Operating Envelopes For Centrifugal Pumps: Problem Statement
Operating Envelopes For Centrifugal Pumps: Problem Statement
0.05256 m3/s
7.05 m
Figure 1. Pump Operating Failures [2] Discharge Head [H] 6.29 bar
loss is assumed to be 0.5 bar. Additionally as the Discharge Vessel High High LL 4.00 m
liquid exits the discharge piping, the exit losses is
taken to be 5 m (~0.04 bar) based on Eq. 1 The control valve details to be checked for are,
Table 6. Control Valve Details
Table 3. Minor Losses
Control Valve Cv@100% Opening FL
Parameter Value Unit
4” Size 236 0.82
PMinor Losses 0.5 bar
6” Size 433 0.84
PExit Losses 0.04 bar
Page 2 of 9
Pump System Pressure Losses 0.0163×5×997.8×1.632
∆𝑃 = = 0.0053 𝑏𝑎𝑟 (5)
2×0.202715
The pump operating point is the point where the
system resistance curve intersects the pump The results for suction side pressure drop can be
performance curve. This can be understood as, summarized as,
for a given flow rate, the resultant pump head Table 7. Suction Side Frictional Losses
arrived at, after accounting for all the static and
Parameter Value Unit
dynamic losses (represented as system
resistance) from the generated pump Total Reynolds Number [Re] 329,372 -
Dynamic Head (TDH).
Flow Behaviour Turbulent -
The factors contributing to system resistance is,
Friction Factor Equation Swamee-Jain -
1. Suction Piping & Fittings Frictional Loss
Friction Factor 0.0163 -
2. Discharge Piping & Fittings Frictional Loss
Suction ε/D 0.00022 -
3. Control Valve Pressure drop
Pressure Drop [ΔP] 0.0053 bar
4. Total Static Head
Suction & Discharge Frictional Pressure Losses The calculations are similarly performed for
discharge side with a discharge side velocity of
To estimate the total static head, the worst case
scenario of Low Low Liquid Level (LLLL) in the 2.82 m/s and the results are summarized below,
suction vessel & High High Liquid Level (HHLL) in Table 8. Discharge Side Frictional Losses
the receiving tank is considered. This is taken so Parameter Value Unit
to ensure that during LLLL, the pump does not
suffer from cavitation due to Net Positive Suction Reynolds Number [Re] 433,408 -
Head (NPSH) deficiency, i.e., even during LLLL, Flow Behaviour Turbulent -
NPSHA > NPSHR. To estimate NPSHA, the suction
line frictional pressure drop is calculated using Friction Factor Equation Swamee-Jain -
the Darcy-Weisbach equation (Appendix B). The Friction Factor 0.0165 -
Suction Velocity (VS) is estimated as,
𝑄 0.05256 Suction ε/D 0.00029 -
𝑉𝑠 = = ≈ 1.63 𝑚/𝑠 (2)
𝐴𝑠 0.03227
Pressure Drop [ΔP] 2.123 bar
The Suction Side Reynolds Number is,
0.202715×1.63×997.8
Total Static Head
𝑅𝑒 = = 329,372 (3)
0.001 The total static head is computed as,
As the calculated suction side Reynolds number is [(ℎ𝐻𝐻𝐿𝐿 +ℎ𝑒𝑙𝑒𝑣 )𝑇𝑎𝑛𝑘 −(ℎ𝐿𝐿𝐿𝐿 +ℎ𝑒𝑙𝑒𝑣 )𝑉𝑒𝑠𝑠𝑒𝑙 ]×𝜌×𝑔
∆𝑃𝑆 = (6)
much higher than 4000, the flow is well into the 105
Page 3 of 9
−1⁄
The calculated NPSHA is 1.23 bara and is higher 0.726 236 2 2
than NPSHR of 0.69 bara. The pump suction 𝐹𝑃 = [1 + ( 42 ) ] = 0.9216 (26)
890
pressure is calculated as, −1⁄
0.28+0.937 236 2 1 2
(ℎ𝐿𝐿𝐿𝐿 +ℎ𝑒𝑙𝑒𝑣 )𝑉𝑒𝑠𝑠𝑒𝑙 ×𝜌×𝑔 𝐹𝐿𝑃 = [ ( 42 ) + 0.822 ] = 0.8197 (27)
𝑃𝑠 = 𝑃𝑣𝑒𝑠𝑠𝑒𝑙 + − 𝑃𝐹 (11) 890
105
The inlet pressure in psig for choke flow equation
(0.25+2)×997.8×9.81
𝑃𝑠 = 1.04 + − 0.0053 (12) is calculated as by considering pressure drop
105
between Pump Discharge and Control valve Inlet
𝑃𝑠 ≈ 1.25 𝑏𝑎𝑟𝑎 (12.78 𝑚) (13)
is very small as,
The Pump Discharge Pressure for the flow rate of
𝑃1 = (7.54 × 14.7) × 14.7 = 96.1 𝑝𝑠𝑖𝑔 (28)
189.2 m3/h & corresponding pump head of 6.29
bara is calculated as, 𝑃2 = 96.1 − (3.59 × 14.7) = 43.4 𝑝𝑠𝑖𝑔 (29)
𝑑 4 4 4
5 0.98 0.82 117.1
𝐾𝐵2 = 1 − (𝐷 ) 1 − [6.065] = 0.811 (22)
2
42
2 6 0.98 0.82 117.1
𝐾1 = 0.5 × [1 − (7.9812 )] = 0.28 (23)
2 7 0.98 0.82 117.1
42
𝐾2 = 1.0 × [1 − (6.0652 )] = 0.319 (24)
8 0.98 0.82 117.1
∑ 𝐾 = 0.28 + 0.319 + 0.937 − 0.811 = 0.726 (25)
9 0.98 0.82 117.1
The selected control valve is 4” valve with Cv of
236 and FL of 0.82 from Table 6. 10 0.9789 0.8198 117.1
Page 4 of 9
Therefore for a flow of 189.2 m3/h, the Cv control valve. If there are no fittings, Fp is taken
required is 117.1 gpmpsi. For the 4” valve to be 1.0. The term K is the algebraic sum of the
selected, the % Cv becomes velocity head loss coefficients of all the fittings
117.1 that are attached to the control valve & is
% 𝐶𝑣 = = 49.6 % (36)
236 estimated as,
Pump Operating Envelope ∑ 𝐾 = 𝐾1 + 𝐾2 + 𝐾𝐵1 − 𝐾𝐵2 (38)
To generate the pump operating envelope, the
Where,
above set of calculations is performed for various
% Cv between 20% to 80% to estimate the total K1 = Upstream fitting Resistance Coefficient [-]
dynamic head at various flows. Below is the K2 = Downstream fitting Resistance Coefficient [-]
pump performance curve that includes the
KB1 = Inlet Bernoulli Coefficient [-]
system resistance curves for various % Cv & flow
rates. KB2 = Outlet Bernoulli Coefficient [-]
Where,
𝑑 4
𝐾𝐵1 = 1 − (𝐷 ) (39)
1
𝑑 4
𝐾𝐵2 = 1 − (𝐷 ) (40)
2
Where,
D1 = Pipe Inlet Diameter [in]
D2 = Pipe Outlet Diameter [in]
If the upstream and downstream piping are of
Figure 3. Pump Operating Envelope equal size, then, KB1 = KB2, and therefore, are
Appendix A – Liquid Control Valve Sizing [1] dropped from the ΣK equation. If the
Based on ANSI/ISA S75.01.01 Standards, to size downstream pipe size is similar to upstream pipe
the control valve, the following Liquid control size, i.e., D1 = D2, then KB1 = KB2. The most
valve sizing set of equations can be used, commonly used fitting in control valve
installations is the short-length concentric
Step 1: Calculate Piping Geometry (Fp) & Liquid
reducer. The equations for these fittings are,
Pressure Recovery Factor (FLP)
2
−1⁄ 𝑑2
∑𝐾 𝐶 2 2 𝐾1 = 0.5 × [1 − (𝐷2 )] , for inlet reducer (41)
𝐹𝑃 = [1 +
𝑁2
(𝑑𝑉2) ] (37) 1
2
𝑑2
𝐾2 = 1.0 × [1 − (𝐷2 )] , for outlet reducer (42)
2
Where,
If the concentric reducers installed on either side
Fp = Piping geometric Factor [-]
of the control valve are identical, then
N1 = Constant [Value = 1.0] 𝑑2
2
∑ 𝐾 = 𝐾1 + 𝐾2 = 1.5 × [1 − ( 2 )] (43)
𝐷
N2 = Constant [Value = 890]
If the concentric reducers installed on either side
Cv = Valve Coefficient [GPM/psi]
of are identical, then, K = K1 + K2. The liquid
d = Control Valve Size [inch] Pressure Recovery Factor (FLP) is calculated as,
−1⁄
The value of Fp is dependent on the fittings such 𝐾1 +𝐾𝐵1 𝐶𝑣 2 1 2
as reducers, elbows or tees that are directly
𝐹𝐿𝑃 = [ (𝑑2) + 𝐹2 ] (44)
𝑁2 𝐿
attached to the inlet & outlet connections of the
Page 5 of 9
Step 2: Calculate Pressure Drop Required for to estimate the final value of Cv. If the FL value
Sizing (PSizing) were to change between iterations, these values
would need to be updated, and Cv re-calculated.
To estimate the pressure drop required for sizing,
Psizing, first the liquid critical pressure ratio (FF) is Appendix B – Line Sizing [3]
calculated. Therefore, Pressure loss in piping without any size changes
𝐹𝐹 = 0.96 − 0.28√𝑃𝑣
𝑃
(45) or fittings occurs due to friction between the fluid
𝑐 and the pipe walls. To estimate the piping
Where, pressure loss, the Darcy-Weisbach correlation is
FF = Liquid Critical Pressure Ratio [-] used as follows,
Owing to the implicit nature of the Colebrook 6. Pumps that are expected to operate less
equation which requires iterations, an alternate frequently can be chosen such that they
correlation may be used to estimate the Darcy operate at lower speeds at the cost of
friction factor, i.e., Swamee-Jain Correlation efficiency. Since the pump is selected to
operate intermittently, a slightly lower
which is calculated for Re > ~4000 as,
efficiency pump is acceptable compared to a
0.25
𝑓= ε⁄D 5.74 (56) higher speed pump. This will also ensure a
log10 [ + ] longer operating life cycle.
3.7 Re0.9
Page 8 of 9
Appendix D – Liquid Control Valve Sizing
Page 9 of 9