The document contains information about electrical load calculations and panel configurations for multiple houses (House A, B, C, etc.). It provides details such as incoming voltage, protection devices, circuit information, and load calculations to determine appropriate feeder sizing and protection. The calculations show the total load exceeds capacity and results in error values.

Uploaded by

Peter Sy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
213 views

Example of Load Computation

The document contains information about electrical load calculations and panel configurations for multiple houses (House A, B, C, etc.). It provides details such as incoming voltage, protection devices, circuit information, and load calculations to determine appropriate feeder sizing and protection. The calculations show the total load exceeds capacity and results in error values.

Uploaded by

Peter Sy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

PANEL NAME: House A, House C, House E

INCOMING VOLTAGE:230V, 1PHASE,60HZ


INCOMING PROTECTION: 40AT/100AF,2P,230,MCCB from Electrican Room
INCOMING FEEDER: 2-8.0 mm² +3.5 mm² THHN Cu in 15 mmØ IMC
PROTECTION CIRCUIT
CKT NO. LOAD DESCRIPTION VA IFL IW ICB
AT AF POLES LINE GROUND CONDUIT
1 General Lighting 2640 12.0 12.0 12.0 15 63 2 2-2.0 mm² 1-2.0 mm² 15mmΦ
2 CO 1,500 6.5 6.5 6.5 20 63 2 2-3.5 mm² 1-2.0 mm² 15mmΦ
3 REFRIGERATOR 500 2.2 2.7 5.4 20 63 2 2-5.5 mm² 1-2.0 mm² 15mmΦ
4 ACU-1(1HP) 746 3.2 4.1 8.1 20 63 2 2-5.5 mm² 1-2.0 mm² 15mmΦ
TOTAL 5,386

PANEL NAME: House B, House D, House F


INCOMING VOLTAGE:230V, 1PHASE,60HZ
INCOMING PROTECTION: 40AT/100AF,2P,230,MCCB from Electrican Room
INCOMING FEEDER: 2-8.0 mm² +3.5 mm² THHN Cu in 15 mmØ IMC
PROTECTION CIRCUIT
CKT NO. LOAD DESCRIPTION VA IFL IW ICB
AT AF POLES LINE GROUND CONDUIT
1 General Lighting 2640 12.0 12.0 12.0 15 63 2 2-2.0 mm² 1-2.0 mm² 15mmΦ
2 CO 1,500 6.5 6.5 6.5 20 63 2 2-3.5 mm² 1-2.0 mm² 15mmΦ
3 REFRIGERATOR 500 2.2 2.7 5.4 20 63 2 2-5.5 mm² 1-2.0 mm² 15mmΦ
TOTAL 4,640
TOTAL LOAD CALCULATION House A, House C, House E
100% LOAD:
ACU-1 746
746

OTHER LOADS:
REF: 500
GL: 2,640
CO: 1,500
4,640
TOTAL: 5,386

IT= 23.4 USE 2-8.0 mm² +3.5 mm² THHN Cu in 15 mmØ IMC
IW= 25.4 USE 40AT/100AF,2P,230,MCCB
ICB= 35.4

TOTAL LOAD CALCULATION House A, House C, House E


100% LOAD:
ACU-1 4,640
4,640

OTHER LOADS:
REF: 500
GL: 2,640
CO: 1,500
4,640
TOTAL: 9,280
IT= 40.3 USE 2-8.0 mm² +3.5 mm² THHN Cu in 15 mmØ IMC
IW= 42.3 USE 40AT/100AF,2P,230,MCCB
ICB= 52.3
PANEL NAME:
VOLTAGE/PHASE: 400V/230V
UPSTREAM: LOAD CENTER
INCOMING PROTECTION: USE 150AT/250AF, 3P, 400V, MCCB
UPSTREME FEEDER: USE 4-50 mm² + 1-14 mm² THHN Cu in 32 mm ØIMC
LOAD BALANCE PROTECTION FEEDER
CKT NO. LOAD DESCRIPTION VA IW ICB
R Y B AT AF POLE LINE GROUND CONDUIT
1 DB-16-01 5,386 23.4 Err:509 Err:509 80 100 2 2-22 mm² 1-8.0 mm² 25 mmØ
2 DB-16-02 5,386 23.4 Err:509 Err:509 80 100 2 2-22 mm² 1-8.0 mm² 25 mmØ
3 DB-16-03 5,386 23.4 Err:509 Err:509 80 100 2 2-22 mm² 1-8.0 mm² 25 mmØ
4 DB-16-04 5,386 23.4 Err:509 Err:509 80 100 2 2-22 mm² 1-8.0 mm² 25 mmØ
5 DB-16-05 5,386 23.4 Err:509 Err:509 80 100 2 2-22 mm² 1-8.0 mm² 25 mmØ
6 DB-16-06 Err:509 Err:509 Err:509 Err:509 70 100 2 2-14 mm² 1-8.0 mm² 20 mmØ
7 DB-16-07 Err:509 Err:509 Err:509 Err:509 70 100 2 2-14 mm² 1-8.0 mm² 20 mmØ
8 DB-16-08 Err:509 Err:509 Err:509 Err:509 70 100 2 2-14 mm² 1-8.0 mm² 20 mmØ
9 DB-16-09 Err:509 Err:509 Err:509 Err:509 70 100 2 2-14 mm² 1-8.0 mm² 20 mmØ
10 DB-16-10 Err:509 Err:509 Err:509 Err:509 70 100 2 2-14 mm² 1-8.0 mm² 20 mmØ
11 DB-16-11 Err:509 Err:509 Err:509 Err:509 80 100 2 2-22 mm² 1-8.0 mm² 25 mmØ
12 DB-16-12 Err:509 Err:509 Err:509 Err:509 80 100 2 2-22 mm² 1-8.0 mm² 25 mmØ
TOTAL Err:509 Err:509 Err:509 Err:509
%DEVIATION Err:509 Err:509 Err:509

FEEDER CALCULATION
TOTAL LOAD FOR TYPE A: 12,118.5
TOTAL LOAD FOR TYPE B: Err:509
TOTAL LOAD FOR TYPE C: Err:509
TOTAL LOAD: Err:509

IT Err:509
IW Err:509 USE 4-50 mm² + 1-14 mm² THHN Cu in 32 mm ØIMC
ICB Err:509 USE 150AT/250AF, 3P, 400V, MCCB