7KG85

SICAM P850 is a power monitoring device that collects, displays, and transmits measured electrical variables like voltage, current, power, and harmonics. It communicates via Ethernet using Modbus TCP or IEC 61850 protocols or optionally via a serial RS485 interface. The device is used in single-phase, three-phase, and four-phase systems for power utilities and industrial applications. It provides flexible communication with automation systems via open protocols to monitor and analyze power quality.

Uploaded by

Ganesh Duraisamy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
190 views16 pages

7KG85

SICAM P850 is a power monitoring device that collects, displays, and transmits measured electrical variables like voltage, current, power, and harmonics. It communicates via Ethernet using Modbus TCP or IEC 61850 protocols or optionally via a serial RS485 interface. The device is used in single-phase, three-phase, and four-phase systems for power utilities and industrial applications. It provides flexible communication with automation systems via open protocols to monitor and analyze power quality.

Uploaded by

Ganesh Duraisamy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

Power Quality devices for all applications

SICAM P850
Power Monitoring Device

siemens.com/powerquality
Contents – SICAM P850

Page

1 Device description 2/19

Function overview 2/20

Function overview, Setup and display 2/21

Setup and display, Data availability 2/22

Measurement system according to


IEC 61000-4-30 Ed. 2 / accuracy 2/23

2
Connection types and connection examples 2/24

Variants and dimensions 2/26

Technical data 2/28

Technical data, selection and ordering data 2/32

2/18 SICAM – Power Quality and Measurements · Siemens SR 10 · Edition 4


Products – SICAM P850
Device description

Device description
SICAM P850 is a new multifunctional device and is used to
collect, display and transmit measured electrical variables
such as AC current, AC voltage, power types, harmonics, etc.
The communications interfaces can be used to output the
1
measurands to a PC and the control center or display them
on a display.

Applications
SICAM P8505 device is used in single-phase systems, three-
phase systems and four-phase systems (with neutral conduc-
tors). It is used primarily in power utilities, but also in other
industrial and commercial applications.

The web server integrated into the device is used to config- 2


ure the parameters and output measured values via HTML
pages on a connected PC / laptop. In devices with displays,
the parameters can also be configured with the function keys
on the front of the device, and the measured values can be
output to the display. The output variables can also be
transmitted to control or other systems such as SICAM PQS
V8.01 via the communications interfaces (Ethernet, e.g., Fig. 2/18  SICAM P850
3
IEC 61850) in the form of digital data.

Mean features SICAM P850 system view


ƒƒ Use in the IT, TT and TN power systems SICAM P850 can communicate flexibly with automation
ƒƒ Ethernet communication via the Modbus TCP or IEC 61850 systems and evaluation stations via open protocols such as
Edition 2 protocol; serial communication via Modbus RTU
and IEC 60870-5-103 via the RS485 interface is optional
IEC 61850 and Modbus TCP.
4
ƒƒ External time synchronization via the Network Time They are available directly from the device in the form of
Protocol (NTP). HTML pages on a connected PC.

Evaluation station – control center


5

Time synchronization via NTP server Web server functions


6
• HTML parameterization
• Value display
Ethernet:
Modbus TCP or IEC 61850 • Analysis

Field device level

7
Serial: Modbus RTU or IEC 60870-5-103

8
Fig. 2/19  Sample application

SICAM – Power Quality and Measurements · Siemens SR 10 · Edition 4 2/19


Products – SICAM P850
Function overview

Device Communication
SICAM P850 is designed as panel flush-mounted device An Ethernet interface and an optional RS485 interface are
with a graphical display for displaying measured values and available for communicating with the control center and
1 parameterization: SICAM P850 (7KG850xxx). SICAM P850 is
also available as DIN rail devices without displays.
other process automation systems. The RS485 interface
supports the transmission of operating measured values,
counts and messages. The Modbus RTU or IEC 60870-5-103
Ethernet communication uses the Modbus TCP or IEC 61850 communication protocol can be used, depending on the
communication protocol. Serial communication is optionally device variant.
available with an RS485 interface via Modbus RTU or
IEC 60870-5-103. The device parameterization, transmission of measured
data, counts and messages / events as well as time synchro-
The front protection class is IP20 for DIN rail devices without nization with the Network Time Protocol (NTP) are support-
displays. Devices for panel flush mounting with displays have ed over Ethernet.

2 protection class IP40 or IP51.


The SICAM P850 device supports the transmission of operat-
ing measured values with the two Ethernet protocol options
– via both Modbus TCP and IEC 61850.
Title
Time synchronization
Display area The device needs to have the date and time during opera-

3 tion for all time-relevant processes. SICAM P850 therefore


uses time synchronization while communicating with
peripheral devices to guarantee a common time basis and to
Softkey functions permit time stamping of the process data. The following
types of time synchronization can be carried out:
Softkeys F1 – F4 ƒƒ Time synchronization via Ethernet NTP (preferred)
SICAM P850 / P855 has an SNTP client (Simple Network

4 Fig. 2/20  Display and softkeys


Time Protocol) that can be connected to two NTP servers
(Network Time Protocol) for external time synchroniza-
tion: the primary and secondary (redundant) NTP servers.
Hardware design ƒƒ External time synchronization via the field bus
SICAM P850 contains the following electrical modules, using the Modbus RTU or IEC 60870-5-103 communica-
depending on the device variant: tion protocol
ƒƒ Digital signal processor (DSP) ƒƒ Real Time Clock (RTC)

5 ƒƒ Display and softkeys


ƒƒ 4 inputs for AC voltage measurements
If external time synchronization is not possible, data can be
synchronized with the time pulse of an internal clock.
ƒƒ 3 inputs for AC current measurements
ƒƒ 2 binary outputs LED signaling
ƒƒ Power supply SICAM P850 automatically monitors the functions of its
ƒƒ Ethernet interface hardware / firmware components. LEDs signal the current
ƒƒ RS485 interface (depending on variant ordered). device status.

6 Measurands RUN ERROR


The following measurands are collected or calculated by the
device from the measured variables: H1 H2
ƒƒ True RMS AC voltage and AC current
ƒƒ 2,048 sampled values, 10 / 12 periods Link / activity Speed
ƒƒ Effective value measurement (TRMS) up to 100th harmonic

7 ƒƒ Line frequency
ƒƒ Active, reactive and apparent power Fig. 2/21  LED indicators
ƒƒ Active, reactive and apparent energy
ƒƒ Power factor and active power factor Display and softkeys
ƒƒ AC voltage and AC current unbalance All SICAM P850 models can be operated via HTML pages,
ƒƒ Harmonics of AC voltage and AC current are stored up to using a connected PC. Devices with displays can also be
the 40th order for evaluation operated using the function keys on the front of the display.

8 ƒƒ THD (Total Harmonic Distortion) of AC voltage and


AC current
ƒƒ Phase angle
ƒƒ Flicker.

2/20 SICAM – Power Quality and Measurements · Siemens SR 10 · Edition 4


Products – SICAM P850
Function overview, Setup and display

On panel flush-mounted devices, the front of the display Parameterization and visualization
accommodates four keys and four LEDs located at the bottom All SICAM P850 devices are operated from a connected PC.
of the display. Of these LEDs, H1, H2 and ERROR can be An internal web browser with HTML pages is generally used
parameterized. The ERROR LED can be parameterized only for
error messages. Parameter settings, measured values and
for parameterization.
1
graphics are displayed on the screen.

Fig. 2/22  Harmonics display Fig. 2/25  Parameterizing the process connections

PHASOR DIAGRAM 14.0 Visualizing values 3


VL3 IL3 Depending on which operating parameters are selected, the
input / output window displays measured values with the
corresponding measurement units or a tabular list that is
updated every 5 seconds.
VL1 ƒƒ Operating measured values

IL2
IL1 ƒƒ Voltage harmonics
ƒƒ Current harmonics
4
VL2 ƒƒ Power and energy
ƒƒ Binary outputs
TAB MENU
ƒƒ Limit values
Fig. 2/23  Phasor diagram ƒƒ Group indications.

USER SCREEN_3 24.0


5
V L12 8v

0 16

AMPS L2
0
0 .5A
10
6
MENU

Fig. 2/24  User-defined view

Fig. 2/26  Graphical display of harmonics


7
Automation functions
Upper and lower limit values can be parameterized for up
to 16 measured values. Alerts can be output if these limit
values are exceeded.

SICAM – Power Quality and Measurements · Siemens SR 10 · Edition 4 2/21


Products – SICAM P850
Setup and display, Data availability

Up to four limit value violations are output on the device via Data availability of the operating measurands
the two binary outputs as well as the H1 and H2 LEDs. In
Operating measured values
addition, all 16 limit value violations can be sent to periph- Data (10 / 12 cycle)

1 eral devices via Ethernet


Interface
Modbus TCP, Modbus RTU,
IEC 60870-5-103, IEC 61850,
HTML and display
Values
Type

AC Voltage UL1, L2, L3 x


UL12, 23, 31 x
UN x
Usum x
Uunsym x
AC Current IL1, L2, L3 x

2 and
I0
Isum
x
x
Iunsym x

or Active Power cos φ (L1), (L2), (L3) x


INV Factor cos φ x
and Group indication 1 Power Factor PFL1, PFL2, PFL3 x

3
PF x
Fig. 2/27  Linking alerts to a group indication Phase Angle φL1, φL2, φL3 x
φ x
Frequency f (System freq.) x
10-s-Freq (10-Freq.)
Harmonics, H_UL1-x, UL2-x, UL3-x
x
Voltage, Magnitude (x = 1 to 40)

4 Harmonics,
Current, Magnitude
H_IL1-x, H_IL2-x,
H_IL3-x (x = 1 to 40)
x

THD_UL1, THD_UL2,
THD, Voltage x
THD_UL3

THD_IL1, THD_IL2,
THD, Current x
THD_IL3

5 Active Power PL1, PL2, PL3 x


Fig. 2/28  Visualizing operating measured values
P x
Other maintenance tasks, such as outputting operating logs QL1, QL2, QL3 x
Reactive Power
and error messages as well as firmware updates, can also be Q x
carried out via the HTML pages. SL1, SL2, SL3 x
Apparent Power
S x
Active Energy WPL1, WPL2,
x

6 – Supply WPL3_Supply
WP_Supply x
Active Energy WPL1, WPL2,
x
– Demand WPL3_Demand
WP_Demand x
Reactive Energy WQL1, WQL2,
x
– Inductive WQL3_Inductive

7
WQ_Inductive x
Reactive Energy WQL1, WQL2,
x
– Capacitive WQL3_Capacitive
WQ_Capacitive x
Apparent Energy WSL1, WSL2, WSL3 x
WS x
Fig. 2/29  Visualizing operating logs
Table 2/5  Data availability

2/22 SICAM – Power Quality and Measurements · Siemens SR 10 · Edition 4


Products – SICAM P850
Measurement system according to IEC 61000-4-30 Ed. 2 / accuracy

Functions of the measurement system Reactive power Q


SICAM P850 is a device for measuring voltage quality + inductive, var – ± 0.5 %
according to IEC 61000-4-30 Ed. 2 and other measurands in – capacitive
single-phase or multi-phase supply systems. The measurement
system is implemented according to Class A. In terms of func-
Apparent power S
Power factor PF 2)
VA



± 0.5 %
± 1 %
1
tional scope, measuring ranges and accuracy, SICAM P850 is a Active power factor
– – ± 1 %
Class S measuring device. cos φ 2)
The basic measuring interval for determining the values of Phase angle φ 2) Degree – ± 2 °
the variables (mains voltage, mains voltage harmonics and Active energy WP
mains voltage unbalance) is a 10-period time interval for Wh – ± 0.5 %
demand
50-Hz supply systems and a 12-period time interval for 60-Hz Active energy WP
Wh – ± 0.5 %
supply systems. The 10 / 12-period measurement is resyn- supply
chronized to each RTC 10-minute limit. Reactive energy WQ
varh – ± 0.5 %
inductive
The values for the 10 / 12-period time intervals are aggregated
over additional time intervals. Apparent energy WS varh – ± 0.5 % 2
Total harmonics
Measurands and their operating measurement uncertainty distortion of voltage % – ± 0.5 %
THD Vph
according to IEC 62586-1
Total harmonics
distortion of current % – ± 0.5 %
Operat. mea­
THD Iph
surem. uncer-
Measurands Unit Rated Value tainty acc. to
IEC 62586-1,
Condition:
Im ≥ 10% Irated 3
Maximum error:
Class S1)
Harmonics of ± 5% Im
Voltage Vph-ph V AC 110 V 0.2 % A –
current H_xIph Condition:
(delta) AC 190 V
Im < 10% Irated
Acc. to AC 400 V
Maximum error:
parameterization AC 690 V
± 0.5% Irated
max. AC 600 V for

Voltage Vph-N V
UL condition
AC 63.5 V 0.2 %
1
2
Tolerance limits apply to the entire nominal operating range
Measurement of 2 % or more of the nominal value of the apparent
4
(star) AC 110 V power within the selected measuring range
Acc. to AC 230 V Table 2/6  Measurement uncertainty according to IEC 62586-1
parameterization AC 400 V
max. AC 347 V for
UL condition Accuracy of the frequency measurement
Voltage VN V AC 63.5 V 0.2 %
AC 110 V
AC 230 V
Circuit Accuracy
5
AC 400 V 0% to 15% Vrated: invalid
max. AC 347 V for
UL condition Voltage to Va-N 15% to 30% Vrated: 40 mHz
Voltage unbalance % – 0.2 %
Vunbal 30% to 120% Vrated: 10 mHz
Frequency f Hz 50 Hz (± 7,5 Hz) 50 mHz 0% to 15% Vrated: invalid
60 Hz (± 9 Hz) (see Table Accuracy
of the frequency
measurement) Voltage to Vb-N
15% to 30% Vrated: 40 mHz 6
Harmonics of % or V – Condition: 30% to 50% Vrated: 30 mHz
voltage H_xVph Vm ≥ 3% Vrated
Maximum error: 50% to 120% Vrated: 20 mHz
± 5% Vm
0% to 15% Vrated: invalid
Condition:

7
Vm < 3% Vrated Voltage to Vc-N 15% to 30% Vrated: 40 mHz
Maximum error:
± 0.15% Vrated 30% to 120% Vrated: 10 mHz
Short-term flicker Pst and – Acc. to IEC 61000-4- Table 2/7  Accuracy of the frequency measurement
and long-term flicker Plt 15 / 30
Current I
AC 1 A
Acc. to parameteriza- A ± 0.2 %
AC 5 A
tion
Current unbalance
Iunbal
% – ± 0.2 %
8
± 0.5%,
Active power P
W – 0.2S acc. to
+ demand, – supply
IEC 62053-21

SICAM – Power Quality and Measurements · Siemens SR 10 · Edition 4 2/23


Products – SICAM P850
Connection types and connection examples

SICAM P850 in various power systems


If SICAM P850 is used in the IT, TT and TN power systems, ƒƒ Three-conductor system with any (unbalanced) load
no special operating conditions need to be observed. (2 current inputs)
1 Connection types
ƒƒ Three conductor system with any (unbalanced) load
(3-current inputs)
The possible connection types in SICAM P850 are: ƒƒ Four-conductor system with equal (balanced) load
ƒƒ Single-phase system ƒƒ Four-conductor system with any (unbalanced) load.
ƒƒ Three-conductor system with equal (balanced) load

2
Terminals SICAM P850 F Voltage E Current Terminals SICAM P850 F Voltage
E Current A A
L1 A L1
A L1
L1 B B
L2 L2

C C
L3 L3
B
B L2
L2 N N

3 C
L3

S1 S2
C
L3 PE a

A
ba

B A
b

B
PE 10 A S1 S2 10 A 10 A 10 A

L L1
P1 P2 P1 P2
L2
N L3

4 Fig. 2/30  C
 onnection example: single-phase system,
1 voltage converter
Fig. 2/31  Connection example: three-conductor system,
2 voltage converters and 1 current converter, equal load

5
E Current Terminals SICAM P850 F Voltage
E Current Terminals SICAM P850 F Voltage A
A A L1
A L1 L1 B
L1 B L2
L2
C
C L3
L3 B
B L2
L2 N
N

C
C L3
each 10 A

6
L3
each 10 A

S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 PE
PE
L1
L1 P1 P2
P1 P2
L2
L2
P1 P2

L3 L3
P1 P2
P1 P2

7 Fig. 2/32  C
 onnection example: three-conductor system,
no voltage converter and 3 current converters, any load
Fig. 2/33  C
 onnection example: three-conductor system,
no voltage converter and 2 current converters, any load

2/24 SICAM – Power Quality and Measurements · Siemens SR 10 · Edition 4


Products – SICAM P850
Connection types and connection examples

Terminals SICAM P850 F Voltage


E Current Terminals SICAM P850 F Voltage E Current
A A
L1 A L1
A

1
L1 B
L1 B
L2 L2

C C
L3 B L3
B L2
L2 N N

C
C L3
L3

a b a b

PE A B A B PE

S1 S2 S1 S2 S1 S2 each 10 A
S1 S2 S1 S2 10 A 10 A 10 A

L1 L1
P1 P2 P1 P2
L2 L2
P1 P2
L3 L3
P1 P2 P1 P2

Fig. 2/34  C
 onnection example: three-conductor system,
N

Fig. 2/35  Connection example: four-conductor system, 2


2 voltage converters and 2 current converters, any load no voltage converter and 3 current converters, any load

A
L1
E Current Terminals SICAM P850
A
L1
B
F Voltage
A
L1
E Current Terminals SICAM P850
A
L1
B
F Voltage
3
L2 L2

C C
L3 B L3
B
L2 L2
a a a N
N

C C
L3 L3
b b b

a b a b B B B
PE

4
PE A B A B A A A

S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 each 10 A
10 A 10 A 10 A
L1 L1
P1 P2 P1 P2
L2 L2
P1 P2 P1 P2
L3 L3
P1 P2 P1 P2
N

5
 onnection example: three-conductor system,
Fig. 2/36  C Fig. 2/37  Connection example: four-conductor system,
2 voltage converters and 3 current converters, any load 3 voltage converters and 3 current converters, any load

E Current Terminals SICAM P850 F Voltage


A

6
L1
A
L1 B
L2
C
L3
B
L2 N

C a b
L3
PE
A B

S1 S2
10 A

L1
P1 P2
L2

7
L3
N

 onnection example: three-conductor system,


Fig. 2/38  C
1 voltage converter and 1 current converter, any load

SICAM – Power Quality and Measurements · Siemens SR 10 · Edition 4 2/25


Products – SICAM P850
Variants and dimensions

SICAM P850 variants

Fig. 2/39  S
 ICAM P850 for panel flush mounting, display side Fig. 2/40  SICAM P850 for panel flush mounting,
terminal side with RS485 interface

Fig. 2/41  S
 ICAM P850 as a DIN rail device, Fig. 2/42  SICAM P850 as a DIN rail device,
DIN rail side terminal side with RS485 interface

2/26 SICAM – Power Quality and Measurements · Siemens SR 10 · Edition 4


Products – SICAM P850
Variants and dimensions

Dimensions

1
123.9
116.4 102.9
8.5
105.5

96
Default IP Address: 192188.0.55

3
Default Subnet Mask: 255.255.255.0

Default IP Address: 192.168.0.55


Default Subnet Mask: 255.255.255.0

95.5

DIN rail mounting Panel flush mounting


4
Mass Device without display: approx. 0.49 kg Sectional drawing for panel 92 (+0.8) mm x 92 (+0.8) mm
Device with display, without door: approx. 0.52 kg flush mounting (W x H) (+0.8 mm = upper limit dimension)
Device with display and door: approx. 0.6 kg Dimension (W x H x D) 96 mm x 96 mm x 100 mm
3.78 inch x 3.78 inch x 3.94 inch

Fig. 2/43  Dimensions


5

SICAM – Power Quality and Measurements · Siemens SR 10 · Edition 4 2/27


Products – SICAM P850
Technical data

Power supply Inputs and outputs

Direct voltage Inputs for alternating voltage measurements (connector block F)

1 Rated input voltages 24 V to 250 V Rated input AC voltages (parameterizable)

Admissible input voltage tolerance ± 20 % 63.5 V


110 V
Permitted ripple of the input voltage 15 % 230 V
Phase-N / PE 400 V (max. 347 V for UL condition)
Maximum inrush current
Operating measurement uncertainty
At ≤ 110 V  < 15 A according to IEC 60688: ± 0.1%

At 220 V to 300  V after 250 µs: ≤ 22 A; after 250 µs: < 5 A 110 V
190 V
400 V
2 Maximum power consumption 3 W Phase-phase 690 V (max. 600 V for UL condition)

Operating measurement uncertainty


IEC 60688: ± 0.1%
Alternating voltage
Maximum input AC voltage
1.2 x rated input AC voltage
Rated input voltages 110 V to 230 V (depending on the parameterization)

3 System frequency at AC

Admissible input voltage tolerance


50 Hz / 60 Hz

± 20 %
Maximum input AC voltage

Phase-N / PE 480 V (max. 347 V for UL condition)


Permitted harmonics at AC 115 V and AC 230 V 2 kHz
Phase-phase 831 V (max. 600 V for UL condition)

Maximum inrush current


Input impedances
At ≤ 115 V  < 15 A
4
a, b, c to N 6.0 MΩ
At 230 V ≤ 22 A; after 250 µs: < 5 A
a-b, b-c, c-a 6.0 MΩ

Maximum power consumption 6 VA Further information about the voltage measurement inputs

Table 2/8  Power supply Power consumption per input for


38 mW
Vrated 400 V
Permissible power frequency 42.5 Hz to 69.0 Hz
5 Measuring error (with calibration)
Typically 0.1% for reference
at 23 °C ± 1 °C
conditions according to IEC 60888
50 Hz or 60 Hz
Table 2/9  Inputs and outputs

2/28 SICAM – Power Quality and Measurements · Siemens SR 10 · Edition 4


Products – SICAM P850
Technical data

Communication interfaces
Inputs for alternating current measurements (connector block E)

Input AC currents Ethernet (connector Z)


1 A
5 A
Ethernet, electrical 1
Rated input current range Connection Device top side
(parameterizable) Operating measurement RJ45 connector socket
uncertainty according to IEC 60688 10 / 100 Base-T acc. to IEEE802.3
± 0.1 % LED yellow: 10 / 100 Mbit / s (off / on)
Max. input current 2x rated input AC current LED green:
− flashing: active
− on: not active
Power consumption per input − off: no connection
Modbus TCP
At 1 A 1 mVA Protocols
IEC 61850 Server
At 5 A 2.5 mVA Voltage strength DC 700 V
2
Further information about the current measurement inputs Transmission rate 10 / 100 MBit / s

Permissible power frequency 42.5 Hz to 69.0 Hz Cable for 10 / 100 Base-T 100 Ω to 150 Ω STP, CAT5
Maximum cable length
Max. rated input voltage 150 V 100 m, if well installed
10 / 100 Base-T
Measuring error (with calibration) Table 2/12  Ethernet
Typically 0.1 % at reference
at 23 °C ± 1 °C
50 Hz or 60 Hz
conditions 3
10 A continuous
Thermal stability 100 A for max. 1 s according to Serial interface (connector J), optional
IEC 60688
RS485
Table 2/10  Inputs for alternating current measurements
Connection RS485 port, terminal side,
9 pin D-Sub socket
Binary outputs (connector block G)

Maximum switching voltage


Protocol
Modbus RTU
(optional)
IEC 60870-5-103
(optional)
4
Min. 1200 Bit / s Min. 9600 Bit / s
Baud rate (adjustable)
Alternating voltage 230 V Max. 115 200 Bit / s Max. 38 400 Bit / s

Direct voltage 250 V Maximum distance of


Max. 1 km (depending on data rate)
transmission
Maximum currents Low: –5 V to –1.5 V
Transmission level

Maximum pulse current for 0.1 s  300 mA


Reception level
High: +1.5 V to +5 V
Low: ≤ –0.2 V
5
High: ≥ +0.2 V
Further information about the binary outputs Not integrated, bus termination
Bus termination using plugs with integrated
Internal impedance 35 Ω
bus terminating resistors
Admissible switching frequency 10 Hz Table 2/13  Serial interface

Number of switching cycles Unlimited 6


Table 2/11  Binary outputs

SICAM – Power Quality and Measurements · Siemens SR 10 · Edition 4 2/29


Products – SICAM P850
Technical data

Mechanical tests
EMC tests for immunity (type tests)
IEC EN 61000-6-2 Vibration and shock stress in stationary use
Standards For more standards see also
1 individual functions
6 kV contact discharge;
Standards IEC 60068
Sinusoidal
8 kV air discharge,
Electrostatic discharge, Class III 10 Hz to 60 Hz: ± 0.075 mm amplitude;
both polarities; 150 pF; Oscillation
IEC 61000-4-2 60 Hz to 150 Hz: 1 g acceleration
Ri = 330 Ω IEC 60068-2-6 test Fc
Frequency sweep rate 1 octave / min
with connected Ethernet cable
20 cycles in 3 orthogonal axes
Radio frequency electromagnetic
10 V / m; 80 MHz to 3 GHz 80% AM; Semi-sinusoidal
field, amplitude-modulated, Class III
1 kHz Shock 5 g acceleration, duration 11 ms,
IEC 61000-4-3
IEC 60068-2-27 test Ea each 3 shocks in both directions of the
2 kV; 5 ns / 50 ns; 5 kHz; 3 axes
Burst length = 15 ms;
Sinusoidal
Fast transient bursts, Class III Repetition rate 300 ms;
2 IEC 61000-4-4 Both polarities;
Ri = 50 Ω;
1 Hz to 8 Hz: ±7.5 mm amplitude
(horizontal axis)
1 Hz to 8 Hz: ±3.5 mm amplitude
Test duration 1 min
(vertical axis)
High energy surge voltages Seismic Vibration
8 Hz to 35 Hz: 2 g acceleration
(SURGE), Installation Class III Impulse: 1.2 μs / 50 μs IEC 60068-3-3 test Fc
(horizontal axis)
IEC 61000-4-5 8 Hz to 35 Hz: 1 g acceleration
Common mode: 2 kV; 12 Ω; 9 μF (vertical axis)
Auxiliary voltage
Diff. mode: 1 kV; 2 Ω; 18 μF Frequency sweep 1 octave / min

3 Measuring inputs, binary inputs


and relay outputs
Common mode: 2 kV; 42 Ω; 0.5 μF
Diff. mode: 1 kV; 42 Ω; 0.5 μF
1 cycle in 3 orthogonal axes
Table 2/16  Vibration and shock stress in stationary use
HF on lines,
10 V; 150 kHz to 80 MHz;
amplitude-modulated, Class III
80 % AM; 1 kHz
IEC 61000-4-6 Vibration and shock stress during transport
Power system frequency
magnetic field 30 A / m continuous; 300 A / m for 3 s Standards IEC 60068
IEC 61000-4-8, Class IV Sinusoidal
4 1 MHz test, Class III,
IEC 61000-4-18
2.5 kV (peak); 1 MHz; τ = 15 μs;
400 surges each s; Oscillation
IEC 60068-2-6 test Fc
5 Hz to 8 Hz: ±7.5 mm amplitude;
8 Hz to 150 Hz: 2 g acceleration
Test duration 1 min; Ri = 200 Ω Frequency sweep 1 octave / min
Table 2/14  EMC tests for immunity 20 cycles in 3 orthogonal axes
Semi-sinusoidal
Shock 15 g acceleration, duration 11 ms,
EMC tests for electromagnetic interference (type test) IEC 60068-2-27 test Ea each 3 shocks
(in both directions of the 3 axes)

5
Standard IEC EN 61000-6-4
Semi-sinusoidal
Radio noise voltage to lines, Continuous Shock 10 g acceleration, duration 16 ms,
150 kHz to 30 MHz
only auxiliary voltage IEC 60068-2-29 test Eb each 1000 shocks
Limit Class A
IEC-CISPR 22 (in both directions of the 3 axes)
Interference field strength 30 MHz to 1000 MHz Free fall
0.5 m
IEC-CISPR 22 Limit Class A IEC 60068-2-32 test Ed
Table 2/15  EMC tests for electromagnetic interference Table 2/17  Vibration and shock stress during transport

2/30 SICAM – Power Quality and Measurements · Siemens SR 10 · Edition 4


Products – SICAM P850
Technical data

Test data

Reference conditions according to IEC 62586-1 for determining Air humidity data
the test data
Ambient temperature 23 °C ± 2 °C
Mean relative air humidity per year ≤ 75 % 1
Maximum relative air humidity 95 %, 30 days a year
Relative humidity 40 % to 60 % RH

Supply voltage VPS ± 1% Condensation during operation Not permitted

Phases (3-wire network) 3 Condensation during transport and storage Permitted

DC field: ≤ 40 A / m
External continuous
Altitude
magnetic fields
AC field: ≤ 3 A / m
Max. altitude above sea level 2000 m
DC components V / I none

Signal waveform sinus 2


General data
50 Hz ± 0,5 Hz
Frequency
Battery
60 Hz ± 0,5 Hz
PANASONIC CR2032
Voltage magnitude Vdin ± 1 % Type
VARTA 6032 101 501
Flicker

Unbalance (all channels)


Pst < 0.1 %

100% ± 0.5 % of Vdin


Voltage

Capacity
3V

230 mAh
3
Harmonic 0 % to 3 % of Vdin Typical life For operation with permanently applied
supply voltage: 10 years
Interharmonic 0 % to 0.5 % of Vdin For operation with sporadically interrupted
supply voltage:
a total of 2 months over a 10-year period
Electrical tests

Standards DIN rail housing IP20


4
IEC EN 61000-6-2 Panel flush mounting IP40 (with display, without door)
IEC EN 61000-6-4 (front) IP51 (with display and door)
Standards
IEC EN 61010-1
IEC EN 61010-2-030 Terminals IP2x

Insulation test according to IEC 61010-1 and IEC EN 61010-2-030


Rated ISO Test
Climate stress tests
5
Inputs / Outputs Insulation Category Standards: IEC 60068
Voltage Voltage
Current Dry cold: IEC 60068-2-1 test Ad
Reinforced 150 V AC 2.3 kV Cat. III
measuring inputs
Dry heat during operation, storage and transport:
Voltage Surge voltage IEC 60068-2-2 test Bd
Reinforced 480 V Cat. III
measuring inputs 9.76 kV
Damp heat: IEC 60068-2-78 test Ca
Supply voltage Reinforced 300 V DC 3,125 kV Cat. III
Change of temperature: IEC 60068-2-14 test Na and Nb
6
Binary outputs Reinforced 300 V AC 3.536 kV Cat. III

Ethernet interface Function < 50 V DC 700 V Cat. III Safety standards


RS485 interface Function < 50 V DC 700 V Cat. III
Standards: IEC EN 61010

IEC EN 61010-1, IEC EN 61010-2-30


Environmental conditions
Table 2/18  Further technical data
7
Temperature data
Operating temperature
Devices with display: the legibility of the display –25 °C to +55 °C
is impaired at temperatures < 0 °C (+32 °F)
Temperature during transport –40 °C to +70 °C

Temperature during storage –40 °C to +70 °C


8
Maximum temperature gradient 20 K / h

SICAM – Power Quality and Measurements · Siemens SR 10 · Edition 4 2/31


Products – SICAM P850
Technical data, selection and ordering data

Technical data
Please refer to the manual for the technical data for
SICAM P850.
1 Description Order No.

Multifunctional Power Meter


SICAM P850  7KG850 -0AA-AA0

Device type
Dimensions 96 mm x 96 mm x 100 mm / 3.78 in. x 3.78 in. x 3.94 in. (W x H x D)
4 Inputs for AC voltage measurements
3 Inputs for AC current measurements

2 2 Binary outputs
Galvanic isolated voltage measurement inputs
web server for parameterization and visualization, and data management
Measurements according to standard IEC 61000-4-30, Class S

Measurement functions
Basic measurements: V, I, f, P (class 0.2S), Q, S, cos φ,
limit violations, energy measurements

3 measurements till 40th harmonics


Transmission measurement values via communication protocols 0

Housing
Snap-on mounting unit without graphical display 0 0
Panel-mounted instrument with graphical display 1

4 Serial Communication Interface


Without 0
RS485 – Modbus RTU 1
RS485 – IEC 60870-5-103 and Modbus RTU 3

Front protection class

5
IP20 (Position 7 = 0) 0
IP40 (Position 7 = 1) 1
IP51 (Position 7 = 2) 2

Ethernet Interface and Communication protocol, RJ45


Modbus TCP 0
Modbus TCP and IEC 61850 Server 2
6 Table 2/19  Selection and ordering data

2/32 SICAM – Power Quality and Measurements · Siemens SR 10 · Edition 4