Toshiba Field Server Driver Protocol

The document provides information about a FieldServer protocol driver for communicating with Toshiba UPS devices over RS-232. The driver allows the ProtoNode to read and write data from the UPS, including status information, alarms, and commands. It is compatible with several FieldServer models but only supports communication with Toshiba UPS models in a one-to-one client/server configuration over a serial connection. The driver implementation and tested capabilities are described.

Uploaded by

Steven Marks
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
88 views

Toshiba Field Server Driver Protocol

The document provides information about a FieldServer protocol driver for communicating with Toshiba UPS devices over RS-232. The driver allows the ProtoNode to read and write data from the UPS, including status information, alarms, and commands. It is compatible with several FieldServer models but only supports communication with Toshiba UPS models in a one-to-one client/server configuration over a serial connection. The driver implementation and tested capabilities are described.

Uploaded by

Steven Marks
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

FieldServer Protocol Driver Sheet

Toshiba UPS
FS-8700-124 Version: 1.02 / Rev. 1.B

DESCRIPTION COMPATIBILITY
The serial TIC UPS driver allows the ProtoNode to FieldServer Model Compatible
transfer data to and from devices over RS-232 using FS-B35 Series Yes
TIC UPS protocol. The ProtoNode can emulate a ProtoNode/ProtoAir Yes
Client. QuickServer FS-QS-10xx No
This driver is intended for use with Toshiba models QuickServer FS-QS-122x Yes
UPS and is implemented to: QuickServer FS-QS-20xx No
QuickServer FS-QS-22xx Yes
• Read information from the UPS such as battery
life, voltages etc. This will be done in user mode
CONNECTION INFORMATION
on the UPS.
Connection Type: RS-232
• Write information and commands such as
Baud Rates: 1200; 2400; 4800; 9600
shutdown commands to the UPS.
Data Bits: 7
• Advanced options such as reading/writing Stop Bits: 1
EEPROM is not supported. No date/time reads or Parity: Even
writes are supported. No string type commands Multidrop Capability: No
are supported.
While the driver has both Server and Client DEVICES TESTED
implementations, the Server is intended for emulation
Tested
and test purposes by FieldServer only. Device
(FACTORY, SITE)
TIC UPS model 1600 FACTORY
1.1 Connection Facts TIC UPS model G900 FACTORY
TIC UPS model G8000MM SITE
FieldServer
Nodes Comments
Mode
As the Toshiba protocol
only allows for 1:1
Client 1 communication, only 1
Client is allowed per
RS-232 port.
The Server is implemented
for emulation purposes
Server 1
only. It has a static address
as per the Toshiba spec.

FORMAL DRIVER TYPE


Serial
Client Only

www.sierramonitor.com
FieldServer Protocol Driver Sheet
Toshiba UPS
FS-8700-124 Version: 1.02 / Rev. 1.B

COMMUNICATIONS FUNCTIONS FAULT ALARM STATUS


COMMAND COMMAND COMMAND
6.1 Read Operations Supported Bit # Function Function Function
Bit 23 Not used Not used
ProtoNode ProtoNode Bit 22 1 1
Description Input over Low battery
as a Client as a Server Bit 21:
current voltage
ALARM ALARM Alarm data
Battery
BC BC Battery current DC over
Bit 20: replacement
BECR BECR Battery estimated charge current
alarm
remaining
DC bus over Parallel
BEMR BEMR Battery estimated minutes Bit 19:
voltage running mode
remaining
DC bus under
BLR BLR Battery life remaining Bit 18: 0
voltage
BPV1 BPV1 Bypass voltage phase 1
Phase
BPV2 BPV2 Bypass voltage phase 2 Bit 17: 0
rotation error
BPV3 BPV3 Bypass voltage phase 3 DC Bus UPS lifetime
BPC BPC Bypass current Bit 16:
imbalance alarm
BPFREQ BPFREQ Bypass frequency Bit 15: Not used Not used
BRHT BRHT Battery rated holding time Bit 14: 1 1
BT BT Battery temperature EEPROM Asynchronous
BVP BVP Battery voltage percentage Bit 13:
error operation
DCBV DCBV DC bus voltage Battery or
FAULT FAULT Fault data Ambient
Bit 12: charger circuit
IC1 IC1 Input current phase 1 overheat
fault
IC2 IC2 Input current phase 2 Overload
IC3 IC3 Input current phase 3 Battery
Bit 11: accumulation
IFRQ IFRQ Input frequency overheat
started
IV1 IV1 Input voltage phase 1 Bit 10: UPS overheat 0
IV2 IV2 Input voltage phase 2 Bit 9: 0 0
IV3 IV3 Input voltage phase 3 Fuse has
Bit 8: 0
OC1 OC1 Output current phase 1 opened
OC2 OC2 Output current phase 2 Bit 7: Not used Not used Not used
OC3 OC3 Output current phase 3 Bit 6: 1 1 1
OFRQ OFRQ Output frequency Countdown
Inverter over UPS fault
OLP1 OLP1 Output load percent phase 1 Bit 5: started for
current detected
OLP2 OLP2 Output load percent phase 2 shutdown
OLP3 OLP3 Output load percent phase 3 Input voltage
Bit 4: UPS overload 0
OV1 OV1 Output voltage phase 1 out of spec
OV2 OV2 Output voltage phase 2 Low battery
Inverter
OV3 OV3 Output voltage phase 3 Bit 3: 0 voltage
overload
SOB SOB Seconds on battery detected
SAD SAD Shutdown after delay Inverter under UPS output
Bit 2: 0
OV12 OV12 Output voltage between voltage from bypass
phase 1 & 2 Overload UPS output
Bit 1: 0
OV23 OV23 Output voltage between 110% load from inverter
phase 2 & 3 UPS input
Inverter over
OV31 OV31 Output voltage between Bit 0: 0 and output
voltage
phase 3 & 1 voltage sync

www.sierramonitor.com
FieldServer Protocol Driver Sheet
Toshiba UPS
FS-8700-124 Version: 1.02 / Rev. 1.B

6.2 Commands Supported by Different 6.3 Write (Control) Operations


Models Supported
G8000 & ProtoNode as ProtoNode as
COMMAND 1600 1800 4200 G9000 Description
G8000MM a Client a Server
ALARM ✓ ✓ Shutdown after
SAD SAD
BC ✓ ✓ ✓ ✓ ✓ delay
BECR ✓ ✓ ✓ BTEST Battery Test1
BEMR ✓ ✓
BLR ✓ ✓ ProtoNode as a Client ProtoNode as a Server
BPV1 ✓ ✓ ✓ ✓ The following models support the listed commands:
BPV2 ✓ ✓ 1600; 1800; 4200 1600; 1800; 4200
BPV3 ✓ ✓ SAD
SAD
BPC ✓ ✓ ✓ ✓ ✓ BTEST
BPFREQ ✓ ✓ ✓ ✓ ✓
BRHT ✓ ✓ ✓ ✓ ✓
BT ✓ ✓ 6.4 Unsupported Functions and Data
BVP ✓ ✓ ✓ ✓ ✓ Types
DCBV ✓ ✓ ✓ ✓
FAULT ✓ ✓ ✓ ✓ ✓ Function Reason
IC1 ✓ ✓ ✓ ✓ ✓ ProtoNode is a data transfer
IC2 ✓ ✓ ✓ Programming device, and as such,
IC3 ✓ ✓ ✓ messages programming messages are
IFRQ ✓ ✓ ✓ ✓ ✓ not required.
IV1 ✓ ✓ ✓ ✓ ✓ Date and time Not supported by other
IV2 ✓ ✓ ✓ functions protocols.
IV3 ✓ ✓ ✓ All string commands:
OC1 ✓ ✓ ✓ ✓ ✓ Type form
Not supported by other
OC2 ✓ ✓ ✓ Serial number
protocols.
OC3 ✓ ✓ ✓ Manufacturer
OFRQ ✓ ✓ ✓ ✓ ✓ Software version
OLP1 ✓ ✓ ✓ ✓ ✓ Not supported by other
E & F commands
OLP2 ✓ ✓ ✓ protocols.
OLP3 ✓ ✓ ✓ A limited set is supported
Write Commands
OV1 ✓ ✓ ✓ ✓ ✓ only – refer to Section 6.3.
OV2 ✓ ✓ ✓
OV3 ✓ ✓ ✓
OV12 ✓
OV23 ✓
OV31 ✓
SOB ✓
SAD ✓ ✓ ✓
STATUS ✓ ✓ ✓ ✓ ✓

1
Due to battery health, this point can only be tested as specified
by TIC.