal design
pressure for the sprinklers
• This criterion is a compromise between cost of the lateral pipe and
application uniformity in the direction of the lateral
• Note that the locations of maximum and minimum pressure along a lateral
pipe can vary according to ground slope and friction loss gradient
∑i=1∑ j=1(hf ) j
n i
(hf )a =
n +1 (91)
where n is the number of sprinklers; (hf)total is the total friction head loss from
0 to L; (hf)i is the friction head loss in the lateral pipe between sprinklers i-1
and i; and (hf)a is the friction loss from the lateral inlet to the location of ha
• As indicated above, (hf)a occurs over approximately the first 40% of the
lateral
• Note that between sprinklers, the friction head loss gradient is linear in the
lateral pipe
• Note also that (hf)0 = 0, but it is used in calculating (ha)f, so the denominator
is (n+1), not n
Hazen-Williams Equation:
1.852
12 ⎛ Q ⎞
J = 1.21(10) ⎜ ⎟ D−4.87 (93)
⎝C⎠
for J in meters of friction head loss per 100 m (or ft/100 ft); Q in lps; and D in
mm
⎛q ⎞
Q = Ql − ⎜ a ⎟ x (94)
⎝ Se ⎠
for multiple, equally-spaced sprinkler outlets spaced at Se (m) from each
other, with constant discharge of qa (lps). Ql is the flow rate at the lateral
inlet (entrance).
• To find the location of minimum pressure, let J = S, where S is the ground
slope (in %, because J is per 100 m), which is negative for downhill-sloping
laterals
• Combining the two above equations and solving for x,
x=
Se ⎡
qa ⎣
(
Ql − 3(10)−7 C ( −S)0.54 D2.63 ⎤
⎦ ) (95)
where x is the distance, in m, from the lateral inlet to the minimum pressure
Merkley & Allen Page 74 Sprinkle & Trickle Irrigation Lectures
• S is in percent; Se and x are in m; D is in mm; and Ql and qa are in lps
• Note that the valid range of x is: 0 ≤ x ≤ L, and that you won’t necessarily get
J = S over this range of x values:
• This means that the above equation for x is valid for all ground slopes: S = 0,
S > 0 and S < 0
• Except for the most unusual circumstances (e.g. non-uniform downhill slope
that exactly matches the shape of the hf curve), the pressure will vary with
distance in a lateral pipe
• According to Keller & Bliesner’s design criterion, the required inlet pressure
head to a sprinkler lateral is that which makes the average pressure in the
lateral pipe equal to the required sprinkler pressure head, ha
3 1
hl = ha + hf + ∆he (96)
4 2
• hl is the required pressure head at the lateral inlet
• Strictly speaking, we should take approximately 0.4∆he in the above
equation, but we are taking separate averages for the friction loss and
elevation gradients – and, this is a design equation
• Of course, instead of head, h, in the above equation, pressure, P, could be
used if desired
• For steep downhill slopes, where the minimum pressure would be at the
lateral inlet, it is best to let
hf = −∆he (97)
• We now have an equation to calculate lateral inlet pressure based on ha, hf,
and he
• This is the same as saying that we will not allow pipes that are too small, that
is, pipes that would produce a large hf value
• An additional head term must be added to the equation for hl to account for
the change in elevation from the lateral pipe to the sprinkler (riser height):
3 1
hl = ha + hf + ∆he + hr (100)
4 2
or, in terms of pressure…
3 1
Pl = Pa + Pf + ∆Pe + Pr (101)
4 2
V. Friction Losses in Pipes with Multiple Outlets
• Pipes with multiple outlets have decreasing flow rate with distance (in the
direction of flow), and this causes the friction loss to decrease by
approximately the square of the flow rate (for a constant pipe diameter)
• Sprinkler and trickle irrigation laterals fall into this hydraulic category
• Multiply the head loss for a constant discharge pipe by a factor “F” to reduce
the total head loss for a lateral pipe with multiple, equally spaced outlets:
JFL
hf = (102)
100
where F is from Eq. 8.9a
1 1 b −1
F= + + (103)
b + 1 2N 6N2
for equally spaced outlets, each with the same discharge, and going all the
way to the end of the pipe.
• All of the flow is assumed to leave through the outlets, with no “excess”
spilled out the downstream end of the pipe
• N is the total number of equally spaced outlets
• The value of b is the exponent on Q in the friction loss equation
NF − (1 − α)
F(α) = (104)
N − (1 − α)
where 0 < α ≤ 1
• If the minimum pressure is at the end of the lateral, which is the case for no
ground slope, uphill, and slight downhill slopes, then the change in pressure
head over the length of the lateral is:
∆h = h f + ∆h e (105)
JaFL
0.20ha − ∆he = (107)
100
and,
⎛ 0.20ha − ∆he ⎞
Ja = 100 ⎜ ⎟ (108)
⎝ FL ⎠
hf = −∆he (109)
⎛ −∆he ⎞
Ja = 100 ⎜ ⎟ (110)
⎝ FL ⎠
1. hmax is either at the lateral inlet or at the end of the lateral, and
2. hmin is somewhere between the lateral inlet and the end
• Given a value of Ja, the inside diameter of the lateral pipe can be calculated
from the Hazen-Williams equation:
0.205
⎡ K ⎛ Q ⎞1.852 ⎤
D=⎢ ⎜ l⎟ ⎥ (111)
⎢⎣ Ja ⎝ C ⎠ ⎥⎦
where Ql is the flow rate at the lateral inlet (Nqa) and K is the units coefficient
in the Hazen-Williams equation
Nn = 396/12 = 33 sprinklers
F = 0.36
Ql = (0.315)(33) = 10.4 lps
∆he = SL = (-0.0253)(396) = -10.0 m
Now, 0.3ha < -∆he (steep downhill). Therefore, may want to use hf = -∆he.
Then, Ja is:
⎛ −∆he ⎞ ⎛ −( −10.0m) ⎞
Ja = 100 ⎜ ⎟ = 100 ⎜ ⎟ = 7.01m /100m (112)
⎝ FL ⎠ ⎝ (0.36)(396) ⎠
For now, let’s use Ja = 7.01 m/100 m. Then, the minimum pipe inside
diameter is (C ≈ 130 for aluminum):
0.205
⎡ 1.21E12 ⎛ 10.4 ⎞1.852 ⎤
D=⎢ ⎜ ⎟ ⎥ = 77.7mm (114)
⎢⎣ 7.01 ⎝ 130 ⎠ ⎥⎦
However, it would be a good idea to also try the 3” size and see how the
lateral hydraulics turn out (this is done below; note also that for Ja = 11.6,
D = 70.0 mm).
1.852
⎛ 10.4 ⎞
J = 1.21E12 ⎜ ⎟ ( 99.1 mm)−4.87 = 2.14m /100m (115)
⎝ 130 ⎠
JFL (2.14)(0.36)(396)
hf = = = 3.06 m (116)
100 100
The required lateral inlet pressure head is:
hl = ha + 0.75hf + 0.5∆he + hr
(117)
hl = 320 / 9.81 + 0.75(3.06) + 0.5( −10.0) + 1.0 = 30.9 m
VI.5. Calculate the pressure and head at the end of the lateral pipe
which is equal to 371 kPa. Thus, the pressure at the end of the lateral
pipe is greater than the pressure at the inlet.
To determine the pressure at the last sprinkler head, subtract the riser
height to get 37.8 m – 1.0 m = 36.8 m (361 kPa)
x=
Se ⎡
qa ⎣
(
Ql − 3(10)−7 C( −S)0.54 D2.63 ⎤
⎦ )
(119)
x=
12 ⎡
0.315 ⎣
(
10.4 − 3(10)−7 130(2.53)0.54 (99.1)2.63 ⎤ = −39.6 m
⎦ )
The result is negative, indicating that that minimum pressure is really at
the entrance (inlet) to the lateral pipe. The minimum sprinkler head
pressure is equal to hl – hr = 30.9 – 1.0 = 29.9 m, or 293 kPa.
The maximum pressure is at the last sprinkler (end of the lateral), and the
minimum pressure is at the first sprinkler (lateral inlet). The percent
pressure variation is:
That is, 21% pressure variation at the sprinklers, along the lateral
This is larger than the design value of 0.20, or 20% variation. But it is
very close to that design value, which is somewhat arbitrary anyway.
VI.8. Redo the calculations using a 3” lateral pipe instead of the 4” size
In this case, the location of the minimum pressure in the lateral pipe is:
x=
12 ⎡
0.315 ⎣
(
10.4 − 3(10)−7 130(2.53)0.54 (73.7)2.63 ⎤ = 196 m
⎦ ) (121)
There are about 196/12 = 16 sprinklers from the lateral inlet to the
location of minimum pressure, and about 17 sprinklers from x to the end
of the lateral.
1.852
⎛ (17)(0.315) ⎞
Jx −end = 1.21E12 ⎜ ⎟ ( 73.7 )−4.87 = 2.65 m /100 m
⎝ 130 ⎠ (122)
(2.65)(0.38)(396 − 196)
(hf )x −end = = 2.01 m (123)
100
Friction loss from the inlet to the end is:
1.852
⎛ 10.4 ⎞
Jinlet −end = 1.21E12 ⎜ ⎟ ( 73.7 )−4.87 = 9.05 m /100 m (124)
⎝ 130 ⎠
hl = ha + 0.75hf + 0.5∆he + hr
(127)
hl = 320 / 9.81 + 0.75(12.9) + 0.5(−10.0) + 1.0 = 38.3 m
giving Pend of (35.4)(9.81) = 347 kPa, which is less than Pl. So, the
maximum lateral pipe pressure is at the inlet.
which turns out to be slightly less than the design value of 20%
⎛ 0.20ha − ∆he ) ⎞
Ja = 100 ⎜ ⎟
⎝ FL ⎠
(131)
⎛ 0.2(320 / 9.81) − 10.0 ⎞
= 100 ⎜ ⎟ = −2.44m /100m
⎝ (0.36)(396) ⎠
which is negative because ∆he > 0.2ha, meaning that it is not possible to
have only a 20% variation in pressure along the lateral, that is, unless
flow control nozzles and or other design changes are made.
Either the 3” or 4” aluminum pipe size could be used for this lateral
design. The 4” pipe will cost more than the 3” pipe, but the required
lateral inlet pressure is less with the 4” pipe, giving lower pumping costs,
assuming pumping is necessary.
Note that it was assumed that each sprinkler discharged 0.315 lps, when
in reality the discharge depends on the pressure at each sprinkler. To
take into account the variations in sprinkler discharge would require an
iterative approach to the mathematical solution (use a computer).
Most sprinkler laterals are laid on slopes less than 2.5%, in fact, most are
on fields with less than 1% slope.
1. a reduction in hf
2. an increase in hf
• In either case, the basic objective is to reduce pressure variations along the
lateral pipe by arranging the friction loss curve so that it more closely
parallels the ground slope
• It is not normally desirable to have more than one pipe size in portable
laterals (hand-move, wheel lines), because it usually makes set changes
more troublesome
• For fixed systems with buried laterals, it may be all right to have more than
two pipe diameters along the laterals
• For dual pipe size laterals, approximately 5/8 of the pressure loss due to
friction occurs between the lateral inlet and the location of average pressure
• Case 1: a lateral on level ground where one pipe size is too small, but the
next larger size is too big...
• The composite friction loss curve for d1 and d2 more closely parallels the
ground slope than the curve with only d1, which means that the pressure
variation along the lateral is less with the dual pipe size design
Section Flow Distance Diameter hf Sum (hf) d(he) head diff from hf/(hf)total
(lps) (m) (cm) (m) (m) (m) (m) ha (%)
1 40.00 9.00 15.00 0.31 0.31 0 49.69 12.08 0.016
2 39.60 18.00 15.00 0.31 0.62 0 49.38 11.77 0.032
3 39.20 27.00 15.00 0.30 0.92 0 49.08 11.47 0.048
4 38.80 36.00 15.00 0.29 1.21 0 48.79 11.18 0.064
5 38.40 45.00 15.00 0.29 1.50 0 48.50 10.89 0.079
6 38.00 54.00 15.00 0.28 1.79 0 48.21 10.61 0.094
⎛ J FL J F x ⎞ ⎛ J F x ⎞
hf = ⎜ 1 1 − 2 2 2 ⎟ + ⎜ 3 2 2 ⎟ (132)
⎝ 100 100 ⎠ ⎝ 100 ⎠
where,
hf = total lateral friction head loss for dual pipe sizes
for,
⎛ 20%ha − ∆he ⎞
Ja = 100 ⎜ ⎟
⎝ FL ⎠ (136)
1 ⎛ 4 ⎞
F1 ≈ 0.351 + ⎜ 1 + ⎟ (137)
2N1 ⎝ 13N1 ⎠
1 ⎛ 4 ⎞
F2 ≈ 0.351 + ⎜1 + ⎟ (138)
2N2 ⎝ 13N2 ⎠
where
L
N1 = (139)
Se
L − x1
N2 = (140)
Se
1.852
⎛Q ⎞
J1 = K ⎜ 1 ⎟ D1−4.87 (141)
⎝C⎠
1.852
⎛Q ⎞
J2 = K ⎜ 2 ⎟ D1−4.87 (142)
⎝ C ⎠
1.852
⎛Q ⎞
J3 = K ⎜ 2 ⎟ D2−4.87 (143)
⎝ C ⎠
where
⎛ L ⎞
Q1 = ⎜ ⎟ qa (144)
⎝ e⎠
S
⎛ L − x1 ⎞
Q2 = ⎜ ⎟ qa (145)
⎝ e ⎠
S
• The coefficient K in Eqs. 141-143 is 1,050 for gpm & inches; 16.42(10)6 for
lps and cm; or 1.217(10)12 for lps and mm
Sprinkle & Trickle Irrigation Lectures Page 89 Merkley & Allen
• Combine the above equations and set it equal to zero:
f ( x1 ) = α1 ⎡α 2 − α3 (L − x1 ) F2 ⎤ − 0.2ha + ∆he = 0
2.852
(146)
⎢⎣ ⎥⎦
where
K
α1 = (147)
100 C1.852
1.852
⎛q L⎞
α2 = ⎜ a ⎟ D1−4.87F1 L (148)
⎝ Se ⎠
1.852
α3 = ( D1−4.87 − D2−4.87 ) ⎛ qa ⎞
⎜ ⎟
⎝ Se ⎠
(149)
df(x1)
=
dx1
(150)
⎡ S (L − x1)0.852 ⎛ 8Se ⎞ ⎤
= α1α3 ⎢ 2.852F2 (L − x1)1.852 − e ⎜ 1 + ⎟⎥
⎢⎣ 2 ⎝ 13(L − x1) ⎠ ⎥⎦
• Note that the solution may fail if the sizes D1 & D2 are inappropriate
• To make things more interesting, give the computer program a list of inside
pipe diameters so that it can find the most appropriate available values of D1
& D2
• Note that the Darcy-Weisbach equation could be used instead of Hazen-
Williams
• In Eq. 146 you could adjust the value of the 0.2 coefficient on ha to determine
its sensitivity to the pipe diameters and lengths
• The following screenshot is of a small computer program for calculating
diameters and lengths of dual pipe size sprinkler laterals
5 1
hl = ha + hf + ∆he + hr
8 2 (151)
• This is the same as the lateral inlet pressure head equation for single pipe
size, except that the coefficient on hf is 5/8 instead of 3/4
• Remember that for a downhill slope, the respective pressure changes due to
friction loss and due to elevation change are opposing
where hcv is the pressure head loss through the flow control device
• For a lateral with flow control devices, the average pressure is not equal to
the nominal sprinkler pressure
havg ≠ ha
(153)
2
⎛q ⎞
ha = ⎜ a ⎟
⎝ Kd ⎠ (154)
• Valves are available for preventing flow through sprinklers until a certain
minimum pressure is reached
• These valves are installed at the base of each sprinkler and are useful where
sprinkler irrigation is used to germinate seeds on medium or high value crops
• The valves help prevent seed bed damage due to low pressure streams of
water during startup and shutdown
• But, for periodic-move, the lines still must be drained before moving
• The question is, for known inlet head, H0, pipe diameter, D, sprinkler spacing,
Se, ground slope, So, sprinkler discharge coefficient, Kd, riser height, hr, and
pipe material (C factor), what is the flow rate through each sprinkler?
• Knowing the answer will lead to predictions of application uniformity
• In this case, we won’t assume a constant qa at each sprinkler
Hazen-Williams equation:
JL
hf = (155)
100
1.852
6⎛Q⎞
J = 16.42 (10 ) ⎜ ⎟ D−4.87
⎝C⎠ (156)
1.852
JSe ⎛Q⎞
= 16.42 (10 ) Se ⎜ ⎟ D−4.87
4
hf =
100 ⎝C⎠ (157)
or,
hf = hw Q1.852 (158)
where Q is the flow rate in the lateral pipe between two sprinklers, and
typically,
q = Kd h (160)
where q is the sprinkler flow rate in lps; h is the pressure head at the
sprinkler in m; and Kd is an empirical coefficient: Kd = KoA, where A is the
cross sectional area of the inside of the pipe
• Suppose there are only four sprinklers, evenly spaced (see the above figure)
• Suppose that we know H0, Kd, C, D, hr, So, and Se
(Q − Q )
2 2
⎛q ⎞
q1 = K d H1 − hr → H1 = hr + ⎜ 1 ⎟ = hr + 1 2 2 (161)
⎝ Kd ⎠ Kd
(Q − Q )
2 2
⎛q ⎞
q2 = K d H2 − hr → H2 = hr + ⎜ 2 ⎟ = hr + 2 2 3 (162)
⎝ Kd ⎠ Kd
(Q − Q )
2 2
⎛q ⎞
q3 = K d H3 − hr → H3 = hr + ⎜ 3 ⎟ = hr + 3 2 4 (163)
⎝ Kd ⎠ Kd
2
⎛ q4 ⎞ Q42
q4 = K d H4 − hr → H4 = hr + ⎜ ⎟ = hr + 2 (164)
⎝ Kd ⎠ Kd
where,
Se
∆he = (169)
So−2 +1
( Q 2 − Q3 ) 2 = H 1.852
1 − h w Q2 − ∆he − hr (171)
K d2
Q4 2
= H3 − hw Q41.852 − ∆he − hr (173)
K d2
f1 = H0 −
( Q1 − Q2 )
2
−h 1.852
− ∆he − hr = 0
w Q1 (174)
K 2d
f2 =
( Q1 − Q2 )
2
−
( Q2 − Q3 )
2
−h 1.852
− ∆he − hr = 0
w Q2 (175)
K 2d K 2d
f3 =
( Q2 − Q3 )
2
−
( Q3 − Q4 )
2
−h 1.852
− ∆he − hr = 0
w Q3 (176)
K 2d K 2d
f4 =
( Q3 − Q4 )
2
−
Q 42
−h 1.852
− ∆he − hr = 0
w Q4 (177)
K 2d K 2d
⎡ ∂f1 ∂f1 ⎤ ⎡ ⎤ ⎡ ⎤
⎢ ∂Q ∂Q2 ⎥ ⎢ δQ1 ⎥ ⎢ f1 ⎥
⎢ 1 ⎥ ⎢ ⎥ ⎢ ⎥
⎢ ∂f2 ∂f2 ∂f2 ⎥ ⎢ ⎥ ⎢ ⎥
⎢ ∂Q ∂Q2 ∂Q3 ⎥ ⎢ δQ2 ⎥ ⎢ f2 ⎥
⎢ 1 ⎥ ⎢ ⎥ =⎢ ⎥ (178)
⎢ ∂f3 ∂f3 ∂f3 ⎥ ⎢ ⎥ ⎢ ⎥
⎢ ⎥ ⎢ δQ3 ⎥ ⎢ f3 ⎥
⎢ ∂Q2 ∂Q3 ∂Q4 ⎥
⎢ ⎥ ⎢ ⎥
⎢ ∂f4 ∂f4 ⎥ ⎢ δQ ⎥ ⎢ f4 ⎥
⎢ ⎥ ⎢ 4
⎥ ⎢ ⎥
⎣ ∂Q3 ∂Q4 ⎦ ⎣ ⎦ ⎣ ⎦
where the two values in the first row of the square matrix are:
∂f1 −2 ( Q1 − Q2 )
= − 1.852hw Q10.852 (179)
∂Q1 2
Kd
∂f1 2 ( Q1 − Q2 )
= (180)
∂Q2 K 2d
∂fn 2 ( Qn−1 − Qn )
= (181)
∂Qn−1 K 2d
∂fn −2Qn−1
= − 1.852hw Qn0.852 (182)
∂Qn 2
Kd
and the three values in each intermediate row of the matrix are:
∂fi 2 ( Qi−1 − Qi )
= (183)
∂Qi−1 K 2d
∂fi 2 ( Qi − Qi+1 )
= (185)
∂Qi+1 K 2d
• The problem could be further generalized by allowing for different pipe sizes
in the lateral, by including minor losses, by allowing variable elevation
changes between sprinkler positions, etc.
• However, it is still a problem of solving for x unknowns and x equations
• For pumped systems (not gravity, as above), we could include a
mathematical representation of the pump characteristic curve to determine
the lateral hydraulic performance; that is, don’t assume a constant H0, but
replace it by some function
• There is a computer program that will do the above calculations for a gravity-
fed lateral with multiple sprinklers
• But, if you want to write your own program in a simpler way, you can do the
calculations by “brute-force” as follows:
I. Split-Line Laterals
Sprinkle & Trickle Irrigation Lectures Page 101 Merkley & Allen
• In the above case, and for only a single lateral on the mainline, the design of
the mainline is relatively simple – it is easy to find the most extreme
operating position
• However, the friction loss along the mainline is about four times greater than
for the split-line configuration
• Note that for the above two configurations the first sprinkler on the laterals
would be at 0.5Se from the inlet, unless the mainline is laid upon a roadway
in the field
Merkley & Allen Page 102 Sprinkle & Trickle Irrigation Lectures
• Buried mainlines tend to last longer, because they are not handled and
banged up after installation
• See example 10.1 from the textbook, an uphill mainline design for two split-
line laterals
• For design, consider the two extreme lateral positions:
• Divide the mainline into two logical lengths, at the mid-point, according to the
two extreme lateral positions
• Determine the total allowable head loss due to friction in each of these logical
lengths, then find two adjacent pipe sizes for each length
• Determine the lengths of each pipe size so that the total head loss is just
equal to the allowable head loss
• This is somewhat analogous to the procedure for designing dual pipe size
laterals
• This is the system layout (shown with both laterals at position B):
Sprinkle & Trickle Irrigation Lectures Page 103 Merkley & Allen
• Pump provides at least 172 ft of head at P
• Lateral inlet pressure head is given as 125 ft of head (Eq. 9.2)
• Supply line and mainline are to be aluminum, in 30-ft lengths
• The figure below shows the hydraulic schematic for this mainline, with
separate friction loss profiles for the two extreme lateral positions
• The mainline is tentatively divided into sizes D1 and D2 for the first half (L1),
and D3 and D4 for the second half (L2). So, there are potentially four different
pipe sizes in the mainline from A to C.
Merkley & Allen Page 104 Sprinkle & Trickle Irrigation Lectures
II. Select the Size of the Supply Line
• We need to select the size of the supply line to know what the head loss is
from P to A (pressure at P is given as 172 ft of head)
• Assume no elevation change between P and A
4Q 4 (1.11 cfs )
D= = = 0.53 ft (186)
πV π ( 5 fps )
• This is 6.4 inches. In Table 8.4, the 6-inch pipe has an inside diameter of
5.884 inches. With this size, the velocity at 500 gpm would be 5.9 ft/s, which
we will accept (could use 8-inch pipe, but 6-inch is probably OK)
• From Table 8.4, the head loss gradient in the 6-inch supply line at 500 gpm is
2.27 ft/100 ft. Then,
• We will tolerate (hf)1 head loss over section L1 of the mainline when both
laterals are operating at B. This will give the required hl at B.
• We can see that (hf)1 is defined as:
⎛ 30 ft ⎞
( Ja )L1 = 100 ⎜ ⎟ = 5 ft per 100 ft (190)
⎝ 600 ft ⎠
• From Table 8.4, this is between the 5- and 6-inch pipe sizes, which have
respective loss gradients of 5.54 ft/100 ft and 2.27 ft/100 ft for the 500 gpm
flow rate. Therefore, choose D1 = 6 inch and D2 = 5 inch.
Sprinkle & Trickle Irrigation Lectures Page 105 Merkley & Allen
• Now we must find out how long D1 should be so that the friction loss is really
equal to 30 ft of head...
• With the adjusted lengths, we will get 30.3 ft of head loss over section L1 for
500 gpm (this is close enough to the allowable 30 ft)
• We will tolerate (hf)3 + (hf)4 head loss over the whole length of the mainline
when one lateral is operating at A and the other at C
• We can calculate (hf)4 straight away because we already know the pipe sizes
and lengths in section L1...
hf 4 =
( 90 ft )( 0.63 ) + ( 510 ft )(1.53 ) = 8.37 ft (194)
100
where the friction loss gradients for 250 gpm are 0.63 ft/100 ft (6” size) and
1.53 ft/100 ft (5” size). These values were taken from Table 8.4.
• Now we need to know the allowable loss for (hf)3, such that the pressure in
the mainline at C will be equal to hl (we know that the pressure at A is 162 ft -
- it is more than enough)...
⎛ 14.6 ft ⎞
( Ja )L2 = 100 ⎜ ⎟ = 2.43 ft per 100 ft (197)
⎝ 600 ft ⎠
Merkley & Allen Page 106 Sprinkle & Trickle Irrigation Lectures
• From Table 8.1, this is between the 4- and 5-inch pipe sizes, which have
respective loss gradients of 4.66 ft/100 ft and 1.53 ft/100 ft for the 250 gpm
flow rate. Therefore, choose D3 = 5 inch and D4 = 4 inch.
• Now we must find out how long D3 should be so that the friction loss is really
equal to 14.6 ft of head...
• With the adjusted lengths, we will get 14.8 ft of head loss over section L2 for
250 gpm (this is close enough to the allowable 14.6 ft)
• Just to be sure, suppose that one lateral is operating halfway between A and
B, and the other halfway between B and C
• The allowable friction loss from point A to the furthest lateral is (hf)2 + ¼∆he,
or 23.0 ft + 3.5 ft = 26.5 ft. The actual friction loss would be:
• OK, the head in the mainline at the furthest lateral is more than enough
• See the figure below for a graphical interpretation of the two laterals in
intermediate positions
Sprinkle & Trickle Irrigation Lectures Page 107 Merkley & Allen
VI. Comments About the Mainline Design
• The lateral inlet pressure will be just right when both laterals operate at B
• The lateral inlet pressure will be just right for a lateral operating at C
• The lateral inlet pressure will always be too high for a lateral operating
between A and B (the inlet pressure to the mainline, at A, is always 162 ft)
• We designed D1 and D2 for the condition when both laterals are at B. This is
a more demanding condition for L1 than when one lateral is at A and the
other at C (in this case, only half the system flow rate is in L1). So, we don’t
need to “check” D1 and D2 again for the case when the laterals are at A and
C.
• We didn’t consider the hydrant loss from the mainline into the sprinkler
lateral, but this could be added to the requirements (say, effective hl)
• This design could be also done using the economic pipe selection method (or
another pipe selection method. It would be a good idea to check to see if the
Merkley & Allen Page 108 Sprinkle & Trickle Irrigation Lectures
172 ft at the pump (point A) could be reduced by using larger supply and
mainline pipes, thus reducing the annual energy costs. However, if the 172 ft
were due to gravity supply, the design would still be all right.
• However, the velocity in the 5-inch pipe at 500 gpm is too high, at 8.5 fps
(always check velocity limits when sizing pipes!)
• How would the mainline design change if it were not split line operation, and
both laterals were operating at location C?
• In this case, intuition and past experience tells us location C is the critical
lateral position – if you don’t agree, then you should test other lateral
positions to convince yourself
• We will tolerate (hf)2 head loss over the entire 1,200-ft length of the mainline
when both laterals are operating at C. This will give the required hl at C.
• We can see that (hf)2 is defined as:
• The allowable loss gradient over the length of the mainline for both laterals
operating at C is
⎛ 23 ft ⎞
Ja = 100 ⎜ ⎟ = 1.92 ft per 100 ft (204)
⎝ 1,200 ft ⎠
• From Table 8.4, this is between the 6- and 8-inch pipe sizes, which have
respective loss gradients of 2.27 ft/100 ft and 0.56 ft/100 ft for the 500 gpm
flow rate
• Determine the respective pipe lengths so that the friction loss is really equal
to 23 ft of head...
Sprinkle & Trickle Irrigation Lectures Page 109 Merkley & Allen
Merkley & Allen Page 110 Sprinkle & Trickle Irrigation Lectures
Lecture 10
Minor Losses & Pressure Requirements
I. Minor Losses
• Minor (or “fitting”, or “local”) hydraulic losses along pipes can often be
estimated as a function of the velocity head of the water within the particular
pipe section:
V2
hml = Kr (208)
2g
where hml is the minor loss (m or ft); V is the mean flow velocity, Q/A (m/s or
fps); g is the ratio of weight to mass (9.81 m/s2 or 32.2 ft/s2); and Kr is a
coefficient, dependent on the type of fitting (valve, bend, transition,
constriction, etc.)
• In using Tables 11.1 and 11.2 for hydrants, the nominal diameter (3, 4, 5,
and 6 inches) is the diameter of the hydrant and riser pipe, not the diameter
of the source pipeline
• Use the diameter of the hydrant for Kr and for computing Vr. However, for
line flow past a hydrant, use the velocity in the source pipeline, as indicated
above.
• Always use the largest velocity along the path which the water travels – this
may be either upstream or downstream of the fitting
• Do not consider velocities along paths through which the water does not flow
Sprinkle & Trickle Irrigation Lectures Page 111 Merkley & Allen
( )
2
Kr = 0.7 1 − Dr2 (209)
( )
2
Kr = K f 1 − Dr2 (210)
and f is the angle of the expansion or contraction in the pipe walls (degrees
or radians), where f ≥ 0
Expansion
Contraction
• For a sudden (abrupt) expansion, the head loss can also be approximated as
a function of the difference of the mean flow velocities upstream and
downstream:
Merkley & Allen Page 112 Sprinkle & Trickle Irrigation Lectures
hml =
( Vus − Vds )
2
(212)
2g
• An extreme (albeit unrealistic) case is for Vds = 0 and hml = Vus2/2g (total
conversion of velocity head)
• Various other equations (besides those given above) for estimating head loss
in pipe expansions and contractions have been proposed and used by
researchers and engineers
0.070 m3 / s
V200 = = 2.23 m / s (213)
⎛ π(0.200 m)2 ⎞
⎜⎜ ⎟⎟
⎝ 4 ⎠
0.070 − 0.016 m3 / s
V150 = = 3.06 m / s (214)
⎛ π(0.150 m)2 ⎞
⎜⎜ ⎟⎟
⎝ 4 ⎠
0.016 m3 / s
Vhydrant = = 3.62 m / s (215)
⎛ π(0.075 m)2 ⎞
⎜⎜ ⎟⎟
⎝ 4 ⎠
Sprinkle & Trickle Irrigation Lectures Page 113 Merkley & Allen
• Note that V200 and V150 are both above the normal design limit of about 2 m/s
• The head loss past the open hydrant is based on the higher of the upstream
and downstream velocities, which in this example is 3.06 m/s
• From Table 11.1, the Kr for flow past the open hydrant (line flow; 6” mainline)
is 0.5; thus,
(3.06)2
(hml )past = 0.5 = 0.24m (216)
2(9.81)
• The head loss due to the contraction from 200 mm to 150 mm diameter (at
the hydrant) depends on the transition
• If it were an abrupt transition, then:
2
⎡ ⎛ 150 ⎞2 ⎤
Kr = 0.7 ⎢1 − ⎜ ⎟ ⎥ = 0.13 (217)
⎢⎣ ⎝ 200 ⎠ ⎥⎦
• Thus, the total minor loss in the mainline in the vicinity of the open hydrant is
about 0.24 + 0.06 = 0.30 m (0.43 psi).
• The loss through the hydrant is determined by taking Kr = 8.0 (Table 11.1; 3”
hydrant):
(3.62)2
(hml )through = 8.0 = 5.3m (219)
2(9.81)
• This is a high loss through the hydrant (about 7.6 psi), so it may be advisable
to use a larger diameter hydrant.
• The pressure in the mainline downstream of the hydrant is (9.81 kPa/m):
⎛ V200
2 2 ⎞
− V150
P150 = P200 − γ (hml )past + γ⎜ ⎟
⎜ 2g ⎟
⎝ ⎠
(220)
⎛ (2.23) − (3.06)
2 2 ⎞
P150 = 300 − (9.81)(0.24) + 9.81⎜ = 295kPa
⎜ 2(9.81) ⎟⎟
⎝ ⎠
Merkley & Allen Page 114 Sprinkle & Trickle Irrigation Lectures
II. Total Dynamic Head
• The Total Dynamic Head (TDH) is the head that the pump “feels” or “sees”
while working, and is calculated to determine the pump requirements
• It includes the elevation that the water must be lifted from the source (not
necessarily from the pump elevation itself) to the outlet, the losses due to
“friction”, the pressure requirement at the outlet, and possibly the velocity
head in the pipeline
• For a sprinkler system, the value of TDH depends on the positions of the
laterals, so that it can change with each set. Pump selection is usually made
for the “critical” or extreme lateral positions, that is, for the “worst case
scenario”.
• Keller & Bliesner recommend the addition of a “miscellaneous” loss term,
equal to 20% of the sum of all “friction” losses. This accounts for:
• The system curve determines the relationship between TDH and flow rate
• This curve is approximately parabolic, but can take more complex shapes
• Note that head losses in pipe systems are approximately proportional to the
square of the flow rate (Q2 or V2)
• For the Hazen-Williams equation, these losses are actually proportional to
Q1.852 or V1.852
• For standard, non-FCN, sprinkler nozzles, the head at the sprinkler is also
proportional to Q2
• Sprinkler systems can have a different system curve for each position of the
lateral(s)
• Defining the system curve, or the “critical” system curve, is important for
pump selection because it determines, in part, the operating point (TDH and
Q) for the system
Sprinkle & Trickle Irrigation Lectures Page 115 Merkley & Allen
IV. Valving a Pump
I. Types of Pumps
1. Positive Displacement
• Piston pumps
• Rotary (gear) pumps
• Extruding (flexible tube) pumps
2. Variable Displacement
• Centrifugal pumps
• Injector pumps
• Jet pumps
Merkley & Allen Page 116 Sprinkle & Trickle Irrigation Lectures
Positive Displacement Pumps
Axial-Flow Impeller
Jet Pump
Sprinkle & Trickle Irrigation Lectures Page 117 Merkley & Allen
• But, with positive displacement pumps, the required pumping energy is a
linear function of the pressure
• Positive displacement pumps can be used with thick, viscous liquids. They
are not commonly used in irrigation and drainage, except for the injection of
chemicals into pipes and for sprayers
• Piston-type pumps can develop high heads at low flow rates
• Air injection, or jet pumps are typically used in some types of well drilling
operations. The air bubbles effectively reduce the liquid density and this
assists in bringing the drillings up out of the well. Needs a large capacity air
compressor.
• Homologous pumps are geometrically similar pumps, but of different sizes
1. Volute Case This is the most common type of irrigation and drainage pump
(excluding deep well pumps). Produce relatively high flow rates at low
pressures.
2. Diffuser (Turbine) The most common type for deep wells. Designed to lift
water to high heads, typically using multiple identical “stages” in series,
stacked up on top of each other.
3. Mixed Flow Uses a combination of centrifugal and axial flow action. For high
capacity at low heads.
4. Axial Flow Water flows along the axis of impeller rotation, like a boat
propeller. Appropriate for high discharge under very low lift (head). An
example is the pumping plant on the west side of the Great Salt Lake.
• In general, larger pumps have higher maximum efficiencies (they are more
expensive, and more effort is given toward making them more efficient)
• Impellers can be open, semi-open, or closed. Open impellers are usually
better at passing solids in the pumped liquid, but they are not as strong as
closed impellers
• Double suction inlet pumps take water in from both sides and can operate
without axial thrust
Merkley & Allen Page 118 Sprinkle & Trickle Irrigation Lectures
Closed Impeller Semi-Open Impeller Open Impeller
Characteristic Curve
Efficiency
Cha
ra cte
risi
cC
urv
Shut-Off Head
Power
0
0 Flow Rate, Q
Sprinkle & Trickle Irrigation Lectures Page 119 Merkley & Allen
III. Centrifugal Pumps in Parallel
• Pumps in PARALLEL
p
from the pumps
converging to a single
discharge pipe
• If only one of the
pumps operates, some 0
type of valve may be 0 Flow Rate, Q
required so that flow does not flow backwards through the idle pump
• Flow rate is additive in this case
pump 1
pump 2
Two Pumps in Parallel
• Pumps in SERIES means that the total flow passes through each of two or
more pumps in line
• Typical installations are for increasing pressure, such as with a booster pump
• Head is additive in this case
Merkley & Allen Page 120 Sprinkle & Trickle Irrigation Lectures
Total Dynamic Head, TDH
Two
in Se
rie
s
One P
ump
0
0 Flow Rate, Q
• It is common for turbine (well) pumps to operate in series
• For centrifugal pumps, it is necessary to exercise caution when installing in
series because the efficiency can be adversely affected
• May need straightening vanes between pumps to reduce swirling
• Note that the downstream pump could cause negative pressure at the outlet
of the US pump, which can be a problem
pump 1 pump 2
Sprinkle & Trickle Irrigation Lectures Page 121 Merkley & Allen
Merkley & Allen Page 122 Sprinkle & Trickle Irrigation Lectures
Lecture 11
Pumps & System Curves
where brake horsepower refers to the input power needed at the pump shaft
(not necessarily in “horsepower”; could be watts or some other unit)
QH
WHP = (222)
3956
where WHP is in horsepower; Q in gpm; and H in feet of head. The
denominator is derived from:
1 HP=0.746 kW (225)
P V2
TDH = ∆Elev + hf + + (226)
γ 2g
Sprinkle & Trickle Irrigation Lectures Page 123 Merkley & Allen
where the pressure, P, and velocity, V, are measured at the pump outlet, and
hf is the total friction loss from the entrance to the exit, including minor losses
P
TDH = ∆Elev + (227)
γ
but recognizing that in some cases P/γ is zero for a zero flow rate
Merkley & Allen Page 124 Sprinkle & Trickle Irrigation Lectures
Consider a centrifugal pump:
• Determine TDH and WHP for a centrifugal pump discharging into the air...
Sprinkle & Trickle Irrigation Lectures Page 125 Merkley & Allen
ε 1.5(10)−6
= = 0.0000051 (229)
D 0.295
Average velocity,
Q 4(0.102)
V= = = 1.49 m/s (230)
A π(0.295)2
⎛ 1,530 ⎞ (1.49 )
2
L V2
hpipe =f = 0.0141⎜ ⎟ = 8.27 m (232)
D 2g ⎝ 0.295 ⎠ 2 ( 9.81)
Kinematic Viscosity
Water Temperature (°C)
(m2/s)
0 0.000001785
5 0.000001519
10 0.000001306
15 0.000001139
20 0.000001003
25 0.000000893
30 0.000000800
40 0.000000658
50 0.000000553
60 0.000000474
( )
−1
ν = 83.9192 T 2 + 20,707.5 T + 551,173 (233)
Merkley & Allen Page 126 Sprinkle & Trickle Irrigation Lectures
From Table 11.2, for a 295-mm (12-inch) pipe and long radius 45-deg flanged
elbow, the Kr value is 0.15
V2 (1.49)2
helbow = Kr = (0.15) = (0.15)(0.11) = 0.017 m (234)
2g 2(9.81)
For the screen, assume a 0.2 m loss. Then, the total head loss is:
With the velocity head of 0.11 m, the total dynamic head is:
QH (102 lps )( 40 m )
WHP = = = 40 kW (54 HP)
102 102 (237)
WHP 40 kW
BHP = = ≈ 53 kW (71 HP)
Epump 0.76
(238)
• This BHP value would be used to select a motor for this application
• These calculations give us one point on the system curve (Q and TDH)
• In this simple case, there would be only one system curve:
System Curve
60
50
Total Dynamic Head (m)
40
30
20
10
0
0 20 40 60 80 100 120 140 160 180
Discharge (lps)
Sprinkle & Trickle Irrigation Lectures Page 127 Merkley & Allen
III. System Curves
• Most sprinkle and trickle irrigation systems have more than one system curve
because either the sprinklers move between sets (periodic-move systems),
move continuously, or “stations” (blocks) of laterals are cycled on and off
• The intersection between the system and pump characteristic curves is the
operating point (Q and TDH)
• A few examples of system curves:
Merkley & Allen Page 128 Sprinkle & Trickle Irrigation Lectures
2. Mostly Static Lift, Little Friction Loss
Sprinkle & Trickle Irrigation Lectures Page 129 Merkley & Allen
4. Two Different Static Lifts in a Branching Pipe
• The figure below shows two center pivots supplied by a single pump on a
river bank
• One of the pivots (#1) is at a higher elevation than the other, and is
further from the pump – it is the “critical” branch of the two-branch pipe
system
• Center pivot #2 will have excess pressure when the pressure is correct at
Center pivot #1, meaning it will need pressure regulation at the inlet to the
pivot lateral
• Use the critical branch (the path to Center pivot #1, in this case) when
calculating TDH for a given operating condition – Do Not Follow Both
Branches when calculating TDH
• if you cannot determine which is the critical branch by simple inspection,
you must test different branches by making calculations to determine
which is the critical one
• Note that the system curve will change with center pivot lateral position
when the topography is sloping and or uneven within the circle
• Of course, the system curve will also be different if only one of the center
pivots is operating
Merkley & Allen Page 130 Sprinkle & Trickle Irrigation Lectures
Center pivot #1
Center pivot #2
275 kPa
833 m
275 kPa
750 m
308 m river
pump
Sprinkle & Trickle Irrigation Lectures Page 131 Merkley & Allen
lateral #5 (critical lateral)
lateral #4
lateral #3
mainline
uphill
lateral #2
lateral #1
pump
Merkley & Allen Page 132 Sprinkle & Trickle Irrigation Lectures
Total Dynamic Head, TDH
1 2
Unstable Stable
A
B
urv e
te mC
Sys
0
0 Flow Rate, Q
I. Affinity Laws
2 3
Q1 N1 H1 ⎛ N1 ⎞ BHP1 ⎛ N1 ⎞
= =⎜ ⎟ =⎜ ⎟ (239)
Q2 N2 H2 ⎝ N2 ⎠ BHP2 ⎝ N2 ⎠
where Q is flow rate; N is pump speed (rpm); H is head; and BHP is “brake
horsepower”
2. Impeller diameter:
Sprinkle & Trickle Irrigation Lectures Page 133 Merkley & Allen
2 3
Q1 D1 H1 ⎛ D1 ⎞ BHP1 ⎛ D1 ⎞
= =⎜ ⎟ =⎜ ⎟ (240)
Q2 D 2 H2 ⎝ D2 ⎠ BHP2 ⎝ D2 ⎠
Comments:
• The affinity laws are only valid within a certain range of speeds, impeller
diameters, flow rates, and heads
• The affinity laws are more accurate near the region of maximum pump
efficiency (which is where the pump should operate if it is selected correctly)
2
H1 ⎛ Q1 ⎞
=⎜ ⎟ (241)
H2 ⎝ Q2 ⎠
• If this relationship is plotted with the pump characteristic curve and the
system curve, it is called the “equal efficiency curve”
• This is because there is typically only a small change in efficiency with a
small change in pump speed
• Note that the “equal efficiency curve” will pass through the origin (when Q is
zero, H is zero)
• Follow these steps to adjust the: (1) speed; or, (2) impeller diameter, such
that the actual operating point shifts up or down along the system curve:
Merkley & Allen Page 134 Sprinkle & Trickle Irrigation Lectures
2
⎛Q ⎞
H1 = H2 ⎜ 1 ⎟ (242)
⎝ Q2 ⎠
3. Plot the values from this table on the graph that already has the
pump characteristic curve
4. Locate the intersection between the pump characteristic curve
and the “equal efficiency curve”, and determine the Q3 and H3
values at this intersection
5. Use either of the following equations to determine the new
pump speed (or use equations involving D to determine the trim
on the impeller):
⎛Q ⎞ H2
Nnew = Nold ⎜ 2 ⎟ or, Nnew = Nold (243)
⎝ Q3 ⎠ H3
• You cannot directly apply any of the affinity laws in this case because you will
either get the right discharge and wrong head, or the right head and wrong
discharge
Apply Affinity
Law from Here
e
rv
Cu
m
te
ys
3 S Operating Point
Head
m
p
Cu
g!
C
ron
y
nc
ur
W
cie
ve
ffi
l E
ua
Eq
0
0 Flow Rate
Sprinkle & Trickle Irrigation Lectures Page 135 Merkley & Allen
III. Specific Speed
2πN Q
Ns = (244)
(gH)0.75
IV. Cavitation
• Air bubbles will form (the water boils) when the pressure in a pump or
pipeline drops below the vapor pressure
• If the pressure increases to above the vapor pressure downstream, the
bubbles will collapse
• This phenomenon is called “cavitation”
• Cavitation often occurs in pumps, hydroelectric turbines, pipe valves, and
ship propellers
• Cavitation is a problem because of the energy released when the bubbles
collapse; formation and subsequent collapse can take place in only a few
thousandths of a second, causing local pressures in excess of 150,000 psi,
and local speeds of over 1,000 kph
• The collapse of the bubbles has also been experimentally shown to emit
small flashes of light (“sonoluminescence”) upon implosion, followed by rapid
expansion on shock waves
• Potential problems:
Patmospheric
Pvapor
1. Large suction pipe to reduce friction loss and increase NPSHa, especially
where NPSHa is already too close to NPSHr (e.g. high-elevation pump
installations where the atmospheric pressure head is relatively low)
2. Eccentric reducer to avoid accumulation of air bubbles at the top of the
pipe
Sprinkle & Trickle Irrigation Lectures Page 137 Merkley & Allen
Required NPSH
• Data from the manufacturer are available for most centrifugal pumps
• Usually included in this data are recommendations for required Net Positive
Suction Head, NPSHr
• NPSHr is the minimum pressure head at the entrance to the pump, such that
cavitation does not occur in the pump
• The value depends on the type of pump, its design, and size
• NPSHr also varies with the flow rate at which the pump operates
• NPSHr generally increases with increasing flow rate in a given pump
• This is because higher velocities occur within the pump, leading to lower
pressures
• Recall that according to the Bernoulli equation, pressure will tend to
decrease as the velocity increases, elevation being the same
• NPSHr is usually higher for larger pumps, meaning that cavitation can be
more of a problem in larger pump sizes
Available NPSH
V2
NPSHa = hatm − hvapor − hf − hlift − (245)
2g
Merkley & Allen Page 138 Sprinkle & Trickle Irrigation Lectures
Vapor Pressure Head
Static Lift
Velocity Head
Available NPSH
• If the pump could create a “perfect vacuum” and there were no losses, the
water could be “sucked up” to a height of 10.34 m (at mean sea level)
• Average atmospheric pressure is a function of elevation above msl
perfect
vacuum
10.34 m
sea level
water
Sprinkle & Trickle Irrigation Lectures Page 139 Merkley & Allen
11
10
9
Vapor Pressure Head (m)
8
7
6
5
4
3
2
1
0
0 10 20 30 40 50 60 70 80 90 100
Water Temperature (C)
Straight line:
hatm = 10.3 − 0.00105 z (247)
Exponential curve:
5.26
⎛ 293 − 0.0065 z ⎞
hatm = 10.33 ⎜ ⎟ (248)
⎝ 293 ⎠
where hatm is atmospheric pressure head (m of water); and z is elevation
above mean sea level (m)
Merkley & Allen Page 140 Sprinkle & Trickle Irrigation Lectures
10.50
10.00
Mean atmospheric pressure (m)
9.50
Straight Line (m)
Exponential Curve (m)
9.00
8.50
8.00
7.50
7.00
6.50
0 500 1000 1500 2000 2500 3000
Elevation above msl (m)
Sprinkle & Trickle Irrigation Lectures Page 141 Merkley & Allen
1. Head Loss due to Friction
ε 0.2 mm
= = 0.000556 (249)
D 360 mm
flow velocity,
Q 0.100 m3 / s
V= = = 0.982 m/s (250)
π
A
( 0.36 ) 2
4
Reynold’s Number,
VD ( 0.982 )( 0.36 )
NR = = = 353,000 (251)
ν 1.003(10)−6
velocity head,
V 2 (0.982)2
= = 0.049 m (252)
2g 2g
L V2 ⎛ 8.1 ⎞
(hf )pipe =f = 0.0184 ⎜ ⎟ ( 0.049 ) = 0.0203 m (253)
D 2g ⎝ 0.36 ⎠
local losses, for the bell-shaped entrance, Kr = 0.04; for the 90-deg elbow, Kr =
0.14. Then,
finally,
(hf )total = (hf )pipe + (hf )local = 0.0203 + 0.0088 = 0.0291 m (255)
Merkley & Allen Page 142 Sprinkle & Trickle Irrigation Lectures
2. Vapor Pressure
3. Atmospheric Pressure
5. Available NPSH
V2
NPSHa = hatm − hvapor − (hf )total − hlift −
2g (256)
NPSHa = 10.1 − 0.25 − 0.0291 − 3.0 − 0.049 = 6.77 m
Sprinkle & Trickle Irrigation Lectures Page 143 Merkley & Allen
Merkley & Allen Page 144 Sprinkle & Trickle Irrigation Lectures
Lecture 12
Center Pivot Design & Operation
• Center pivots are used on about half of the sprinkler-irrigated land in the USA
• Center pivots are also found in many other countries
• Typical lateral length is 1,320 ft (400 m), or ¼ mile
• The lateral is often about 10 ft above the ground
• Typically, 120 ft pipe span per tower (range: 90 to 250 ft), often with one-
horsepower electric motors (geared down)
• At 120 ft per tower, a 1,320-ft lateral has about 10 towers; with 1-HP motors,
that comes to about 10 HP just for moving the pivot around in a circle
• The cost for a ¼-mile center pivot is typically about $55,000 (about $435/ac
or $1,100/ha), plus about $20,000 (or more) for a corner system
• For a ½-mile lateral, the cost may be about $75,000 (w/o corner system)
• In the state of Nebraska there are said to be 43,000 installed center pivots,
about 15% of which have corner systems
• Center pivots are easily (and commonly) automated, and can have much
lower labor costs than periodic-move sprinkler systems
• Center pivot maintenance costs can be high because it is a large and fairly
complex machine, operating under “field” conditions
• The typical maximum complete rotation is 20 hrs or so, but some (120-acre
pivots) can go around in only about 6 hrs
• IPS 6” lateral pipe is common (about 6-5/8 inches OD); lateral pipe is
generally 6 to 8 inches, but can be up to 10 inches for 2,640-ft laterals
• Long pivot laterals will usually have two different pipe sizes
• Typical lateral inflow rates are 45 - 65 lps (700 to 1,000 gpm)
• At 55 lps with a 6-inch pipe, the entrance velocity is a bit high at 3 m/s
• Typical lateral operating pressures are 140 - 500 kPa (20 to 70 psi)
• The end tower sets the rotation speed; micro switches & cables keep other
towers aligned
• Corner systems are expensive; can operate using buried cable; corner
systems don’t necessarily irrigate the whole corner
• Without a corner system or end gun, π/4 = 79% of the square area is
irrigated
• For a 1,320-ft lateral (without an end gun), the irrigated area is 125.66 acres
• For design purposes, usually ignore soil WHC (WaZ); but, refill root zone at
each irrigation (even if daily)
• Center pivots can operate on very undulating topography
• Some center pivots can be moved from field to field
• Below are some sample center pivot arrangements
Sprinkle & Trickle Irrigation Lectures Page 145 Merkley & Allen
Merkley & Allen Page 146 Sprinkle & Trickle Irrigation Lectures
Sprinkle & Trickle Irrigation Lectures Page 147 Merkley & Allen
• Some pivots have an end gun that turns on in the corners, in which all other
sprinklers shut off via individual solenoid-actuated valves. The pivot stops in
the corner while the end gun runs for a few minutes.
• Others just slow down in the corners, turning on an end gun, but leaving the
other sprinklers running (at lower discharges)
• Many farmers like extra capacity in the center pivot so they can shut off
during windy times of the day, and still complete the irrigations in time
• Corner systems have angle detectors so that sprinklers in the corner arm
turn on and off individually (or in groups) as the arm swings out and then
back in again
• Center pivots have safety switches to shut the whole thing off if any tower
gets too far out of alignment. Some also have safety switches to shut them
off if the temperatures gets below freezing (ice builds up and gets heavy,
possibly collapsing the structure). Some have safety switches connected to
timers: if a tower has not moved in a specified number of minutes, the
system shuts down. There may also be safety switches associated with the
chemical injection equipment at the lateral inlet location.
Merkley & Allen Page 148 Sprinkle & Trickle Irrigation Lectures
II. System Capacity
• The general center pivot design equation for system capacity is based on Eq.
5.4 from the textbook:
Ad R2d R2Udk f
Qs = K = = (257)
fT k1fT k1TEpa
where,
• The gross application depth, d, is equal to dn/Epa, where Epa is the design
application efficiency, based on uniformity and percent area (pa) adequately
irrigated
• The operating time, T, is generally 20-22 hrs/day during the peak-use period
• R is the effective radius, based on the wetted area from the center pivot
• The effective radius is about 400 m for many pivots
• R ≈ L + 0.4w, where L is the physical length of the lateral pipe, and w is the
wetted diameter of the end sprinkler
• This assumes that approximately 0.8 of the sprinkler radius beyond the
lateral pipe is effective for crop production
• Note that, for center pivots, Qs is proportional to Ud, and d and f are generally
not used, which is similar to drip irrigation design
• If a center pivot is operated such that the water holding capacity of the soil is
essentially ignored, and water is applied frequently enough to satisfy peak-
use crop water requirements, then use dn/f = Ud, and
k f Ud k f Ud
d' = = (258)
Epa DEpaReOe
Sprinkle & Trickle Irrigation Lectures Page 149 Merkley & Allen
where d' is the gross application depth (mm/day or inches/day); and kf is a
peak-use period evaporation factor, which accounts for increased soil and
foliage evaporation due to high frequency (daily) irrigation
• When LR > 0.1, the LR can be factored into the equation as:
0.9k f Ud
d' = (259)
(1 − LR)DEpaR eOe
which is the same as Eq. 14.1b from the textbook, except that DEpa, Re and
Oe are all as fractions (not percent)
• Values of kf can be selected for the peak period from Table 14.1 of the
textbook for varying values of frequency, f
• Values for non-peak periods can be computed as described in the textbook
on page 314:
where kf and PT are for the peak-use period (Table 14.1), and k'f and PT' are
the frequency coefficient and transpiration percentage (PT) for the non-peak
period
T
PT = (261)
ET
• PT and PT' can be thought of as the basal crop coefficient (Kcb), or perhaps
Kcb - 0.1 (relative to alfalfa, as per the note in Table 14.1)
• It represents the transpiration of the crop relative to an alfalfa reference
• A major design difficulty with a center pivot is maintaining the application rate
so that it is less than the intake rate of the soil
• This is especially critical near the end of the lateral where application rates
are the highest
• As one moves along the center pivot lateral, the area irrigated by each unit
length of the lateral (each 1 ft or 1 m of length) at distance r from the pivot
point can be calculated as:
q a 2 πr 2r
= = = (263)
Qs A πR 2 R 2
or,
2rQs
q= (264)
R2
where q can be in units of lps per m, or gpm per ft
• This gives the amount of water which should be discharging from a specific
unit length of lateral at a radial distance r from the pivot point
• The q value at the end of the lateral (r = R) per ft or m is:
2Qs
qend = (265)
R
• Use q to select the nozzle size, where qnozzle = q Se
V. End-Gun Discharge
• This last equation is very similar to Eq. 14.20a, except for the omission of the
Sj term
• Equation 14.20b is for the end gun discharge, assuming that the end gun is
used primarily to compensate for the lack of pattern overlap at the end of the
lateral
• Equation 14.20b can be justified as follows:
• Assuming the “basic” circle discharge, Qb, includes the end gun discharge,
qg, we can write:
Qb qg
≈ (266)
πL2 ∆L ( 2πL' )
Sprinkle & Trickle Irrigation Lectures Page 151 Merkley & Allen
or, perhaps more precisely,
Qb qg
≈ (267)
πL2 ∆L ( 2π (L '+ ∆L / 2 ) )
but ∆L/2 is generally very small compared to L’, and this is ostensibly
assumed in Eq. 14.20b, so after solving the above for qg you will arrive at Eq.
14.20b:
2L' ∆L
qg ≅ Qb ; for ∆L < 0.03L (268)
L2
VI. Application Rate
• For a center pivot, Se = 1 (based on a unit distance along the lateral) and Sl =
w (wetted width in the tangential direction), so the average application rate
(called AR) at a distance r along the lateral is:
k f d k f (Ud − Pe )
U'd = = (270)
f DEpa
Merkley & Allen Page 152 Sprinkle & Trickle Irrigation Lectures
• At the end of the lateral (r = R), the average application rate can be
calculated as:
2πRU'd ReOe
ARr =R = (271)
60 T w
where ARx is the maximum application rate (in the center of the pattern) (ARx
is in mm/min for U’d in mm/day)
• In the above equation, k3 is 1.61 for English units, or 60 for metric units
• It is usually a better approximation to assume an elliptical pattern under the
sprinklers than to assume a rectangular pattern, even though both are only
approximations
(400)(9)(0.95)(1.0)
AR x = = 0.69 mm / min (273)
(7.5)(22)(30)
• ARx is the peak AR (at the top of the ellipse, or directly beneath the lateral),
so an “average” (ARav) can be calculated, representing the average AR
beneath the wetted area perpendicular to the lateral pipe
• The calculated value of 0.69 mm/min is 41.4 mm/hr, which could be tolerated
only by a very sandy soil
Sprinkle & Trickle Irrigation Lectures Page 153 Merkley & Allen
• For a rectangular pattern, ARav = ARx
• For an elliptical pattern, ARav = (π/4)ARx
• Therefore, in the example, ARav = (π/4)(0.69) = 0.54 mm/min
• If d were 10 mm, it would take tt = 10/0.54 = 18 minutes to apply the water at
the rate ARav. (may want to use d Re Oe instead of just d in such a
calculation)
• Re can be taken from Fig. 6.8 or from examples in Table 14.3
• Guidelines for determining CI are given in Table 14.4
• The center pivot speed (at the end of the lateral) is w/tt, where tt is the time of
wetting
• In the preceding example, w is 30 m and tt is 18 min
• Therefore, the speed should be about 30 m/18 min = 1.7 m/min at the end
• Note that with spray booms, w is larger, and AR is smaller for the same q
value
Merkley & Allen Page 154 Sprinkle & Trickle Irrigation Lectures
Lecture 13
Center Pivot Nozzling
• The wetted width of the application package can be reduced closer to the
pivot point because the towers are moving at a slower speed at inner points;
therefore, the application intensity (AR) is less (qr ∝ r)
• Generally, if spray booms are required near the end of the center pivot, spray
drops can be used toward the center, and the spray drops nearest the pivot
point will produce something like a fine mist
• At the far end of the lateral the application may be more like a torrential rain
• Generally, impact and spray sprinklers would not be mixed on a center pivot
because the pressure requirements are substantially different
• The minimum wetted width at any radius r along the pivot (for an elliptical
pattern) can be calculated as:
8r Ud
wr = (274)
60 T AR x DEpa
r U'dReOe
ARr ≤ (275)
7.5 T w d
• The term “ReOe” is included in the above equation to account for evaporation
and wind drift losses, and pipe leakage
• Note that 60/8 = 7.5 and that we are using f = 1 day
• Divide by Re in the above equation to obtain AR at the nozzle
• The wetting time at any radius r (assuming an elliptical pattern) along the
lateral is:
4D f
( t t )r = (276)
π ARr
where Df is the total cumulative application (d Re Oe)
Sprinkle & Trickle Irrigation Lectures Page 155 Merkley & Allen
II. Center Pivot Nozzling Example
Given:
Ud = 8 mm/day
Pe = 0 mm/day
T = 22 hrs/day
Qs = 73.6 lps
R = 400 m
Speed = 21.6 hrs/revolution
ARx = 2.3 mm/min (allowable)
kf = 1.02
DEpa = 0.74
Re = 0.94
Oe = 0.99
Calculations:
• Calculate Ud’:
k f (Ud − Pe ) 1.02 ( 8 − 0 )
U'd = = = 11.0 mm/day (277)
DEpa 0.74
2πr
Sr = (278)
t
where Sr is the speed in m/min; t is the minutes per full-circle revolution; and
r is the radius from the pivot point in m
wr
τ= (279)
Sr
• The values of wd can be selected from available boom lengths, which in this
case is 6, 8, 10, and 12 m. For less than 4-m width, no boom is required.
Select wd values such that ARx is not exceeded.
Merkley & Allen Page 156 Sprinkle & Trickle Irrigation Lectures
• Spreadsheet calculations:
r q wr wd ARr tau Qr
(m) (lps/m) (m) (m) (mm/min) (s) (lps)
0 0.0000 73.6
40 0.0368 1.14 3 0.829 928 72.9
80 0.0736 2.28 3 1.658 464 70.7
120 0.1104 3.42 6 1.244 619 67.0
160 0.1472 4.56 6 1.658 464 61.8
200 0.1840 5.70 6 2.073 371 55.2
240 0.2208 6.84 8 1.866 413 47.1
280 0.2576 7.98 8 2.177 354 37.5
320 0.2944 9.12 10 1.990 387 26.5
360 0.3312 10.26 10 2.239 344 14.0
400 0.3680 11.39 12 2.073 371 0.0
• Most manufacturers prefer to specify the actual nozzle sizing and spacing
along center pivots at the factory (rather than have the buyer specify these)
for reasons of liability (they have specialized computer programs which
attempt to maximize uniformity)
• Therefore, the designer will generally only specify the flow rate, pressure,
and type of nozzle (spray drop, booms, impacts, etc.), and the manufacturer
will specify individual nozzle sizes
• The following figure shows a center pivot with booms (the booms are greatly
exaggerated in width to show the concept)
Sprinkle & Trickle Irrigation Lectures Page 157 Merkley & Allen
III. Sprinkler/Nozzle Configurations
Merkley & Allen Page 158 Sprinkle & Trickle Irrigation Lectures
2. Uniform Sprinkler Size where the distance between sprinklers decreases
with r
3. Combination of 1 and 2
Sprinkle & Trickle Irrigation Lectures Page 159 Merkley & Allen
Sizing Individual Nozzles:
1. Determine q for each spacing along the lateral (see Eq. 14.20a):
2Qs
qr = r Sr (280)
R2
where R is the maximum effective radius of the center pivot (approximately
equal to L + 0.4w); Sr is the sprinkler spacing at a distance r from the pivot
point; and r, Sr and R have the same units (m or ft)
2. Beginning at the design pressure at the end of the lateral, L (where q is
known), determine Pr:
where (hfr)end is the friction loss from point r to the far (downstream) end of
the lateral. Note that (∆He)end-r often averages out to zero as the pivot makes
its way around the circle, if the field slope is uniform (see the next figure).
Merkley & Allen Page 160 Sprinkle & Trickle Irrigation Lectures
3. Select the best nozzle size to provide qr at a pressure of Pr
4. Return to Step 1 and repeat for the next r-Sr location
5. The required pressure at the pivot point is Pr = 0
no slope
uniform slope
centered on a hill
centered on a depression
IV. Trajectory Angles of Impact Sprinklers
• For center pivots, sprinklers with 6° to 18° trajectory angles (low angle) are
preferred because drift losses are minimized (see Table 14.3 in the textbook)
• Other things being the same, wind drift and evaporation losses can be higher
with center pivots than with other types of sprinkler systems because of the
relative height of the sprinklers above the ground
• But, you can use drop-down sprayers on a “goose-neck” pipe – some of
these may be only a few centimeters from the mature crop canopy
V. End Guns
• The discharge for an end gun can be computed as (see Eq. 14.21):
Sprinkle & Trickle Irrigation Lectures Page 161 Merkley & Allen
⎛ 2Sr Q ⎛ Sr ⎞⎞
⎜ 2 ⎜ L + ⎟⎟
R ⎝ ⎠⎠
Qg = ⎝
2
(282)
0.93
where L is the lateral length; R is the effective length of the pivot (R = L + Sr);
Qg is the end gun discharge; Q is the total center pivot flow rate (includes
Qg); Sr is R - L, which equals the effective wetted radius (or 75% of the gun
radius)
⎛ L2 ⎞
Qg ≈ Q ⎜ 1 − 2 ⎟ (283)
⎜ R ⎟
⎝ ⎠
2 (R − L ) Q [L + 0.5(R − L)]
=
0.93R2
2QL (R − L ) + Q (R − L )
2
(284)
2
0.93 R
Q ⎛ L2 ⎞
= ⎜ 1 − ⎟
0.93 ⎜⎝ R2 ⎟⎠
• A part circle rotation (typically about 150°) is generally used to achieve best
uniformity under the area covered by the gun sprinkler, which is beyond the
end of the lateral pipe
• If the rotation of the end gun covered 180° or more, it might make it too
muddy for the wheels of the end tower – so with 150° (or so) the path in front
of the end tower stays relatively dry
Merkley & Allen Page 162 Sprinkle & Trickle Irrigation Lectures
Booster Pump
• The total discharge in the lateral pipe (not the flow rate from sprinklers at r) at
any point r is approximately:
⎛ r2 ⎞
Qr = Qs ⎜ 1 − 2 ⎟ (285)
⎜ R ⎟
⎝ ⎠
Friction Loss
1.852
⎛Q⎞
hf = khFpL ⎜ ⎟ D−4.87 (286)
⎝C⎠
Sprinkle & Trickle Irrigation Lectures Page 163 Merkley & Allen
where kh is 10.50 for hf and L in ft, Q in gpm, and D in inches; kh is
16.42(10)4 for hf and L in m, Q in lps, and D in cm
• Fp is the multiple outlet friction factor for a center pivot (see Fig. 14.12)
• Fp = 0.555 for a center pivot with a “large” number of outlets and no end gun
when using the Hazen-Williams equation.
• Other sources suggest using Fp = 0.543
• The value of C is about 130 for galvanized steel, or 145 for epoxy-coated
steel
Compute friction loss as though the center pivot were R m long rather than L,
and then subtract the non-existent friction past the point L, where R is the
effective (wetted) radius and L is the physical length of the lateral pipe.
A traditional way to consider the effects of an end gun on friction loss is:
1.852 1.852
⎛Q⎞ −4.87 ⎛ Qg ⎞
hf = khFpR ⎜ ⎟ D − khFg (R − L) ⎜ ⎟ D−4.87
⎝C⎠ ⎝ C ⎠ (287)
where Q is the total flow rate of the pivot plus the end gun; and Qg is the flow
rate of the end gun
• A center pivot may be assembled with dual pipe sizes (8- and 6-inch pipe, or
8- and 6 5/8-inch, for example)
Merkley & Allen Page 164 Sprinkle & Trickle Irrigation Lectures
• One requirement to note is that the tower spacing must be closer for the 8-
inch pipe due to the added weight of water in the 8-inch pipe, and traction
problems from towers which are too heavy and sink into the soil
• Therefore, balance the savings in hf with added cost for the system
• Tower spacing is often 100 ft (30 m) for 8-inch pipe, and 150 ft (45 m) for 6-
inch pipe
• Weight per tower = Wt of tower + Wt of 1 span (steel) + Wt of water in the
span
where Hl is the pressure head required at ground level, at the pivot point; Ha is
the pressure head requirement of the last nozzle (or end gun); hf is the total
friction loss along the pivot lateral; ∆He is the elevation increase between the
pivot point and lateral end; Hr is the height of the lateral pipe less the vertical
length of any drop tubes; and Hminor is the sum of all minor losses along the
lateral
n
( )
Hl = Hend + ∑ ⎡ hfi + ∆Hei + Hr + Hmin or ⎤
⎣ ⎦
i=0 (289)
where Hend is the desired nozzle pressure head at the pivot end; i is the outlet
number along the lateral (i = 0 at the end, and i = n at the pivot point); n is
the number of outlets (sprinklers) on the lateral; ∆Hei is the elevation
Sprinkle & Trickle Irrigation Lectures Page 165 Merkley & Allen
difference between two adjacent points (i and i+1) along the lateral; and hfi is
the friction loss between outlet i and i+1, where i+1 is upstream of i. This last
term is defined as:
Ji ∆Li
hfi = (290)
100
where,
1.852
12 ⎛ Qi
⎞
Ji = 1.21(10) ⎜ ⎟ Di−4.87 (291)
⎝C⎠
and,
i
Qi = ∑ q j (292)
j= 0
• Hminor includes short hose connections between pipe segments (at towers)
• Therefore, actual computed hj values should be used with the selected
nominal nozzle size (or FCN size), where hj is the pressure head at outlet j
• The desired qj is:
⎛ 2Q ⎞ ⎛ 2Q ⎞
q j = rjSrj ⎜ 2 ⎟ = rj∆Li ⎜ 2 ⎟ (293)
⎝R ⎠ ⎝R ⎠
L 2π r (He ) r,α
Hew = ∫ ∫ 2πL2
dr dα (294)
r =0 α
Merkley & Allen Page 166 Sprinkle & Trickle Irrigation Lectures
where r is a weighting term; and (He)r,α is the elevation at radius r and pivot
rotation angle α.
Sprinkle & Trickle Irrigation Lectures Page 167 Merkley & Allen
Merkley & Allen Page 168 Sprinkle & Trickle Irrigation Lectures
Lecture 14
Center Pivot Uniformity Evaluation
I. Introduction
• The calculation of an application uniformity term must take into account the
irrigated area represented by each catch container
• It is more important to have better application uniformity further from the pivot
point than nearer, because the catch containers at larger distances represent
larger irrigated areas
• If the catch containers are equally spaced in the radial direction, the area
represented by each is directly proportional to the radial distance
⎛ ⎛ ⎞⎞
∑ i=1( diri ) ⎟⎟ ⎟⎟
n
⎜ n ⎜
⎜ ∑ r d −
i=1⎜ i i
∑i=1ri ⎟⎠ ⎟⎟
n
CU = 100 ⎜ ⎜ (295)
⎜ 1.0 − ⎝
⎜ ⎟
∑ i=1( diri )
n
⎜ ⎟
⎝ ⎠
• If the radial distances, ri, are equal, the sequence number of the can
(increasing with increasing radius) can be used instead of the actual distance
for the purpose of calculating application uniformity
• Consider the following two figures:
Sprinkle & Trickle Irrigation Lectures Page 169 Merkley & Allen
slope?
catch containers
leg # #1
3 g
le
slope?
leg #
2
catch containers
level field?
no wind?...
CU = 100%
Merkley & Allen Page 170 Sprinkle & Trickle Irrigation Lectures
III. Standard Uniformity Values
• You can also calculate the “standard” CU or DU if you weight each catch
value by multiplying it by the corresponding radial distance
• To obtain the low ¼, rank the unweighted catches, then start summing radii
(beginning with the radius for the lowest catch value) until the cumulative
value is approximately equal to ¼ of the total cumulative radius
• This may or may not be equal to ¼ of the total catch values, because each
catch represents a different annular area of the field
• Finally, divide the sum of the catches times the radii for this approximately ¼
area by the cumulative radius
• This gives the average catch of the low ¼
• Don’t rank the weighted catches (depth x radius) because you will mostly get
the values from the low r values (unless the inner catches are relatively high
for some reason), and your answer will be wrong
• Don’t calculate the average of the low ¼ like this…
(because the lowest ¼ of the catches generally represents
something different than ¼ of the irrigated area):
• Actually, the equation at the right is all right, except for the
value “n/4”, which is probably the wrong number of ranked
values to use in representing the low ¼
• You can set up a table like this in a spreadsheet application:
largest
Totals: ---- ----
• Note that when you rank the depths, the radius values should stay with the
same depth values (so that the radius values will now be “unranked”; all
mixed up)
• To get the average weighted depth for the whole pivot area, divide the total
“Cumulative d*r” by the total “Cumulative r” (column 5 divided by column 2)
• Find the row corresponding closest to ¼ of the total “Cumulative r” value, and
take the same ratio as before to get the weighted average of the low ¼ area
• Look at the example data analysis below:
Sprinkle & Trickle Irrigation Lectures Page 171 Merkley & Allen
Ranked catches
Radius, r Cum. r Depth, d d*r Cum. d*r
120 120 0.52 62.6 62.6
900 1,020 0.95 851.9 915
160 1,180 1.29 205.8 1,120
340 1,520 1.31 445.6 1,566
1000 2,520 1.46 1,456.3 3,022
1040 3,560 1.46 1,514.6 4,537
240 3,800 1.48 355.3 4,892
800 4,600 1.50 1,203.9 6,096
860 5,460 1.53 1,315.0 7,411
480 5,940 1.58 757.3 8,168
1280 7,220 1.58 2,019.4 10,188
980 8,200 1.60 1,569.9 11,758
540 8,740 1.63 878.2 12,636
360 9,100 1.65 594.2 13,230
460 9,560 1.67 770.4 14,000
880 10,440 1.70 1,495.1 15,496
320 10,760 1.72 551.5 16,047 1/4 area (11,055)
1140 11,900 1.75 1,992.2 18,039
1160 13,060 1.75 2,027.2 20,067
280 13,340 1.82 509.7 20,576
720 14,060 1.82 1,310.7 21,887
1300 15,360 1.82 2,366.5 24,253
200 15,560 1.84 368.9 24,622
420 15,980 1.84 774.8 25,397
440 16,420 1.89 833.0 26,230
1020 17,440 1.89 1,931.1 28,161
1200 18,640 1.92 2,301.0 30,462
600 19,240 1.94 1,165.0 31,627
640 19,880 1.94 1,242.7 32,870
1060 20,940 1.94 2,058.3 34,928
1100 22,040 1.94 2,135.9 37,064
220 22,260 1.97 432.5 37,497 1/2 area (22,110)
1080 23,340 1.97 2,123.3 39,620
380 23,720 1.99 756.3 40,376
740 24,460 1.99 1,472.8 41,849
920 25,380 1.99 1,831.1 43,680
1220 26,600 1.99 2,428.2 46,108
300 26,900 2.01 604.4 46,713
180 27,080 2.03 364.8 47,077
820 27,900 2.04 1,671.8 48,749
1260 29,160 2.04 2,568.9 51,318
660 29,820 2.06 1,361.7 52,680
1180 31,000 2.06 2,434.5 55,114
680 31,680 2.09 1,419.4 56,534
940 32,620 2.11 1,985.0 58,519
560 33,180 2.14 1,196.1 59,715
260 33,440 2.16 561.7 60,276
1120 34,560 2.18 2,446.6 62,723
700 35,260 2.23 1,563.1 64,286
760 36,020 2.23 1,697.1 65,983
100 36,120 2.25 224.5 66,208
960 37,080 2.26 2,167.0 68,375
520 37,600 2.28 1,186.4 69,561
620 38,220 2.28 1,414.6 70,976
1240 39,460 2.28 2,829.1 73,805
500 39,960 2.33 1,165.0 74,970
140 40,100 2.35 329.6 75,300
400 40,500 2.40 961.2 76,261
780 41,280 2.52 1,968.9 78,230
40 41,320 2.57 102.9 78,333
80 41,400 2.57 205.8 78,538
840 42,240 2.79 2,344.7 80,883
580 42,820 2.82 1,633.0 82,516
60 42,880 3.23 193.7 82,710
1320 44,200 3.79 4,998.1 87,708
20 44,220 3.83 76.7 87,784
Merkley & Allen Page 172 Sprinkle & Trickle Irrigation Lectures
• Notice that the depth values (3rd column) are ranked from low to high
• Notice that the maximum value of cumulative r is 44,220 & maximum
cumulative d*r is 87,784. Then, the weighted average depth for the entire
center pivot is equal to 87,784/44,220 = 1.985 (whatever units)
• One quarter of 44,220 is equal to 11,055 which corresponds most closely to
the row in the table with depth = 1.72. For the same row, divide the two
cumulative columns (Col 5/Col 2) to get 16,047/10,760 = 1.491, which is
approximately the average of the low ¼.
• Finally, estimate the distribution uniformity for this data set as:
⎛ 1.491 ⎞
DU ≅ 100 ⎜ ⎟ ≅ 75% (297)
⎝ 1.985 ⎠
• Note that in this example, the average of the low ¼ was, in fact, based on
approximately the first n/4 ranked values
14000
12000
Weighted Catch Values
10000
8000
6000
4000
2000
0
0 10 20 30 40 50 60 70
Sprinkle & Trickle Irrigation Lectures Page 173 Merkley & Allen
IV. The Field Work
• It may take a long time for the full catch in containers near the pivot point,
and because these represent relatively small areas compared to the total
irrigated area, it is usually acceptable to ignore the inside 10% or 20% of the
radius
• The pivot quickly passes the outer cans, but takes longer to completely pass
the inner cans, so you can collect the data from the outer cans sooner
• The pivot should not be moving so fast that the application depth is less than
about 15 mm
• Catch containers can be placed beyond the physical length of the lateral
pipe, but if they are so far out that the catches are very low, these can be
omitted from the uniformity calculations
• Catch containers should be spaced in the radial direction no further than
about 30% of the average wetted diameter of the sprinklers
• There is often an access road leading to the pivot point for inspection,
manual operation, maintenance, and other reasons
• If the crop is dense and fairly tall (e.g. wheat or maize) it will be difficult to
perform the evaluation unless the cans are placed on the access road
• Otherwise, you can wait until the crop is harvested, or do the test when the
crop is still small
• Some people recommend two radial rows of catch cans, or even two parallel
rows, to help smooth out the effects of the non continuous movement of
towers (they start and stop frequently to keep the pivot lateral in alignment)
• Some have used troughs instead of catch cans to help ameliorate this
problem.
• Note that if the field is sloping or undulating, the results from one radial row
of catch cans may be quite different from those of a row on another part of
the irrigated circle
• See Merriam and Keller (1978)
Merkley & Allen Page 174 Sprinkle & Trickle Irrigation Lectures
Linear Move Systems
I. Introduction
Water Supply
Sprinkle & Trickle Irrigation Lectures Page 175 Merkley & Allen
• Hose-fed systems require periodic manual reconnection to hydrants on a
mainline – it is kind of like a period-move system, and you have to ask
yourself whether the linear move machine is worth the cost in this case!
• With the automatic hydrant coupling machines (see Fig. 15.3) there are two
arms with pipes and an elbow joint that bends as the linear move travels
down the field. The two arms alternate in connecting to hydrants so as not to
disrupt the irrigation nor the forward movement of the machine. These are
mechanically complex.
• The advantage of hose-fed and automatic coupling linear moves is that you
don’t need to have a small, uniform slope in the direction of travel, because
water is supplied from a pressurized mainline instead of an open channel
• On ditch-fed systems there can be a structure at the end of the field that a
switch on the linear move contacts, shutting down the pump and reversing
the direction of movement so that it automatically returns to the starting end
of the field.
• The advantages and disadvantages of the ditch-feed system are:
Pros
• Low pressure (energy) requirement
• Totally automated system
• More frequent irrigations than hose-fed, since no one needs to be
available to move the hose
Cons
• Trash and seeds and sediment pass through screen and may plug
nozzles
• The pump must be on (move with) the lateral, causing extra weight
• Should have uniform slope along the lateral route
Pros
• Easy irrigation of a rectangular field (important if land is expensive, but
not important if land is cheap and water is scarce)
• Application rate is uniform over length of lateral, rather than twice the
average value at the end of the center pivot
• No end gun is required
Cons
• The lateral does not end up right back at the starting point immediately
after having traversed the irrigated area – you either have to
“deadhead” back or irrigate in both directions
• May be more expensive than a pivot due to extra controls, pump on
ditch feed, or more friction loss in the flexible feed hose (the hose is
fairly expensive)
Merkley & Allen Page 176 Sprinkle & Trickle Irrigation Lectures
II. System Costs
• A main strategy in linear move design is to minimize the cost per unit area.
This is done by maximizing the area covered per lateral (length of field)
• Generally, the lateral length is limited to 400 to 800 m. Therefore, the major
difficulties and objectives in linear design are to:
1. Maximize the irrigated area per lateral (this minimizes $/area). In other
words, how large a field can be irrigated by one machine?
2. Prevent runoff by matching ARx with Isoil + SS/ti (this tends to limit the field
length, because if AR is small, it won’t be possible to finish in f’ days),
where SS is the allowable surface storage in (mm or inches); and, ti is the
time of irrigation
3. Determine whether spray nozzles can be used without causing runoff
4. Minimize labor (for moving hoses and supervising)
as long as possible
• The allowable surface storage, SS, is the maximum amount of ponding
without incurring surface runoff
• SS is a function of the general topography and the microtopography, and of
the amount of foliar interception (water can “pond” on the crop leaves too)
Sprinkle & Trickle Irrigation Lectures Page 177 Merkley & Allen
• SS is usually less than about 5 mm unless small basins are created along
furrows, for example
• ARx limits the field length because it corresponds to some minimum time to
finish an irrigation, for a given gross application depth, whereby a maximum
interval (f) is calculated in the preliminary design steps
Pa 3 1
Hl = + hf + Hr + ∆He + (hf )minor + (hf )hose (298)
γ 4 2
• Or, if using flow control nozzles, with a minimum pressure required at the end
(assuming the minimum pressure occurs at the end):
Pend
Hl = + hf + Hr + ∆He + (hf )minor + (hf )hose (299)
γ
where Hr is the height of the lateral or spray boom above the ground; and,
(hf)minor are the hydrant coupler and tower connection losses.
• The parameter (hf)hose is the loss in the flexible hose connection on a hose-
fed system
• Note that (hf)hose may be a major loss, since the hose diameter is usually less
than 5” or 6".
1.852
⎛Q⎞
hf = khFL ⎜ ⎟ D−4.87 (300)
⎝C⎠
where kh = 10.50 for hf and L in ft, Q in gpm, and D in inches; Kh = 1.21(10)10
for hf and L in m, Q in lps, and D in mm. F is the multiple outlet friction factor
for a linear move (F ≈ 0.36).
• For hose-fed systems, the maximum hose length for dragging the hose is
220 ft. Therefore, there could be about 400 ft between hydrants.
• For hose-fed systems with a cable/winch system for assisting in dragging the
hose (towers only have a moderate amount of tractive power), the maximum
hose length is 330 feet (640 feet between hose hydrants).
• Flexible hoses normally come in 5-inch ($18/ft) and 6-inch ($25/ft) diameters
• The Hazen-Williams C value for the hose can usually be taken as 150
Merkley & Allen Page 178 Sprinkle & Trickle Irrigation Lectures
Lecture 15
Maximizing Linear Move Field Length
I. The Procedure
• The following procedure for maximizing field length is from Allen, 1983, Univ.
Idaho and Allen, 1990 (Irrig. Symp. Paper), and is used in the USUPIVOT
computer program
• The basic strategy is to examine different application depths and different w
values to maximize the area covered by the sprinkler system, and or to
minimize labor requirements
dn = f (Ud)
d = dn/Epa
(Df)max = d.Re
df = (i/10)(Df)max where i = 1 to 10
and,
f' = df DEpa/(100 Ud)
f = f' - days off (days off may be zero because the system is automatic),
where f' = irrigation frequency for depth df. DEpa is used here (in percent)
because Ud is net, not gross
Sprinkle & Trickle Irrigation Lectures Page 179 Merkley & Allen
5. Determine the maximum ARx for a particular df value using the following
two equations (assuming an elliptical pattern):
⎛ ( SF )( AR x ) ⎞ ⎛ n+1 n ⎞
1 n
⎜1− ⎜
⎟ k (n + 1)n+1 (D − SS − c )n+1 ⎟
⎝ k ⎠⎝⎜ ⎟
AR x = ⎠ (301)
2 2
⎛π⎞ ⎛ D ⎞
1.05 − 1.6 ⎜ ⎟ ⎜ − 0.5 ⎟
⎝ 2 ⎠ ⎝ df ⎠
where,
−n−1
⎛⎛ −0.5 ⎞
2 2⎞ ⎛ 2 ⎞
⎜⎜ ⎛ π ⎞ ⎛ D ⎞ ⎛ π ⎞ ⎛ D ⎞ ⎟
2 2 ⎟ ⎜ −1.6 AR2x ⎜ ⎟ ⎜ − 0.5 ⎟ ⎟ ⎟
⎜ ⎜ 1.05 AR x − 1.6 AR x ⎜⎝ 2 ⎟⎠ ⎜ d − 0.5 ⎟ ⎟ ⎜
⎜⎝ ⎝ f ⎠ ⎠ ⎝ ⎝ 2 ⎠ ⎝ df ⎠ ⎟⎠ ⎟
D=⎜ ⎟
⎛ ( SF )( AR x ) ⎞ ⎛ −1 ⎞ ⎛ 1 ⎞
⎜ ⎟
⎜
df n ⎜ 1 − ⎟ ⎜⎜ ( n + 1) n+1 ⎟⎟ ⎜ k n+1 ⎟ ⎟
⎜ ⎝ k ⎠⎝ ⎠ ⎝⎜ ⎟
⎠ ⎟
⎝ ⎠
+SS + c
(302)
and ARx is the peak application per pass (mm/min); D is the applied depth
at time t = ∫ (AR) dt (mm); SS is the allowable surface storage (after
ponding) before runoff occurs (usually less than about 5 mm); c is the
instantaneous soil infiltration depth, from SCS soil intake families (mm); k
is the coefficient in the Kostiakov-Lewis equation; and df is the total depth
of water applied to the ground surface (mm)
• The parameter “n” is defined as: n = a -1, where “a” is the Kostiakov
exponent (see NRCS soil curves at www.wcc.nrcs.usda.gov/nrcssirrig)
• Note that SS is a function of the field topography and micro-topography,
and is affected by foliar interception of applied water
• These last two equations have π in them because there is an inherent
assumption of an elliptical water application profile from the sprinklers or
sprayers
• Recall that ARav = (π/4)ARx for an elliptical pattern
• SF is a relative sealing factor (in terms of soil water infiltration), and may
have values in the range of 0 to about 0.36
Merkley & Allen Page 180 Sprinkle & Trickle Irrigation Lectures
• The higher values of SF tend to be for freshly tilled soils, which are
generally most susceptible to surface sealing from the impact of water
drops
• Lower values of SF are for untilled soils and vegetative cover, such as
alfalfa or straw, which tend to reduce the impact of water drops on the soil
and help prevent runoff too
• If the linear move irrigates in both directions (no deadheading), then df is
one-half the value from these two equations
df
ti = (303)
π
( AR x )
4
7. Compute the speed of the system for the required ti:
If S ≥ Smax (this may occur for a high intake soil or for a very light
application with surface storage) then reduce the application rate and
increase time as follows:
w
ti = (304)
Smax
4 df
AR x = (305)
π ti
Thus,
S = Smax (306)
60 f T − 2 treset
X= (307)
⎛ 1 1 t ⎞
⎜⎜ + + hose ⎟
⎟
⎝ S wet Sdry 100 ⎠
where,
Sprinkle & Trickle Irrigation Lectures Page 181 Merkley & Allen
X = maximum length of field (m);
f = system operating time per irrigation (days);
T = hours per day system is operated (21-23);
treset = time to reset lateral at each end of the field (min);
those = time to change the hose (min/100 m);
Swet = maximum speed during irrigation (m/min); and
Sdry = maximum dry (return) speed (m/min)
labor =
(
2 treset + 0.01X those + 2 t super ) (308)
60 f
where labor is in hrs/day; and tsuper is minutes of supervisory time per 100
m of movement
60 f T − 2 treset
X= (309)
⎛ 1 t ⎞
2⎜ + hose ⎟
⎝ S wet 100 ⎠
XL
Areamax = (310)
10,000
labor
Lha = (311)
Areamax
12. Repeat steps 4-11 for a new w (different application device or different
operating pressure)
13. Select the nozzle device and application depth which maximizes the field
length (or fits available field length) and which minimizes labor
requirements per ha
Merkley & Allen Page 182 Sprinkle & Trickle Irrigation Lectures
14. System capacity:
π AR x w L
Qs = (312)
4k 3 Re
where k3 = 96.3 for L and w in ft, Qs in gpm, and ARx in in/hr; and k3 = 60
for L and w in m, Qs in lps, and ARx in mm/min
df w L
Qs = (313)
ti k 3 R e
• There is no “surge” effect of soil surface sealing due to a brief time period
between irrigation passes (when irrigating in both directions)
• The infiltration curve used represents soil moisture conditions
immediately before the initiation of the first pass
• The infiltration curve used holds for all frequencies (f) or depths (df)
evaluated, while in fact, as f↑, θ↓, so that the Kostiakov coefficients will
change. Therefore, the procedure (and field ring infiltration tests) should
be repeated using coefficients which represent the Kostiakov equation for
the soil moisture condition which is found to be most optimal in order to
obtain the most representative results.
Sprinkle & Trickle Irrigation Lectures Page 183 Merkley & Allen
Linear Move Design Example
I. Given Parameters
• Hose-fed linear move, irrigating in only one direction in a 64-ha field (400 m
wide and 1,600 m long)
• The pressure is 140 kPa (20 psi) for spray booms with a preliminary w if 10
m (33 ft)
• The soil infiltration characteristics are defined for the Kostiakov-Lewis
equation as:
Z = 5.43τ0.49 (314)
Ud = 7.7 mm/day
MAD = 50%
Z = 0.9 m
Wa = 125 mm/m
Oe = 1.00
Re = 0.94
Epa = 85%
dx = (0.5)(0.9)(125) = 56 mm (315)
dx 56
f' = = = 7.3 ⇒ f ' = 7 days (316)
Ud 7.7
Merkley & Allen Page 184 Sprinkle & Trickle Irrigation Lectures
2. Net and gross application depths:
dn = f Ud = (7)(7.7) = 54 mm (317)
dn 54
d= = = 64 mm (318)
Epa 0.85
D f = dR e = (64)(0.94) = 60 mm (319)
⎛ i ⎞
df = D f ⎜ ⎟ (320)
⎝ 10 ⎠
Assume no days off (no down time during the peak use period)
4 df 4(24)
ti = = = 34 min (323)
π AR x π (0.91)
60 f T − 2 treset
X= =
⎛ 1 1 t ⎞
⎜⎜ + + hose ⎟
⎟
⎝ S wet Sdry 100 ⎠ (325)
60(2.8)(22) − 2(30)
= = 970 m
⎛ 1 1 10 ⎞
⎜ + + ⎟
⎝ 0.3 3.5 100 ⎠
(
2 treset + 0.01 those + 2 t sup er X ) =
60 f
(326)
2(30) + 0.01[10 + 2(5)][970]
= = 1.5 hrs / day
60(2.8)
where treset is the reset time at the end of the field (min); those is the hose
reconnection time (min/100 m); and tsuper is the “supervisory” time
(min/100 m)
Merkley & Allen Page 186 Sprinkle & Trickle Irrigation Lectures
12. Repeat steps 4-11 for a new w (different application device or operating
pressure). (not done in this example).
13. Select the nozzle, device and application depth that maximizes the field
length (or fits the available field length), and which minimizes labor
requirements per ha.
Note: 38.8 ha << 64 ha, which is the size of the field, (970 m << 1600 m
which is the length of the field). Therefore, it is important to continue
iterations (steps 11 and 12) to find an application depth and or new w
(different sprinkler or spray device) to reach 1600 m and 64 ha, if
possible.
Additional Observations:
• For a 6-m spray boom, applying a 12-mm depth per each 1.4 days
would almost irrigate the 64 ha. However, the labor requirement is
doubled, as the machine must be moved twice as often. This
additional cost must be considered and weighed against the larger
area irrigated with one linear move machine.
• If larger spray booms were used (w = 16 m rather than 10 m) (these
would be more expensive) then 18 mm could be applied each 2.1
days, and all 64 ha could be irrigated with one machine.
• If low pressure impact sprinklers were used (these would be less
expensive than spray booms, but energy costs would be higher), then
w = 22 m, and 30 mm could be applied each 3.5 days (more water
can be applied since the application rate is spread over a wider area
from the lateral), and all 64 ha could be irrigated. In addition, ETc
would be less since the soil would be wetted less often. Also, the soil
intake rate would be higher each irrigation because of a drier
antecedent moisture at the time of irrigation.
• Notice that required wetting time for rotation times (f) greater than 2
days are identical between all types of spray devices. This is
because, for the large depths applied, a minimum wetting time is
required. The system speed is adjusted to fit the w value of the water
application device.
• If no acceptable solution for this problem were found, then
alternatives to be evaluated would be to irrigate in both directions, or
to consider a ditch-fed linear move (this requires a leveled ditch, but
does not required time for moving hoses and hose friction losses).
• You could also consider a “robot” controlled machine that
automatically connects alternating arms to hydrants on a buried
mainline (but this is a very expensive alternative)
• You might begin to wonder whether an investment in a linear move
machine is justifiable when there is a significant labor requirement for
reconnecting the supply hose, resetting at the end of the field, and
Sprinkle & Trickle Irrigation Lectures Page 187 Merkley & Allen
supervising operation. That is, why not put in a center pivot or a side
roll system instead?
• If one linear move cannot cover the entire field length in the available
period, “f” (days), you could consider two linear move machines for
the same field
π AR x w L π (0.91)(10)(400)
Qs = = = 51 lps (809 gpm)
4k 3Re 4(60)(0.94) (327)
alternatively,
df wL (24)(10)(400)
Qs = = = 51 lps (809 gpm) (328)
ti k 3R e (33.6)(60)(0.94)
Note that the computed Qs is larger than one based strictly on Ud and T,
because the machine is shut off during reset and hose moving
Ad (38.3)(24)
Qs = 2.78 = 2.78 = 44 lps (700 gpm) (16)
fT (2.8)(22)(0.94)
But this flow rate is too low – it does not consider hose moving and
reset time. So, the 51 lps system capacity should be used for design
Merkley & Allen Page 188 Sprinkle & Trickle Irrigation Lectures
Lecture 16
Trickle Irrigation System Components & Layout
• “Trickle” and “drip” are terms used to describe what can be generally called
“micro-irrigation systems”, in which water is applied in relatively precise
quantities and precise times and at precise locations
• Land-leveling costs notwithstanding, trickle irrigation systems are usually the
most expensive types of on-farm water application system to install
• They can also be expensive to operate and maintain
• Usually, trickle irrigation systems are installed in areas where water is scarce
and or expensive, crop value is very high, or topographical and other
conditions might preclude the successful use of other types of irrigation
systems
• Not all micro-irrigation systems are complex and expensive
• Labor-intensive forms of micro-irrigation continue to be practiced in many
areas of the world, especially for vegetable and other “cash” crops
• For example, people may carry water in buckets or shoulder harnesses to
carefully pour at each plant in a field
• Or, porous pots are buried at regular intervals along rows and filled with
water individually, which seeps out into the surrounding soil
• Sometimes water is merely splashed onto crop beds by hand
Advantages
Sprinkle & Trickle Irrigation Lectures Page 189 Merkley & Allen
Disadvantages
1. Systems are expensive to purchase and install ($1,000 to $6,000 per ha)
2. Susceptibility to clogging of emitters, which usually have very small
openings – so, it is important to spend time and money on maintaining the
system, applying chemicals, and keeping filters clean
3. Possibly low distribution uniformity due to low operating pressures and
possibly due to steep slopes, especially along laterals, and due to clogging
4. Where laterals are on steep slopes, the water will drain out the downhill end
at every startup and shut-down.
5. Soils with very low intake rates will exhibit ponding and runoff
6. Salt tends to accumulate at the soil surface and around the wetted area --
when it rains, these accumulated salts may be driven into the root zone
7. These systems tend to require more capable and diligent management
because of the susceptibility to clogging, and because the systems are
usually designed to operate continuously during peak ET periods (can’t
afford to let the system shut down during these periods). These systems do
not usually take full advantage of the soil storage (buffer) capacity.
Merkley & Allen Page 190 Sprinkle & Trickle Irrigation Lectures
5. Other equipment
• Valves & air vents
• Vacuum Relief Valves
• Pressure Relief Valves
• Various Pipe Fittings and Appurtenances
• Not all trickle irrigation systems will have all of these components
• For example, some systems are gravity-fed and require no pumping
• Simple systems may not have submains and manifolds
• Some systems do not have pressure relief or other types of safety valves
• Systems with relatively dirty water will have multiple levels of filtration, others
may have only minimal screening
1. Drip Emitters
Sprinkle & Trickle Irrigation Lectures Page 191 Merkley & Allen
• Double chamber with orifices between chambers and orifices to
discharge water into the soil (acts something like a manifold to
control pressures and provide greater uniformity)
• Can be removed and reused next year (typically 4-5 years life)
• Can be “disked up” and left in the field as chunks of plastic
• Porous or “leaky” pipe, made from old tires or new materials
3. Micro-Sprayers
Merkley & Allen Page 192 Sprinkle & Trickle Irrigation Lectures
VI. Typical Trickle System Layouts
• The discharge equation for emitters is similar to that used for sprinkler
nozzles, but the exponent on the head or pressure term is variable
• An exponent of ½ corresponds to orifice flow, which is how some, but not all,
emitters are designed
• The general emitter equation is:
q = K dHx (329)
• The two basic emitter design objectives, other than energy dissipation, are:
⎛ q'n ⎞
EU' = 100 ⎜ ⎟ (330)
⎜ qa ⎟
⎝ ⎠
where EU’ is the field test emission uniformity; qn’ is the average discharge of
the low ¼ emitters from the sampling; and qa is the average discharge of all
emitters sampled
• EU’ should be at least 95% for properly designed and properly maintained
trickle irrigation systems
• Note that it is impossible to calculate EU’ based on field measurements if the
system is being designed (hasn’t been installed yet) – in this case there are
other equations to approximate EU (recall the design efficiency for sprinkler
systems)
• Most nonuniformity in micro irrigation systems is caused by: (1) emitter
plugging, wear, and manufacturing variations; and, (2) nonuniform pressure
distribution in pipes and hoses
Merkley & Allen Page 194 Sprinkle & Trickle Irrigation Lectures
X. Manufacturer’s Coefficient of Variation
• Emitters of the same type and manufacture have variations in discharge (at
the same operating pressure) due to small differences from manufacturing
tolerances. Some variation is allowed in the interest of cost savings.
• The manufacturer’s coefficient of variation is defined as:
s
ν= (331)
qa
Sprinkle & Trickle Irrigation Lectures Page 195 Merkley & Allen
XII. Valves & Automation
1. Volumetric Valves
• Manually turned on
• Automatically turn off
2. Sequential Operation
• Manually turned on
• Automatic sequencing from low to high elevation
3. Fully Automatic
• Note that time-based systems may give varying application depths over time
if the system flow rate changes due to clogging of filters
• This can be partially corrected by using pressure compensating emitters
• However, the use of a volume-based system with a flow meter may be best
because the flow rate measurement also gives an indication about filter
clogging
Merkley & Allen Page 196 Sprinkle & Trickle Irrigation Lectures
Lecture 17
Filtration for Trickle Irrigation Systems
I. Introduction
Sprinkle & Trickle Irrigation Lectures Page 197 Merkley & Allen
3. Can provide nutrients which support the growth of bacteria in the
pipes
4. Can accumulate at the ends of pipelines and clog valves
5. Can contain weed seeds which aggravate weed control in the irrigated
area
6. Cost the farmer money
• These filters do not remove salts from the irrigation water (unless reverse
osmosis membranes are used, which are very uncommon in irrigation
systems and are not covered here)
Merkley & Allen Page 198 Sprinkle & Trickle Irrigation Lectures
III. Use of Reservoirs in pre-Filtration
1. To buffer differences in supply and demand rates. The supply from a canal
or well seldom coincides exactly with the system requirements (flow rate and
duration), and the system requirements can change due to different numbers
of stations in operation, “down time”, and duration of sets.
2. To allow for settling of some of the suspended particles. In these cases the
reservoir serves as a “settling basin”. Precipitated sediment can be
periodically removed from the reservoir with equipment or manual labor.
100,000
10,000
Settling velocity (mm/min)
1,000
100
10
0
Coarse sand Medium sand Fine sand Very fine Silt Clay
sand
Longer settling basins will allow more time for suspended particles to fall to
the bottom before arriving at the pump intake.
Sprinkle & Trickle Irrigation Lectures Page 199 Merkley & Allen
3. To aerate water pumped from wells, thereby oxidizing and precipitating
manganese and iron out of the water (some groundwater has manganese
and iron, and these can cause plugging of emitters). Only 1.5 ppm of either
manganese or iron can cause severe clogging problems in trickle laterals
and emitters (see Table 18.1 in the textbook).
4. To allow for air to escape when the water comes from a “cascading” well, in
which air becomes entrained into the water. Air in pipelines can dampen the
effects of water hammer, but also causes surges and blockages of flow.
5. To allow oils to collect on the water surface. Oils can cause rapid clogging of
most types of filters, requiring special cleaning with solvents and possible
replacement of sand media. When pumping from a reservoir the inlet is
below the water, and oil does not enter.
V. Sand Separators
• Sand separators are used to remove sand (but not organic matter) from the
water
• Most work by spinning the water in an enclosed column (or cone) to remove
sand through a centrifuge-type action
• There are no moving parts
• Solid particles with a density of approximately 1.5 g/cm3 can be removed by
these devices (most sand has a density of about 2.65 gm/cm3)
Merkley & Allen Page 200 Sprinkle & Trickle Irrigation Lectures
• Can remove from 70 to 95% of dense particles
• Periodic purging of accumulated sand (manual
or automatic) is necessary to maintain
performance
• Must have the correct flow rate through the
sand separator for proper operation, otherwise
less sand will be removed from the water
• Most sand separators have a pressure loss of
between 5 and 12 psi, from inlet to outlet. This
pressure loss does not change with time, only
with flow rate.
• Some sand separators are designed to fit down
into wells to protect the impellers and pump
bowls, but they are not as efficient as above-
ground sand separators
• Sand separators cannot remove all of the sand, and may pass large amounts
when the system is starting or stopping
• Therefore, screen filters should be installed downstream
• Sand separators are available but are not used as much as they were in the
past because people are using media tanks and other filters instead
• When taking water from a deep well, an alternative to using a sand separator
is to properly develop the well and use a good quality well screen
1. Introduction
• Every installation should have at least two tanks so that back-flushing can
occur during operation, but many designers recommend at least three tanks
in which only one is back-flushed at a time
• New media should be rinsed with clean water before placing it in the tanks
because it may have dust and other particles in it
• Some tanks have not performed well when the installers failed to rinse the
media first (resulting in fine particles passing into the irrigation system when
the tanks are first put into use)
• These filters are very good for removing relatively large amounts of organic
and inorganic matter, but some pre-screening is usually necessary with
surface water supplies
• High volume filtration at 20 to 30 gpm/ft2 (1.3 to 2.0 cm/s)
• Some silt and clay particles can also be removed by sand media filters, but
not by most screen-type filters. However, much silt and clay can pass
through a media filter too.
• Large volumes of particle contaminants can be collected in the sand media
before the media must be cleaned, or “back-flushed”
• In some cases the water must be pre-cleaned before entering the sand tanks
to prevent rapid accumulation of particle contaminants
• Media filters can also remove some sand from the supply water, but this
sand cannot always be effectively back-flushed from the media -- for large
amounts of sand, there should be a sand separator upstream of the media
tanks
• Industrial media filters are often five feet deep (or more), but have smaller
flow rates and less frequent back-flushing than agricultural media filters,
which may be only 14 inches deep
• Many of the particles captured by agricultural media filters stay within the
upper few inches of the sand because they are back-flushed frequently
• Flow through the filter is usually from inside to outside (debris is trapped on
the inside surface during operation) to prevent collapse of the screens
• Cleaning can be manual or automatic, and there are many varieties of
automatic cleaning methods
Sprinkle & Trickle Irrigation Lectures Page 203 Merkley & Allen
• Some filter designs have a rotating suction mechanism to clean the dirty
(inner) side of the screen element
• Manually-cleaned filters can have slow or quick release cover latches -- the
slow release latches are preferred because the quick release version can
“explode” if opened while the system is at operating pressure (dangerous to
personnel)
2. Disc Filters
Merkley & Allen Page 204 Sprinkle & Trickle Irrigation Lectures
Kind of Problem Hazard Level
low moderate severe
suspended solids 50 ppm 50-100 ppm > 100 ppm
pH 7.0 7.0-8.0 > 8.0
salts 500 ppm 500-2,000 ppm > 2,000 ppm
bicarbonate -- 100 ppm --
manganese 0.1 ppm 0.1-1.5 ppm > 1.5 ppm
total iron 0.2 ppm 0.2-1.5 ppm > 1.5 ppm
hydrogen sulfide 0.2 ppm 0.2-2.0 ppm > 2.0 ppm
bacteria count 10,000/liter 10,000-50,000/liter > 50,000/liter
1. Slimy bacteria
These can grow inside pipes and inside emitters.
The chemicals used to kill this bacteria are
chlorine, ozone, and acids.
Sprinkle & Trickle Irrigation Lectures Page 205 Merkley & Allen
5. Plant root entry into underground emitters
This is mainly a problem in permanent (several years) buried trickle
irrigation laterals. Can use acid injection at end of each season for
perennials to kill roots that are in the buried drip tubing. Or, use
herbicides to kill roots in the tubing without damaging the plants.
Some emitters and plastic drainage pipe have herbicide in the plastic
to discourage roots from entering.
• Injection of chemicals should be after the system starts, and stopping before
the system is turned off
• As a rule of thumb, one can assume an average pipe flow velocity of 1 fps, or
0.3 m/s, divide this into the longest pipe distance in the system (from pump to
farthest emitter), and determine the time
• This is the time to wait after starting the pump, and the time to allow for
flushing before turning the pump off
• Chemicals should be injected on a mass basis per set, not time. Thus, one
would want to apply a certain number of lbs or kg of a chemical in an
irrigation set, and it does not matter that it is all applied quickly or over a long
time (provided that the starting and stopping delay discussed above is
adhered to)
• The minimum injection rate can be put into equation form:
qc =
Fr A
=
(kg / ha )(ha ) = lph (332)
ctr Ta ( kg / liter )( 0.8 )( hrs / set )
where Fr is the mass application rate per unit area; A is the area irrigated per
set; c is the concentration of the chemical; tr is some kind of uniformity ratio,
taken to be 0.8; and Ta is the hours per set, or hours of chemical injection, if
shorter than the set time
Merkley & Allen Page 206 Sprinkle & Trickle Irrigation Lectures
Lecture 18
Trickle Irrigation Planning Factors
Widely-Spaced Crops
Closely-Spaced Crops
• The wetted soil area, Aw, is not measured at the soil surface, but from a
horizontal plane about 30 cm below the soil surface (actually, it depends on
root depth and soil type)
• The same is true for Pw
• The reason we are interested in Pw is to calculate the application depth “dx,”
as discussed in the following lecture
• This wetted area is distorted for sloping terrain, but the distortion is uniform
for uniform slopes (all other factors being the same)
• Wetted soil area can be estimated from empirical relationships and tables
(Table 19.1 in the textbook), but it is best to have site-specific field data in
which potential emitters are operated in the design area
• That is, test the emitter(s) and spacings in the field before completing the
irrigation system design
• Calculate percent wetted area, Pw, as follows:
⎛ N pS e w ⎞
Pw = 100 ⎜ ⎟ , for Se < 0.8w (333)
⎜ S pS rPd ⎟
⎝ ⎠
where Np is the number of emission points (emitters) per plant; Se is the
spacing of emitters along a lateral; w is the wetted width along the lateral; Sp
is the spacing of plants along a row; Sr is the spacing between rows; and Pd
is the fraction (not percent) of area shaded (see Lecture 19)
• Note that the numerator of Eq. 333 is wetted area, and the denominator is
actual plant area
• Note also that some emitters have multiple emission points
Merkley & Allen Page 208 Sprinkle & Trickle Irrigation Lectures
• Se is the spacing between emitters on the lateral; however, if Se is greater
than 0.8w, then use 0.8w instead:
⎛ 0.8N p w 2 ⎞
Pw = 100 ⎜ ⎟ , for Se ≥ 0.8w (334)
⎜ S pS r Pd ⎟
⎝ ⎠
• Sample calculation:
• Suppose Sr = Sp = 3.0 m, Pd =
80%, and w = 1.1 m
• Determine Np for Pw ≥ 33%
Np (0.88)(1.1)
0.33 = (336)
(3.0)(3.0)(0.80)
whereby Np = 2.45. Then,
3(0.88)(1.1)
Pw = = 0.40 (337)
(3.0)(3.0)(0.80)
⎛ N S' ( S' + w ) ⎞
Pw = 100 ⎜ ⎟ , for Se ≤ 0.8w
p e e
( )
(338)
⎜ 2 Pd S pS r ⎟
⎝ ⎠
or,
⎛ 1.44 w 2 N ⎞ 72 w 2 N
Pw = 100 ⎜ ⎟=
p p
, for Se ≤ 0.8w
( ) ( )
(339)
⎜ 2Pd S pS r ⎟ Pd S pS r
⎝ ⎠
Sprinkle & Trickle Irrigation Lectures Page 209 Merkley & Allen
Se’=0.8w
0.5w
w
Se ’
0.5w
Se Se
Double laterals
• As in the previous equation, if Se > Se’, use Se’ instead of Se in the above
equation for double laterals
• In the above equation, the denominator has a “2” because Np for double
lateral systems is always at least 2
• For micro-spray emitters, the wetted area is greater than that measured at
the surface (because it is measured below the surface):
⎡ ⎛ Se ⎞ ⎤
⎢ N p ⎜ A s + (PS ) 2 ⎟ ⎥
Pw = 100 ⎢ ⎝ ⎠ ⎥ , for S ≤ 0.8 w (340)
e
⎢ S pS rPd ⎥
⎢ ⎥
⎣ ⎦
where As is the surface area wetted by the sprayer; and PS is the perimeter
(circumference) of the wetted surface area
• In the above equation for Pw, the term in the inner parenthesis is:
Se π w 2 π w Se π w ⎛ w ⎞
A s + (PS ) = + = ⎜ + Se ⎟ (341)
2 4 2 2 ⎝2 ⎠
where w is the diameter corresponding to As, assuming a circular area
Merkley & Allen Page 210 Sprinkle & Trickle Irrigation Lectures
Salinity in Trickle Irrigation
• Salinity control is specialized with trickle irrigation because (usually) less than
100% of the area is wetted, and because water movement in the soil has
significant horizontal components
• Irrigation water always contains salts, and fertilizers add salt to the crop root
zones -- salinity management in the crop root zone is a long-term
management consideration with trickle systems, as it is with any other
irrigation method
• Salts tend to accumulate, or “build up”, at the periphery of the wetted bulb
shape under the soil surface
1. Rain can push salts near the surface down into the crop root area (but
a heavy rain can push them all the way through the root zone)
2. If and when the irrigation system is not operated for a few days, there
can be pressure gradients in the soil that pulls salts from the periphery
up into the root zone
Sprinkle & Trickle Irrigation Lectures Page 211 Merkley & Allen
• Annual leaching with surface irrigation or sprinklers (on a trickle-irrigated
field) may be necessary to clean salts out of the root zone, unless there is a
rainy period that provides enough precipitation to leach the soil
• If the irrigation water has high salinity, trickle systems can provide for higher
crop production because the frequent irrigations maintain the soil salinity
nearer to the ECw (this is often not the case with sprinklers and surface
irrigation systems - salinity concentrates due to ET processes between water
applications)
• According to Keller, the relative crop yield can be estimated as (Eq. 19.6):
• This is the relative crop yield (or production) in terms of soil water salinity
only
• ECw is the electrical conductivity of the irrigation water
• (ECe)max is the zero yield point, and (ECe)min is the 100% yield threshold
value
• (ECe)max may be as high as 32, and (ECe)min can be as low as 0.9
• This is based on the linear relationship between relative yield and salinity as
adopted years ago by FAO and other organizations
• Of course, calculated Yr values must be between 0 and 1
• Salinity of the soil extract, ECe, is measured by taking a soil sample to the
laboratory, adding pure water until the soil is saturated, then measuring the
electrical conductivity -- most published crop tolerance and yield relationships
are based on the ECe as a standard reference
• Crops don’t instantly die when the salinity approaches (ECe)max; the osmotic
potential increases and roots cannot extract the water that is there
• There can also be specific toxicity problems with minerals at high salinity
levels
• According to Allen, the relative yield will be near 100% for ECw less than
about 2(ECe)min, provided that frequent irrigations are applied (maintaining
salinity concentrations in root zone)
where LRt is the leaching requirement under trickle irrigation (fraction); and
ECdw is the electrical conductivity of the “drainage water”, which means the
water that moves downward past the root zone
ECw
LR t = (344)
2 (ECe )max
1. For continuous trickle system operation (daily or once every two days),
the soil water in the root zone is maintained near field capacity, which can be
taken as approximately 50% saturation (θv) for many soils. Thus,
(recall that ECe is measured after adding distilled water to the soil sample
until it is saturated)
3. Substitute this last equation into Eq. 19.7 from the textbook to obtain:
EC w
LR t = (348)
6 (ECe )min − 2ECw
Sprinkle & Trickle Irrigation Lectures Page 213 Merkley & Allen
this is similar to the leaching requirement as calculated for sprinkler
irrigation in Eq. 3.3 (coefficients 5 and 1 instead of 6 and 2), except that
(ECe)min is for 100% yield rather than 10% reduction in yield
Merkley & Allen Page 214 Sprinkle & Trickle Irrigation Lectures
Lecture 19
Water Requirements in Trickle Irrigation
• The daily transpiration rate under a trickle system is based on Ud and the
percent area shaded (covered) by the plant leaves. Eq. 19.9:
Td = 0.1 Ud Pd (349)
1.0
0.9
0.8
0.7
Closely-spaced crops
0.1*sqrt(Pd)
0.6
0.5
pi/4 = 0.785
0.4
0.3
0.2
0.1
0.0
0 10 20 30 40 50 60 70 80 90 100
Pd
Sprinkle & Trickle Irrigation Lectures Page 215 Merkley & Allen
• The reduction from Ud is justified by considering the typical reduction in wet
soil evaporation with trickle irrigation
• The maximum Pd for a mature orchard is usually about π/4 (0.785), which is
the ratio of the area of a square and the circle it encloses:
• Tree spacing is generally such that the trees do not compete for sunlight, and
the area of each tree is equal to the square of the spacing between them (for
a square spacing)
Ts = 0.1 U Pd (350)
(
Dn = (U − Pe − Ms ) 0.1 Pd ) (351)
• This is the same as for sprinkle irrigation (or surface irrigation), but with an
adjustment for percent wetted area. Eq. 19.12 is:
Merkley & Allen Page 216 Sprinkle & Trickle Irrigation Lectures
MAD Pw
dx = Wa Z (352)
100 100
• Essentially, the same net volume of water is applied as with other irrigation
methods, but on a smaller area of the surface (and subsurface)
• Then, the maximum irrigation interval is:
dx
fx = (353)
Td
and f’ (round down from fx to get whole number of days) is less than or equal
to fx, but often assumed to be 1 day for trickle system design purposes.
Then,
• The transmission ratio (peak use period) takes into account the two-
dimensional infiltration pattern, or bulb shape, under trickle irrigation
• Even if the net depth is exactly right, there will almost always be some deep
percolation (more than that which may be required for leaching purposes)
• The transmission ratio, Tr, is used as a factor to increase required gross
application depth from dn
• The transmission ratio is equivalent to the inverse of the distribution
efficiency, DEpa, as given in Chapter 6 of the textbook
• The transmission ratio is lower for heavy-textured (“fine”) soils because there
is more lateral water movement in the soil, and the bulb shape is flatter; thus,
potentially less deep percolation losses
• Table 19.3 gives approximate values of Tr for different soil textures and root
depths (1.0 < Tr < 1.1) – obtain more representative values from the field, if
possible
• Then, for LRt < 0.1, or Tr > 1/(1-LRt), Eq. 19.15a:
⎛d T ⎞
d = 100 ⎜ n r ⎟ (355)
⎝ EU ⎠
• EU takes into account pressure variations due to friction loss and elevation
change, and the manufacturer’s variability in emitter production
• If f’ = 1 day, then dn can be replaced by Td in Eq. 19.15a
Sprinkle & Trickle Irrigation Lectures Page 217 Merkley & Allen
• For LRt > 0.1, or Tr < 1/(1-LRt), Eq. 19.15c:
100dn
d= (356)
EU (1.0 − LR t )
• Equation 19.16:
d
G= SpSr (357)
f'
with d in mm; Sp and Sr in m; and G in liters/day
• Equation 20.11:
G
Ta = (358)
Npqa
Merkley & Allen Page 218 Sprinkle & Trickle Irrigation Lectures
2
1⎛ n ⎞
∑ (qi2 )
n
− ⎜ ∑ qi ⎟
i=1
n ⎜⎝ i=1 ⎟⎠ σ
ν= = (359)
⎛1 n ⎞ qavg
n − 1 ⎜ ∑ qi ⎟
⎜n ⎟
⎝ i=1 ⎠
or,
n
∑ ( qi − qavg )
2
1 i=1
ν= (360)
qavg n −1
• For a large sample (n > 50) the data will usually be normally distributed
(symmetrical “bell-shaped” curve) and,
• The system coefficient of variation takes into account the probability that the
use of more than one emitter per plant will cause an effective decrease in the
combined discharge variability per plant due to differences in the emitters
(not due to pressure variability due to pipe friction losses and elevation
changes)
• On the average, discharge variability due to manufacturer tolerances will
tend to balance out with more emitters per plant
Sprinkle & Trickle Irrigation Lectures Page 219 Merkley & Allen
ν
νs = (361)
N'p
where Np’ is the minimum number of emitters from which each plant receives
water (see page 493 of the textbook)
L w = w + (N − 1)Se (362)
where Lw is the length of the wetted strip; and N is the number of emitters
(assumed to be evenly spaced). Then,
⎛L − w⎞
N = 1+ ⎜ w ⎟ (363)
⎝ Se ⎠
or,
⎛ Sp − w ⎞
Np ' ≈ 1 + ⎜ ⎟ (364)
⎝ Se ⎠
• In new system designs it is not possible to go out to the field to measure the
EU’ (Eq. 17.2) – a different approach is required to estimate EU
• The design EU is defined as (Eq. 20.13):
qn
EU = 100 (1 − 1.27 νs ) (365)
qa
Merkley & Allen Page 220 Sprinkle & Trickle Irrigation Lectures
• EU gives a lower (more conservative) value than EU’, and the equation is
biased toward lower discharges to help ensure that the least watered areas
will receive an adequate application
• Graphical interpretations of these relationships are given in Figs. 20.9 and
20.10
• To use the tabular values of area under the curve (e.g. from a statistics
book), it is necessary to use qavg = 0 and σ = 1 (the alternative is to integrate
the above equation yourself, which can also be done)
• Actually, qavg never equals zero, but for the determination of the 1.27
coefficient it will not matter
• In the tables, for area = 75%, the abscissa value (q, in our case) is about
0.675
• The same tables usually go up to a maximum abscissa of 3.49 (recall that
99.75% of the values are within ±3σ, so 3.49 is usually far enough)
• Anyway, for 3.49, the area is about 99.98%, and that is from -∞ to +3.49 (for
qavg = 0 and σ = 1), for the high ¼
• For the low ¼, take the opposite, changing to q = -0.675 and q = -3.49
• In this case (qavg = 0 and σ = 1), the equation reduces to:
2
e −0.5q
occurrences = (367)
2π
Sprinkle & Trickle Irrigation Lectures Page 221 Merkley & Allen
• For q = 0.675, occurrences = 0.31766718
• For q = 3.49, occurrences = 0.0.00090372
• Finally,
0.31766718 − 0.00090372
= 1.268 (368)
0.9998 − 0.7500
V. System Capacity
A N pq a
Qs = 2.78 (369)
N s S pS r
where Ns is the number of stations (sets); and A is the total net irrigated area.
Or,
A qa
Qs = 2.78 (370)
N s S eS l
Merkley & Allen Page 222 Sprinkle & Trickle Irrigation Lectures
where the coefficient “2.78” is for Qs in lps; A in ha; qa in lph; and Sp, Sr, Se,
and Sl in m (10,000 m2/ha divided by 3,600 s/hr = 2.78)
• The approximate number of hours the system must operate per irrigation
season (or per year, in many cases) is equal to the required gross seasonal
application volume, divided by the system flow rate:
Vs
Ot = K (371)
Qs
Sprinkle & Trickle Irrigation Lectures Page 223 Merkley & Allen
Merkley & Allen Page 224 Sprinkle & Trickle Irrigation Lectures
Lecture 20
Emitter Selection & Design
I. Introduction
g π D4 H
Ac = (372)
ν qK
where lc is the length of the flow path; D is the inside diameter; H is the
pressure head; ν is the kinematic viscosity (a function of water temperature);
q is the flow rate; K is for units conversion; and g is the ratio of force to mass
Sprinkle & Trickle Irrigation Lectures Page 225 Merkley & Allen
• When is it valid to assume laminar flow? Consider that a Reynolds number
of 4,000 is probably as high as you can go without transitioning from laminar
to turbulent flow:
VD 4Q
= < 4,000 (373)
ν π νD
short
long
longest
• In black PE lateral hose, sunlight warms the water significantly as the velocity
slows down, and water viscosity decreases
• Long-path emitters would ideally be progressively longer along the lateral to
compensate and provide a more uniform discharge along the lateral
• Tortuous-path emitters also have long paths, but not laminar flow. This is
because the path has many sharp bends, and is in the form of a maze
• Tortuous-path emitters tend to behave hydraulically like orifices, and so do
many short-path emitters
• Flow rate is nearly independent of the viscosity, at least over typical ranges
in viscosity
• Many short-path emitters have pressure compensating features
Merkley & Allen Page 226 Sprinkle & Trickle Irrigation Lectures
IV. Orifice Emitters
2gHno2
q = a'K
( )
(374)
1 + no2
• Vortex emitters have a whirlpool effect in which the water must exit through
the center of the whirlpool
• Energy is dissipated by the friction from spinning in a chamber, and from
exiting through an orifice in the center
• As mentioned in a previous lecture, the exponent on the pressure head is
approximately equal to 0.4 (in the discharge equation). Thus, these can
usually be considered to be (partially) pressure compensating
Sprinkle & Trickle Irrigation Lectures Page 227 Merkley & Allen
• As defined previously, pressure compensating emitters always have a
pressure head exponent of less than 0.5 (otherwise they aren’t considered to
be pressure compensating)
VIII.Self-Flushing Emitters
• You can calculate the exponent, x, based on a pair of measured flow rates
and pressure heads
• Recall a rule of logarithms: log (ax) = x (log a)
• The solution can be obtained graphically, but is more quickly accomplished
with calculators and electronic spreadsheets
• If you have more than two pairs of q and H, then you can take the logarithmic
transformation of the equation and perform linear regression; however, the
regression will be mathematically biased toward the smaller values
• These are 15 basic steps, following the material presented in Chapters 17-24
of the textbook, that can be followed for the design of many trickle systems
• These are basic steps and represent a summary of the generalized design
process, but remember that each design situation will have some unique
features
1. Collect data on the crop, climate, soil, topography, and irrigation water
quality, field shape & size, water availability.
Merkley & Allen Page 228 Sprinkle & Trickle Irrigation Lectures
2. Select an emitter and determine an emission point layout such that 33% <
Pw < 67%. This will determine the number of emitters per plant, Np.
Emitter selection may involve field testing to determine the wetted width
(or diameter), w.
3. Calculate dx, fx, and Td. Note that fx will almost always be greater than
1.0.
4. Select a target value for EU (usually 70-95%; see Table 20.3) and
estimate the peak-use transmission ratio, Tr (usually 1.00-1.10; see Table
19.3).
5. Calculate the leaching requirement, LRt, based on crop type and irrigation
water quality.
7. Calculate the gross volume of water required per plant per day, G.
⎛ dS pS r ⎞
G = K⎜ ⎟ (375)
⎝ f ⎠
8. Calculate the daily hours of operation, Ta, (per station, or subunit) during
the peak-use period.
G
Ta = (376)
N pq a
If Ta = 24 hrs, then Ns = 1
If Ta = 12 hrs, then Ns = 1 or 2
If Ta = 8 hrs, then Ns = 2 or 3, and so on
10. Adjust Np and qa so that TaNs is equal to, or slightly less than, 90%(24
hrs/day) = 21.6 hrs/day. First, try adjusting qa because this is usually less
expensive than increasing Np. If the emitter is pressure compensating, or
if qa must be greatly altered, you may need to change Np (or you may
need to select a different emitter).
11. Having determined the value of qa, calculate the minimum allowable
emitter discharge, qn
Sprinkle & Trickle Irrigation Lectures Page 229 Merkley & Allen
q a EU
qn = (377)
100 (1.0 − 1.27 νs )
Note that if EU is high and νs is high, it could be that qn > qa (but this
would not be a reasonable calculation result!)
12. Calculate the average (nominal) and minimum lateral pressure heads
1/ x
⎛ q ⎞
h=⎜ ⎟ (378)
⎝ Kd ⎠
1/ x
⎛q ⎞
hn = ha ⎜ n ⎟ (379)
⎝ qa ⎠
15. Finally, size the laterals, headers, manifolds and mainline(s) according to
hydraulic design criteria.
Merkley & Allen Page 230 Sprinkle & Trickle Irrigation Lectures
Lecture 21
Pipe Specifications & Trickle Lateral Design
• All of these pipe materials are called “thermoplastic” because the material
can be repeatedly softened by increasing the temperature, and hardened by
a decrease in temperature
• The pressure rating of plastic pipe (especially PVC) decreases rapidly with
increasing temperature of the pipe and or water
• For example, at about 43°C (109°F) the PVC pressure rating
drops to one-half of the nominal value at 23°C (73°F), and
almost the same amount for PE
• PE pipe temperature can easily reach 43°C on a sunny day
• Unlike most metal pipes, these plastic pipe materials are immune to almost
all types of corrosion, whether chemical or electrochemical
• The resistance to corrosion is a significant benefit when chemigation is
practiced in a pressurized irrigation system
• The dimension ratio (DR) of a plastic pipe is the ratio of average diameter (ID
or OD) to wall thickness
• PVC, ABS and some PE are OD-based, while other PE pipe is ID-based
Sprinkle & Trickle Irrigation Lectures Page 231 Merkley & Allen
• Plastic pipe is currently manufactured up to a maximum diameter of 54
inches
• There are several standard dimension thickness
ratios (SDR) for several values, each with
its own pressure rating (at 23°C)
• Different types of PVC, ABS and PE
compounds exist, some of which are
stronger than others diameter
• Some plastic pipe is manufactured with
non-standard dimension ratios; in these
cases the ratio is called “DR” rather than
“SDR”
• Some pipe sizes are correspond to iron
pipe size (IPS), plastic irrigation pipe (PIP), and others
• These are different standards for indirectly specifying pipe dimension ratios
and pressure ratings
2S 2S
PR = = (OD-based) (381)
SDR − 1 ⎛ OD ⎞
⎜ t − 1⎟
⎝ ⎠
2S 2S
PR = = (ID-based) (382)
SDR + 1 ⎛ ID ⎞
⎜ t + 1⎟
⎝ ⎠
• Common terms used in the industry for PVC pipe include Class 160, Class
200, Schedule 40, Schedule 80 and Schedule 120 (in increasing strength
and decreasing SDR)
• With the “schedule” classification, the higher the schedule, the thicker the
walls, for a given nominal pipe diameter
Merkley & Allen Page 232 Sprinkle & Trickle Irrigation Lectures
• The maximum allowable operating pressure is approximately equal to:
(schedule)SE
P= (383)
1000
where P is the operating pressure (psi); S is the allowable stress in the pipe
material (psi); E is the “joint efficiency”; and “schedule” is the schedule
number (e.g. 40, 80, 120, etc.)
• Joint efficiency (or “joint quality factor”) for PVC is approximately 1.00, due to
the fact that it is seamless
• Class 160 and 200 refer to 160 psi and 200 psi ratings, respectively
• The Schedule 40 and 80 specifications have carried over from classifications
used in iron pipes
• Schedule 80 is seldom used in irrigation because its pressure rating is much
higher than the maximum pressures found in most irrigation systems
• Schedule 40 is commonly used in irrigation
Sprinkle & Trickle Irrigation Lectures Page 233 Merkley & Allen
Abbreviation Meaning
ABS Acrylonitrile-Butadiene-Styrene
DR Dimension Ratio
ID Inside Diameter
IPS Iron Pipe Size
ISO International Organization for Standardization
OD Outside Diameter
PE Polyethylene
PIP Plastic Irrigation Pipe
PR Pressure Rating
PVC Polyvinyl Chloride
SDR Standard Dimension Ratio
• To start a new system design, Keller & Bliesner recommend limiting the
lateral pressure variation to 0.5∆Hs, where ∆Hs is calculated from Eq. 20.14
• Then, 0.5∆Hs remains for the manifolds (if manifolds are subunits, or
“stations”)
• In lateral designs, the pipe diameter is usually chosen (not calculated), and if
the pressure variation or loss is “out of range”, then a different size can be
selected
• There are usually only a few lateral diameters to choose from
Merkley & Allen Page 234 Sprinkle & Trickle Irrigation Lectures
III. Trickle Lateral Hydraulics
7 Q1.75
J = 7.83(10) (384)
D4.75
for J in m/100 m; Q in lps; and D in mm
• The Blasius equation estimates the D-W “f” factor for smooth pipes
• If you want to calculate relative roughness, use ε = 1.5(10)-6 m
⎛S +f ⎞
J' = J ⎜ e e ⎟ (385)
⎝ Se ⎠
where fe is an equivalent length of lateral hose for each emitter, spaced
evenly at a distance of Se
• The fe pipe length is one way that minor hydraulic losses are calculated in
pipes
• From Eq. 8.7a, a dimensionless friction loss equation can be developed (see
Fig. 8.2), which is useful in semi-graphical hydraulic design work for trickle
irrigation laterals
• This is discussed in detail in the following lectures
• For a given lateral pipe size, lateral length, emitter spacing, and nominal
discharge per emitter, the lateral inlet pressure must be determined such that
the average lateral pressure is “correct”
• Then, the manifold can be designed to provide this lateral inlet pressure with
as little variation (with distance) as possible
• Figure 22.1 shows four different hydraulic cases for single lateral designs
• The design of pairs of laterals is essentially a compound single lateral
problem, with the added criterion that the minimum pressure be the same in
both laterals
• Not including riser height, the required lateral inlet pressure is (Eq. 22.6):
H'n = Hl − (h f + ∆he ) − ∆H c
(387)
H'n = H c − ∆H c
• If the ground slope along the direction of the laterals is less than 3% or so, it
is usually recommendable to run laterals off both sides (uphill and downhill)
of each manifold
• If the ground slope along the direction of the laterals is more than 3%, it may
be best to run the laterals only in the downhill direction
• The design objective for a pair of laterals is to have equal values of minimum
pressure, Hn’, in uphill and downhill laterals
• This means that the downhill lateral will always be longer for laterals of equal
pipe size on sloping ground
• The manifold should be located in-between rows of plants (trees), not over a
row
• For laterals on flat ground, the manifold goes in the center of the field (the
trivial solution)
• Use the dimensionless friction loss curves (Fig. 8.2) to locate the optimal
manifold position in a sloping field
• The laterals run along the 0.021 m/m slope
• The combined uphill + downhill lateral length is 315 m
Merkley & Allen Page 236 Sprinkle & Trickle Irrigation Lectures
• The spacing of plants (trees) is
Sp = 4.5 m
315 m
= 210 emitters (388)
1.5 m/emitter
2. Total nominal discharge for the pair of laterals is:
Qpair =
( 210 emitters )( 3.5 lph/emitter ) = 12.25 lpm (389)
( 60 min/hr )
3. From Table 8.2 (page 141), J ≅ 13.3 m/100m. The adjusted J is:
⎛ S e + fe ⎞ ⎛ 1.5 + 0.12 ⎞
J' = J ⎜ ⎟ = 13.3 ⎜ ⎟ = 14.4 m/100 m (390)
⎜ Se ⎟ ⎝ 1.5 ⎠
⎝ ⎠
4. Multiple outlet factor, F = 0.36 for 210 outlets
Sprinkle & Trickle Irrigation Lectures Page 237 Merkley & Allen
7. Ratio of elevation change to friction loss for the pair:
⎛ ∆he ⎞ 6.62
⎜ ⎟ = = 0.41 (393)
⎝ f ⎠pair
h 16.3
8. From the nondimensional graphical solution (Fig. 8.2): x/L = 0.69. Then, x
= (0.69)(315 m) = 217 m. Look at the figure below:
• Looking at the above figure, a straight line was drawn from the origin
(0, 0) to (1.0, 0.41), where 0.41 is the ratio calculated above
• The nondimensional curve was overlapped and shifted vertically so
that the curve was tangent to the same straight line, then traced onto
the graph
• The nondimensional curve was then shifted vertically even more so
that the inverse half-curve (dashed) intersected the (1.0, 0.41) point,
also tracing it onto the graph
• The intersection of the two traced curve segments gave an abscissa
value of about 0.69, which is the distance ratio
Merkley & Allen Page 238 Sprinkle & Trickle Irrigation Lectures
9. Finally, adjust x for tree spacing,
• This manifold position give the same minimum pressure in both the uphill
and downhill laterals
• Minimum pressure in the downhill lateral is located approximately
(0.35)(315 m) = 110 m from the closed end, or 216 - 110 = 106 m from
the manifold.
• Note that this procedure could also be used for sprinklers, but it would
probably only be feasible for solid-set, fixed systems
Sprinkle & Trickle Irrigation Lectures Page 239 Merkley & Allen
Merkley & Allen Page 240 Sprinkle & Trickle Irrigation Lectures
Lecture 22
Numerical Solution for Manifold Location
I. Introduction
• In the previous lecture it was seen how the optimal manifold location can be
determined semi-graphically using a set of non-dimensional curves for the
uphill and downhill laterals
• This location can also be determined numerically
• In the following, equations are developed to solve for the unknown length of
the uphill lateral, xu, without resorting to a graphical solution
• In the uphill lateral, the minimum head is at the closed end of the lateral
(furthest uphill location in the subunit)
• This minimum head is equal to:
where hn’ is the minimum head (m); hl is the lateral inlet head (m); hfu is the
total friction loss in the uphill lateral (m); xu is the length of the uphill lateral
(m); and S is the slope of the ground surface (m/m)
(hfd)1 hfu
(hfd)2
xm xu
h n’ h n’
• In the downhill lateral, the minimum head may be anywhere from the inlet to
the outlet, depending on the lateral hydraulics and the ground slope
• The minimum head in the downhill lateral is equal to:
Sprinkle & Trickle Irrigation Lectures Page 241 Merkley & Allen
where (hfu)1 is the total friction loss in the downhill lateral (m); (hfu)2 is the
friction loss from the closed end of the downhill lateral to the location of
minimum head (m); and xm is the distance from the manifold (lateral inlet) to
the location of minimum head in the downhill lateral (m)
• The location of minimum head is where the slope of the ground surface, S,
equals the friction loss gradient, J’:
S = J' (397)
where both S and J’ are in m/m, and S is positive (you can take the absolute
value of S)
• Using the Hazen-Williams equation, the friction loss gradient in the downhill
lateral (at the location where S = J’) is:
⎡ Se + fe ⎤ ⎡ ⎛ qa (L − xu − xm ) ⎞ ⎤
1.852
⎢ 10 −4.87 ⎥
J' = ⎢ ⎥ 1.212(10) ⎜ ⎟ D (398)
⎣ Se ⎦ ⎢⎣ ⎝ 3,600Se C ⎠ ⎥
⎦
0.571
⎡ 3,600Se ⎤ ⎡⎛ SD4.75 ⎞ ⎛ Se ⎞ ⎤
xm = L − xu − ⎢ ⎥ ⎢⎜⎜ 5 ⎟⎟ ⎜ S + f ⎟
⎥ (400)
⎣ qa ⎦ ⎢⎣⎝ 7.89(10) ⎠ ⎝ e e ⎠ ⎥⎦
• The above three “F” values are as defined by Eq. 8.9 in the textbook
• The friction loss gradients (in m/m) are:
Ju ' = K J ( xu )
1.852
(404)
Jd1 ' = K J (L − xu )
1.852
(405)
Jd2 ' = K J (L − xu − xm )
1.852
(406)
Sprinkle & Trickle Irrigation Lectures Page 243 Merkley & Allen
⎛ Se + fe ⎞ ⎡
1.852 ⎤
− ⎛ q ⎞
⎟ ⎢1.212(10) D ⎥
10 4.87
KJ = ⎜ ⎜
a
⎟ (407)
⎝ S e ⎠ ⎢ ⎝ 3,600S C
e ⎠ ⎥
⎣ ⎦
• Using the definitions above, solve for the length of the uphill lateral, xu
• Then, xd = L - xu
• Note that you might prefer to use the Darcy-Weisbach and Blasius equations
for the manifold calculations; they may be more accurate than Hazen-
Williams
• The “OptManifold” computer program uses the Darcy-Weisbach & Blasius
equations
Merkley & Allen Page 244 Sprinkle & Trickle Irrigation Lectures
Where do these Equations Come From?
L V2
hf = f (408)
D 2g
• Blasius equation, for estimating f for small diameter (D < 125 mm) “smooth
pipes” (e.g. PE & PVC), and based on more complete equations that are
used to plot the Moody diagram
−0.25
f ≅ 0.32NR (409)
VD 4Q
NR = = (410)
ν νπD
• The kinematic viscosity, ν, is equal to about 1.003(10)-6 m2/s for water at
20°C
• Then, for this kinematic viscosity,
−0.25 −0.25
⎛ 4Q ⎞ ⎛Q⎞
f ≅ 0.32 ⎜ ⎟ ≈ 0.0095 ⎜ ⎟ (411)
⎝ νπD ⎠ ⎝D⎠
Sprinkle & Trickle Irrigation Lectures Page 245 Merkley & Allen
• Putting the above into the Darcy-Weisbach equation:
−0.25
⎛Q⎞ L V2
hf = 0.0095 ⎜ ⎟ (412)
⎝D⎠ D 2g
or:
Q1.75
hf ≅ 0.00079L (413)
D4.75
where hf is in m; L is in m; Q is in m3/s; and D is in m
• Eq. 8.7a is obtained by having Q in lps, and D in mm, whereby the above
coefficient changes to 7.9(10)7
• Finally, in the above, use L(x/L) instead of L, and Q(x/L) instead of Q, and
call it “hfx”:
⎡Q ( x / L ) ⎤⎦
1.75
hfx ≅ 0.00079L(x / L) ⎣ (414)
D4.75
• Then,
hfx
= (x / L) ( x / L ) = (x / L)
1.75 2.75
(415)
hf
which is Eq. 8.10b and the basis for the nondimensional friction loss curves,
valid for plastic pipes with D < 125 mm
• The difference between the minimum pressure head and the pressure head
at the closed end of a lateral, ∆Hc, is used to calculate the minimum head in
the lateral, Hn’
• This is because the pressure head at the end of the lateral is easily
calculated as:
H c = H l − h f − ∆he (416)
• But the minimum pressure head does not necessarily occur at the end of the
lateral when the lateral runs downhill
• Thus, in general,
Merkley & Allen Page 246 Sprinkle & Trickle Irrigation Lectures
H'n = H c − ∆H c (417)
1. The minimum pressure in the lateral occurs where the ground slope (for a
uniform slope) equals the slope of the friction loss curve. The dimensionless
friction loss curve is defined as (Eq. 8.10b or Eq. 22.3b):
2.75
⎛ hfx ⎞ ⎛x⎞
⎜ ⎟ =⎜ ⎟ (418)
⎝ hf ⎠pair ⎝ L ⎠
⎛h ⎞
d ⎜ fx ⎟
1.75
⎝ hf ⎠pair ⎛x⎞
= 2.75 ⎜ ⎟ (419)
⎛x⎞ ⎝L⎠
d⎜ ⎟
⎝L⎠
⎛ ∆he ⎞ SL 100S
⎜ ⎟ = = (420)
⎝ hf ⎠pair ⎛ J'FL ⎞ J 'F
⎜ 100 ⎟
⎝ ⎠
4. Then,
100S
= 2.75 ( y )
1.75
(421)
J'F
in which y is the value of x/L where the minimum pressure occurs (0 ≤ y ≤ 1);
S is the ground slope (m/m); J’ is the friction loss gradient for the flow rate in
the pair of laterals (m/100 m); and F is the reduction coefficient for multiple
outlet pipes (usually about 0.36)
Sprinkle & Trickle Irrigation Lectures Page 247 Merkley & Allen
5. Solve for y:
1/ 1.75
⎛ 100S ⎞
y=⎜ ⎟ (422)
⎝ 2.75 J'F ⎠
or,
1/ 1.75
⎛ 100S ⎞
y≈⎜ ⎟ (423)
⎝ J' ⎠
where F ≈ 0.36
Merkley & Allen Page 248 Sprinkle & Trickle Irrigation Lectures
6. Referring to the figure on the previous page, the following equality can be
written:
∆Hc 100 y S
y 2.75 + = (424)
(hf )pair J'F
where,
J'FL
(hf )pair = (426)
100
and y can be approximated as in step 5 above (for F = 0.36)
−0.57
∆Hc = 8.9LS1.57 ( J' ) (427)
for ∆Hc in m; L in m; S in m/m; and J’ in m/100 m. Note that J’ and L are for
the pair of laterals, not only uphill or only downhill
⎛x ⎞
Hl = Ha + α (hf )pair + ⎜ − 0.5 ⎟ ( ∆he )pair (428)
⎝L ⎠
with,
1/ x
⎛q ⎞
Ha = ⎜ a ⎟ (429)
⎝ Kd ⎠
J'FL
(hf )pair = (430)
100
Sprinkle & Trickle Irrigation Lectures Page 249 Merkley & Allen
100S
( ∆he )pair = (hf )pair = SL (431)
J'F
1. Given that for a single lateral approximately ¾ of the friction loss occurs
from the inlet to the point where the average pressure occurs (multiple
outlets, uniform outlet spacing, constant discharge from outlets, single
lateral pipe size) we have the following:
2. Recall that,
2.75
⎛ hfx ⎞ ⎛x⎞
⎜ ⎟ =⎜ ⎟ (433)
⎝ hf ⎠pair ⎝ L ⎠
Then,
2.75
⎛x⎞
(hf )downhill =⎜ ⎟ (hf )pair
⎝L⎠
(434)
2.75
(hf )uphill = ⎛⎜ 1 −
x⎞
(hf )pair
⎝ L ⎟⎠
3. Combining equations:
3 ⎡⎛ x ⎞ ⎛ x ⎞2.75 ⎛ x ⎞⎛ x⎞
2.75 ⎤
α (hf )pair = (hf )pair ⎢⎜ ⎟ ⎜ ⎟ + ⎜1− ⎟ ⎜1− ⎟ ⎥ (435)
4 ⎢⎣⎝ ⎠ ⎝ ⎠
L L ⎝ L ⎠⎝ L ⎠ ⎥⎦
3 ⎡⎛ x ⎞
3.75 3.75 ⎤
⎛ x⎞
α = ⎢⎜ ⎟ + ⎜1− ⎟ ⎥ (436)
4 ⎢⎝ L ⎠ ⎝ L⎠ ⎥⎦
⎣
Merkley & Allen Page 250 Sprinkle & Trickle Irrigation Lectures
• This last equation for α is Eq. 22.25 from the textbook
• See the figure below
Sprinkle & Trickle Irrigation Lectures Page 251 Merkley & Allen
Merkley & Allen Page 252 Sprinkle & Trickle Irrigation Lectures
Lecture 23
Manifold Hydraulic Design
I. Introduction
• Manifolds in trickle irrigation systems often have multiple pipe sizes to:
• In small irrigation systems the reduction in pipe cost may not be significant,
not to mention that it is also easier to install a system with fewer pipe sizes
• Manifold design is normally subsequent to lateral design, but it can be part of
an iterative process (i.e. design the laterals, design the manifold, adjust the
lateral design, etc.)
• The allowable head variation in the manifold, for manifolds as subunits, is
given by the allowable subunit head variation (Eq. 20.14) and the calculated
lateral head variation, ∆Hl
• This simple relationship is given in Eq. 23.1:
• Eq. 23.1 simply says that the allowable subunit head variation is shared by
the laterals and manifold
• Recall that a starting design point can be to have ∆Hl = ½∆Hs, and ∆Hm =
½∆Hs, but this half and half proportion can be adjusted during the design
iterations
• The lateral pressure variation, ∆Hl, is equal to the maximum pressure minus
the minimum pressure, which is true for single-direction laterals and
uphill+downhill pairs, if Hn’ is the same both uphill and downhill
• Equation 20.14 (page 502 in the textbook) gives the allowable pressure head
variation in a “subunit”
• This equation is an approximation of the true allowable head variation,
because this equation is applied before the laterals and manifold are
designed
• After designing the laterals and manifold,
the actual head variation and expected
EU can be recalculated
(
H max − H n = 2 H a − H n ) (438)
(
H max − H n = 4 H a − H n ) (439)
• For a sloping friction loss gradient (multiple outlets) on flat ground with dual
pipe sizes, about 63% of the friction head loss occurs from the lateral inlet to
the location of average pressure. Then 100/(100-63) = 2.7 and,
(
H max − H n = 2.7 H a − H n ) (440)
(
∆Hs = 2.5 H a − H n ) (441)
• After the design process, the final value of ∆Hs may be different, but if it is
much different the deviation should be somehow justified
Merkley & Allen Page 254 Sprinkle & Trickle Irrigation Lectures
III. Pipe Sizing in Manifolds
1. Semi-graphical
2. Hydraulic grade line (HGL)
3. Economic pipe sizing (as in Chapter 8 of the textbook)
• The graphical method uses “standard” head loss curves for different pipe
sizes and different flow rates with equally-spaced multiple outlets, each outlet
with the same discharge
• The curves all intersect at the origin (corresponding to the downstream
closed end of a pipe)
• Below is a sample of the kind of curves given in Fig. 23.2 of the textbook
• Instead of the standard curves, specific curves for each design case could be
custom developed and plotted as necessary in spreadsheets
• The steps to complete a graphical design are outlined in the textbook
• The graphical procedure is helpful in understanding the hydraulic design of
multiple pipe size manifolds, but may not be as expedient as fully numerical
procedures
Sprinkle & Trickle Irrigation Lectures Page 255 Merkley & Allen
3.8
3.6
3.4
3.2
3.0
Friction Head Loss (ft)
2.8
2.6
2.4
2.2
2.0
1.8
1.6
1.4
1.2
1.25 inch
1.0
1.50 inch
0.8
2.00 inch
0.6
2.50 inch
0.4 3.00 inch
0.2 4.00 inch
0.0
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320
Step 1:
flow direction
(∆Hm)a
So ∆Em
1
0 manifold flow rate Qm
xd
Merkley & Allen Page 256 Sprinkle & Trickle Irrigation Lectures
Step 2:
flow direction
(∆Hm)a
So ∆Em
1
0 manifold flow rate Qm
xd
Step 3:
flow direction
(∆Hm)a
So ∆Em
1
0 manifold flow rate Qm
xd
Sprinkle & Trickle Irrigation Lectures Page 257 Merkley & Allen
Step 4:
flow direction
(∆Hm)a
So ∆Em
1
0 manifold flow rate Qm
xd
Step 5:
flow direction
(∆Hm)a
So ∆Em
1
0 manifold flow rate Qm
xd
Merkley & Allen Page 258 Sprinkle & Trickle Irrigation Lectures
Step 6:
flow direction
(∆Hm)a
So ∆Em
1
0 manifold flow rate Qm
xd
HGL Design Procedure
• The HGL procedure is very similar to the graphical procedure, except that it
is applied numerically, without the need for graphs
• Nevertheless, it is useful to graph the resulting hydraulic curves to check for
errors or infeasibilities
• The first (upstream) head loss curve starts from a fixed point: maximum
discharge in the manifold and upper limit on head variation
• Equations for friction loss curves of different pipe diameters are known (e.g.
Darcy-Weisbach, Hazen-Williams), and these can be equated to each other
to determine intersection points, that is, points at which the pipe size would
change in the manifold design
• But, before equating head loss equations, the curves must be vertically
shifted so they just intersect with the ground slope curve (or the tangent to
the first, upstream, curve, emanating from the origin)
• The vertical shifting can be done graphically or numerically
Sprinkle & Trickle Irrigation Lectures Page 259 Merkley & Allen
• The manifold has multiple outlets (laterals or headers), and the “section flow
rate” changes between each outlet
• The “system flow rate” would be the flow rate entering the manifold
• After completing the manifold pipe sizing, the required manifold inlet pressure
head can be determined (Eq. 23.4):
Hm = Hl + k hf + 0.5∆Em (442)
where k = 0.75 for single-diameter manifolds; k = 0.63 for dual pipe size
laterals; or k ≈ 0.5 for three or more pipe sizes (tapered manifolds); and ∆El
is negative for downward-sloping manifolds
• As with lateral design, the friction loss curves must be shifted up to provide
for the required average pressure
• In the case of manifolds, we would like the average pressure to be equal to
the calculated lateral inlet head, Hl
• The parameter ∆El is the elevation difference along one portion of the
manifold (either uphill or downhill), with positive values for uphill slopes and
negative values for downhill slopes
V. Manifold Design
• Manifolds should usually extend both ways from the mainline to reduce the
system cost, provided that the ground slope in the direction of the manifolds
is less than about 3% (same as for laterals, as in the previous lectures)
• As shown in the sample layout (plan view) below, manifolds are typically
orthogonal to the mainline, and laterals are orthogonal to the manifolds
Merkley & Allen Page 260 Sprinkle & Trickle Irrigation Lectures
• Manifolds usually are made up of 2 to 4 pipe diameters, tapered
(telescoping) down toward the downstream end
• For tapered manifolds, the smallest of the pipe diameters (at the downstream
end) should be greater than about ½ the largest diameter (at the upstream
end) to help avoid clogging during flushing of the manifold
D1 D2 D3>0.5D1
• The maximum average flow velocity in each pipe segment should be less
than about 2 m/s
• Water hammer is not much of a concern, primarily because the manifold has
multiple outlets (which rapidly attenuates a high- or low-pressure wave), but
the friction loss increases exponentially with flow velocity
• The objective is the same as for pairs of laterals: make (Hn)uphill equal to
(Hn)downhill
• If average friction loss slopes are equal for both uphill and downhill manifold
branches (assuming similar diameters will carry similar flow rates):
Downhill side:
( ∆Hm )a = hfd − ∆E ⎛⎜
x⎞
⎟ = hfd − Y∆E (443)
⎝ ⎠
L
Uphill side:
L−x⎞
( ∆Hm )a = hfu + ∆E ⎛⎜ ⎟ = hfu + (1 − Y)∆E (444)
⎝ L ⎠
where x is the length of downhill manifold (m or ft); L is the total length of the
manifold (m or ft); Y equals x/L; and ∆E is the absolute elevation difference of
the uphill and downhill portions of the manifold (m or ft)
Juphill = Jdownhill
hfu h (445)
= fd
L−x x
where J-bar is the average friction loss gradient from the mainline to the end
of the manifold (J-bar is essentially the same as JF)
Sprinkle & Trickle Irrigation Lectures Page 261 Merkley & Allen
Then,
hfd = Jx
(446)
hfu = J(L − x)
and,
( ∆Hm )a = Jx − Y∆E
(447)
( ∆Hm )a = J(L − x) + (1 − Y) ∆E
then,
( ∆Hm )a + Y∆E
=J
x (448)
( ∆Hm )a − (1 − Y) ∆E
=J
L−x
• Equating both J-bar values,
⎛ Qbeg − Qend ⎞
LD = L ⎜ ⎟ (453)
⎝ Q m ⎠
where Qbeg is the flow rate at the beginning of diameter “D” in the EPST (lps
or gpm); Qend is the flow rate at the end of diameter “D” in the EPST, which is
the breakeven flow rate of the next larger pipe size) (lps or gpm); L is the
total length of the manifold (m or ft); and Qm is the manifold inflow rate (lps or
gpm). (see Eq. 23.7)
(d) Determine the total friction loss along the manifold (see Eq. 23.8a):
where,
• The above equation is for four pipe sizes; if there are less than four sizes, the
extra terms are eliminated from the equation
• An alternative would be to use Eq. 23.8b (for known pipe lengths), or
evaluate the friction loss using a computer program or a spreadsheet to
calculate the losses section by section along the manifold
• Eq. 23.8b is written for manifold design as follows:
a −1 ⎛ a
FK Qm x1 x a2 − x1a x 3a − x a2 x a4 − x 3a ⎞
hf = ⎜ + + + ⎟ (455)
100La −1 ⎜⎝ D1c Dc2 D3c Dc4 ⎟⎠
• Again, there may be up to four different pipe sizes in the manifold, but in
many cases there will be less than four sizes
∆Hm = hf + S xu (456)
⎛ 0.36 ⎞
∆Hm = hf + S ⎜ 1 − xd
n ⎟⎠
(457)
⎝
Merkley & Allen Page 264 Sprinkle & Trickle Irrigation Lectures
where n is the number of different pipe sizes used in the branch; and S is the
ground slope in the direction of the manifold (m/m)
(f) if ∆Hm < 1.1 (∆Hm)a, then the pipe sizing is all right. Go to step (g) of this
B B B B B B
EPST). This will artificially increase the break-even flow rates in the
table (chart).
• The new flow rates to use in re-doing the EPST can be estimated for s >
0 as follows:
1/ b
⎛ hf ⎞
Qnew old
= Qs ⎜ ⎟ (458)
s ⎜ ( ∆Hm ) − ∆Em ⎟
⎝ a ⎠
and for s < 0 as:
1/ b
⎛ ⎞
⎜ hf ⎟
old ⎜ ⎟
Qnew
s = Qs (459)
⎜ ∆H ⎛ 0.36 ⎞ ⎟
⎜ ( m )a − ∆El ⎜ 1 − n ⎟ ⎟
⎝ ⎝ ⎠⎠
•The above two equations are used to change the flow rates to compute
the EPST
• The value of Qm remains the same B B
• This will make the laterals shorter, Qm will decrease, and ∆Hl may B B B B
decrease
• This alternative may or may not help in the design process
Sprinkle & Trickle Irrigation Lectures Page 265 Merkley & Allen
(4) Decrease ∆Hl (use larger pipe sizes) B B
(5) Increase Ha B B
• For non-critical manifolds, or where ∆Hm < (∆Hm)a, decrease Qs (or just B B B B B B B B
Fs = 0.38S1.25
f + 0.62 (461)
where Sf = Qlc/Qla; Qlc is the lateral discharge at the end of the manifold
B B B B B B B B
and Qla is the average lateral discharge along the manifold. Then,
B B
⎛ JL ⎞
hf = Fs F ⎜ ⎟
⎝ 100 ⎠ (462)
Merkley & Allen Page 266 Sprinkle & Trickle Irrigation Lectures
(a) Uphill Side of the Manifold
• Get the smallest allowable pipe diameter and use only the one diameter
for this part of the manifold
• First, determine the minimum pipe diameter for the first pipe in the
downhill side of the manifold, which of course will be the largest of the
pipe sizes that will be used
• This can be accomplished by finding the inside pipe diameter, D, that will
give a friction loss curve tangent to the ground slope
• To do this, it is necessary to: (1) have the slope of the friction loss curve
equal to So; and, (2) have the H values equal at this location (make them
B B
• See the following figure, based on the length of the downstream part of
the manifold, xd B B
• Some manifolds will only have a downhill part – others will have both
uphill and downhill parts
H flow direction
(∆Hm)a
hf
e
rv
D1 = ???
cu
ss
lo
i on
fr ict
So ∆Em
1
0
0 manifold flow rate Qm
xd
Sprinkle & Trickle Irrigation Lectures Page 267 Merkley & Allen
• For the above figure, where the right side is the mainline location and the
left side is the downstream closed end of the manifold, the friction loss
curve is defined as:
JFL
H = ( ∆Hm )a + ∆Em − hf + (463)
100
1.852
⎛Q⎞
J = K⎜ ⎟ D−4.87 for 0 ≤ Q ≤ Qm (464)
⎝C⎠
1 1 0.852
F= + + (465)
2.852 2N 6N2
⎛ x ⎞⎛ Q ⎞
N = ⎜ d ⎟⎜ ⎟ for N > 0 (466)
⎝ Sl ⎠ ⎝ Qm ⎠
where N is the number of outlets (laterals) from the location of “Q” in the
manifold to the closed end
⎛ Q ⎞
L = xd ⎜ ⎟ (467)
⎝ Qm ⎠
• The total head loss in the downhill side of the manifold is:
1.852
J F x ⎛Q ⎞
hf = hf hf d = 0.01K ⎜ m ⎟ D−4.87Fhf x d (468)
100 ⎝ C ⎠
dH 1 ⎛ dJ dF dL ⎞
= ⎜ FL + JL + JF ⎟ (469)
dQ 100 ⎝ dQ dQ dQ ⎠
where,
Merkley & Allen Page 268 Sprinkle & Trickle Irrigation Lectures
dJ 1.852KQ0.852
= (470)
dQ C1.852D4.87
dF xd ⎛ 1 0.852 ⎞
=− ⎜ + ⎟ (471)
dQ SlQmN2 ⎜⎝ 2 3N ⎟⎠
dL x
= d (472)
dQ Qm
⎛ Q ⎞
H = SoL = So x d ⎜ ⎟ (473)
⎝ Qm ⎠
and,
dH So x d
= (474)
dQ Qm
• Combine the two equations defining H (this makes the friction loss curve
just touch the ground surface):
⎛ Q ⎞ JFL
So x d ⎜ ⎟ = ( ∆Hm )a + ∆Em − hf + (475)
⎝ Qm ⎠ 100
−0.205
⎡ 1.852 ⎛ So x dQ ⎞⎤
⎢ 100C ⎜ − ( ∆H )
m a − ∆ Em ⎟⎥
D= ⎢ ⎝ Qm ⎠⎥
( )
(476)
⎢ K Q 1.852 1.852
FL − Qm Fhf x d ⎥
⎢ ⎥
⎣⎢ ⎦⎥
So x d 1 ⎛ dJ dF dL ⎞
= ⎜ FL + JL + JF ⎟ (477)
Qm 100 ⎝ dQ dQ dQ ⎠
Sprinkle & Trickle Irrigation Lectures Page 269 Merkley & Allen
• Combine the above two equations so that the only unknown is Q (note: D
appears in the J & dJ/dQ terms of the above equation)
• Solve for Q by iteration; the pipe inside diameter, D, will be known as part
of the solution for Q
• The calculated value of D is the minimum inside pipe diameter, so find the
nearest available pipe size that is larger than or equal to D:
• Now calculate the equation of the line through the origin and tangent to
the friction loss curve for D1 B B
⎛ Q ⎞
H = StL = St x d ⎜ ⎟ (479)
⎝ Qm ⎠
then,
⎛ Q ⎞ JFL
St x d ⎜ ⎟ = ( ∆Hm )a + ∆El − hf + (480)
⎝ Qm ⎠ 100
St x d 1 ⎛ dJ dF dL ⎞
= ⎜ FL + JL + JF ⎟ (481)
Qm 100 ⎝ dQ dQ dQ ⎠
• Then take the next smaller pipe size, D2, and make its B B
JFL
H = H0 + (482)
100
where H0 is a vertical offset to make the friction loss curve tangent to the
B B
Merkley & Allen Page 270 Sprinkle & Trickle Irrigation Lectures
• Equating heads and solving for H0, B B
⎛ Q ⎞ JFL
H0 = St x d ⎜ ⎟− (483)
⎝ Qm ⎠ 100
• Again, set the slope of the friction loss curve equal to St, B B
St x d 1 ⎛ dJ dF dL ⎞
= ⎜ FL + JL + JF ⎟ (484)
Qm 100 ⎝ dQ dQ dQ ⎠
• Now you have the equation for the next friction loss curve
• Determine the intersection with the D1 friction loss curve to set the lengthB B
for size D1; this is done by equating the H values for the respective
B B
1.852
Hbig − Hsmall +
FLK ⎛ Q ⎞
⎜ ⎟
100 ⎝ C ⎠
(Dbig
−4.87 −4.87
− Dsmall )=0 (485)
Hsmall = H0 (487)
⎛ Q ⎞
LD1 = x d ⎜ 1 − ⎟ (488)
⎝ Qm ⎠
• Continue this process until you have three or four pipe sizes, or until you
get to a pipe size that has D < ½D1 B B
Sprinkle & Trickle Irrigation Lectures Page 271 Merkley & Allen
Comments about the HGL Method B
• The above equation development could also be done using the Darcy-
Weisbach equation
• Specify a minimum length for each pipe size in the manifold
so that the design is not something ridiculous (i.e. don’t just
blindly perform calculations, but look at what you have)
• For example, the minimum allowable pipe length might be
something like 5Sl
B B
• Below is a screen shot from a computer program that uses the HGL
method for manifold pipe sizing
Merkley & Allen Page 272 Sprinkle & Trickle Irrigation Lectures
Sprinkle & Trickle Irrigation Lectures Page 273 Merkley & Allen
Merkley & Allen Page 274 Sprinkle & Trickle Irrigation Lectures
Lecture 24
Hydraulic Design of Mainline & Supply Line
I. Introduction
Sprinkle & Trickle Irrigation Lectures Page 275 Merkley & Allen
III. Mainline, Supply, and Control Head Design
Merkley & Allen Page 276 Sprinkle & Trickle Irrigation Lectures
• The critical subunit will define the “worst case” for which the
pumping unit should be designed. It may then be possible to
reduce pipe sizes in other subunits if they will have excess head
available.
Example calculation:
• Size sections A-B, B-C and C-D for a trickle irrigation mainline
having three manifolds
• First, decide on the number of stations, Ns B B
This could be 1, 3 or 6:
• Set up a table to see the effect of Ns on the flow rates and Ot per B B B B
Number of Stations
1 2 3
Qs (lps) B B 30 30 30
Ot/station (hrs)
B B 1000 330 165
Ot, CD B B 1000 330 330
QCD B B 10 30 30
Ot, BC B B 1000 660 660
QBC B B 20 30 30
Ot, AB B B 1000 1000 1000
QAB B B 30 30 30
• Ot, CD, for example, is the number of hours that water is flowing in
B B
1. static lift
2. well losses (if applicable)
3. supply line losses (elevation and friction)
4. control head pressure losses
5. losses to the critical subunit plus inlet pressure, (Hm + B B
Hfe)c
B B B B
Sprinkle & Trickle Irrigation Lectures Page 279 Merkley & Allen
Merkley & Allen Page 280 Sprinkle & Trickle Irrigation Lectures
Sprinkle and Trickle Irrigation Text Errata
September 1, 2004
p. 17: Second line add comma between wetted and may to read: --- “but lower leaves, if
wetter, may” -----.
p. 32: Equation 3.1. In definitions of terms, change “WA” to “Wa”; and for depth Z
change metric dimension from “mm” to “m”.
p. 38: In full sentence above Table 3.5, pluralize value to read: ---“the ECe values
presented in Table 3.5” ----.
p. 39 End of fifth line from top should be changed from LR < 0.1 to LR > 0.1.
p. 46: Third line from bottom of third paragraph, change “as” to “an” to read: ---
“making too sharp an “S” turn”----.
p. 70: Fig. 5.6. Two errors: a) the wind speed should be “5 m/s” not “1 m/s”; and b) the
sprinkler location “0” on the right hand (vertical) scale is not offset to reflect wind, it
should be shifted to where the lower “6” is located.
p. 83: Table 5.4. Change last number in first column from “(0.40)” to “(0.15)”.
p. 99: Table 6.2. For CU = 94% and pa = 80% the value given should be “94”.
p. 131: Sample Calculation 7.1. In last line of GIVEN: change “5-ft” to “50-ft”.
p.134: The value for the constant “K “ below Equation 8.1 for metric units would be
slightly more accurate if changed from 1.212 to 1.217 x 1012.
p.138: The value for the constant “K “ below Equation 8.7a for metric units would be
slightly more accurate if changed from 7.89 to 7.88 x 107.
p. 141: In the Flow rate column for (gpm): the 6.0 should be followed by “6.1” rather
than “0.1”.
1
p. 146: Two typos in the text one line above and two lines below Equation (8.9a), change
“form” to “from”.
p. 147: Sample Calculation 8.1. At end of last line, change “7.07” to “70.7”.
p. 164: Table 8.12. The heading for the first column should simply be “Method”, strike
out “(or size for C-D)”.
p. 167: Equation 8.19. Change “Table 8.11” to “Table 8.9” in definition for EAE(e).
p. 170: Fig. 8.8. The long FIXED PLUS OPERATING COSTS arrow should have had its
arrowhead at and terminated at the point where it crossed the solid line.
p. 197: Fig. 9.7. In the left hand caption unit line, change “5 = 5%” to “S = 5%”.
p. 209: Sample Calculation 10.2. In the line above the fourth equation from the bottom
of the page, the sentence should read, “The final hf2 with all 6-in. pipe is:”
p. 218: Sample Calculation 10.5. In GIVEN: under Economic relationships: change “Cp”
to “Cp”.
p. 219: Sample Calculation 10.5. In CALCULATION: Step 2, change the “0.0001” in the
equation to “0.001”.
p. 223: Table 11.2. Change the bottom Equation for “sudden contractions” to:
[
K r = 0.7 1 − (D r )2 ] 2
p. 226: Sample Calculation 11.1. In CALCULATIONS: in first line change “K” to “Kr”
and in fifth line from bottom, change “interests” to “intersects”.
p. 230: The fifth text line should read: “The static head ----- and C is:”
p. 231: Equation 11.4a. Change the “Qg” in the middle term on the right side to “Qs”.
2
p. 242: Near bottom, change “H = 1197 ft” to “H = 197 ft”
p. 256: Table 12.2. Change caption to read “.hp / 100 ft…” rather than “.hp / 1000 ft…”
p. 292: Below Equation 13.4. In the definition of T, change “180o $ T # 360o” to “180o
# T # 360o”.
p. 313: Table 14.1. Change the values in the “Irrigation interval” columns for both 5 and
6 days for Pasture - Peak from “0.02” to “1.02”.
p. 322: In first line, change “(0.3 in. / hr)” to “(0.4 in. / hr)”.
p. 324: Table 14.2. This table is out of date. The Irrigation Association’s Center Pivot
manual has an updated equivalent.
p. 343: Sample Calculation 14.6. Change the subscript of R’ from “R’e” to “R’n” in two
places a) in the sixth line from top of page; and b) in the line above the last equation.
p. 361: Error in four places, should read “…for the 168-mm (6 5/8-in.)…” (i.e., change
all occurrences of “6-in.” to “6 5/8-in.”).
(h f − h fj )6 = (h f )
− h fj J 6 / J 8 = 1.16 x 5.97 / 2.31 = 3.0 m
8
Note that in the equation for (hf)8,6 that one should also subtract out for the hf due
to the end gun; however, this turns out to be small (0.04 m).
p. 395: In the line below Equation (15.5), change “LET” to “LET” and “indix” “index”.
p. 407: In eleventh line from bottom, change “drop” to “crop”; and in sixth line from
bottom, change “precipitaton” to “precipitation”.
p. 443: Table 18.2. In first column change “Very find sand” to “Very fine sand”.
3
p. 456: Sample Calculation 19.1. In first equation “w” under CALCULATIONS: change
the “.15” to “1.5”, but the calculation is OK.
p. 462: Equation 19.3, 19.4, and 19.5. A “Pd” should be added to the denominator to
allow for applications to sparse plantings. As is, it applies only to dense mature orchards.
Otherwise, for sparse plantings, the canopy area should be used rather than Sp x Sr, but
this could become confusing. Therefore, the denominators should read: “Sp x Sr x
Pd/100”.
p. 492: At the end of last bullet near top of page, change “(1 + ν)” to “(1 " ν)”.
p. 496: Fig. 20.8. The three curves should be labeled from top to bottom: “LARGE ON-
LINE”; STANDARD ON-LINE”; AND “SMALL ON-LINE”.
p. 512 The G calculated using Equation 19.16a be changed from 9.3 to 93.3 gal/day.
p. 516: Near bottom of page in reference to “Seasonal Irrigation Efficiency” should refer
to Table 19.4 (rather than 19.3).
p. 521: In the second equation on the page for using Equation 19.11, change “[0.1 +
(75)0.5]” to “[0.1 (75)0.5]”, but calculation is OK.
L (1 − F) a / b −1 / b
∆H c = S J
100
(see Equation 23.14b). This form is simpler and it might be more didactic to present both
forms. (S is absolute slope).
p. 537: Fig. 22.5. Insert arrows to show where “Av. hfp” refers to (left-hand side, middle
of figure). “Av. hfp” should refer to the vertical distance between the horizontal dashed
line and the lower end of the hfp “curve” (i.e., the vertical height of the hatched area that
is beneath the dashed line).
4
p. 538: Equation 22.19, 22.20. Add “-x/Lp ∆Ep” to each equation so that they read as:
2.75
⎛ ⎞
(H )d = h fp ⎜⎜ x ⎟
⎟
+ ∆H c + H 'n −
x
∆E p (22.19)
⎝ Lp ⎠ Lp
2.75
⎛ ⎞ ⎛ x ⎞⎟
(H )u = h fp ⎜⎜1 − x ⎟⎟ + ⎜1 −
⎜ ⎟
∆E p + H 'n (22.20)
⎝ Lp ⎠ ⎝ Lp ⎠
Furthermore, in the legend following Equation 23.14a, change explanation for Hx to:
“Hx = hydraulic head (minimum) at point x along a pipe-friction curve that is tangent to
the HGL, m (ft). (this is contrasted against Hx on page 577, which is a friction loss)“
p. 567: Equation 23.14b. Change the exponent on (x/L) to “a” instead of “1/a”.
p. 570: The numerical values in the second equation should be: 640/177 = 3.6 (not
640/17).
p. 581: Change referenced publication in next to last line to read: “Trickle Irrigation for
Crop Production “.
p. 598: Table 24.6. An “=” sign is missing in the equation in the middle of the table, it
should read: “(Hm + Hfe) = (50.2 + 7.4) =”.
5
BIE 5110/6110
Sprinkle & Trickle Irrigation
Fall Semester 2004 – Exam #1
Include units in all results. Indicate any assumptions that you might make.
Name__________________________________
Almonds (deciduous trees, with no cover crop) have been planted in an 80-acre
orchard and will be irrigated with a set sprinkler system. The climate can be
characterized as “moderate.” The topsoil is 2.7 ft of silty clay loam, and below that are
3.1 ft of clay loam soil. The soil intake rate is 0.5 inch/hr.
Use an MAD value of 30%. ECw is 0.47 dS/m and the estimated water application
efficiency will be Ea = 85%. There is no effective rain during the peak-use period. For
these preliminary calculations, and based on the spacing of the trees, use a sprinkler
spacing of 40 ft x 50 ft.
a) Obtain the values for average Wa, average Z, Ud, U, and ECe from
the tables in Chapter 3 of the textbook.
b) Calculate the maximum net application depth per irrigation, dx.
c) Calculate the maximum irrigation interval, nominal irrigation
interval (whole number of days), and the net application depth per
irrigation, dn.
d) What is the gross depth to apply per irrigation?
e) What is the irrigation set time, Sto, in hours?
Suppose you applied the economic pipe sizing method. What if you were using the
Hazen-Williams equation and based all your calculations on a system capacity of 100
lps, but now you realize a calculation mistake was made, and the system capacity
should really be 115 lps.
A section flow rate, q, (threshold between two adjacent pipe sizes) was 50 lps, but now
it needs to be adjusted for the new system capacity of 115 lps.
What is the new section flow rate for this system capacity?
1 of 8
3. Set Sprinkler Lateral Design (25 pts)
a) How many sprinklers will operate on the lateral if the first sprinkler
is spaced Se from the lateral inlet?
b) For a dual pipe size lateral, what is the allowable friction loss
gradient, Ja?
c) What two adjacent IPS-PVC thermoplastic pipe sizes would you
recommend? Specify the nominal diameters in inches according
to Table 8.3.
d) What are the respective lengths (x1 and x2) of the two pipe sizes?
Round the lengths to a multiple of Se for each size.
e) What is the required lateral inlet pressure head, hl?
f) What is the pressure at the downstream end of the lateral during
operation?
g) Is the mean velocity at the lateral inlet too high?
4. (25 pts) A portable aluminum sprinkler lateral has a nominal diameter of 4 inches and
goes downhill at a uniform slope of -0.5%. The inlet flow rate is 260 gpm, the lateral
length is 840 ft, and the sprinkler spacing along the lateral is 30 ft. The lateral inlet
pressure head is hl = 30.0 m.
2 of 8
Solutions:
a) Obtain the values for average Wa, average Z, Ud, U, and ECe from
the tables in Chapter 3 of the textbook.
• From Table 3.1, Wa range is the same for the topsoil & subsoil. Use Wa =
½(145 + 208) = 176.5 mm/m.
• From Table 3.2, for almonds, Z = ½(0.6 + 1.2) = 0.9 m.
• From Table 3.3, for deciduous orchard w/o cover crop in a “moderate” climate,
Ud = 4.8 mm/day, and U = 533 mm/season.
• From Table 3.5, ECe = 2.0 dS/m for almonds.
dx 47.7 mm/irrig
fx = = = 9.94 days/irrig
Ud 4.8 mm/day
ECw 0.47
LR = = = 0.049
5ECe − ECw 5(2.0)-0.47
dn 43.2 mm/irrig
d= = = 50.8 mm/irrig
Ea 0.85
The soil intake rate is given, at 0.5 inch/hr, which equals 12.7 mm/hr. Then, the
minimum set time is:
3 of 8
50.8 mm/set
( Sto )min = = 4.0 hrs/set
12.7 mm/hr
Note the graph on page 67 of the lecture notes. The lines separating the adjacent
pipe sizes do not change because, in this problem, none of the economic
parameters have changed. The relationship between Q and q is fixed along the
slope of 2:1 on the log-log plot, or 1.852:1 in our case (with Hazen-Williams, as
specified).
We have:
Qs = K ( q−1.852 )
Then,
100 = K ( 50−1.852 )
115 = K ( qnew −1.852 )
or,
1/ −1.852
⎛ 115 ⎞
qnew = 50 ⎜ ⎟ = 46.6 lps
⎝ 100 ⎠
a) How many sprinklers will operate on the lateral if the first sprinkler is
spaced Se from the lateral inlet?
304 m/lat
= 38 sprink/lat
8 m/sprink
b) For a dual pipe size lateral, what is the allowable friction loss
gradient, Ja?
Since there are more than 30 outlets along the lateral pipe, F = 0.36. The nominal
sprinkler pressure head is 280 kPa/9.81 = 28.5 m. Then,
4 of 8
The lateral inflow rate is:
With Ja = 6.3 m/100 m, Table 8.3 gives the following two adjacent PVC pipe sizes:
2” and 2½.” Note that the respective pipe IDs are 55.7 mm and 67.4 mm.
d) What are the respective lengths (x1 and x2) of the two pipe sizes?
Round the lengths to a multiple of Se for each size.
This problem requires a few iterations. Use C = 150 for PVC with Hazen-Williams.
Use units of lps and mm. From the lecture notes, we have:
1.217(10)12
α1 = 1.852
= 1.135(10)6
100(150)
1.852
⎡ (10 / 60)(304) ⎤
α2 = ⎢ ⎥⎦ (67.4)−4.87 (0.36)(304) = 4.152(10)−6
⎣ 8
1.852
α3 = ( 67.4 −4.87
− 55.7 −4.87
) ⎛⎜⎝ 108/ 60 ⎞⎟⎠ = −1.464(10)−12
Note that F1 = 0.36 due to the 38 sprinklers over the length L. F2 will depend on x1.
Make a table of values, arbitrarily choosing an initial x1 value of 150 m, and
searching for f(x1) = 0:
x1 (m) N F2 f(x1)
150 19 0.38 -1.10
100 26 0.37 0.19
125 22 0.37 -0.55
112 24 0.37 -0.19
105 25 0.37 0.03
⎛x ⎞ ⎛ 200 ⎞
Q2 = ⎜ 2 ⎟ qa = ⎜ ⎟ (10 / 60) = 4.17 lps
⎝ Se ⎠ ⎝ 8 ⎠
5 of 8
1.852
⎛ 6.33 ⎞
( 67.4 )
−4.87
J1 = 1.217(10)12 ⎜ ⎟ = 4.30 m/100m
⎝ 150 ⎠
1.852
⎛ 4.17 ⎞
( 67.4 )
−4.87
J2 = 1.217(10) ⎜
12
⎟ = 1.99 m/100m
⎝ 150 ⎠
1.852
⎛ 4.17 ⎞
( 55.7 )
−4.87
J3 = 1.217(10) ⎜
12
⎟ = 5.03 m/100m
⎝ 150 ⎠
Finally,
5 1
hl = ha + hf + ∆he + hr
8 2
5 1
hl = 28.5 + (7.0) + ( −1.2) + 1.0 ≅ 33 m (320 kPa)
8 2
hend = hl − hf − ∆he
= 33 − 7 + 1.2
≅ 27 m
Q 4(6.33 lps)
V= = = 1.77 m/s
A π(0.0674 m)2 (1,000 l/m3 )
6 of 8
4. (25 pts) Portable aluminum sprinkler lateral.
⎛ 9.14 ⎞ ⎡
⎟ ⎣16.4 − 3(10) (130(0.5) (99.1) )⎤⎦ = 181 m
−7
x=⎜ 0.54 2.63
⎝ 0.586 ⎠
1.852
⎛ 16.4 ⎞
( 99.1)
−4.87
J1 = 1.217(10) ⎜ 12
⎟ = 5.00 m/100 m
⎝ 130 ⎠
1.852
⎛ (8)(0.586) ⎞
( 99.1)
−4.87
J2 = 1.217(10) ⎜ 12
⎟ = 0.49 m/100 m
⎝ 130 ⎠
J1FL J F (L − x)
(hf )x =181m = 1
− 2 2
100 100
(5.00)(0.37)(256) (0.49)(0.42)(75)
(hf )x =181m = − = 4.6 m
100 100
or, 15 ft of head loss. Note that hl is given in m, while all other values are given in
English units. Finally,
7 of 8
hx =181 m = hl − (hf )x =181 m − ∆he
= 30.0 − 4.6 − 181(−0.005)
≅ 26 m (86 ft, or 37 psi)
Q 4(16.4 lps)
V= = = 2.1 m/s
A π(0.0991 m)2 (1,000 l/m3 )
Whereby V > 2.0 m/s, so the entrance velocity in the lateral is higher than what we
might nominally allow. This suggests consideration of a larger pipe size.
8 of 8
BIE 5110/6110
Sprinkle & Trickle Irrigation
Fall Semester 2004 – Exam #2
Include units in all results. Indicate any assumptions that you might make.
Don’t show more than three significant digits in the results.
Name__________________________________
1. (60 pts) Two gun sprinklers are supplied water from a pump at an open reservoir
(water surface at 203 ft above msl), as shown in the figure below:
gun #1
(elev = 219 ft)
reservoir
(elev = 203 ft)
t
5f
pump 450 f
36
(elev = 209 ft) t
“T” (elev = 217 ft)
ft
0
20
gun #2
(elev = 228 ft)
There is a common 4-inch (ID = 4.280”) PVC supply line from the pump to a “T”. The
supply line is 450 ft long.
A 3-inch (ID = 3.284”) PVC pipe goes 365 ft from the “T” to gun #1, and another 3-inch
pipe goes 200 ft from the “T” to gun #2. The sprinkler height above the buried lateral
pipe is hr = 8.00 ft for both guns.
The flow rate vs. pressure data for the gun sprinkler give the following relationship:
q = 11.7P0.49
The suction side of the pump has the same 4-inch PVC pipe as the supply line, 12 ft
in length, with two 45-degree long-radius, flanged elbows, a basket strainer, and a
foot valve.
1 of 7
a) Develop one point on the system curve using the Hazen-Williams
equation (with C = 150) for friction losses. Use a flow rate of 80
gpm for gun sprinkler #1.
b) Calculate the flow rate for gun sprinkler #2.
c) Calculate the total system flow rate, Qs.
d) Calculate TDH for this flow rate. Show your calculations for minor
losses.
2. (20 pts) For the B2TPM Berkeley™ pump and 6-½” impeller, and the same system,
suppose now that the desired operating point is for Q = 150 gpm.
3. (20 pts) For the same B2TPM Berkeley™ pump and 6-½” impeller, suppose that the
desired operating point is 150 gpm at a TDH of 150 ft. If the nominal pump speed is
3,600 RPM, what is the required speed for the desired operating point?
4. (5 bonus pts) Which of the following are a function of a center pivot’s radial speed?
(check all that apply)
wetted width, w
net application depth, dn
average application rate, ARavg
maximum application rate, ARx
friction loss in the lateral pipe, hf
2 of 7
Solutions:
1. (60 pts) Two gun sprinklers are supplied water from a pump at an open reservoir
(water surface at 203 ft above msl), as shown in the figure below:
Move along the pipes from sprinkler #1 to the “T,” then to sprinkler #2 to determine the
flow rate there, then get the system flow rate (Qs = Q1 + Q2), and finally move to the
pump to determine Ppump.
1/ 0.49
⎛ 80 ⎞
P1 = ⎜ ⎟ = 50.6 psi
⎝ 11.7 ⎠
hT = h1 + hr + ∆he + hf
1.852
⎛ 80 ⎞
hT = 117 + 8 + (219 − 217) + 10.5(365) ⎜ ⎟ (3.284)−4.87
⎝ 150 ⎠
hT = 127 + 0.00109(80)1.852
hT = 131 ft
h2 = hT + ∆he − hf − hr
1.852
⎛Q ⎞
h2 = 131 + (217 − 228) − 10.5(200) ⎜ 2 ⎟ (3.284)−4.87 − 8
⎝ 150 ⎠
h2 = 131 − 11 − 0.000599Q1.852
2 −8
h2 = 112 − 0.000599Q1.852
2
3 of 7
Flow rate at gun sprinkler #2:
0.49
⎛ 112 − 0.000599Q1.852 ⎞
0.49
⎛ h ⎞
Q2 = 11.7 ⎜ 2 ⎟ = 11.7 ⎜ 2
⎟
⎝ 2.31⎠ ⎝ 2.31 ⎠
hpump = hT + ∆he + hf
hpump = 131 + (217 − 209) + 0.000371Q1.852
s
Velocity head:
8 ( Q / 448.86 )
2
V2 8Q2
= 2 4 = = 7.72(10)−6 Qs2
2g gπ D 32.2π (4.280 /12)
2 4
4 of 7
⎛ V2 ⎞
(h )
f,minor suction = 2.21⎜ ⎟
⎝ 2g ⎠
Static lift:
(hlift )suction = 209 − 203 = 6 ft
V. Total dynamic head (TDH):
Ppump V2
TDH = + (hf )suction + (hf,minor )suction + (hlift )suction +
γ 2g
then,
2. (20 pts) For the B2TPM Berkeley™ pump and 6-½” impeller, and the same system,
suppose now that the desired operating point is for Q = 150 gpm.
5 of 7
10.3 − 0.00105(203 * 0.3048)
hatm = = 33.6 ft
0.3048
For water at 12°C,
⎛ 17.27(12) ⎞
hvapor = 0.0623 exp ⎜ ⎟ = 0.143 m (0.469 ft)
⎝ 12 + 237.3 ⎠
Velocity head:
V2
= 7.72(10)−6 Qs2 = 7.72(10)−6 (150)2 = 0.174 ft
2g
Minor losses:
⎛ V2 ⎞
(h )
f,minor suction = 2.21⎜ ⎟ = 2.21(0.174) = 0.384 ft
⎝ 2g ⎠
3. (20 pts) For the same B2TPM Berkeley™ pump and 6-½” impeller, suppose that the
desired operating point is 150 gpm at a TDH of 150 ft. If the nominal pump speed is
3,600 RPM, what is the required speed for the desired operating point?
Follow the steps in the lecture notes. Make a table for the equal efficiency curve,
using Q2 = 150 gpm, and H2 = 150 ft:
6 of 7
Q1 H1
(gpm) (ft)
100 66.67
120 96.00
140 130.67
160 170.67
180 216.00
Plot the equal efficiency curve and look for the intersection with the pump
characteristic curve, defining point (Q3,H3). From the graph, Q3 ≈ 158 gpm, and H3 ≈
167 ft. Then,
⎛Q ⎞ ⎛ 150 ⎞
Nnew = Nold ⎜ 2 ⎟ = 3,600 ⎜ ⎟ = 3,418 RPM
⎝ 3⎠
Q ⎝ 158 ⎠
4. (5 bonus pts) Which of the following are a function of a center pivot’s radial speed?
(check all that apply)
wetted width, w
; net application depth, dn
average application rate, ARavg
maximum application rate, ARx
friction loss in the lateral pipe, hf
7 of 7
BIE 5110/6110
Sprinkle & Trickle Irrigation
Fall Semester 2004 – Final Exam
Include units in all results. Indicate any assumptions that you might make.
Don’t show more than three significant digits in any of the results.
Name__________________________________
1. (35 pts) A mature citrus orchard will be drip-irrigated (drip emitters) using a single
lateral per row of trees in a 132-ha field area. Other information:
q = 0.28P0.481
for q in lph; and P in kPa.
1 of 10
11. Calculate the leaching requirement, LRt.
12. Calculate the gross depth to apply per irrigation, d.
13. Calculate the gross volume of water per tree per day, G.
14. Calculate ha, corresponding to qa = 3.85 lph, in m of water head.
15. Calculate the water application time, Ta.
16. Select the number of stations, Ns.
17. Determine the minimum number of emitters per tree, Np’.
18. Calculate the system coefficient of variation, νs.
19. Calculate the minimum allowable emitter flow rate, qn.
20. Calculate the allowable subunit pressure head variation, ∆Hs.
21. Calculate the system capacity, Qs.
22. Calculate the total gross seasonal depth to apply, Dg.
23. Calculate the gross seasonal volume of irrigation water, Vs.
24. Calculate the required number of operating hours per season, Ot.
2. (30 pts) A rectangular field of strawberries will be trickle irrigated. The laterals are 380-
m long in the direction of the 17.8-mm inside diameter PE laterals. Nominal emitter
flow rate is 2.75 lph at a pressure head of 11.5 m. The emitters are in-line, without any
barbs, spaced at 0.4 m along the lateral hose, which lies along a uniform ground slope
of 0.761%. The strawberries are spaced at 0.5 m in the field rows. The emitter
exponent is x = 0.544, and the system flow rate is 8.05 lps.
3. (35 pts) A trickle irrigation system with a manifold inflow rate of 8.4 lps has an allowable
subunit pressure head variation of ∆Hs = 4.72 m. The calculated pressure variation
along the lateral pipes is ∆Hl = 2.44 m, and the total length of the manifold will be 290
m. There is a uniform ground slope of 1.73% in the manifold direction. The following
PVC pipe sizes are available:
Size I.D.
(inches) (inches)
1.5 1.610
2.0 2.067
2.5 2.469
3.0 3.068
4.0 4.000
6.0 6.000
2 of 10
What you need to do:
Solutions:
Sp 6.0
Np = = = 3.73
Se 1.61
⎛N S w⎞ ⎛ (3.73)(1.61)(2.01) ⎞
Pw = 100 ⎜ p e ⎟ = 100 ⎜ ⎟ = 43.0%
⎜S SP ⎟ ⎝ (6.0)(6.0)(0.78) ⎠
⎝ p r d⎠
MAD Pw
dx = Wa Z = (0.2)(0.43)(175)(1.2) = 18.1 mm
100 100
5. Calculate the average peak daily “transpiration” rate, Td.
3 of 10
dx 18.1
fx = = = 4.0 days
Td 4.50
9. Determine (ECe)max.
From Table 19.2, for a citrus (e.g. orange) crop, (ECe)max = 8 dS/m.
From Table 19.3, for a “deep-rooted” (Z > 1.5 m) crop and a “medium-textured”
soil: Tr = 1.00.
EC w 0.89
LR t = = = 0.056
2 (ECe )max 2(8)
⎛d T ⎞ ⎛ (4.50)(1.00) ⎞
d = 100 ⎜ n r ⎟ = 100 ⎜ ⎟ = 4.89 mm/day
⎝ EU ⎠ ⎝ 92% ⎠
13. Calculate the gross volume of water per tree per day, G.
d 4.89
G= SpSr = (6.0)(6.0) = 176 liter/day/tree
f' 1
14. Calculate ha, corresponding to qa = 3.85 lph, in m of water head.
4 of 10
1/ 0.481
⎛ 1 ⎞ ⎛ 3.85 ⎞
ha = ⎜ ⎟⎜ ⎟ = 23.7 m
⎝ 9.81 ⎠ ⎝ 0.28 ⎠
G 176
Ta = = = 12.3 hrs/day
Npqa (3.73)(3.85)
Two stations would require 2(12.3) = 24.6 hrs/day. Thus, there can be only one
station (Ns = 1) in this design.
⎡ ⎛ S + w − 2Se ⎞ ⎤
N'p = 2 ⎢ trunc ⎜ 1 + p ⎟⎥ + 1
⎣ ⎝ 2S e ⎠⎦
In this problem,
ν 0.0487
νs = = = 0.022
N'p 5
qaEU (3.85)(92)
qn = = = 3.64 lph
100 (1 − 1.27νs ) 100 (1 − 1.27(0.022) )
5 of 10
which corresponds to a head of:
1/ 0.481
⎛ 1 ⎞ ⎛ 3.64 ⎞
hn = ⎜ ⎟⎜ ⎟ = 21.1 m
⎝ 9.81⎠ ⎝ 0.28 ⎠
ANpqa (132)(3.73)(3.85)
Qs = 2.78 = 2.78 = 146 lps
NsSpSr (1)(6.0)(6.0)
( ) (
Dn = U 0.1 Pd = 660 0.1 78 = 583 mm )
Then, gross seasonal depth is:
100Dn 100(583)
Dg = = = 671 mm
Es (1 − LR t ) 92(1 − 0.056)
Dg A (671)(132)
Vs = = = 88.6 ha-m
1000 1000
24. Calculate the required number of operating hours per season, Ot.
Vs ⎛ 88.6 ⎞
Ot = 2778 = 2778 ⎜ ⎟ ≈ 1,690 hrs/season
Qs ⎝ 146 ⎠
6 of 10
2. Optimal Manifold Location
380 m
= 950 emitters
0.4 m/emitter
(0.726)1.75
J = 7.83(10)7 = 51.4 m/100 m
(17.8)4.75
Note that this is a high value for J, and is beyond the values given in Table 8.2.
The multiple-outlet factor, F, is 0.36 for 950 outlets. Take fe = 0 since the emitters
are in-line.
(51.4)(0.36)(380)
(hf )pair = = 70.3 m
100
which is equal to about 100 psi.
⎛ ∆he ⎞ 2.89
⎜ ⎟ = = 0.041
⎝ hf ⎠pair 70.3
Plot the above value (0.041) on the ordinate of the dimensionless friction loss graph
(Fig. 8.2) at x/L = 1.0, then draw a straight line from the origin to this point. Slide
the dimensionless curve for the downhill portion of the laterals until it is tangent to
7 of 10
the line, then trace it. Slide the curves up further so that the uphill curve passes
through the plotted point. Determine the intersection of the two curves:
x/L ≈ 0.52
Then, the downhill portion of the pair of laterals will have a length of:
Ld = (380)(0.52) ≈ 198 m
The uphill portion of the pair of laterals will have a length of:
Graphically, the location of minimum pressure in the downhill lateral would be:
Lmin = 0.1(380) = 38 m
as measured from the end of the downhill lateral, or 198 – 38 = 160 m from the
manifold location.
3
α= ⎡⎣(0.52)3.75 + (1 − 0.52)3.75 ⎤⎦ = 0.112
4
and,
⎛x ⎞
hl = ha + α (hf )pair + ⎜ − 0.5 ⎟ ( ∆he )pair
⎝L ⎠
1.75
⎛ (182)(2.75) ⎞
⎜ ⎟
7 ⎝ (0.4)(3600) ⎠
J = 7.83(10) = 14.2 m/100 m
(17.8)4.75
Friction loss:
8 of 10
(14.2)(0.36)(182)
(hf )up = = 9.30 m
100
Minimum pressure head:
3. Manifold Design
Draw a line from the origin to (8.4, 5.02). Draw a parallel line from (0.0, 2.28) to
(8.4, 7.30). These two lines define the band within which the friction loss curves
should be contained.
Look at the six friction loss curves on the attached graph. The smallest four sizes
are too small to fit within the band. The largest (6 inches) is too large because the
friction loss curve goes outside the band. Start with the 4-inch pipe size, but not at
the point (8.4, 7.30); start at (8.4, 5.02) such that the curve can fit within the band.
Trace the curve for the 4-inch pipe on the graph.
4Q 4(0.0084)
V4 −inch = = = 1.04 m/s
πD 2 ⎡⎛ 4 ⎞ ⎤
2
π ⎢⎜ ⎟ (0.3048)⎥
⎣⎝ 12 ⎠ ⎦
Note that the 4-inch pipe could be used for the whole length of the manifold and still
accommodate the allowable pressure head variation. But part of the manifold
9 of 10
should be 3-inch pipe, thereby reducing the head variation further, and also
decreasing the pipe cost.
Trace the 3-inch friction loss curve on the graph, making it tangent to the lower line
(ground slope line). This curve intersects the 4-inch curve at a flow rate of about
3.45 lps. The entrance velocity to the 3-inch pipe would be:
4Q 4(0.00345)
V3 −inch = = = 0.72 m/s
πD 2 ⎡⎛ 3.068 ⎞ ⎤
2
π ⎢⎜ ⎟ (0.3048)⎥
⎣⎝ 12 ⎠ ⎦
Then, use two pipe diameters (4- and 3-inch) with the following lengths of pipe in
the manifold:
⎛ 3.45 ⎞
L3 −inch = 290 ⎜ ⎟ = 119 m
⎝ 8.4 ⎠
where, of course, the upstream end has the 4-inch pipe. These lengths could be
rounded as necessary to accommodate the lateral spacing.
10 of 10
BIE 5110/6110
Sprinkle & Trickle Irrigation
Fall Semester, 2004
Assignment #1 (100 pts)
Due: 15 Sep 04
Given:
Weather data:
1. Go to http://climate.usu.edu/
2. Click on "Utah Climate Center Data (Use Microsoft Explorer)"
3. Look at the instructions for selecting a region
4. Select a region which includes Utah
5. Click on the "Update Station List" button
6. At the upper left you see a list of stations
7. Click on the list and type "L"
8. Scroll down further to "logan usu exp stn"
9. Under "Element," select "Maximum Air Temperature"
10. Check the "Full period of record" box
11. Click on the "Export Data" button at the top
12. Click on the "Update Output" button at the lower left
13. Type "Ctrl-A" to select all, then "Ctrl-C" to copy
14. Paste it into Notepad or Word
15. Clean up the data and import to Excel
16. Go back and select “Minimum Air Temperature" and get that data
17. Go back and select “Total Precipitation" and get that data, too
Required:
• Perform calculations to answer all of the questions as shown in the table format on the next page
• Show your steps in logical order, and write down your assumptions (if any) in determining the
respective values
• Do you work neatly
Notes:
1. Many years of weather data for Logan, Utah (Experiment Station site), are given on the web site.
2. Determine the mean monthly values (Jan – Dec) of maximum daily air temperature for the entire
period of record (about 34 years). To do this in Excel, you may want to use functions like
COUNTIF and SUMIF.
3. Plot the mean monthly values of maximum air temperature and determine which month is the
warmest; this month will be used below as the peak-use (peak ET) month.
4. Use the precipitation data to calculate the 75% rainfall probability value for the peak-use month to
determine the net crop ET requirement during that month. This means you need to calculate the total
rainfall (inches) for the peak-use month for the 34 years of record. You can consider that the 75%
rainfall value is all “effective” rainfall for that particular month.
5. You may notice some problems with the data sets from the Utah Climate Center web site. Document
these problems and describe how you have dealt with them.
6. Assume that there will be only six days of irrigation per week (one day off), even during the peak-use
period.
7. Obtain needed soil, root depth, EC and ET information from tables in the text (Chapter 3), or from
another source (if so, name that source). Use average values where max-min ranges are given in
the tables.
8. Use Eq. 3.1 to calculate the maximum net application depth per irrigation.
9. Use Eq. 3.2 to calculate the maximum irrigation interval, then to calculate the net application depth.
10. Use Eq. 3.3 to calculate the leaching requirement.
11. Use Eqs. 5.3a and 5.3b to determine the gross application depth.
12. Use Eq. 5.4 to calculate system flow capacity.
Table Format for BIE 5110/6110 Assignment #1 (Fall 2004)
Given Values:
Crop: .........................................................................
Topsoil depth (m):.....................................................
Subsoil depth (m): ....................................................
Location ....................................................................
Field area (ha): .........................................................
MAD (%): ..................................................................
Irrigation water salinity, ECw (dS/m):........................
Application efficiency (%): ........................................
Soil intake rate (mm/hr)............................................
Time to change sets (hrs): .......................................
Lateral length (m) .....................................................
Lateral spacing (m)...................................................
Calculated Values:
To determine the mean monthly values of maximum daily air temperature, the
SUMIF function was used in Excel to key on the column with the month names for the 34
years of record. The COUNTIF function was used in the same way, for each month, to
determine the number of records in each month. Finally, for each month, the sum of
temperature values was divided by the corresponding record count to arrive at an average
monthly value:
80
Average Monthly Tmax (deg F)
70
60
50
40
30
20
10
0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
It is seen that the month of July has the highest maximum monthly temperature for
the 34 years of record, and is closely followed by August. This will be the month for which
peak ET will occur in Logan, Utah.
To determine the rainfall probability for the month of July, the total daily rainfall
values for that month were summed up for each year of record. Following are the
tabulated results:
As seen in the table above, based on the 34 years of record, there is a 69.7%
probability that the total July rainfall in Logan, Utah, will be 0.26 inches or more (column
“Up”). There are really not enough data points to determine the 75% level of confidence,
so use 0.26 inches of rain in July (the peak ET month) with an approximately 70% level of
exceedance. This is equivalent to 6.6 mm.
Given Values:
Crop: ......................................................................... Sweet corn
Topsoil depth (m):..................................................... 0.5 m
Subsoil depth (m): .................................................... 1.4 m
Location .................................................................... Logan, Utah
Field area (ha): ......................................................... 25 ha
MAD (%): .................................................................. 35%
Irrigation water salinity, ECw (dS/m):........................ 1.02 dS/m
Application efficiency (%): ........................................ 88%
Soil intake rate (mm/hr)............................................ 14 mm/hr
Time to change sets (hrs): ....................................... 0.5 hrs
Lateral length (m) ..................................................... 180 m
Lateral spacing (m)................................................... 12 m
Calculated Values:
Note: most of the following is specifically for the peak-use period and does not dictate what the irrigation
scheduling might be throughout the growing season. These are calculations leading to system design.
The topsoil depth is given as 0.5 m, and we have 0.5 m for the average effective root depth of sweet corn,
so the subsoil Wa is not considered herein.
MAD ⎛ 35 ⎞
dx = Wa Z = ⎜ ⎟ (125 )( 0.5 ) = 21.9 mm
100 ⎝ 100 ⎠
Maximum irrigation interval (days):
For July, we have determined that there is a 70% probability of a monthly total of 0.26 inches (6.6 mm), or
more, of rain. This comes to an average of 6.6/31 = 0.21 mm/day, which is very little rain. This fact,
together with the realization that the rain might not fall during the peak-use period, may lead us to
conclude the safer choice is to assume zero effective rainfall during the peak-use period.
dx 21.9 mm
fx = = = 3.42 days
Ud 6.4 mm/day
Nominal irrigation interval (days):
f ' = trunc ( fx ) = 3 days
The specification in this case is for one day off per week, but with f’ = 3 days, we can assume that the one
day off will not fall within the three-day interval during the peak-use period, which might involve only two or
three irrigations. Thus, let f = f’ = 3 days.
Leaching requirement:
ECw 1.02
LR = = = 0.075
5ECe − EC w 5 ( 2.5 ) − 1.02
dn 19.2
d= = = 21.8 mm
(Ea /100 ) 0.88
Minimum set operating time (hrs):
With 21.8 mm to apply and a soil intake rate of 14 mm/hr, this gives 1.56 hrs minimum set time (so as
not to exceed the soil intake rate).
Make the nominal set time equal to 2.0 hours for convenience. With 0.5 hrs to move each set, there
are a total of 2.5 hrs/set.
With 24 hrs per day, there can be 24/2.5 = 9.6 sets/day. Round this down to a whole number: 8 sets per
day, giving a total daily operations time of 8(2.5) = 20 hrs.
Lateral spacing on mainline is Sl = 12 m. Lateral length is 180 m. The area per lateral is:
U − Pe 559 mm - 0 mm
= = 29.1 irrigations
dn 19.2 mm/irrig
We could do a seasonal analysis of the probability of rainfall exceedance, but we can already surmise
that most of the rain will fall during times other than the peak-use period. So, to be conservative in our
design, we assume no seasonal effective rainfall. On the other hand, it is very unlikely that a farmer in
Logan, Utah would irrigate a corn field 29 times in a season, which could indicate a nonzero contribution
from rain and or the possibility that the effective root depth for sweet corn is somewhat more than 0.5 m.
Also, there may be a significant residual water content (from snowmelt and rain) in the soil at the
beginning of the growing season.
At 8 sets/day and 2.0 hours set time, there are 16 hours of system operation per day:
Qs = 2.78
Ad
= 2.78
( 25 ha )( 21.8 mm ) = 31.6 lps
fT ( 3 days )(16 hrs/day )
This gives a capacity of 31.6/25 = 1.26 lps per ha, which is a reasonable value.
BIE 5110/6110
Sprinkle & Trickle Irrigation
Fall Semester, 2004
Given:
A solution for the economic selection of pipe sizes is needed. The solution is to be
based on the following data:
Required:
• Determine the cutoff flow rate values for each adjacent pair of pipe sizes (you are
not required to graph the pipe selection chart)
• The solution is to include the PVC pipe with nominal sizes 6, 8, 10, 12, 14, 16, and
18 inches, as shown above.
• You can use either the Hazen-Williams or Darcy-Weisbach equations.
• For PVC pipe, use a Hazen-Williams “roughness” factor of C = 150.
• Or, for Darcy-Weisbach, use the Blasius equation for smooth pipe.
• Assume that MAC is negligible.
Solution:
BIE 5110/6110
Economic Pipe Selection Method
Assignment #2, Fall 2004
Given data:
useful life: 22 years inflation: 0.001 per year motor efficiency: 0.94
interest rate: 0.024 per year area: 58 ha pump efficiency: 0.88
depth: 0.89 m/year electricity: 0.06104 $/kWh
capacity: 210 lps Hazen-Williams: 150 C factor
Size UAC
(inches) ($/20 ft/yr) ($/100 ft/yr)
6 2.07 10.36
8 3.14 15.71
10 4.48 22.38
12 5.79 28.95
14 6.90 34.52
16 9.11 45.56
18 11.71 58.56
EAE= 1.0096
E'= 50.87 $/kW/yr
Difference in WHP between adjacent pipe sizes:
Sizes delta J
(inches) m/100 m (note: m/100 m is equivalent to ft/100 ft)
6 and 8 0.16756 (however, must use 102 for lps or 3,960 for gpm)
8 and 10 0.20889
10 and 12 0.20593
12 and 14 0.17449
14 and 16 0.34566
16 and 18 0.40743
Given:
Required:
L 252 m
Nn = = = 21
Se 12 m
There will be 21 sprinklers per lateral. The multiple-outlet friction loss factor for 21
sprinklers is:
1 ⎡ 4 ⎤
F = 0.351 + 1+ = 0.38
2(21) ⎣ 13(21) ⎥⎦
⎢
(21)(22 lpm)
Ql = Nnqa = = 7.70 lps
60 s / min
⎛ −0.38 ⎞
∆he = ⎜ ⎟ (252 m) = −0.958 m
⎝ 100 ⎠
⎛ 0.20ha − ∆he ⎞
Ja = 100 ⎜ ⎟
⎝ FL ⎠
⎛ 0.2(21.5 m) − ( −0.958 m) ⎞
= 100 ⎜ ⎟
⎝ (0.38)(252 m) ⎠
= 5.49 m/100m
From Table 8.1 (page 140) in the textbook, the nominal size of the aluminum lateral pipe is
the outside diameter, and the wall thickness is 0.05 inches. The 2” size has ID = 1.9”, the
3” size has ID = 2.9”, and so forth. From our calculated minimum diameter, we must
round up to the 3” nominal size. Then, the inside diameter is (2.9 inch)(2.54) = 7.37 cm.
1.852
⎛ 7.70 lps ⎞
J = 16.42(10) ⎜ 6
⎟ (7.37 cm)−4.87 = 5.22 m/100m
⎝ 130 ⎠
JFL (5.22)(0.38)(252 m)
hf = = = 5.00 m
100 100
hl = ha + 0.75hf + 0.5∆he + hr
= 21.5 m + 0.75(5.00 m) + 0.5( −0.958 m) + 1.3 m
= 26.1 m ( 2.52 atm )
The minimum pressure in the lateral pipe is located at a distance x from the inlet (qa is 22
lpm/60 = 0.367 lps; D is 73.7 mm):
x=
Se ⎡
qa ⎣ (
Ql − 3(10)−7 C( −S)0.54 D2.63 ⎤
⎦ )
=
12 ⎡
0.367 ⎣
(
7.70 − 3(10)−7 130(0.38)0.54 (73.7)2.63 ⎤
⎦ )
= 190 m
according to the equations in the lecture notes on pages 64 and 65. This “x” value
(distance) is confirmed (approximately) by assuming an inlet pressure head of 26.1 m, a C
value of 130, and so forth, calculating the head loss segment-by-segment in a
spreadsheet:
Sprinkler Distance Q hf head
Position (m) (lps) (m) (m)
0 0 7.70 0.0000 26.10
1 12 7.33 0.6262 25.52
2 24 6.97 0.5721 24.99
3 36 6.60 0.5203 24.52
4 48 6.23 0.4707 24.09
5 60 5.87 0.4234 23.72
6 72 5.50 0.3785 23.38
7 84 5.13 0.3358 23.09
8 96 4.77 0.2955 22.84
9 108 4.40 0.2576 22.63
10 120 4.03 0.2221 22.45
11 132 3.67 0.1891 22.31
12 144 3.30 0.1585 22.20
13 156 2.93 0.1304 22.11
14 168 2.57 0.1048 22.05
15 180 2.20 0.0819 22.02
16 192 1.83 0.0615 22.00
17 204 1.47 0.0439 22.00
18 216 1.10 0.0290 22.02
19 228 0.73 0.0170 22.05
20 240 0.37 0.0080 22.09
21 252 0.00 0.0022 22.13
whereby the minimum head is found somewhere between 192 and 204 m from the lateral
inlet. The difference in the calculations are due to the F-factor for multiple outlets. It is also
seen that the maximum pressure head is at the lateral inlet (hmax = 26.1 m), which might
have been expected because the ground slope is very small.
Thus, the minimum pressure is at a distance of approximately 190 m from the lateral inlet,
which is nearest sprinkler number 190/12 ≈ 16.
hend = hl − hf − ( −∆he )
= 26.1 − 5.0 + 0.958 = 22.1 m
The head loss due to friction from sprinkler 16 to the end of the lateral is estimated as (from
Table 8.7, F = 0.46 for 21 – 16 = 5 outlets):
1.852
⎛ (0.367)(5) lps ⎞
Jx −end = 16.42(10) ⎜
6
⎟ (7.37 cm)−4.87 = 0.366 m/100m
⎝ 130 ⎠
The friction loss from the inlet to distance x = 190 m is, then, 5.00 – 0.101 m = 4.90 m. The
elevation change from the inlet to 190 m is (-0.0038)(12)(16) = -0.730 m. Finally, the
minimum pressure head in the lateral pipe is:
Given:
Required:
• Recognize that the extreme lateral position is when two laterals are at the mid-point
of the mainline, and the other two at the uphill end of the mainline
• This is because the mainline runs uphill, so pressure must decrease monotonically
from upstream to downstream along the mainline pipe
• Also, the critical point is the uphill end of the mainline, because that must be the
location of minimum pressure in the mainline
• Thus, for the extreme lateral position, the two laterals at the mid-point will have
more than enough pressure if the last two laterals have just the required pressure
• Mainline design, then, should focus on providing Pmin = 275 + 25 kPa in the pipe
• These facts should be obvious
1,200 m
mainline
uphill @ 0.387%
(2) Allowable Loss due to Friction
• The allowable friction loss is the available pressure at the mainline inlet, minus the
elevation change, hydrant loss, and required lateral inlet pressure
• As in the example mainline design in the lecture notes, do not consider minor losses
due to flow past closed hydrants along the mainline
• And, as in the example problems in the lecture notes, it may help to look at this
problem using a schematic diagram
• First, convert pressures to heads and determine the elevation change along the
length of the mainline:
Elevation change:
275 + 25
hl + hhydrant = = 30.58 m
9.81
• Let L1 be the length of pipe diameter D1, and L2 the length for diameter D2
L1 L2
(hf)a
39.65 m
30.58 m
4.64 m
1,200 m
• Allowable loss due to friction along the entire length of the mainline pipe:
• Calculate the required mainline pipe inside diameter assuming only one pipe size
• Recognize that at the extreme lateral position, the full system flow rate goes from
the beginning of the mainline to the mid-point, where only half the system flow rate
continues to the end of the mainline
• Make the allowable friction loss equal to the actual friction loss
J1 (L / 2 ) J2 (L / 2 )
( hf ) a = +
100 100
where L = 1,200 m; and (hf)a = 4.43 m
4.43 = 6 ⎢ ⎥⎢ s Q + ⎜ 2 ⎟ ⎥
⎣ C1.852 ⎦ ⎣⎢ ⎝ ⎠ ⎦⎥
4Q 4(0.135)
V= = = 1.81 m/s
πD 2
π(0.3081)2
which is not too high, but as seen above, the friction loss would be too high
• It might also be noted that 135 lps is more than 2,000 gpm, a flow rate for which an
irrigation system would almost always use 12” or 15” nominal pipe size
• Based on the preceding, try 15” pipe (Table 8.6) for the first half of the mainline:
1.852
⎛Q ⎞ ⎛L⎞
(hf )15 " = 1.217(10) ⎜ s ⎟
10
D−4.87 ⎜ ⎟
⎝ C⎠ ⎝ 2⎠
1.852
⎛ 135 ⎞ ⎛ 1,200 ⎞
(hf )15 " = 1.217(10) ⎜10
⎟ (369.7)−4.87 ⎜ ⎟ = 1.88 m
⎝ 150 ⎠ ⎝ 2 ⎠
• This leaves (hf)a – (hf)15” = 4.43 – 1.88 = 2.55 m allowable head loss in the second
half of the mainline
• The allowable friction loss gradient in the second half of the mainline is:
⎛ 2.55 ⎞
Ja = 100 ⎜ ⎟ = 0.425 m
⎝ 600 ⎠
• At ½ Qs = 67.5 lps, this is very close to the J value for the 10” pipe in Table 8.5
• Using that 10” pipe,
1.852
⎛ 67.5 ⎞
(hf )10 " = 1.217(10) ⎜
10
⎟ (259.7)−4.87 ( 600 ) = 2.90 m
⎝ 150 ⎠
• Using the 15” pipe on the first half of the mainline, and 10” pipe on the second half,
the total friction loss would be: (hf)total = 1.88 + 2.90 = 4.78 m
• Then, the pressure at the last pair of laterals would be:
which is very close to the required 275 kPa at the lateral inlets
• The design could involve three pipe sizes along the mainline
• But, in this case it works out well to use two sizes: 15” SDR 41 PIP for the first half
of the mainline, and 10” SDR 41 IPS for the second half of the mainline
• Thus, there will be 600 m of 15” mainline, and 600 m of 10” mainline
• The pressure will be just about right at the end of the mainline, only 3 kPa below
that which is required
• The pressure at other lateral positions will be more than enough
(5) Notes
• Tables 8.5 and 8.6 do not use the same friction loss equation
• Table 8.6 is based on Hazen-Williams with C = 155
• Minor losses past closed hydrants were not considered – if they were, it might be
necessary to use a combination of 12” and 10” pipe in the second half of the
mainline
• It might also be necessary to use a combination of 12” and 10” pipe in the second
half of the mainline if we include a safety factor for uncertainties
BIE 5110/6110
Sprinkle & Trickle Irrigation
Fall Semester, 2004
Given:
Required:
1. Field Area:
The field is given to be rectangular. Note that there are 43,560 ft2/acre. The irrigated
area is the length of the mainline (1,320 ft) multiplied by twice the length of one lateral
(2 x 600 ft):
(1,320)(1,200)
= 36.4 acres
43,560
2. System Capacity:
Ad (36.4)(1.9)
Qs = 453 = 453 = 373 gpm
fT (7)(12)
3. Velocity Checks:
Table 8.4: 5-inch aluminum pipe has an inside diameter of 4.900 inches (0.408 ft).
Note that the maximum recommended velocity, in general, for sprinkler systems is 5 to
7 fps.
Qs 4(373 gpm)
VQs = = = 6.36 fps
A π (60 s/min)(7.481 gal/ft 3 )(0.408 ft)2
Qs 2(373 gpm)
VQs /2 = = = 3.18 fps
2 A π (60 s/min)(7.481 gal/ft 3 )(0.408 ft)2
Qs 2(373 gpm)
Vhydrant = = = 4.77 fps
2 A π (60 s/min)(7.481 gal/ft 3 )(0.333 ft)2
All of the above velocities are below 7 fps, so they are found to be acceptable.
4. Reynolds Numbers and Darcy-Weisbach f:
VD 4Q
Re = =
ν πD ν
Assume a water temperature of 10°C. From the table on page 126 of the lecture notes
(or from any other reference), the kinematic viscosity at this temperature is ν =
1.306(10)-6 m2/s.
From the table on page 138 (Chapter 8) of the textbook, the roughness height of
aluminum pipe (with couplers as an equivalent length of pipe) is 0.005 ft. Then, from
the Swamee-Jain equation:
fQs = 0.0213
and,
fQs/2 = 0.0225
5. Velocity Heads:
There are three different velocity heads to be considered, based on the three velocities
given in 3(a) – 3(c) above. These are:
2
Vhydrant (4.77 fps)2
= = 0.353 ft
2g 2(32.2 ft/s2 )
Flow Path Kr
Past closed hydrant 0.5
Past open hydrant 0.6
Through open hydrant 7.5
At the start of an irrigation, one pair of laterals is at the first hydrant (#1), which is 30 ft
from the beginning of the mainline. The second pair of laterals is at a distance of 660 ft
from the first pair, at hydrant #23. At each subsequent set, the laterals move Sl = 30 ft
down the mainline.
The second set will find the first pair of laterals at hydrant #2, and the second pair at
hydrant #24. Finally, the last set of the irrigation will have the first pair at hydrant #22,
and the second pair at hydrant #44 (the last one on the mainline).
The minimum pressure head required in the mainline pipe at a open hydrant is the
required lateral inlet pressure head of (44 psi)(2.31 ft/psi) = 102 ft, plus the head loss
through the hydrant valve, which is:
V2 ⎛ 4.772 ⎞
(hf )hydrant = Kr = 7.5 ⎜ ⎟ = 2.65 ft
2g ⎝ 2(32.2) ⎠
Then, the minimum pressure head required in the mainline pipe at a open hydrant is:
1,320 ft
1,200 ft
mainline
downhill @ 0.18%
Note that for every one of the 22 lateral positions, the second pair of laterals is always
660 ft downstream of the first pair of laterals.
Make a table of lateral positions in which the number of upstream closed laterals
increases by one for each new lateral position (because the pair of laterals moves
further from the upstream end of the mainline). Thus, the pipe friction loss and the
minor losses due to flow past a closed hydrant increase with each lateral position. On
the other hand, the change in elevation partially offsets these friction losses. Note that
from the upstream end of the mainline to the first pair of laterals, the discharge is equal
to the entire system flow rate. Consider the following table:
First Pair of Laterals
Lateral Distance to Elev Pipe hf Number of (hf)minor Req'd at Mainline
st
Position 1 Pair (ft) Change (ft) (ft) US hydrants (ft) Inlet (ft)
1 30 -0.054 0.98 0 0.00 105.9
2 60 -0.108 1.97 1 0.31 107.2
3 90 -0.162 2.95 2 0.63 108.4
4 120 -0.216 3.93 3 0.94 109.7
5 150 -0.270 4.92 4 1.26 110.9
6 180 -0.324 5.90 5 1.57 112.1
7 210 -0.378 6.88 6 1.88 113.4
8 240 -0.432 7.87 7 2.20 114.6
9 270 -0.486 8.85 8 2.51 115.9
10 300 -0.540 9.84 9 2.83 117.1
11 330 -0.594 10.82 10 3.14 118.4
12 360 -0.648 11.80 11 3.45 119.6
13 390 -0.702 12.79 12 3.77 120.9
14 420 -0.756 13.77 13 4.08 122.1
15 450 -0.810 14.75 14 4.40 123.3
16 480 -0.864 15.74 15 4.71 124.6
17 510 -0.918 16.72 16 5.02 125.8
18 540 -0.972 17.70 17 5.34 127.1
19 570 -1.026 18.69 18 5.65 128.3
20 600 -1.080 19.67 19 5.97 129.6
21 630 -1.134 20.65 20 6.28 130.8
22 660 -1.188 21.64 21 6.59 132.0
Do the same thing as for the first pair of laterals, but considering that part of the
mainline has the full system flow rate, and part has only half of the system flow rate.
Also, the minor loss due to “line flow” past one open hydrant (location of the first pair of
laterals) must be added to the head losses.
The losses from the second pair of laterals to the upstream end of the mainline must be
added to the 105-ft head requirement (see above) in the mainline at the location of the
second pair of laterals. These losses include pipe friction and minor losses. Consider
the following table (next page):
It is seen that for each of the 22 lateral positions, the second pair of laterals require a
higher pressure head at the upstream end of the mainline. This is because the downhill
slope of the mainline is very small, so the friction losses dominate the pressure variation
along the mainline. Thus, the following graph is for the required pressure head at the
upstream end of the mainline from the perspective of the second (downstream) pair of
laterals for each position, thereby giving more than enough pressure in the mainline at
the location of the first pair of laterals.
Second Pair of Laterals
Distance to Distance to Elev Pipe Number of closed (hf)minor Req'd at Mainline
Position 1st Pair (ft) 2nd Pair (ft) Change (ft) hf (ft) US hydrants (ft) Inlet (ft)
1 30 690 -1.242 6.70 21 2.10 112.6
2 60 720 -1.296 7.68 22 2.42 113.8
3 90 750 -1.350 8.67 23 2.73 115.0
4 120 780 -1.404 9.65 24 3.05 116.3
5 150 810 -1.458 10.63 25 3.36 117.5
6 180 840 -1.512 11.62 26 3.67 118.8
7 210 870 -1.566 12.60 27 3.99 120.0
8 240 900 -1.620 13.58 28 4.30 121.3
9 270 930 -1.674 14.57 29 4.62 122.5
10 300 960 -1.728 15.55 30 4.93 123.8
11 330 990 -1.782 16.53 31 5.24 125.0
12 360 1,020 -1.836 17.52 32 5.56 126.2
13 390 1,050 -1.890 18.50 33 5.87 127.5
14 420 1,080 -1.944 19.48 34 6.19 128.7
15 450 1,110 -1.998 20.47 35 6.50 130.0
16 480 1,140 -2.052 21.45 36 6.81 131.2
17 510 1,170 -2.106 22.43 37 7.13 132.5
18 540 1,200 -2.160 23.42 38 7.44 133.7
19 570 1,230 -2.214 24.40 39 7.76 134.9
20 600 1,260 -2.268 25.39 40 8.07 136.2
21 630 1,290 -2.322 26.37 41 8.38 137.4
22 660 1,320 -2.376 27.35 42 8.70 138.7
140
Required US Mainline Head (ft)
135
130
125
120
115
110
0 2 4 6 8 10 12 14 16 18 20 22
Sprinkler Lateral Position
BIE 5110/6110
Sprinkle & Trickle Irrigation
Fall Semester, 2004
Given:
Required:
1. The nominal pump speed is listed on the Cornell sheet as 1200 RPM. The exact
speed for the pump curves is 1175 RPM.
2. From the graph, at 550 gpm and 72 ft head, the efficiency is approximately 75%, to
the nearest whole number; or more generally, the efficiency is between 74 and
75%.
3. At the desired operating point, the WHP is:
QH (550)(72)
WHP = = = 10.0 HP
3956 3956
or, 7.46 kW.
WHP 10.0
BHP = = = 13.3 HP
Epump 0.75
or, 9.94 kW. Interpolating on the graph, the BHP appears to be approximately 14
HP, or perhaps slightly less than 14 HP. Thus, the calculated value agrees fairly
well with the graphical value, given the need for interpolation “by eye.” Also, the 14
HP estimate is sufficient to determine a power unit (motor) to drive this pump.
5. Select the nearest pump curve which is above the desired operating point (unless a
pump curve is only slightly below the desired operating point). In this case, choose
the curve for the 14” nominal diameter.
6. For this, apply the procedure given in the lecture notes. Develop some points for
the “equal efficiency” curve, and make them near the desired operating point such
that the curve will intersect with the pump curve.
Q1 H1
(gpm) (ft)
560 74.6
570 77.3
580 80.1
590 82.9
600 85.7
After graphing the points from the above table, the intersection with the 14” pump
characteristic curve is approximately:
H3 = 77 ft
Q3 = 568 gpm
Finally, reduce the pump speed as follows:
⎛ 550 ⎞
Nnew = 1175 ⎜ ⎟ = 1138 RPM
⎝ 568 ⎠
Note that the intersection (Q3, H3) is usually close to the actual operating point
without a change in speed, N, and the value of Q3 is not much different than Q2. In
this case, the adjustment in speed is slight and it might not be worth the expense to
gear down to Nnew; instead, it might be better to accept the actual operating point
without changing speeds.
To know the actual operating point without changing speeds, we would need
sufficient information to develop the system curve.
7. The intersection (Q3, H3) is already known from the previous calculations, so
calculate the required impeller diameter straight away as follows:
⎛ 550 ⎞
Dnew = 14 ⎜ ⎟ = 13.6 inches
⎝ 568 ⎠
where it is assumed that the nominal diameter is the actual standard diameter. The
table below the graph shows maximum impeller diameters, but to apply them it
would be necessary to consult the manufacturer to be sure.
⎛ 17.27(10) ⎞
hvapor = 0.0623exp ⎜ ⎟ = 0.125 m (0.411 ft)
⎝ 10 + 237.3 ⎠
From Table 8.5, the suction pipe has an ID of 6.301 inches. Then, pipe area is:
π(6.301/12)2
Apipe = = 0.217 ft 2
4
The flow rate is: Q = 550/448.86 = 1.23 cfs. And, the velocity head is:
V2 (1.23)2
= = 0.500 ft
2g 2(32.2)(0.217)2
1.852
⎛ 550 ⎞
hf = 10.5 ( 8.0 ) ⎜ ( 6.301)
−4.87
⎟ = 0.12 ft
⎝ 150 ⎠
Minor losses on suction side of pump: From Table 11.2 for a flanged “long-radius”
45-degree elbow, 6” nominal size, Kr = 0.17. Also from Table 11.2, for a “basket
strainer,” Kr = 0.85. Then,
10. This pump installation will not be expected to cavitate because NPSHa >> NPSHr.
BIE 5110/6110
Sprinkle & Trickle Irrigation
Fall Semester, 2004
Given:
0.18% downhill
800 ft
0.10% uphill
1,100 ft
mainline
pump
560 ft
• In the above figure, only some of the laterals and sprinklers are shown, but remember
that the field area is covered with sprinklers in a fixed, permanent system.
• There are 27 laterals along the mainline.
1
• Note the field slopes along mainline and lateral directions.
• The suction (upstream) side of the pump has a 4-ft static lift from a pond and 10 ft of 8”
PVC pipe (ID = 8.205”) with one 90-degree elbow and a strainer screen at the inlet.
• The mainline is 8” PVC pipe (ID = 8.205”), and is 1,100-ft long.
• Sprinkler riser height is: hr = 3.0 ft.
• A Berkeley model 4GQH pump curve as shown on the following page. You will use
the characteristic curve for 1600 RPM.
• Ignore minor losses along the mainline and laterals.
Required:
2
Solution:
0.5(800 + 560)(1100)
A= = 17.2 acres
43,560
Due to the trapezoidal field shape, and the fact that there are 27 laterals at Sl = 40 ft,
the effective irrigated area is slightly less than 17.2 acres.
Pressure Flow
(psi) (gpm) ln(P) ln(q)
25 0.88 3.2189 -0.1278
30 0.97 3.4012 -0.0305
35 1.05 3.5553 0.0488
40 1.12 3.6889 0.1133
45 1.19 3.8067 0.1740
50 1.25 3.9120 0.2231
q = 0.173P0.506
for q in gpm; and P in psi. Note that the exponent is close to 0.500, which is expected
for a straight-bore nozzle. But notice also that allowing for the flexibility in the
exponent, x, gives a better mathematical fit to the manufacturer’s data.
3. Let the first lateral be located at ½Sl from the lower edge of the field (where the pump
is located). Calculate the number of sprinklers per lateral by rounding the potential
lateral length by Se. The potential lateral length is calculated by linear interpolation
along the left side of the field area (see the figure given above). The equation is given
below, and the calculation results are shown in the following table.
⎛ 800 − 560 ⎞
L = 800 − (1,100 − y) ⎜ ⎟
⎝ 1,100 ⎠
where y is the distance along the mainline (ft); and L is the potential lateral length (ft).
3
Distance Length No. of
Lateral (ft) (ft) Sprinklers
1 20 564.4 14
2 60 573.1 14
3 100 581.8 15
4 140 590.5 15
5 180 599.3 15
6 220 608.0 15
7 260 616.7 15
8 300 625.5 16
9 340 634.2 16
10 380 642.9 16
11 420 651.6 16
12 460 660.4 17
13 500 669.1 17
14 540 677.8 17
15 580 686.5 17
16 620 695.3 17
17 660 704.0 18
18 700 712.7 18
19 740 721.5 18
20 780 730.2 18
21 820 738.9 18
22 860 747.6 19
23 900 756.4 19
24 940 765.1 19
25 980 773.8 19
26 1,020 782.5 20
27 1,060 791.3 20
4. Develop a computer program to start with a given pressure at the furthest downstream
sprinkler on lateral #27, calculate the flow rate at that sprinkler, calculate the pressure
at the next upstream sprinkler, then the flow rate at that sprinkler, and so on, until
reaching the mainline. Calculate the pressure in the mainline at the location of lateral
#26, then iterate along lateral #26 to get the same pressure in the mainline at that
location. Repeat for all other laterals, moving in the upstream direction, until a
pressure is obtained for the upstream end of the mainline. The system flow rate is
known from these calculations (sum of all individual sprinklers). Assume pipe leakage
is zero.
Knowing the system flow rate, determine the losses in the suction side of the pipe, and
determine TDH by adding the velocity head at the beginning of the mainline, the
pressure head at the beginning of the mainline, the static lift on the suction side, and
the hydraulic losses on the suction side of the pump.
4
Preliminary calculations and assumptions:
Assume a water temperature of 10°C, giving a kinematic viscosity of: 1.306(10)-6 m2/s,
or 1.406(10)-5 ft2/s.
Use the Swamee-Jain equation with ε = 1.5(10)-6 m, or 4.92(10)-6 ft for PVC to obtain
the Darcy-Weisbach friction factor, f.
From Table 8.3, the ID of the lateral pipe is 1.754 inches (0.1462 ft). The ID of the
mainline pipe is 8.205 inches (0.6838 ft).
Once the pressure at the upstream end of the mainline is calculated, the additional
TDH values include static lift, velocity head, and losses in the suction side of the pump,
plus the riser height. Assume the pump outlet is at the same elevation as the
upstream end of the mainline (you don’t know if the mainline or laterals are buried, nor
how deep they might be, but this information could be used to develop a somewhat
more specific design).
V2
TDH = 2.308Pmain + hlift + hr + (hf )suction +
2g
where TDH is in ft; Pmain is the pressure at the upstream end of the mainline (psi); hlift is
given as 4.0 ft; hr is given as 3.0 ft; (hf)suction are the hydraulic losses in the suction pipe
(ft); and the last term is the velocity head (ft).
The iterative part is to determine Pmain; the rest of the TDH terms are easy to calculate
directly.
V2 8Q2
= 2 4 = 0.1151Q2
2g gπ D
L V2
hf = f = 1.684 f Q2
D 2g
5
Putting it all together:
or,
TDH = 2.308Pmain + 7.0 + Q2 [1.684 f + 0.2314]
Qs Pmain TDH
P (psi) (gpm) (psi) Re f (ft)
20 367.2 21.8 108,347 0.01761 57.50
25 411.2 27.2 121,318 0.01721 70.09
30 451.0 32.7 133,061 0.01689 82.66
35 487.6 38.1 143,853 0.01663 95.21
40 521.6 43.5 153,902 0.01641 107.74
45 553.6 48.9 163,344 0.01622 120.26
50 583.9 54.3 172,277 0.01605 132.77
55 612.7 59.7 180,777 0.01590 145.28
60 640.2 65.1 188,901 0.01577 157.77
where P is the pressure at the furthest downstream sprinkler on lateral #27; Qs is the
total system flow rate; Pmain is the pressure at the upstream end of the mainline (just
downstream of the pump); Re is the Reynold’s number in the suction pipe; f is the value
from Swamee-Jain; and TDH is the total dynamic head.
5. The system curve (Qs versus TDH) is superimposed upon the pump manufacturer’s
curves, as shown in the figure below.
6. The operating point (intersection of the system curve and the 1600 RPM pump curve)
is seen to be approximately:
Qs = 568 gpm
TDH = 126 ft
(568)(12)(3600)
AR avg = = 0.075 inch/hr
(458)(40)(40)(448.86)
or 1.9 mm/hr.
6
300
275
250
225
200
TDH (ft)
175
150
125
100
75
50
25
0 200 400 600 800 1000 1200 1400 1600
Flow rate (gpm)
RelRough = 0.00000492 / D
Re = 4 * Q / (viscosity * Pi * D)
7
hf = 8# * f * L * (Q / Pi) ^ 2 / (32.2 * D ^ 5)
End Function
Qlat = 0# 'cfs
For i = 1 To n
Qs = 0.173 * P ^ 0.506 'gpm
Qlat = Qlat + Qs / 448.86 'cfs
h = P * 2.308 + hf(Qlat, Dlat, Se) + SoLat * Se 'ft
P = h / 2.308 'psi
Next
Lateral = h
End Function
ParabolaFit = 0
foo = x(2) - x(1)
Bisection = Abs(foo) < 0.0000000001
C0 = x(1) ^ 2
c1 = (x(3) - x(1)) / foo
c2 = x(2) ^ 2 - C0
boo = x(3) ^ 2 - C0 - c1 * c2
Bisection = Abs(boo) < 0.0000000001
'------------------------
' Parabolic interpolation
'------------------------
c = c - target
ParabolaFit = (-b + Sqr(b * b - 4 * a * c)) / (2 * a)
Exit Function
End If
End If
8
If Bisection Then
'--------------
' Use bisection
'--------------
End Function
Dim n As Integer
Dim lat As Integer
Dim LatHead(1 To 3) As Double
Dim Pressure(1 To 3) As Double
Dim Qlat As Double, x As Double
Dim Qmain As Double, L As Double, NewP As Double, hmain As Double
hmain = 0
Qmain = 0
'--------------------------------------------
' Determine number of sprinklers this lateral
'--------------------------------------------
x = 20 + (lat - 1) * Sl
L = 800# - (1100# - x) * 0.2181818
n = Round(L / Se, 0)
'--------------------------------------
' Calculate lateral inlet pressure head
'--------------------------------------
'------------------------------------
' No need to iterate for last lateral
'------------------------------------
'------------------------------------------------
' Iterate to match lateral inlet & mainline heads
'------------------------------------------------
Pressure(1) = P / 4
Pressure(3) = 3 * P
Pressure(2) = (Pressure(1) + Pressure(3)) / 2
9
If (LatHead(1) > hmain) Or (LatHead(3) < hmain) Then
'-------------------------------
' Failed to bracket the solution
'-------------------------------
QsPmain = -100
Exit Function
End If
For i = 1 To 50
'----------------------------------
' Search by parabolic interpolation
'----------------------------------
Pressure(2) = NewP
LatHead(2) = Lateral(NewP, n, Qlat)
'-------------------
' Solution converged
'-------------------
Exit For
End If
Next
End If
'-----------------------------------------
' Move upstream one hydrant along mainline
'-----------------------------------------
'----------------------------
' Return the system flow rate
' or the mainline pressure
'----------------------------
If Flow Then
QsPmain = Qmain * 448.86 'gpm
Else
QsPmain = hmain / 2.308 'psi
End If
End Function
10
BIE 5110/6110
Sprinkle & Trickle Irrigation
Fall Semester, 2004
Do you work in an organized, neat way. Write down any assumptions you make.
Given:
q = 0.32P0.53
1
Required:
2
Required:
I. Emitter spacing
Sp 6.2
Np = = = 3.33
Se 1.86
⎛N S w⎞ ⎛ (3.33)(1.86)(2.33) ⎞
Pw = 100 ⎜ p e ⎟ = 100 ⎜ ⎟ = 50.1%
⎜S SP ⎟ ⎝ (6.2)(6.2)(0.75) ⎠
⎝ p r d⎠
MAD Pw
dx = Wa Z = (0.25)(0.501)(178)(2.0) = 44.6 mm
100 100
V. Average peak daily transpiration rate
dx 44.6
fx = = = 10.5 days
Td 4.24
VIII. Target EU
Table 20.3: “point-source” water applicators with Np > 3 gives recommended EU range of
90 to 95%. In this design iteration, choose EU = 92%.
3
IX. Maximum ECe
X. Transmission ratio
From Table 19.3, for a “deep-rooted” (Z > 1.5 m) crop and a “medium-textured” (see Wa
above) soil: Tr = 1.00.
EC w 0.61
LR t = = = 0.038
2 (ECe )max 2(8)
⎛d T ⎞ ⎛ (4.24)(1.00) ⎞
d = 100 ⎜ n r ⎟ = 100 ⎜ ⎟ = 4.61 mm/day
⎝ EU ⎠ ⎝ 92% ⎠
d 4.61
G= SpSr = (6.2)(6.2) = 177 liter/day/tree
f' 1
XIV. Nominal emitter pressure head
1/ 0.53
⎛ 1 ⎞⎛ 4 ⎞
ha = ⎜ ⎟⎜ ⎟ = 12.0 m
⎝ 9.81 ⎠ ⎝ 0.32 ⎠
G 177
Ta = = = 13.3 hrs/day
Np qa (3.33)(4)
4
Two stations would require 2(13.3) = 26.6 hrs/day. Thus, there can be only one station
(Ns = 1) in this design.
See the figure below, showing a tree spacing of 6.2 m, and emitter spacing of 1.86 m, and
a wetted width of 2.33 m:
It is seen that, on average, four emitters contribute some irrigation water to each tree.
Alternatively,
⎛ 5 m/tree ⎞
N'p = trunc ⎜ + 2⎟ = 4
⎝ 1.86 m/emitter ⎠
where “trunc” means to truncate (round down) to the nearest whole number.
ν 0.062
νs = = = 0.031
N'p 4
qaEU (4)(92)
qn = = = 3.83 lph
100 (1 − 1.27νs ) 100 (1 − 1.27(0.031) )
1/ 0.53
⎛ 1 ⎞ ⎛ 3.83 ⎞
hn = ⎜ ⎟⎜ ⎟ = 11.0 m
⎝ 9.81 ⎠ ⎝ 0.32 ⎠
5
XX. Allowable subunit head variation
ANpqa (44)(3.33)(4)
Qs = 2.78 = 2.78 = 42.4 lps
NsSpSr (1)(6.2)(6.2)
which is less than the well capacity of 125 lps. Thus, the well has sufficient flow rate to
accommodate this design.
Assume a TR value of 1.00 (Table 19.4). Then, Es = EU = 92%. Effective rain and
residual soil moisture are given to be zero. Thus,
( ) (
Dn = U 0.1 Pd = 541 0.1 75 = 469 mm )
Then, gross seasonal depth is:
100Dn 100(469)
Dg = = = 530 mm
Es (1 − LR t ) 92(1 − 0.038)
Dg A (530)(44)
Vs = = = 23.3 ha-m
1000 1000
Vs ⎛ 23.3 ⎞
Ot = 2778 = 2778 ⎜ ⎟ ≈ 1,530 hrs/season
Qs ⎝ 42.4 ⎠
6
BIE 5110/6110
Sprinkle & Trickle Irrigation
Fall Semester, 2004
Given:
A rectangular field of orchard trees, 550-m long in the direction of the PE laterals. The
preliminary design data are as follows:
Required:
Determine the following using either: (1) the semi-graphical, non-dimensional, design
procedure, or (2) a completely numerical design procedure:
Show all of your work neatly, step by step. Adjust the manifold location uphill by as much as
0.75(Sp), or downhill by as much as 0.25(Sp) so that is is positioned midway between two plant
rows.
1. How many trees on the uphill side?
2. How many trees on the downhill side?
3. Is Hn’ the same on the uphill & downhill sides?
Solution:
Given:
Size I.D.
(inches) (inches) (mm)
0.5 0.622 15.8
0.75 0.824 20.9
1 1.049 26.6
1.25 1.380 35.1
1.5 1.610 40.9
2 2.067 52.5
2.5 2.469 62.7
3 3.068 77.9
4 4.000 101.6
6 6.000 152.4
8 8.000 203.2
10 10.000 254.0
Required:
ν = 1.306(10)-6 m2/s.
4Q ⎛Q⎞
NR = = 9.75(10)5 ⎜ ⎟
νπD ⎝D⎠
−0.25
⎛Q⎞
f = 0.0102 ⎜ ⎟
⎝D⎠
• Darcy-Weisbach:
⎛ Q1.75 ⎞
hf = 0.169 ⎜ 4.75 ⎟
⎝D ⎠
2.5
Friction loss (m)
2.0
1.5
1.0
0.5
0.0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
Manifold flow rate (lps)
• Make the head loss curve for the largest of the three diameters (3 inch) pass
through the point (5,3.98). Do this by observing that at 5 lps, the head loss from the
3-inch curve is 2.907 m. Add 3.98 – 2.907 = 1.073 m to all points on the curve for
the 3-inch pipe size, thereby shifting it vertically as needed, then draw a straight line
through the origin, tangent to this shifted curve (see the figure below).
• Next, vertically shift the curve for the 2.5-inch pipe so that it is tangent to the tangent
line, as shown in the second figure on the next page.
• Draw a vertical line at the intersection between these two curves, defining the length
of the 3-inch pipe size. The break point is at 1.71 lps. This gives the following
length for the 3-inch pipe size (assuming a linear change in flow rate along the
manifold):
⎛ 1.71 − 5.00 ⎞
L3 " = 200 ⎜ ⎟ ≈ 132 m
⎝ −5.00 ⎠
• Finally, make the 2-inch curve tangent to the tangent line (by vertical shifting), then
draw a vertical line at the intersection of this curve with the 2.5-inch curve. See the
final graph below.
4.0
2 inch (52.5 mm)
2.5 inch (62.7 mm)
3.5
3 inch (77.9 mm)
Lower limit
3.0 Upper limit
Tangent line
2.5
Friction loss (m)
2.0
1.5
1.0
0.5
0.0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
Manifold flow rate (lps)
4.0
2 inch (52.5 mm)
2.5 inch (62.7 mm)
3.5
3 inch (77.9 mm)
Lower limit
3.0 Upper limit
Tangent line
2.5
Friction loss (m)
2.0
1.5
1.0
0.5
0.0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
Manifold flow rate (lps)
4.0
2 inch (52.5 mm)
2.5 inch (62.7 mm)
3.5
3 inch (77.9 mm)
Lower limit
Upper limit
3.0
Tangent line
Break 1
2.5
Friction loss (m)
2.0
1.5
1.0
0.5
0.0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
Manifold flow rate (lps)
4.0
2 inch (52.5 mm)
2.5 inch (62.7 mm)
3.5
3 inch (77.9 mm)
Lower limit
Upper limit
3.0
Tangent line
Break 1
2.5 Break 2
Friction loss (m)
2.0
1.5
1.0
0.5
0.0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
Manifold flow rate (lps)
• The break point between the 2.5 and 2.0 curves is at 0.48 lps. This gives the
following length for the 2.5-inch pipe size:
⎛ 0.48 ⎞
L 2" = 200 ⎜ ⎟ ≈ 19 m
⎝ 5.00 ⎠
• Then, the 2.5-inch pipe size would have a length of 200 – 19 – 132 = 49 m.
• In summary:
• Note that the design would also be acceptable (within allowable limits) if only two
sizes were used: 3-inch and 2.5-inch. This would also simplify installation and
would not increase the cost significantly.
• Note also that the maximum average velocity in each of the pipe sizes is well within
acceptable limits.
• Finally, observe that the smallest pipe diameter (2 inches) is greater than ½ the
largest pipe diameter (3 inches), as desired for the manifold design.
• Note that if a different kinematic viscosity is applied, a different pipe sizing solution
might be obtained.
BIE 5300/6300 Assignment #4
Broad-Crested Weir Calibrations
28 Sep 04 (due 05 Oct 04)
I. You have to design a BCW for a concrete-lined trapezoidal canal with a bottom
width of 2.0 m, inverse sides slopes of 1.25:1 (H:V), lining depth of 2.7 m, and
maximum discharge of 12 m3/s. The Manning roughness is estimated to be
0.013, and the longitudinal bed slope is 0.000123 m/m. Make sure the BCW will
operate under free-flow conditions up to Qmax = 12 m3/s.
(a) Give the design dimensions for the BCW, and provide any relevant
comments about the design and your assumptions.
(b) What is the minimum flow rate which can be accurately measured with
your BCW design?
(c) Will the upstream canal walls need to be raised after installing the BCW
when operating at Qmax = 12 m3/s?
(d) Would you recommend including a DS ramp on the BCW? Why or why
not?
(e) Suppose you include two 1-inch diameter PVC drainage pipes at the
base of the BCW. What is the estimated discharge through the pipes at
the 12 m3/s capacity of the BCW? Is this a significant fraction of Qmax?
II. Use a spreadsheet or your own custom computer program to check the
calibration of your BCW design from the problem above, but based only on
energy-balance from upstream to the location of critical flow on the sill. In this
case, you will assume free-flow conditions at the BCW.
(a) Do the comparison for the full flow range of the BCW.
(b) Make a graph (two curves) of hu versus Q for the full calibration (from
the problem above) and for the simpler energy-balance calibration.
(c) Are the two calibrations significantly different in this case?
III. Suppose the Parshall flume at the location (Logan Canyon) of our field exercises
is getting badly deteriorated and needs to be replaced. A decision is made to
install a BCW instead of the Parshall flume, at approximately the same location.
Based on your lab data, and a Qmax of 40 cfs, what BCW design dimensions and
features would you propose?