7KG85
7KG85
SICAM P850
Power Monitoring Device
siemens.com/powerquality
Contents – SICAM P850
Page
2
Connection types and connection examples 2/24
Device description
SICAM P850 is a new multifunctional device and is used to
collect, display and transmit measured electrical variables
such as AC current, AC voltage, power types, harmonics, etc.
The communications interfaces can be used to output the
1
measurands to a PC and the control center or display them
on a display.
Applications
SICAM P8505 device is used in single-phase systems, three-
phase systems and four-phase systems (with neutral conduc-
tors). It is used primarily in power utilities, but also in other
industrial and commercial applications.
7
Serial: Modbus RTU or IEC 60870-5-103
8
Fig. 2/19 Sample application
Device Communication
SICAM P850 is designed as panel flush-mounted device An Ethernet interface and an optional RS485 interface are
with a graphical display for displaying measured values and available for communicating with the control center and
1 parameterization: SICAM P850 (7KG850xxx). SICAM P850 is
also available as DIN rail devices without displays.
other process automation systems. The RS485 interface
supports the transmission of operating measured values,
counts and messages. The Modbus RTU or IEC 60870-5-103
Ethernet communication uses the Modbus TCP or IEC 61850 communication protocol can be used, depending on the
communication protocol. Serial communication is optionally device variant.
available with an RS485 interface via Modbus RTU or
IEC 60870-5-103. The device parameterization, transmission of measured
data, counts and messages / events as well as time synchro-
The front protection class is IP20 for DIN rail devices without nization with the Network Time Protocol (NTP) are support-
displays. Devices for panel flush mounting with displays have ed over Ethernet.
7 Line frequency
Active, reactive and apparent power Fig. 2/21 LED indicators
Active, reactive and apparent energy
Power factor and active power factor Display and softkeys
AC voltage and AC current unbalance All SICAM P850 models can be operated via HTML pages,
Harmonics of AC voltage and AC current are stored up to using a connected PC. Devices with displays can also be
the 40th order for evaluation operated using the function keys on the front of the display.
On panel flush-mounted devices, the front of the display Parameterization and visualization
accommodates four keys and four LEDs located at the bottom All SICAM P850 devices are operated from a connected PC.
of the display. Of these LEDs, H1, H2 and ERROR can be An internal web browser with HTML pages is generally used
parameterized. The ERROR LED can be parameterized only for
error messages. Parameter settings, measured values and
for parameterization.
1
graphics are displayed on the screen.
Fig. 2/22 Harmonics display Fig. 2/25 Parameterizing the process connections
IL2
IL1 Voltage harmonics
Current harmonics
4
VL2 Power and energy
Binary outputs
TAB MENU
Limit values
Fig. 2/23 Phasor diagram Group indications.
0 16
AMPS L2
0
0 .5A
10
6
MENU
Up to four limit value violations are output on the device via Data availability of the operating measurands
the two binary outputs as well as the H1 and H2 LEDs. In
Operating measured values
addition, all 16 limit value violations can be sent to periph- Data (10 / 12 cycle)
2 and
I0
Isum
x
x
Iunsym x
3
PF x
Fig. 2/27 Linking alerts to a group indication Phase Angle φL1, φL2, φL3 x
φ x
Frequency f (System freq.) x
10-s-Freq (10-Freq.)
Harmonics, H_UL1-x, UL2-x, UL3-x
x
Voltage, Magnitude (x = 1 to 40)
4 Harmonics,
Current, Magnitude
H_IL1-x, H_IL2-x,
H_IL3-x (x = 1 to 40)
x
THD_UL1, THD_UL2,
THD, Voltage x
THD_UL3
THD_IL1, THD_IL2,
THD, Current x
THD_IL3
6 – Supply WPL3_Supply
WP_Supply x
Active Energy WPL1, WPL2,
x
– Demand WPL3_Demand
WP_Demand x
Reactive Energy WQL1, WQL2,
x
– Inductive WQL3_Inductive
7
WQ_Inductive x
Reactive Energy WQL1, WQL2,
x
– Capacitive WQL3_Capacitive
WQ_Capacitive x
Apparent Energy WSL1, WSL2, WSL3 x
WS x
Fig. 2/29 Visualizing operating logs
Table 2/5 Data availability
Voltage Vph-N V
UL condition
AC 63.5 V 0.2 %
1
2
Tolerance limits apply to the entire nominal operating range
Measurement of 2 % or more of the nominal value of the apparent
4
(star) AC 110 V power within the selected measuring range
Acc. to AC 230 V Table 2/6 Measurement uncertainty according to IEC 62586-1
parameterization AC 400 V
max. AC 347 V for
UL condition Accuracy of the frequency measurement
Voltage VN V AC 63.5 V 0.2 %
AC 110 V
AC 230 V
Circuit Accuracy
5
AC 400 V 0% to 15% Vrated: invalid
max. AC 347 V for
UL condition Voltage to Va-N 15% to 30% Vrated: 40 mHz
Voltage unbalance % – 0.2 %
Vunbal 30% to 120% Vrated: 10 mHz
Frequency f Hz 50 Hz (± 7,5 Hz) 50 mHz 0% to 15% Vrated: invalid
60 Hz (± 9 Hz) (see Table Accuracy
of the frequency
measurement) Voltage to Vb-N
15% to 30% Vrated: 40 mHz 6
Harmonics of % or V – Condition: 30% to 50% Vrated: 30 mHz
voltage H_xVph Vm ≥ 3% Vrated
Maximum error: 50% to 120% Vrated: 20 mHz
± 5% Vm
0% to 15% Vrated: invalid
Condition:
7
Vm < 3% Vrated Voltage to Vc-N 15% to 30% Vrated: 40 mHz
Maximum error:
± 0.15% Vrated 30% to 120% Vrated: 10 mHz
Short-term flicker Pst and – Acc. to IEC 61000-4- Table 2/7 Accuracy of the frequency measurement
and long-term flicker Plt 15 / 30
Current I
AC 1 A
Acc. to parameteriza- A ± 0.2 %
AC 5 A
tion
Current unbalance
Iunbal
% – ± 0.2 %
8
± 0.5%,
Active power P
W – 0.2S acc. to
+ demand, – supply
IEC 62053-21
2
Terminals SICAM P850 F Voltage E Current Terminals SICAM P850 F Voltage
E Current A A
L1 A L1
A L1
L1 B B
L2 L2
C C
L3 L3
B
B L2
L2 N N
3 C
L3
S1 S2
C
L3 PE a
A
ba
B A
b
B
PE 10 A S1 S2 10 A 10 A 10 A
L L1
P1 P2 P1 P2
L2
N L3
4 Fig. 2/30 C
onnection example: single-phase system,
1 voltage converter
Fig. 2/31 Connection example: three-conductor system,
2 voltage converters and 1 current converter, equal load
5
E Current Terminals SICAM P850 F Voltage
E Current Terminals SICAM P850 F Voltage A
A A L1
A L1 L1 B
L1 B L2
L2
C
C L3
L3 B
B L2
L2 N
N
C
C L3
each 10 A
6
L3
each 10 A
S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 PE
PE
L1
L1 P1 P2
P1 P2
L2
L2
P1 P2
L3 L3
P1 P2
P1 P2
7 Fig. 2/32 C
onnection example: three-conductor system,
no voltage converter and 3 current converters, any load
Fig. 2/33 C
onnection example: three-conductor system,
no voltage converter and 2 current converters, any load
1
L1 B
L1 B
L2 L2
C C
L3 B L3
B L2
L2 N N
C
C L3
L3
a b a b
PE A B A B PE
S1 S2 S1 S2 S1 S2 each 10 A
S1 S2 S1 S2 10 A 10 A 10 A
L1 L1
P1 P2 P1 P2
L2 L2
P1 P2
L3 L3
P1 P2 P1 P2
Fig. 2/34 C
onnection example: three-conductor system,
N
A
L1
E Current Terminals SICAM P850
A
L1
B
F Voltage
A
L1
E Current Terminals SICAM P850
A
L1
B
F Voltage
3
L2 L2
C C
L3 B L3
B
L2 L2
a a a N
N
C C
L3 L3
b b b
a b a b B B B
PE
4
PE A B A B A A A
S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 each 10 A
10 A 10 A 10 A
L1 L1
P1 P2 P1 P2
L2 L2
P1 P2 P1 P2
L3 L3
P1 P2 P1 P2
N
5
onnection example: three-conductor system,
Fig. 2/36 C Fig. 2/37 Connection example: four-conductor system,
2 voltage converters and 3 current converters, any load 3 voltage converters and 3 current converters, any load
6
L1
A
L1 B
L2
C
L3
B
L2 N
C a b
L3
PE
A B
S1 S2
10 A
L1
P1 P2
L2
7
L3
N
Fig. 2/39 S
ICAM P850 for panel flush mounting, display side Fig. 2/40 SICAM P850 for panel flush mounting,
terminal side with RS485 interface
Fig. 2/41 S
ICAM P850 as a DIN rail device, Fig. 2/42 SICAM P850 as a DIN rail device,
DIN rail side terminal side with RS485 interface
Dimensions
1
123.9
116.4 102.9
8.5
105.5
96
Default IP Address: 192188.0.55
3
Default Subnet Mask: 255.255.255.0
95.5
At 220 V to 300 V after 250 µs: ≤ 22 A; after 250 µs: < 5 A 110 V
190 V
400 V
2 Maximum power consumption 3 W Phase-phase 690 V (max. 600 V for UL condition)
3 System frequency at AC
± 20 %
Maximum input AC voltage
Maximum power consumption 6 VA Further information about the voltage measurement inputs
Communication interfaces
Inputs for alternating current measurements (connector block E)
Permissible power frequency 42.5 Hz to 69.0 Hz Cable for 10 / 100 Base-T 100 Ω to 150 Ω STP, CAT5
Maximum cable length
Max. rated input voltage 150 V 100 m, if well installed
10 / 100 Base-T
Measuring error (with calibration) Table 2/12 Ethernet
Typically 0.1 % at reference
at 23 °C ± 1 °C
50 Hz or 60 Hz
conditions 3
10 A continuous
Thermal stability 100 A for max. 1 s according to Serial interface (connector J), optional
IEC 60688
RS485
Table 2/10 Inputs for alternating current measurements
Connection RS485 port, terminal side,
9 pin D-Sub socket
Binary outputs (connector block G)
Mechanical tests
EMC tests for immunity (type tests)
IEC EN 61000-6-2 Vibration and shock stress in stationary use
Standards For more standards see also
1 individual functions
6 kV contact discharge;
Standards IEC 60068
Sinusoidal
8 kV air discharge,
Electrostatic discharge, Class III 10 Hz to 60 Hz: ± 0.075 mm amplitude;
both polarities; 150 pF; Oscillation
IEC 61000-4-2 60 Hz to 150 Hz: 1 g acceleration
Ri = 330 Ω IEC 60068-2-6 test Fc
Frequency sweep rate 1 octave / min
with connected Ethernet cable
20 cycles in 3 orthogonal axes
Radio frequency electromagnetic
10 V / m; 80 MHz to 3 GHz 80% AM; Semi-sinusoidal
field, amplitude-modulated, Class III
1 kHz Shock 5 g acceleration, duration 11 ms,
IEC 61000-4-3
IEC 60068-2-27 test Ea each 3 shocks in both directions of the
2 kV; 5 ns / 50 ns; 5 kHz; 3 axes
Burst length = 15 ms;
Sinusoidal
Fast transient bursts, Class III Repetition rate 300 ms;
2 IEC 61000-4-4 Both polarities;
Ri = 50 Ω;
1 Hz to 8 Hz: ±7.5 mm amplitude
(horizontal axis)
1 Hz to 8 Hz: ±3.5 mm amplitude
Test duration 1 min
(vertical axis)
High energy surge voltages Seismic Vibration
8 Hz to 35 Hz: 2 g acceleration
(SURGE), Installation Class III Impulse: 1.2 μs / 50 μs IEC 60068-3-3 test Fc
(horizontal axis)
IEC 61000-4-5 8 Hz to 35 Hz: 1 g acceleration
Common mode: 2 kV; 12 Ω; 9 μF (vertical axis)
Auxiliary voltage
Diff. mode: 1 kV; 2 Ω; 18 μF Frequency sweep 1 octave / min
5
Standard IEC EN 61000-6-4
Semi-sinusoidal
Radio noise voltage to lines, Continuous Shock 10 g acceleration, duration 16 ms,
150 kHz to 30 MHz
only auxiliary voltage IEC 60068-2-29 test Eb each 1000 shocks
Limit Class A
IEC-CISPR 22 (in both directions of the 3 axes)
Interference field strength 30 MHz to 1000 MHz Free fall
0.5 m
IEC-CISPR 22 Limit Class A IEC 60068-2-32 test Ed
Table 2/15 EMC tests for electromagnetic interference Table 2/17 Vibration and shock stress during transport
Test data
Reference conditions according to IEC 62586-1 for determining Air humidity data
the test data
Ambient temperature 23 °C ± 2 °C
Mean relative air humidity per year ≤ 75 % 1
Maximum relative air humidity 95 %, 30 days a year
Relative humidity 40 % to 60 % RH
DC field: ≤ 40 A / m
External continuous
Altitude
magnetic fields
AC field: ≤ 3 A / m
Max. altitude above sea level 2000 m
DC components V / I none
Capacity
3V
230 mAh
3
Harmonic 0 % to 3 % of Vdin Typical life For operation with permanently applied
supply voltage: 10 years
Interharmonic 0 % to 0.5 % of Vdin For operation with sporadically interrupted
supply voltage:
a total of 2 months over a 10-year period
Electrical tests
Technical data
Please refer to the manual for the technical data for
SICAM P850.
1 Description Order No.
Device type
Dimensions 96 mm x 96 mm x 100 mm / 3.78 in. x 3.78 in. x 3.94 in. (W x H x D)
4 Inputs for AC voltage measurements
3 Inputs for AC current measurements
2 2 Binary outputs
Galvanic isolated voltage measurement inputs
web server for parameterization and visualization, and data management
Measurements according to standard IEC 61000-4-30, Class S
Measurement functions
Basic measurements: V, I, f, P (class 0.2S), Q, S, cos φ,
limit violations, energy measurements
Housing
Snap-on mounting unit without graphical display 0 0
Panel-mounted instrument with graphical display 1
5
IP20 (Position 7 = 0) 0
IP40 (Position 7 = 1) 1
IP51 (Position 7 = 2) 2